Escolar Documentos
Profissional Documentos
Cultura Documentos
Standards compared:
GERMANY:
Verband Deutscher Elektrotechniker (VD E)
a) Regeln für die Bewertung und Prüfung
von elektrischen Maschinen. R. E. M. 1923
b) Regeln für die Bewertung und Prüfung
von Transformatoren. R. E. T. 1923
ERITAIN:
I. British Engineering Standards Committee.
(B.E.S.A.):
a) Standardization Rules for Electrical Ma-
chinery No. 72-1917.
b) British Standard Specification for the
Electrical Performance of Industrial Motors
and Generators with Class A lnsulation.
No. 168 - 1923 .
2 . British Electrical andAllied Manufactures
Association, (B. E. A.. M.A.):
Standardization Rules for Electrical Ma-
chinery. Fourth Edition 1920. Provisionally
adopted.
U.S.A.
Standards of the American Institute of Elec-
trical Engineers (A.IEE) Iq22 Revision
(Exduding Railway- and Tramway Motors
and non-stationary Ra ilway Transformers.)
British delegates was agreed to for submission to the National Comrn it-
tees to the effect that overload ratings within the I.E.C. maximum
continuous rating be recognised and that, for general lndustrial machines
(the class to be defined later) · where overloads have to be provided, the
overload only to be applied under such conditions of air temperature
as will not cause the limits of maximum temperature Iaid down by
the I.E.C. to be exceeded, viz. 50° C for Class A Insulation measured
by thermometer at a maximum ambient air temperature of 40° C.
This means clearly that the overload can onIy be applied at ambient
air temperatures below 40 C.°
As far as Britain is concerned Report No. I68-I9z3 ot the B. E. S . A.
contains the Standard specificaiion tor Indusirial Motors and Generators
i, e. Machines {rom I B.H-P. or kY A uptaards with Class A Insulation
wound ior voltages not exceeding 7000 Volts hauing both Continuous- and
Short-Time Ratings. - This report came to hand onIy Iate but it was
possible to include the principal requiremenis tohich are marked thus: ><
In this connection it is important to note that the American dele-
gates have declared that they object to the Geneva proposals. Under
these circumstances an international agreement on this important
question does not .app ear to be within easy reach.
In the various countries quite a number of revisions appeared
necessary which had to take into consideration not onIy the enormous
strides made by the different branches of Electrical Engineering, but
also the experience gained in the application of the rules .
The study of the Iatest editions of the Standards of the three
countries mentioned above, (the indusion of other countries would not
have been conducive to lucidity), shows that the views adopted on the
principal points are related closely enough to allow a proper comparison
to be made.
The purpose of this booklet is to enable the engineer or mercbant
buying from or selling to foreign countries, to inform bimself quickly
on any of tbe principal points telling in the design and performance
of electrical machinery wbich he may be called upon to judge.
It is hoped, however, that it will also be of some use to the
student and even to the consulting engineer in framing specifications.
For manufacturers and in cases of disputes, where legal decisions
are involved, it will always be necessary to fall back on the original
wording of the rules published by the bodies mentioned on the
frontispiece; even in cases like this, the collation with tbe practice
adopted in another country may afford guidance for the settlement
of disputed points, on which the rules of tbe respective country migbt
not prove precise enough.
Charlottenburg-Westend I9 23 · F. N.
Contents.
Seetion I.
Rotating Machines, exc1uding Railway- and Tramway-Motors.
page
Standard pressures and Frequencies 7
Rating-Classification • • . • • . • • 8
Heating • . • • . • . • . • •• . 9
a) Standard- and max. permissible Temperatures of cooling media , 9
b) Determination of End Temperatures and Temperature Rises, Heating
Test • . • • • • • . . . . • • • . . • • . • • • • . • • . 9
c) Method of measurement of Temperature of the cooling media 10
d) Method of measurement of Temperature Rises 10
e) Correction of Temperature Rises for Altitude II
f) Permissible Temperature Rises . • . . 12
Inherent Regulation 25
Overspeed Test 26
Tolerances 27
Appendix to Section I.
British Electrical and Allied Manufacturers' Association Rutes (B. E.A.M.A.-
Rutes). • • . • . • • . • . • • • • • • . • . • • • • . • • • • • • 28
Section 11.
Transformers.
