Você está na página 1de 153

SCHEDULE -A

SCHEDULE OF APPOXIMATE QUANTITES TO ACCOMPANY THE TENDER FOR THE


WORK OF “CONSTRUCTION OF BASEMENT FLOOR + GROUND FLOOR + 1st FLOOR
TO 6th FLOOR - HOSPITAL BUILDING OF NO : 175, TAMBARAM - VELACHERY MAIN
ROAD, COMPRISED IN SURVEYNO : 81/1B2, AT GOWRIVAKKAM VILLAGE,TAMBARAM
TALUK,KANCHIPURAM DISTRICT. CHENNAI."

(A) The quantities here given are those upon which the lumpsum tender cost of the work is based.
But they are subject to alternation, omissions, deductions or additions as provided for in the conditions
of this contract and not necessarily shown the actual quantities of work to be done. The unit rates noted
below are those governing payment for extras or deductions or omissions according to the conditions of
the contract as set forth in the preliminary specifications of the detailed standard specifications and
other conditions of the specification of this contract.

(B) It is to be expressly understood that the measured work is to be taken net (Not withstanding)
any custom of practice to the contrary according to the actual quantities where in place and finished
according to the drawings or as may be ordered from time to time by the Executive Engineer and the
cost calculated by measurement or weight at the respective prices, without any additional charges for
the necessary contingent works connected herewith. The rates quoted are for works in site and
complete in every aspects.

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE IN Rs.
S.NO QUALITY DESCRIPTION OF WORK UNIT AMOUNT
TNBP NO. (IN FIGURES AND IN WORDS)

Earthwork excavation for foundation with all leads and lifts in all soils
and sub soils and to the required depth as may be directed except
3
3 hard rock requiring blasting inclusive of shoring, strutting and bailing 1M
1 2650 M
out water wherever earth in layers of 60cm thick well consolidated
depositing the surplus warth in places shown and levelling the site
with all leads and lifts etc., complete all respects.

Filling in basement with filling sand in layers not excedding 60cm 3


3 1M
2 156 M thick well watered rammed and consolidated complying with relevant
standard specification the cost of supplying filling sand.

Refilling in basement with selected excavated warth other than sand


complying with relevant standard specifications including spreading 3
3 1M
3 427 M in layers not exceeding 23cm thick, watering and consolidation by
hand ramming etc., complete as dirested by the departmental
officers.

CONTRACTOR No.OF CORRECTIONS


Page 2

Filling in foundation with filling sand in layers not excedding 50cm 3


3 1M
4 140 M thick well watered rammed and consolidated complying with relevant
standard specification the cost of supplying filling sand.

Refilling in foundation with selected excavated warth other than sand


complying with relevant standard specifications including spreading 3
3 1M
5 140 M in layers not exceeding 50cm thick, watering and consolidation by
hand ramming etc., complete as dirested by the departmental
officers.

Cement concrete in foundation M25 grade concrete,1:1:2 (one part


of cement, one part of sand and 2 part of hard broken stone) using 3
3 1M
6 395 M 40mm size hard broken stone inclusive of shoring strutting, bailing
out water, ramming, curing, etc., complete as directed by the
departmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 3

Supplying, fabricating and placing in position the following kinds of


steel grills for reinforcement for all RCC works and other civil works
1 MT
7 1050 MT etc., including the cost of steel, binding wire and fabrication of
reinforcement grills etc., complete complying with relevant standard
specification.

providing and laying the READY MIX CONCRETE of M25 grade


using Portland Pozzalona cement including the use of plasticizer of
approved make and dosage of required grade, laying in position at
all locations and levels using 20mm size and downgraded ISS HBG
aggregates in all types of works including hire charges for pump and
pumping charges to required location, machine vibrating, pumping, 3
8 1M
curing, providing fixtures like fan clamps etc as specified, charges for
conveyance of RMC from plant to the site or all as required excluding
cost of reinforcement and fabrication charges, centering and
shuttering, mix design details to get approved before
commencement of the officers etc., complete as per IS 4926-
1976/1990.

