Você está na página 1de 7

Lampu Tingkat

Luas Titik Lux Rata


Ruang Jam Penerangan Watt W/M² Keterangan
(m²) Jenis Jumlah Penerangan -Rata
Nyala (Lux)
1 68.9
2 102.7
Lobby
110 Pijar 20 W 14 12 3 83 69.12 280 2.54 Standar
Utama
4 69
5 22
1 550
2 458
Lobby ULT 83 Pijar 20 W 16 12 3 284 407 320 3.85 Boros
4 265
5 478
1 86
WC 6 Pijar 20 W 5 12 48.79 100 16.67 Boros
2 11.58
1 315.4
Subbag. TU 15 TL 36 W 13 12 2 243 237.47 468 31.2 Boros
3 154
1 81.1
Pijar 20 W 80
2 72.1
Ruang Arsip 15 4 12 78 14.93 Standar
3 91.7
TL 36 W 144
4 67.1
1 111
2 116
Q 104
35 TL 36 W 18 12 3 178.8 168.96 648 18.51 Boros
(Keuangan)
4 235
5 204
1 90.2
Q 110 10 TL 36 W 3 12 119.6 108 10.8 Standar
2 149
1 114.7
2 240
TL 36 W 7 12 138.25 252
Q 112 20 3 154.1 14.6 Standar
4 44.2
Pijar 20 W 2 12 5 123.5 123.5 40
1 258
2 241
3 260
Q 102 30 TL 36 W 16 12 236 576 19.2 Boros
4 201
5 215
6 241
1 151
2 250
3 164.6
Q 101 30 TL 36 W 29 12 166.3 1044 34.8 Boros
4 215
5 157.5
6 104.6
7 121.4
1 228
Q 114 30 TL 36 W 7 12 248 254 8.47 Standar
2 268
R. 1 171
Internasional 30 TL 36 W 8 12 159.65 288 9.6 Standar
Office 2 148.3
1 7.9
Lorong Kiri 24 Pijar 20 W 3 12 2 10.79 10.23 60 2.5 Standar
3 12
1 14.4
Lorong
24 Pijar 20 W 3 12 2 15.7 37.5 60 2.5 Standar
Kanan
3 82.4
1 329
ULT
48 TL 36 W 10 12 2 345 333 360 7.5 Standar
Akademik
3 325
ULT Pijar 20 W 7 1 444 140
48 12 325.5 3.67 Standar
Keuangan TL 36 W 1 2 207 36
 Lantai 1

Lampu Tingkat
Luas Titik Lux Rata
Ruang Jam Penerangan Watt W/M² Keterangan
(m²) Jenis Jumlah Penerangan -Rata
Nyala (Lux)
1 1495
Q216 TL 36 W 3 12 2 206 682 108 Boros
3 345
1 2300
Q217 TL 36 W 3 12 2 232 879.7 108 Boros
3 105.2
1 220
Q201 bag. 1 TL 36 W 27 12 2 198.3 182.17 972.0 Boros
3 128.2
1 709
Q201 bag. 2 TL 36 W 12 12 462 432 Boros
2 215
1 236
Q201 bag. 3 TL 36 W 4 12 2 272 186.73 144.0 Standar
3 52.2
Ruang
TL 36 W 2 12 1 185 185 72 Standar
Pusrenbang
1 623
2 217
Ruang Rapat TL 36 W 12 12 329.25 432 Standar
3 244
4 233
1 212
Ruang Senat 2 112.7
TL 36 W 8 12 654.175 288 Boros
Q203 3 441
4 1851
Pudir I (staff 1 210
TL 36 W 18 12 217.5 648 Standar
pudir) bag. 1 2 225
1 114.5
2 2520
Pudir I (staff
TL 36 W 16 12 3 530 752.7 576 Boros
pudir) bag. 2
4 430
5 169
1 316
2 292
Pudir III TL 36 W 18 12 3 72.2 186.66 648 Standar
4 110.3
5 142.8
1 173.5
2 166
Pudir II TL 36 W 15 12 197.95 540 Standar
3 120.3
4 332
1 276.3
Ruang Rapat
TL 36 W 10 12 2 140.2 208.17 360 Standar
Ekskutif
3 208
1 283
Ruang
TL 36 W 3 12 2 170.3 540 108 Boros
Direktur
3 1167
1 72.8
Pudir IV TL 36 W 6 12 2 70.1 363 216 Boros
3 947
 Lantai 2

Lampu Tingkat
Luas Titik Lux Rata
Ruang Jam Penerangan Watt W/M² Keterangan
(m²) Jenis Jumlah Penerangan -Rata
Nyala (Lux)
1 267
Ruang Kelas TL 36 W 4 12 2 168 261 144 Standar
3 348
1 100.6
Q308 TL 36 W 2 12 2 316 219.53 72 Standar
3 242
1 145.8
Q309 TL 36 W 2 12 2 159.4 136.13 72 Standar
3 103.2
1 274
Q310 TL 36 W 2 12 2 103.9 277.63 72 Standar
3 455
1 190.1
Q311 TL 36 W 2 12 2 241 313.03 72 Standar
3 508
1 352
Q312 TL 36 W 11 12 353.5 396 Boros
2 355
1 187.3
Q313 TL 36 W 2 12 2 108.8 142.1 72 Standar
3 130.2
1 476
Q314 TL 36 W 5 12 2 257 319.33 180 Standar
3 225
 Lantai 3
Data Perhitungan
 Gedung Direktorat (Q)
Lantai 1