Rating-Classification • . • • . • . . . . • • • . . . . • • . • • • • • 31
Heating. • . • • . • . . . . . . . . . . • • • • . . . . • . . • 33
a) Standard and max, permissible Temperatures of cooling media 33
b) Determination of End-Temperatures and Temperature Rises • 33
c) Methods of measurement of Temperature of cooling media 34
d) Methods of measurement of Temperature Rises 35
e) Correction of Temperature Rises for Altitude • 35
f) Permissible Temperature Rises • . . • . • • • 36
6 Contents,
page
High-Pressure Test and Insulation Resistance 38
I. High-Pressure Test 38
2. Surge Test (Germany only) .•••. 40
3. Winding Test and Insulating Resistance Test 40
Working in parallel (Germany only) 40
Overloads • . . • • . • • . • 40
Efficiency, Transformer Losses 41
1. General ' 41
2. Classification of Losses and their measurement 41
Inherent Regulation 41
Tolerances 41
Appendix to Section H.
British Electrical and Allied Manufacturers' Association Rules (B.E.A.M.A.-
Rules) • . . . . • . . . . • • . . • . • • • . • • • • • • • . 42
SECTION I.
Rotating Machines.
Standard pressures and Frequencies and Classification
of Rating.
Germany Britain
U. S. A.
Generators_I Motors
5° 50 I 60 (usual)
8 Seetion I.
Rating- Classification.
Germany Britain U. S. A.
Heating.
Continuation: Heating.
G crmany Britnin U. S. A.
Continuation: Heating.
d) Methods of measurement of Temperature rises.
Class 1I: 4
7::1ass A J as line 1 Bl 55 Class A i
~CI)
.~
_01
_ 1- ~
same as ö'
as Item 1 -11 85 150 - 5 I~
==i====1 ......
same asGermany ; ... III C'
~ I cotton} imprag- Germany as line 2 90 so CI) III
silk nate~ . class II also when I' ~b/l --:r5~
,- t-i
4 (not 0,1· as Item 2
t Idass II alse I~ ~o il- i m m ers ed ~e
pap er immer.s.)1
--;-I~ 6 "2 .,
oil-immers.." as line 3 55 cJ~
95 , 55
I ::l . ' (=
, =~===!::===F== -e
b/l._
Class III: All windings not tot. enclosed ) 40 ( I .9 !t
III
cotton 60 tot. enclosed ) 50( "0
in com-' except 95 , e CI)
I
5 silk
pound Items 9& 10 ~.::
.l:l::l
pap er I ... <J
=;=,= = = = =1 ....!:l
III <J
_LI ~ Class A .l:l 0
6 i Class IV: I as Item 5 i 95 60 8 III
i ......
o ... 9 I'0
IEnamelled wire 2 Enamelled wire : o
1Il.l:l 95 55
I 9
= =1== ===== ' b/llll
I .9 "0
I Class V: . 10 Class B I as line I I~I~ "Oe
Mica, Asbestos pre- 1 I Class B Cl 01
i parates if bind ing as Item 5 115 80 11 MiCa,AS?e~' as line 2 I IIO 1 70 _ sameasGermany
110/ 70
Imatter may be de - tos andsimi- 1 _ ~
stroyed wirheut im- lar material as line 3 115 75 2 I class V
pairing the insulat . 12 115 I 75
Class VI: Resteieted Class C, ire I no limits
by inOu- Class C no limits
I Raw Mica, I ence on 13
, proof and _ yet spe- yet spe-
8 Porcelain, fire as Item 5 refractory cified - , sameasGermany
adjacent cified
proof materials parts only material I class VI IE T IT R
I
Single-Iayer P a rt of machine Insular ion
field coils 100
- (ClassO)
9 Classes I-VI 65 single-Iayer field Class B
with expo-
coils (on stator and Class A
sed surfaces - I rotor) with expo -
(8S) (4S)
14 ins ula ted 100160 2 se d surfaces *) 100 60 120 80
10 Classes 1- VI Continu- bjgh~r
tha n - Sho rt Restrio ted Olh er Rotor Held (80)
ously short Items 1- 7 I circuited by inftu- 2 winding s
circuited ence on
95 (t~)EI 75
as 15 uninsulated winding s
windings adjaccnt
11 1 uninsulated It em 8 I
I I parts only Rotor wi nding s ~
I(7S) (~~ I ~I~
lron eore l ron eore -
wlthout witbout ) as lin e in siots (80) (40)
12 16 I - 2 115 75
- embedded as Item 8 embedded 15 ( 95 55
w ln dl ngs wl ndl ngs Short eire. wmd- (8S) (4S)
rron eore Iron eores I as lines I ings insulated on 120 80
w lth as Items with stat. and rotat. 100 60
13 - 17 I - cmbedded I-I2
embedded 1- 7 eo res and uninsul.