3 3
a 295 M In basement floor 1M
3 3
b-1 140 M In Ground floor 1M
3 3
b-2 335 M In Bunker Area 1M
3 3
c 143 M In First floor 1M
3 3
d 143 M In Second floor 1M
3 3
e 142 M In Third floor 1M
3 3
f 139 M In Fourth floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 4
3 3
g 135 M In Fifth floor 1M
3 3
h 127 M In Sixth floor 1M
3 3
i 45 M In Terrace floor 1M

Providing form work for centering, shuttering etc., for al reinforced


concrete work such as foundation footings, plinth beam, RCC walls,
Roof beams and slabs, and grade beams etc., including strutting and
shuttering wherever required using MS sheets of suitable size of BG
10, stiffened with MS angle of size 25mm x 25mm x 3mm laid over
silver oak (Country wood) joists of size 10cm x 6.5 cm (Spaced
9
about 91cm center to center) distance and supported by casurina
props of size
10cm-13cm dia (spaced at 75 cm center to center) and removing the
same after a specified period without damaging RCC works in all
floors etc., complete as directed by the departmental officer. (for
column footing, Grade beam / Plinth beam)

2 2
a 398 M In foundation 1M
2 2
b 1822 M In basement floor 1M
2 2
c-1 861 M In Ground floor 1M
2 2
c-2 636 M In Bunker Area 1M
2 2
d 896 M In First floor 1M
2 2
e 896 M In Second floor 1M
2 2
f 896 M In Third floor 1M
2 2
g 896 M In Fourth floor 1M
2 2
h 896 M In Fifth floor 1M
2 2
i 896 M In Sixth floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 5
2 2
j 270 M In Terrace floor 1M
2 2
k 653 M In Ramp & Staircase 1M

Brickwork in all 23cm walls in cement mortar 1:6 (One of cement and
six of sand) using ground moulded II class chamber burnt bricks of
10 size 9" x 4 ½" x 3 for super structure in the following floors including
fixing the frames of doors and windows, scaffolding, proper setting
curing etc, complete in all respects.

3 3
a - M In basement floor 1M
3 3
b 144 M In Ground floor 1M
3 3
c 153 M In First floor 1M
3 3
d 170 M In Second floor 1M
3 3
e 171 M In Third floor 1M
3 3
f 145 M In Fourth floor 1M
3 3
g 165 M In Fifth floor 1M
3 3
h 128 M In Sixth floor 1M
3 3
i 43 M In Terrace floor 1M

Brick Partition wall 12cm thick in cement mortar 1:3 (One of cement
and three of sand) using ground moulded II class chanber burnt
11 bricks of size 9" x 4 3/8 " x 3" Including fixing the frames of doors
and windows, scaffolding and proper setting, curing, finishing etc.,
omplete as directed by the deparmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 6
3 3
a - M In Basement Floor 1M
3 3
b - M In Ground Floor 1M
3 3
c 9 M In First Floor 1M
3 3
d 9 M In Second Floor 1M
3 3
e 13 M In Third Floor 1M
3 3
f 19 M In Fourth Floor 1M
3 3
g 6 M In Fifth Floor 1M
3 3
h 103 M In Sixth Floor 1M

Providing 7.5 cm thick staircase parapet wall using Country bricks of


size 8 3/4" x 4½" X 2" in cement mortar 1:4 (One of cement and four
of sand) and plastering the hand rails portion only with red oxide
3 plastering in cement mortar 1:4 (one of cement and four of sand) 20 3
12 12 M 1M
mm thick using 9.8kg of red oxide powder per 10M2 and plastering
either side of parapet with CM 1:4 (One of cement and four of sand)
20mm thick providing skirting, finishing smooth complete in all
respects in all floors.

