Você está na página 1de 4

LV SWITCHGEAR -TECHNICAL DATA SHEET

Instructions:
1 Kindly do not alter the contents of the cell which contain formulas
2 Click the appropriate TABS to select/go to the respective sheets.
3 Cells/Columns colour coding
Data Contain standard / Formulas / Results
Data to be Entered Manually
Select from Drop down
Resp. Dept. Prepared by

Doc No: PTC-BFA-D-008, Rev. 0 Date Approved by


Title: LV Switchgear - Technical Data Sheet 21.06.2017

LOW VOLTAGE SWITCHGEAR - TECHNICAL DATA SHEET - MCC

Sl. No Description Unit Requirement Data Vendor Confirmation

1 General Information
IEC 61439, IEC 60947-2, IEC
60947-3, IEC 60947-4,
1.1 Design Standard Yes / No
IEC 61869, IEC 60529,
IEC 60865, IEC 60269
1.2 Quantity Nos. As per RFQ
1.3 Type of installation Indoor
1.4 Design ambient temperature °C 40
1.5 Altitude m 1000

2 Electrical data
2.1 Rated Voltage V 400
2.2 Rated Insulation Voltage V 690
Rated Power frequency withstand Voltage
2.3 kV 2.5
(1 min)
2.4 Rated frequency Hz 50
2.5 Rated Current A As per the RFQ
2.6 Short circuit current kA 50
2.7 Duration of Short-time withstand current s 1
2.8 Rated peak withstand current kA 105
2.9 Maximum Temperature rise °C 65

3 Construction
Metal Enclosed,
3.1 Type of Construction
Air Insulated
3.2 Panel Installation Floor Mounted
3.3 Single/Double Front Single Front
3.4 Circuit Breaker Installation Withdrawable
3.5 Degree of Protection IP 42
Form of Internal Seperation - Incoming
3.6 Form 3b
ACB/MCCB and Outgoing ACB sections
Form of Internal Seperation - Outgoing
3.7 Form 3b
MCCB sections
3.8 Earthing System TN-S
3.9 Enclosure Material CRCA Sheet Steel
Minimum Thickness of Load Bearing
3.10 mm 2
members
3.11 Minimum Thickness of Enclosure walls mm 1.5
3.12 Paint Shade RAL 2004
3.13 Maximum height of Instrument mounting mm 2000
3.14 Minimum height of Instrument mounting mm 200
3.15 Maximum height of Operating device mm 1800
3.16 Minimum height of Operating device mm 200
3.17 Bus bar material Tinned Copper
3.18 Incomer Connection Cables
3.19 Cable / Bus Duct Entry Bottom
3.20 Control Transformer One at each bus
Resp. Dept. Prepared by

Doc No: PTC-BFA-D-008, Rev. 0 Date Approved by


Title: LV Switchgear - Technical Data Sheet 21.06.2017

LOW VOLTAGE SWITCHGEAR - TECHNICAL DATA SHEET - MCC

Sl. No Description Unit Requirement Data Vendor Confirmation

230V AC for >15KW


3.21 Control Supply Voltage
& 24V DC <=15KW
3.22 Name plate Required
3.23 Caution Plate Required
Resp. Dept. Prepared by

Doc No: PTC-BFA-D-008, Rev. 0 Date Approved by


Title: LV Switchgear - Technical Data Sheet 21.06.2017

LOW VOLTAGE SWITCHGEAR - TECHNICAL DATA SHEET - MCC

Sl. No Description Unit Requirement Data Vendor Confirmation

3.24 Neoprene Gaskets for Door Required


3.25 Lifting Hooks Required
3.26 Base Channel for mounting Required
3.27 Space Heater, Thermostat & Illumination Required