I windi~ windlngs ) 6a ( I shorteire windings as Britai n line 15
- ::0
o
Commu- ~ I Comm u- Comm utator s, co!- ET TR I
95 60
ta~or. and I I
18 I i - I t at ors a nd
I
0 50 I lector rings, bare E
sliprings slipr ings 9 1>45 ( met allic surfaces 115 75 ~.
1
L - I
I I! P la cing of I Insuiation Placing of I In sulation . a::
Bearings _
- I 'g I temperature
~ Class A I Class B te mpera tur e so
(Class 0) Class B (')
~ I t>"
~I i I ::. detector E T I TRI E T I T R detector Class A
6'
16 -
II
All other Ia s It em 8 II Between 2 I 5 ° C more than
-I Wlndmgs witb 2
coll-stdes per slot.
ET TR IET TR (l)
!"
par t s 19 3 coil-sides in De t, between top-
1 one siot lInes 4-6 IUnes 10 -12 3 and bortom coll- (8S) (4S)
sides and bct.ween I120 80
a pprox, 100 60
20 II 3 Between eOIl'/
slde and core cotl-sides and eore
below same as line s
5000 Volts 4- 6 I 10--12 For wmdlngs with (80) (40)1 115 1 75
I
No tempera ture detectors specifi ed. 0
I coll-side per slot 95 55
C more eacb and s be- minus 1 0 for everF;
Same as / 1 1000 II Voltsforover 3 tweendetector
cotl-slde and 1000 Volts by wbie
2I 3
lIne 2 0 but 0"' 5000 Volts than lInes core and coil-slde th e terminal pressure
I
5 000 Volts 4-6 I 10--12 and wedge exceeds 5000 Volts
Note. Method of measurement : *) Motors and g enerators euer sooo V *) W he n th ermometers are applied direct
11/~O C less for each 1000 V or part there- to bare wi nding surface the Temp. Rise
Items 1-9. Method I. Check ed by 2
of by wh ich the rated pressure exceeds shall b e 10°C h ig her than g iven by method I.
n 10-16. 2. -
" 5000 V . **) For enclosed machines the Temp. Rise
Data marked thus } ( r efer (also) to shall be taken 50 C higher than the values
industrial machines from I B. H. P . kW for aIl windings except short circuited in- .;;
or kVA upw ards, see Preface. sulated win ding s.
I. High-Pressure Tests. z
Germany Britain D.S.A.
I I. High-Pressure Test I. High-Pressure Test I . Test of Dielectric Strength
Kature 2. Surge-Test for wind ings 2. Insulation Resistance* 2. Insulation Resistance
of Tests over 2500 V. Data marked thus ) ( refer (also) to
i 3· Test on Turns * . industrial machines; see Preface.
-- . .- - .
I. High-Pressure Test I. High-Pressure Test I. Test 01 Dielearie Strength
Wave form . sinusoidal sinusoidal sinusoidal
.- - - ---- - _ ._ - . --~ - - - - -- - -
-
in general any between 25 not less than rated frequency ;
Frequenc)' rated, or 50 cyclcs p. sec. rated I and 100 per sec . 60 cycles per sec. recommended
Duration one minute one minute one minute
-- - C/l
Temperature ~
working Temperature working Temperature working Temperature ~
during Test
ö'
l:l
Rated Output Test pressure Test pressure Rated Output Test pressure
I I ~
a Rated Part of I Rated Winding Normal circuit I
min./lllI.
Cl> Winding
terminal min. Machine I Output voltage E Volts Volts
....... Volts Volts mia.{mlI.
pressure E Volts i Volts . Sm.1I machinos leu than 25 V. I SOO
-- -- .. .. I -
Output I
below I Small .1660Watts or
2E a11 ; Generators 0,5 H.P. vol-
a - I smaller than 3E 74 6 Watts E - 900 -
Cl> +Soo Maebines I':' and Motors tage under
I
SOO Watts I
or I H.P. SOO
und er 27SV. to 2SV.
- 8"' -- I
.~ Output larger of 746 Watts ) 2 E )2000{ all Maehines except
2E all as otherwise speeified 2E
b ...