Plastering two sides of the Brick Partition wall & RCC wall with CM
1:5 (One of cement and five of sand) 20mm thick including providing 2
13 1M
band cornice, curing, finishing, scaffolding etc., complete as directed
by the departmental officers

2 2
a 873 M In Basement Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 7
2 2
b-1 1179 M In Ground Floor (Masonry wall) 1M
2 2
b-2 641 M In Ground Floor (RCC wall) 1M
2 2
c 1331 M In First Floor 1M
2 2
d 1475 M In Second Floor 1M
2 2
e 1530 M In Third Floor 1M
2 2
f 1357 M In Fourth Floor 1M
2 2
g 1404 M In Fifth Floor 1M
2 2
1938 M In Sixth Floor 1M
2 2
h 297 M In Terrace Floor 1M

White washing walls with two coats using dean shell


lime including the cost of lime, gum, brushes and
14
scaffolding etc., complete in all respects as directed
by the departmental officers in all floors.

2 2
a 873 M In Basement Floor 1M
2 2
b-1 1179 M In Ground Floor (Masonry wall) 1M
2 2
b-2 641 M In Ground Floor (RCC wall) 1M
2 2
c 1331 M In First Floor 1M
2 2
d 1475 M In Second Floor 1M
2 2
e 1530 M In Third Floor 1M
2 2
f 1357 M In Fourth Floor 1M
2 2
g 1404 M In Fifth Floor 1M
2 2
h 1938 M In Sixth Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 8
2 2
i 297 M In Terrace Floor 1M

Special ceiling plastering for all RCC works in


cement mortar 1:3 (One of cement and three of sand)
10mm thick induding hacking the RCC surface, providing
15
necessary water band using the same mix of mortar
wherever necessary proper finishing, curing,
scaffolding etc., complete with relevant standard specification.

2 2
a 391 M In Basement Floor 1M
2 2
b 519 M In Ground Floor 1M
2 2
c 612 M In First Floor 1M
2 2
d 554 M In Second Floor 1M
2 2
e 565 M In Third Floor 1M
2 2
f 572 M In Fourth Floor 1M
2 2
g 569 M In Fifth Floor 1M
2 2
h 527 M In Sixth Floor 1M

Painting the walls with two coats of cement paint of approved quality
over one coat of white cement paint primer induding the cost of
16
cement paint, brushes scaffolding curing etc.
all complete as directed by the departmental officers.

2 2
a 873 M In Basement Floor 1M
2 2
b-1 1179 M In Ground Floor (Masonry wall) 1M
2 2
b-2 641 M In Ground Floor (RCC wall) 1M

CONTRACTOR No.OF CORRECTIONS


Page 9
2 2
c 1331 M In First Floor 1M
2 2
d 1475 M In Second Floor 1M
2 2
e 1530 M In Third Floor 1M
2 2
f 1357 M In Fourth Floor 1M
2 2
g 1404 M In Fifth Floor 1M
2 2
h 1938 M In Sixth Floor 1M
2 2
i 297 M In Terrace Floor 1M

Painting the Doors with two coat of first dass synthetic enamel paint
of approved quality and colour in addition over the existing primer
17
coat including the cost of paint patty brushes and scaffolding etc.
complete as directed by the departmental officers.

2 2
a - M In Basement Floor 1M
2 2
b 25 M In Ground Floor 1M
2 2
c 59 M In First Floor 1M
2 2
d 48 M In Second Floor 1M
2 2
e 73 M In Third Floor 1M
2 2
f 51 M In Fourth Floor 1M
2 2
g 38 M In Fifth Floor 1M
2 2
h 55 M In Sixth Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 10

Providing Ellis Pattern flooring 20mm thick (Ellis pattern) with layer of
cement concrete 1:3 (one of cement and three of hard broken stone)
18 (No sand) using hard blue granite chips of size 3mm to 10mm and
surface rendered smooth over RCC slab including supplying and
fixing 20mm dia GI pipe outlet etc., complete in all respects.

2 2
a 441 M In Basement Floor 1M
2 2
b 519 M In Ground Floor 1M
2 2
c 612 M In First Floor 1M
2 2
d 554 M In Second Floor 1M
2 2
e 565 M In Third Floor 1M
2 2
f 572 M In Fourth Floor 1M
2 2
g 569 M In Fifth Floor 1M
2 2
h 527 M In Sixth Floor 1M
2 2
i 128 M In Sixth Floor 1M

Supplying and dadoing of the walls with first quality


printed design color glazed tiles of size 300mm x 200mm x 600mm
19 of approved quaky laid in cement mortar 1:2 ( one of cement and
two of sand) lOmm thick and pointing with white cement neatly etc
complete in all respects as directed by the departmental officers.