Ruang Q101 h = jam nyala x lama pemakaian (per bulan)


KW1TL = 36 x 29 = 1.04 KW = 12 x 20 = 240
KW2TL = 16 x 29 = 0.46 KW TDL = Rp. 1500/bulan

Energy Saving = (KW1 - KW2) h


= (1.04 – 0.46) 240
= 81.2 KWh

investasi 29 x 47,000
Cost Saving = Energy Saving x Harga TDL SPP = cost saving = = 0.93 tahun
121,800
= 81.2 x Rp 1500/bulan
= Rp 121,800

Ruang Subbag TU
KW1TL = 36 x 13 = 0.46 KW
KW2TL = 16 x 13 = 0.20 KW

Energy Saving = (KW1 - KW2) h


= (0.46 – 0.20) 240
= 62.4 KWh

investasi 13 x 47,000
Cost Saving = Energy Saving x Harga TDL SPP = cost saving = = 0.54 tahun
93,600
= 62.4 x Rp 1500/bulan
= Rp 93,600

Lantai 2

Ruang Pudir III


KW1TL = 36 x 18 = 0.65 KW
KW2TL = 16 x 18 = 0.28 KW

Energy Saving = (KW1 - KW2) h


= (0.65 – 0.28) 240
= 88.8 KWh

investasi 18 x 47,000
Cost Saving = Energy Saving x Harga TDL SPP = cost saving = = 0.53 tahun
133,200
= 88.8 x Rp 1500/bulan
= Rp 133,200
Ruang Pudir II
KW1TL = 36 x 15 = 0.54 KW
KW2TL = 16 x 15 = 0.24 KW

Energy Saving = (KW1 - KW2) h


= (0.54 – 0.24) 240
= 72 KWh

investasi 15 x 47,000
Cost Saving = Energy Saving x Harga TDL SPP = cost saving = = 0.54 tahun
108,000
= 72 x Rp 1500/bulan
= Rp 108.000

Lantai 3

Ruang Q312
KW1TL = 36 x 11 = 0.39 KW
KW2TL = 16 x 11 = 0.17 KW

Energy Saving = (KW1 - KW2) h


= (0.39 – 0.17) 240
= 52.8 KWh

investasi 13 x 47,000
Cost Saving = Energy Saving x Harga TDL SPP = cost saving = = 0.64 tahun
79,200
= 52.8 x Rp 1500/bulan
= Rp 79,200

ANALISIS:

1. Beberapa ruangan terdapat lampu yang rusak sehingga menurunkan nilai intensitas cahaya pada
beberapa titik yang telah kami tentukan.
2. Untuk gedung Akuntansi kami menemukan beberapa ruangan yang memiliki nilai intensitas
cahaya yang berlebihan (intensitas cahaya > 350 lux), yaitu ruang lobby ULT, Q216, Q217,
Q201 bagian 2, Q203, Pudur I bagian 2, Pudir IV, Ruang Direktur, Q312
3. Ada beberapa ruangan juga yang memiliki lumen tak sebanding dengan jumlah lampu yang
terpasang dan hasil ini dari pengambilan beberapa titik di satu ruangan, seperti Q101, Subbag
TU, Pudir III, dan Pudir II
BAB V
Kesimpulan dan Rekomendasi

Kesimpulan Tata Cahaya


Dari data yang didapat bisa disimpulkan bahwa:
1. Banyak lampu yang rusak menyebabkan penurunan intensitas cahaya.
2. Terjadi beberapa pemborosan pada Gedung Direktorat.
3. Pencahayaan dapat terbantu dengan kondisi cuaca sekitar.
4. Pada gedung direktorat ada beberapa titik yang lumen nya rendah, hal ini dikarenakan tempat yang tertutup
dari cahaya luar dan tingginya atap gedung.

Rekomendasi Sistem Pencahayaan:

1. Untuk gedung direktorat perlu mengurangi jumlah lampu pada beberapa ruangan yang terdapat jendela dan
sinar matahari bisa masuk ke dalam ruangan.
2. Sebaiknya tirai yang terdapat pada jendela dibuka yang sinar mataharinya bisa masuk ke dalam ruangan.
3. Untuk menghemat energy, matikan lampu pada titik yang terkena kontak sinar matahari agar membantu
pencahayaan didalam ruangan.
4. Pada beberapa ruangan perlu mengganti lampu TL dengan lampu TL LED 16 watt untuk menghemat biaya
konsumsi listrik dengan pertimbangan jumlah lumen pada lampu TL sama dengan jumlah lumen pada lampu
LED.

Você também pode gostar