Po
than sooW. 3E or I H.P. +1000 aboveP -
ll) +1000 Maehines 3 H. • (see below) +1000
u EuptosoooV . and over {
- H
>(01ll"
Cl>
below A.C . ma.! more than
~ 1,5 E I - ehines con- 300 Volts
.5 aU Maehi· 746 Watts +37S 2,73 E' + 1000
nected to
't:l E over 2E nes in ser- E' voltage
c c: - permanently grounded
sooo V. +5 000 vice (i. e. of eireuit to
'i single phase systems.
not new) of and over ground
I 746 Watts +75 0
I'SE I~ (Not 3·phase with neutral
-'öi grounded)
- -- - !
mau.
with Exciter Separ a tely excited 150 0
0 circuit always rotaring Iield windings lOE ) 2000 ( Field win- min .
closed with or : zE max, dings of 1500
d .c E ) Exeiter volts not over 750 < - loE
"CJ 35 0 0 A.C. Gene- max,
without start- 3 +1000
I»
= ing from A. C. Exciter same as field rators i 3500
CIl windings
side
'C - - - --
0:
= with Exeiter min,
41
'" starting 41 for starting min .
winding sec- I for 1500 c:
2" tionalized IOE zooo iwith A.C. with IOE )20oo( :a", with A.C. with
10 E 1500
c 41
without orwith +1000
:aCJ=
fields closed- CJ
·
Cl "41
r field shorts max.
0: I
max.
">
starting from :s eircuited 3500 circuited 3500
='
° ""
uB A.C. side CIl CIl CIl
:St>
0 ._- ..- -- -- - - -- - - - - -- _._-- --- :3 =
°:3 " 41
o 0
t:s with discon- =1:: EU for startlag
o 41
So :3'" neetable ex- for starting ""Cl withA.C. with
0
" >
.cc: .ce:
t:l:: e: eiter circuit 10E CJ 0 with A.C. with l;lCl
fields open 000
zooo break-up 5000 - circuited and 5 -
witbout start- +1000 ~u I»CIl
'0 ing trom A. C. CIlI» switch CIl"
0 sectionalized ~
CIl ........ 0
bIl .... oS" o 0 while starting
side 0 ... ~
-~ 0
_ ._._-- -- --, -- "':s e,
c
:a= ~t:l:: for starting IJQ
.9 M
for starting 5000
~blI
.~
.~
= 'Co 8000 'C = .~
withA.C.witb 5000 8000
with A.C. for for e:'C Iields open for for ~
... c: . ~ :3 III
Exciter
as Item f but 20E without Exciter Exciler
g ....41 witb starting 2000 'i Volts ~ti circuited and Exciler n
break-up Volts Volts Volts I:T
'ü 'C r:: .~ eonneeted lus than from 275
from A.C.side +1000 'C less than 250,>275( S'
V switch and 250 alld V a11 in series 275 to 750 Cl>
~ " !"
t.t: fields open ) 275 < above
t.t: while starting
non-reverslng 2E 2 E+ 1000
Jlote. E represenls: Wound Phase-wcuad ordinary
I
1. Tbe rated terminal pressure of the machine, accordinl 10 + 500 Rotors of In- _. _ - I
Rotors of outpul as above )or 2E
with field WilldiDIS the rated exciter pressure, + 10 0 0 < ~uct:n Motors reversing 4E+ 1000
2. }'or differellt direct connected Willdillgs of one Induction I 1
or more maehines the highest possible pressure alainsl Motors reversing ~I-=-- Standard machines produced
the frame whell Olle pole is Ifounded. + 1000 ( in large quantities 2500 V. 20010 higher
3. For pbase-wound Rotor WilldilllS of asyn- Note. E represeats: or le.. than above
chronous motor.; noa-reeerslng : the rotor pressure, a) Tbc test pressure shall be based ou the
revcrsiDI : 1,5 times rotor pressure, rated pre..ure or the highesl pressure reached 15 0/0 lower than
4. For macbines with one rotor pole, permanently between any part of the windini and Ihe frame, Assembled apparatus tested
as electrical unlt lewest ind ividual
Irounded 1.1 times raled pressure. which ever is greater, test pressure
Short circuited wiadings need not be tested, b) For a machine driven by water·wheel aad
_. exposed 10 runaway conditions or for a machine Note . E represents :
0) SequCDco of Tests : 1, 2, 3. exposed to possible exccss pressure, pressure limi- Tbc normal voltaie of the circuit to which
ling dev ices should be employed otherwise test as the ma chlne is counected.
nuder a) is necessary. For Rotors of Inductica Molors the normal v.
--- ~. Sequence : ad"v7is-a-'b-'l-e-.- ·befö-re , : induced voltaie.
16 Section I.
The surge test wh ich serves to ensure the efficiency of the insulation
against surges occurring under ordinary working conditions shall be
made with th e completely
assembled machine on the
factory test bed as far as
possible in accordance with
the diagrams of connections
as shown below for Syn-
a chronous- and Asynchronous
rnachines. (G = Generator,
M= Motor.)
The machine on test
shall be connected to cab-
Ies or static condensers (C)
over sphere spark-gaps (F) with solid spheres of at least 50 mm
diameter.