2 2
a 50 M In Basement Floor 1M
2 2
b 529 M In Ground Floor 1M
2 2
c 701 M In First Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 11
2 2
d 774 M In Second Floor 1M
2 2
e 841 M In Third Floor 1M
2 2
f 715 M In Fourth Floor 1M
2 2
g 729 M In Fifth Floor 1M
2 2
h 1051 M In Sixth Floor 1M
2 2
i 138 M In Terrace Floor 1M

Supplying and fixing First quality woods for all doors the of outer
frame 9" width and 2" thickness and the thickness of door panel
should be 2" thick.The edges or outer frame of door panel cover by
½" thick lipping (the wood whick used in frame) and it should not
20 allow leakage of water even at most ranging storms and should have
key lockable action, security protective hinges, strong locking
systems and as per size for arresting noise and energy loss. The
door should be got approved from the Executive Engineer before use
on works.

2 2
a - M In Basement Floor 1M
2 2
b 25 M In Ground Floor 1M
2 2
c 58 M In First Floor 1M
2 2
d 48 M In Second Floor 1M
2 2
e 73 M In Third Floor 1M
2 2
f 51 M In Fourth Floor 1M
2 2
g 38 M In Fifth Floor 1M
2 2
h 55 M In Sixth Floor 1M
2 2
i 5 M In Sixth Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 12

Supplying and fixing UPVC windows of casement type corporation)


from the profile the size of outer frame 60mm x 58mm and shutter
profile are reinforcement with GI/1mm 125GSM and 100 % corrosion
free, the profiles are multi chambered sections with wall thick of
2mm. The EPDM rubber (black colour) covered with overall the
edges of frame and shutter and shutter will be provided with Espag
multi power point locks and also it operates has handle. The corners
and joints should be welded and cleaned. Radiations free pin
21 headed plain or brown color glass 4mm thick should be provided to
the shutter and it should not allow leakage of water even at most
ranging storms and should have key lockable action, security
protective hinges, strong locking systems and as per size for
arresting noise and energy loss. The connecting mechanism
between sash and outer frame that enables opening of the window.
The window should be fixed to the wal with 100 % packing with
screws and silicon packing all round the frames. The window should
be got approved from the Executive Engineer before use on works.

2 2
a - M In Basement Floor 1M
2 2
b 16 M In Ground Floor 1M
2 2
c 54 M In First Floor 1M
2 2
d 65 M In Second Floor 1M
2 2
e 61 M In Third Floor 1M
2 2
f 72 M In Fourth Floor 1M
2 2
g 68 M In Fifth Floor 1M
2 2
h 66 M In Sixth Floor 1M

CONTRACTOR No.OF CORRECTIONS


Page 13
2 2
i 18 M In Sixth Floor 1M

Providing and supplying of 12mm thick toughened glass to all


windows as per the design approved by the Executive Engineer
22 induding cost of material, labour charges, fixing, transporting to the
site fixing etc complete in all respects as directed by the
departmental officers.

2 2
a - M In Basement Floor 1M
2 2
b 2.5 M In Ground Floor 1M
2 2
c 30 M In First Floor 1M
2 2
d 36 M In Second Floor 1M
2 2
e 34 M In Third Floor 1M
2 2
f 41 M In Fourth Floor 1M
2 2
g 37 M In Fifth Floor 1M
2 2
h 38 M In Sixth Floor 1M
2 2
i 5 M In Terrace Floor 1M

Supplying and fixing 12mm thick first quality plywood


for all furnitures like cupboard, tables and partitions
with proper veneer or mica and termite finish.
2 2
23 300 M The design approved by the Executive Engineer 1M
induding cost of material, labour charges, fixing,
transporting to the site fixing etc complete
in all respects as directed by the departmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 14

Providing and fixing of 12mm thick toughened


glass to all interior partitions and skylight as
2 per the design approved by the Executive Engineer 2
24 200 M 1M
induding cost of material, labour charges, fixing,
transporting to the site fixing etc complete in all
respects as directed by the departmental officers.