The Test Capacitance of the cables or condensers shall be as folIows:
Capacitance in each
Rated voltage E
phase min, p, F.
kV
(Mikrofarads)
2,5 to 6 °,°5
up to 15 0 ,02
over 15 0,01
Each spark-gap shall be set for 1,1 times rated Voltage. The ma-
chine shall be excited by a d. c. supply to abt. 1,3 times rated voltage
at ratedspeed or with 3-phase a. c. at rated frequency respectively.
The spark-gaps shall be caused to break down in any manner (say by
temporarily reducing or bridging of the gap) and the arcing maintained
for aperiod of 10 secs. During the test the spark-gap shall be placed
in an air current of a velocity of 3 m per sec.
Care shall be taken to make all connections for the purposes of
this test as short as possible.
Polyphase machines may be tested in single phase connection. The
connections shall in this case be changed as often as necessary so that
every phase will be subjected to the surge test,
Rotating Machines. 17
I
a All windings
except Item b
I 1,3 )Megohms Megohms
Rated volts voltage at terminals
= RatedkVAorHP+looo( = rating in kVA+looo
bl Polyphase I
! Windings ! I The formula applies only
! with fixed I i
i Ito dry apparatus not for
i (not dis- ! oil -immersed types.
,
I
I connectable) 1,5
i I
I
connections II
i I Megohms
I between the ,
I
I
i
Rated
vol lage 100 I I
1000 10000
I
100 0,°9 1 0,°5 -
I 1000 O,QI 0 ,5 0 0,°9 1
100000 - 9,1
I 5°
Nett el , Compariscn, 2
18 Section I.
All machines with conti- The machines shall be Continuously rated ma-
nuous rating - must be capable of withstanding chines shall be required
capable of withstanding on test the following Ex- to carry momentaryloads
IS times rated current for cesscurrents or torques in of ISO per cent of the
2 Minuus, following cont. excess of those corre- amperes corresponding
full load run, without dele- sponding to their Brit, to tbe continuous rating
terious effect or resulting Stand. Rating the pr es- keeping the rheostat
lasting deformation. sure b eing maintained for rated load excita-
as near tbe rated value tion,
This test shall be carried
as possible:
out for
Motors & Rotary Converters
a ) Machines jor conü- Motors for conttnuous
at rated pressure ; for Gene-
nuous seruice. seruice shall be requi-
rators the pressure should
red to develop running
be regulated as closely as Excess Am -
peres : ISO percent torque at least I7s o/o of
possible to the rated pres-
that corresponding to
sure, (See Note b elow.) Duration: IS seconds,
the running torque at
Motors shall be required
b) Indudion Motors for their rated load without
to develop tbe follow ing
continuous service, stalling.
max, running torques (or
more) without stalling. Excess torque
without stal-
max. Torque
Rating: (% of rated) ling : I7S per cent Machines with nominal
Continuous (except for abnormally ratlng, See as for Trans-
Short-Time low speed motors or formers. page 32.
Intermittent 20 % high frequencies).
Motors IkW
Generators Sustained Momentary
bIl
BHP or kVA Overload I Overload
.S per 1000 Revs. p. M. Torque or eurrent respeetively
~
~
not totally enelosed
I
Duration % Duration
[totally enclosed] Ofo
below 4 to 1 below 3 ~o I 25 1/2 hour
[-] [-) 5° IMin
U> [5°] [15 sees]
::I
0 4 & upwards 3 & upwards
::I
.9
..... D .C.up to 100 15 sees
d
0 150 H.P. incl. - 25 2 hours
[75] [15 sees]
<J [-] [-]
A.C. a11 100 15 sees
siaes ") - f7S] I [15 sees]
........
0
... a11 sizes
I all sizes -
[-]
-
[-] I[::] I 30 sees
[30 sees]
.l:l
U> I
t) not for motors of abnormally low speeds or high frequeney.
*) for single phase motors overloads are not yet speeified.
Germany
I Britain
I U.S.A.
I test,
20 Section I.
Efficiency *).
r) General
Germany U.S. A.
Recognized Efficiences:
I. Directly measured Efficiency I. Direct1y measured Efficiency
Output Output
= Input' = Input '
2 . Conventional Efficiency (deter - 2 . Conventional Efficiency (derer-
General conditions :
Unless otherwise specified the Unless otherwise specified the
conventional efficiency is to be conventioal efficiency is to be
employed. employed. Efficieney figures shall
Efficiency figur es sha11 corre- eorrespond to rated load , sine
spond to normal working condi- wave form, temperaiure of reterence
tions unless stated otherwise. When °
(at a11 loads) 75 C (tests shall
using method 2 the resistances preferably not be made at an am-
measured by D. C. sha11 be cor- bient temperature of less than
rected to a reierence temperaiure of 150C) . The efficiency of alter-
750 C. For measurement of other nators shall be stated at the rated
losses no temperature correction power faetor . Sine wave shall
shall be made. be standard unless different wave
form is inherent in the operati on
of the system.
Effideney.
r) General
Germany U. S. A.
I =====,======
-= ===·_=~c==============-=,===~I
M iscellaneous losses :
Alllossesdue to auxiliaryapparatus- a) Field-Rheosta: Lasses shall be in-
but these only - of the maehine cluded in the g enerator losses
itself shall be eharged against the where there is a field rheostat
maehine efficieney. Sueh are: in series with the field magnets,
a) Lasses in Regulating-, Series-; Cali- even when the maehine is separa-
braüng-, Shunt- and similar resis- tely excited,
tances , Choking ,0Us, Aux üiary b) V,ntilating Blouur. When a blower
transjormers erc . whieh are neees- is supplied as part of a maehine
sary for the regular working. set, the power required to drive
(Exception see under c.) it shall be eharged against the
b) Ex,iter losses in ease of direet or eomplete unit, but not against the
indireet eoupled exciter j not in maehine alone.
ease of separate ez c ita tion, c) Otner Auxiliary Apparatus sueh as
e) Lasses in booster maehines 0/ Rotary aseparate exciter for a generator
Conuerters, if they form part of the or motor, shall have its losses
eonverter proper but not the losses eharged against the plant of which
of the transformers and ehoking the generator and exciter are
eoils belonging to the eonverter. I apart and not against the
These losses shall be stated se- generator. An exception should
parately. be noted in the ease of Turbo-
d) Lasses in b,arings supplied with the generator sets with direet-eonneeted
maehine but not in bearings sup- ezciters, in whieh ease the losses
plied by another firm. in the ezciter shall be eharged
against the g enerator, The
e) The power eonsumption of the
aetual energy of excitation and
ventilating blower if this is part of
the field-rheostat losses, if any,
the maehine proper. The power
shall be eharged against the
eonsumption in ease of separat,
generator.
ventilating blowlT as also that of
watIT and oilpumps is not to be d) FOT the Booster type 0/ Syn'Monous
ConviTters where the booster forms
eharged against the maehine effi-
an integral part of . the unit its
cieney but shall be stated se-
parately. losses shall be included in the
total eonverter losses.
22 Section I.
References:
Germany (G.)
J U.S.A.
Germany .-,-.,J~-,-.~---"'='-'-=.======-========t
U.S.A.
Overspeed Test.
(Britain none specified.)
Germany U.S.A.
c- o
1,25
1,2
when equipped when equipped
Generators driven by
3 with emergency with emergency
steam turbines
governor acting at governor
10 % overspeed
--
Synchronous and Cascade
4 Converters
1,2 -
Test speed
5 Motors for constant speed no-load speed 1,25
1 ,2
Tolerances.
(U.S.A. none specified.)
Tolerances
Guarantees for:
Germany Britain
11
Output ±o/oof rated
otol,lkW 1O
Speed of Shunt wound ± 50f0of speed at the
1,ItOIlkW 7,5
Motors temp, of fuU load
over 11 kW 5
Appendix to Section I.
British Electrical and Allied Manufactures Association Rules.
Fourth Edition 1920.
I 3
Standard pressures Temperature Test. f) Permissibl«
and Frequencies. Temperotur« Rises,
The temp. test shall
1. Generators: be carried out at
Ventilation
D. C. 1 A. e.
230 44 0
rated output for:
Insu- I
I l»'
.t>""g
~
4 60 550 I. Machineswith con- I a tiIon
'C
I'"
.c;: öi::S
- () =
Ö Ü0
VI
Classification
d) Methods 01 mea-
surement 01 Tempern-
terials.
1-
b~~:J
of Rating: ture rises. Higher values
a) continuous permissible
1. Thermometer
b) short-time Prepa- (not specified)
Method (generally) rates
Heating. 2. Resistancel\lethod
a) Standard and max. Raw,
(for special cases), Mica
permissible Tempera- Por- Higher values
tures 01 Cooling Media: e) Correäion 01 Tem- celain, permissible
Normal 250e (air) perature Rises tor fire
(not specified)
l\Iax. 35 0 e [air), Altitud«. p~~~f I
terials
b) Determination 01 Temp, Rise to be
Bnd-Temperatures and reduced 21 / 2 per cent
Temperature Rises for each 1000 feet.