Supplying and fixing cuddappah slab 20mm thick of various size


2 (both sides polished) for cupboard planks in all pantry area, labour 2
25 10 M 1M
charges for fixing in proper position with necessary bearing packing
with Cement Mortar and finishing etc. complete in all

Manufacturing and supplying of SS Handrails weight


as per the design approved by the Executive Engineer
1 kg
26 7500 Kg induding cost of material, labour charges, welding,
transporting to the site fixing etc complete in all
respects as directed by the departmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 15

Manufacturing and supplying of MS grills


weight as per the design approved by the
Executive Engineer induding cost of material, 1 kg
27 3530 Kg
labour charges, welding, transporting to the site
fixing etc complete in all respects as directed
by the departmental officers.

Weathering course in concrete broken brick


jelly 20mm size in pure slacked lime over RCC
roof slab the proportion being 32:12 1/2
(Thirty two parts of broken brick jelly and twelve
and half of slacked lime) laying to a thickness of 110mm
2 and compacked and wel beaten to 80mm by 2
28 575 M 1M
using wooden hand beater of weight not exceeding
2 kg hand beating sprinkling liberaly with lime water
and a small proportion of solution prepared by
soaking kadukkai dry nut powder and jaggery (velam)
and giving required slope and thickness on roof etc.
completed as directed by the departmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 16

Supplying and fixing in position white / colour glazed


model floor mounted European water closet of best
quality and approved make with 100mm "P° or 'IS" trap
connecting with CI pipe of 100mm dia / PVC pipe of 110mm dia,
double flapped rigid PVC black seat and seat cover with
CP brass hinges including cost of white cement,
cement for packing, spun yam, teak wood plugs,
brass screws, etc., including supplying and fixing 10 litres
capacity PVC / 12.5 litres capacity porcelain low level
flushing tank with a pair of CI brackets, etc.,
complete with all fittings, such as, 15mm brass bal valve
1 No
29 44 Nos with polythene float with brass handle, union coupling
(Each)
connected by means of 40mm white PVC flush hand using Indian
adopter joint including all internal fittings, such as, 15mm brass
connections, 15mm GM wheel valve, 15mm brass nipple (2 Nos),
15mm nylon connection, TW plugs, screws and also giving
necessary connection to the PVC pipe and painting the CI brackets
with 2 coats of approved paint over one coat of red oxide primer,
dismantling the masonry and redoing the dismantling masonry to
original conditions ,etc complete complying with standard
specifications. (The EWC and flushing tank with all accessories
should be got approved by the Executive Engineer before use on
work)

CONTRACTOR No.OF CORRECTIONS


Page 17

RATE IN Rs.
S.NO QUALITY DESCRIPTION OF WORK UNIT AMOUNT
TNBP NO. (IN FIGURES AND IN WORDS)
Providing Pavement and Cement Concrete Road

Filling in foundation and basement with selected


excavated warth other than sand complying with
3
3 relevant standard specifications including spreading 1M
30 516 M
in layers not exceeding 60cm thick, watering and consolidation by
hand ramming etc., complete as dirested by the departmental
officers.

Filling in foundation and basement with


3
3 filling sand in layers not exceeding 60cm thick well watered rammed 1M
31 219 M
and consolidated complying with relevant standard specification
including the cost of supplying filling sand

Providing and fixing of 65mm thick selected


pavement blocks for all outer area, the design approved by the 3
2 1M
32 858 M Executive Engineer induding cost of material, labour charges, fixing,
transporting to the site fixing etc complete in all respects as directed
by the departmental officers.

CONTRACTOR No.OF CORRECTIONS


Page 18

RATE IN Rs.
S.NO QUALITY DESCRIPTION OF WORK UNIT AMOUNT
TNBP NO. (IN FIGURES AND IN WORDS)
Construction of compound wall and gates

Earth work excavation for foundation with all leads


and lifts in all soils and subsoils to the required depth
as may be directed except hard rock requiring
3
3 blasting inclusive of shoring strutting and bailing out 1M
33 228 M
water wherever necessary refilling the sides of foundation with
excavated earth in layers of 15 cm thickness well consolidated
depositing the surplus earth in places shown and leveling the site
with all

Filling in foundation and basement with river sand


3
3 in layers not exceeding 60cm thick well watered rammed and 1M
34 144 M
consolidated complying with relevant standard specification including
the cost of supplying river sand.