Rotating Machines.
4 5 6
II
55 !
2250 Volts !
tor field
coils (Res.) i Above I 2 E', B. Ln s u l a t i o n
- _ _-'--...... _.J...__.. _ 2250 Volts 1 -
. - Resistanee Test.
Shunt Note:
~ield wind-'
i I In general the follow-
field mgs of syn-, ing insulation resis-
60 65 70
coils of
D.C.ma- (Res.) (Res.) i (Res.)
chronous i ; tance is sufficient evi-
maehines I
ehines I I intended to
dence that the wind-
I i be started ings are in condition
!r;~s:r~_J ,
of 35 0 C (the permissible Tem- "breakup"
perature rises as above) are to switch,or 0,25
will always _
be reduced by 20010 except for be short cir-
Mica, Asbestos and fire proof cuited at above i
materials. starting 350 Volts :
3° Appendix to Section I (Rotating Machines).
Overloads, Commutation
Tolerances.
Test, Starting.
O
_ _v_e_rl_oa_d_ t_o_rq_u_e
roo %
1-------
Duration
30 Sees
Power Factor 90 to 85
< 85 to 75
< 75 to 65 I
3
4
6
<65 8
Commutation test.
f(tlt load
plus
Efficiency x 4) }
~
01
Continuation : Rating-Classification.
Germany Britain U. S. A.
1 _ _- _
._-====-====-,~---=--==t==-C==-o.-='-'='---·T-~ - --_
I .=- -= -= =-'-=-= = == = = =1
d) Shori- Time Rating. b) Short- Time Ra - b) Short - Time Rating. The T.
The T. shall give tbe ting is the output shall be able to operate at its
rated output for the at wbicb a T . can rated output during a limited
specified period witbout work for a limited period to be specified in eaeh
exceeding tbe limits period (to be spe- ease witbout exeeeding any of
mentioned under a) , eified in eaeh the limitations establisbed.
case) and eomply
with tbese rules,
e) Duty- cycl« Rating. c) Duty eyeie
» c) Duty - Cyele Operation. For
Periods under pressure Rating purposes of rating eitber a con-
of max. 5 Min. are fol- (in special cases) tinuous or a short-time equiva-
lowed by periods during is the continuous lent load may be selected which
wbich tbe T. is switcbed rating whieh is shall simulate as nearly as pos-
off (en tir ely), the dura- the thermal equi- sible tbe thermal conditions of
t ion of wbich is not valent of the cy- the aetual duty-cycle.
s uffic ie nt to enable tbe cle of duty spec i- d) Nominal Rating. (For special
T. to reach the tempe- fied . cases). Tbe nominal rating of a
ratur e of the cooling substation transformer*) carrying
medium. Tbe T . sball traction load shall be the KVA-
give the rated load output at astated power factor
under the same condi- input, which, having produced
tions as mentioned un- a constant temperature in tbe
der c), transformer may be increased
f) Agricultural Rating. 50 % [or 2 hours, without produ-
cing temp, rises exceeding by
100 °/0 overload is ad-
missible for 12 hours more than 5 ° C tbe limiting va-
per day and during lues stated bereafter. These T .s
should be capable of carrying
approx, 500 bours per
IOO % ouerload for one minute witb-
year. The T . sball give
I60 % oi the rated load out disqualifying them for conti-
nuous service.
contiuously w ithout ex-
ceeding the limits men-
e) Rating of Protedtue Reactors,
tioned under a) on P. R. sball be rated by:
I . KV A absorbed by normal cur-
IOO % ouerload as above
rent,
the specified limits for
2 . Normal current , frequency as
temperature and tempe-
lim (delta) voltage. -
rature rise may be ex-
3. Sb ort circuit current which tbe
ceeded by IO ° C.
P. R. is required to stand.
* a1so for Substation macbines.
Transformers. 33
Heating
Nett c I. ComparisoD. 3
34 Se ction II .
Continuation: Heating.
Continuation: Heating.
upto
I 10000 Volts I3,25 E 25 F 00
All I ;---_...L_
1
10O:~01ts 1+,75 EI -15000
I
if measured
up to I cold:
Air cooled 10000Volts 3,74 E 1 28oo
(windings
not if measured
immersed) over cold:
10600 Volts 2,02 EI
+ 17'5 0
primary I
less than 5°00
up to E A. C. single I
I 2000 Volts
3000 Volts Transf. phase ! 2,73 E'
I+82000
for direct primary permanently + 1000
Transformer connection over E' voltage
2000 Volts 10000 grounded 300 Volts
- --~- - ~- - to
Bushings and above (not 3-phase of circuit
consumers with earthed to ground
over + ' - circuit secondary neutral)
3000 Volts
I20000
(L.P.) I 2 E+ 1000
windings
I
same as same as
Auto Trans-j apparatus Auto Trans- apparatus
former
- to wh ich former
- to which
I connected
connected
E represents:
I. The rated terminal pressure when test- Note: Note: >-cl
ing individual windings against core. I I. The test must be based on the highest E represents the normal voltage of
2. For Current and regulating T.s with pressure E to which the windings may the circuit to which the machine is
~
CI>
2.Insulation 2. Insulation
3. Test on Turns. Resistance Test.
Resistance.
Germany U.S.A.
I. General.
Recogniud Efficiencies : Losses only Recognlzed Efficiencies:
mentioned, tberefore Conventional I. Directly measured Effieieney
Etfieieney implieitly reeognized only. Output
Misce/lanlOlls lasses: Tbe power con- = Input
sumption of motors for separate venti- 2. Conventional Efficieney (deter-
lating blowers as also tbat of water- mined Irom Iosses),
or oil-eireulating pumps sball be
stated separately.
General conditions: see page 20 . I General conditions: see page 20.
2. Classification oi Losses and their Measurement.
No-load Losses are eonsidered equi- No-load Losses inc1ude the eore
valent to tbe input at normal rated loss, tbe IliR loss due to tbe exciting
pressure on tbe primary side, at rated current and the dielectric loss in tbe
frequeney and with the seeondary insulation,
terminals disconnected, They in- Th~y shall be measured witb open
c1ude the eore loss, the dieleetric secondary circuit at the rated fre-
1055 and the 19 R loss due to the no- quency, and with an applied primary
load current. The n. 1. 1. are gene- voltage giving the rated secondary
rally measured from secondary side, voltage plus the IR drop wbicb occurs
I in the secondary under rated load
conditions.
Load Losses are considered equi- Load Losses inc1ude PR losses and
valent to the PR losses at rated stray Ioad-losses due to eddy-currents
current and frequency, at working caused by fluxes varying with' tbe
temperature measured within the load,
terminals.
They shall be measured by applying They sball be measured by apply-
the impedance voltage to the T. with ing a primary voltage, at rated Ire-
the secondary windings short cir- quency, sufficient to produce rated
cuited. Stray-load losses due to eddy- load current in tbe with the windings
currents are included in the losses secondary windings short-circuited,
measured as before.
- -- - - - - - - - - - - -- -- _ .. - _._-- - - - -- - - - -- - ---~- - --_ ._ - --
Inherent Regulation
to be measured at the temperature attained under normal operation.
The I. R. of a T. at a specified Brita in U.S .A.
Power Factor is the rise of tbe se-
eondary voltage in per eent of the Same as Germany.
rated seeondary pressure if the load Unless a P. F. is speci-
is altered from rated load to no load fied the regulation is
and with . primary voltage and fre- understood to refer to
queney eonstant. P.F.= I.
- - -_ ._ - -- .._ - -------- - - - - - - - -_ ._- - - - - - - - - - - - - -
Tolerances.
Germany. for losses 10 % of eopper and eore losses.
Britain • • for temp, rise expresslj' none,
'.'--- - - - - - - - - - - - - - - - - - - - - _ ---1
Appendix LO Seetion II (Transformers).
/)ü Grlllldz"It/,n (G~.) ~"ls;r,dl'H tln. "/lA",jii},r", ' ·(lyk,.i('rsfrt;S ~" ""f/,relb", mit ,(tiN jtwn·lti:,,,
1~'lItw,rl""rlfak/or (Umrcclmultgssd.liissd) 1'n''''''lJitlj"d,t de« I ~t'rk(Jufs/Jrt'is . U6t'r den zur Zt'it K,llrnd(1l
C,.,,.,,IIII,,,,g"'''';;IS<I g,bt" alk Bu,""andl.mgm "nt·;' der /",,.1"1: ~,,.tif,,,iII;t:st Austm» ft
Verlag von ]ulius Springer in Berlin W 9
Die Grutld zahlttl (GZ) ttllsprtchttl den 'utlCtflih rt tl V{)rk ritcsp rtilttl un d t rc dJttl ",il d"n jtwdligm
I:"lI fw t rl unCJf ak tor (U", r t d ",u lIcsschliisscl j tltrvit /fa <h t den Vtrkauf sp,-tis . Übt r den zur Z d t gdfm dm
U",rtchn ullc ssd,!üsst l Ct bm al/t Bud ,handlung", sowit der VtrlaC bt rt itwi//ig sl A u!kunfl.