Cement concrete 1:4:8 (one of cement, four of sand


and eight of hard broken stone) using 40mm size 3
3 1M
35 80 M hard broken stone inclusive of shoring, strutting, bailing out water,
ramming, curing, etc complete as directed by the departmental
officers

CONTRACTOR No.OF CORRECTIONS


Page 19

Providing form work for centering, shuttering etc., for all reinforced
concrete work such as plinth beam, raft beam, raft slab, grade beam
etc., including strutting and shuttering wherever required using MS
sheets of suitable size of BG 10, stiffened with MS angle of size
25mm x 25mm x 3mm laid over silver oak (Country wood) joists of
2
2 size 10cm x 6.5 cm (Spaced about 91cm center to center) distance 1M
36 196 M
and supported
by casurina props of size 10cm-13cm dia (spaced at
75 cm center to center) and removing the same after a specified
period without damaging RCC works in all floors etc., complete as
directed by the departmental officer. (for column footing, Grade
beam / Plinth beam)

Supplying, fabricating and placing in position the


following kinds of steel grills for reinforcement for all RCC works and
1 MT
37 MT other civil works etc., including the cost of steel, binding wire and
fabrication of reinforcement grills etc., complete complying with
relevant standard specification.

Brickwork in cement mortar 1:5 (One of cement and


five of sand) using ground moulded II class chamber burnt bricks of 3
3 1M
38 60 M size 9" x 4 3/8" x 2 314" in foundation and basement including
dewatering wherever necessary proper setting and curing etc.
complete in all respects.

CONTRACTOR No.OF CORRECTIONS


Page 20

Plastering the walls with cement mortar 1:5,


2
2 (One of cement and five of sand) 12mm thick including providing 1M
39 540 M
band comice curing etc., Complete in all respects as directed by the
departmental officers

Manufacturing and supplying of gate in MS grills as per


the design approved by Executive Engineer including cost of 1 kg
40 911 Kg
materials, labour charges, welding, transporting to the site fixing etc.,
complte in all respects as directed by the departmental officers.

Painting the walls with two coats of cement paint of


2
2 approved quality over one coat of white cement paint primer 1M
41 581 M
including the cost of cement paint, brushes scaffolding curing etc. all
complete as directed by the departmental officers

Painting the new iron work with one coat of first class
synthetic enamel paint of approved quality and colour in addition 2
2 1M
42 34 M over the existing primer coat including the cost of paint patty brushes
and scaffolding etc. complete as directed by the departmental
officers

CONTRACTOR No.OF CORRECTIONS


Page 21

RATE IN Rs.
S.NO QUALITY DESCRIPTION OF WORK UNIT AMOUNT
TNBP NO. (IN FIGURES AND IN WORDS)
Construction of sump, sullage treatment plant (S.T.P) & pumproom

Open earthwork excavation for foundation with all


leads and lifts in all soils and sub soils and to the required depth as
may be directed except hard rock requiring blasting inclusive of
3
3 shoring, strutting and bailing out water wherever necessary 1M
43 628 M
(Excluding refilling the sides of foundation with excavated earth) in
layer of 15cm thick well consolidated depositing the surplus earth in
places shown and levelling the site with all leads and lifts etc.
complete complying with relevant standard specification

Refilling foundation with PCC (plain cement concrete)


3
3 1:5 for refilling in foundation and basement including spreading in 1M
44 44 M
layers not exceeding 15cm thick, watering and consolidation by hand
ramming, etc., complete as directed by the departmental officers

Filling in foundation with river sand in layers not


3
3 exceeding 15cm thick well watered rammed and consolidated 1M
45 44 M
complying with relevant standard specification including the cost of
supplying river sand.

CONTRACTOR No.OF CORRECTIONS


Page 22

Cement concrete 1:4:8 (One of cement, four of sand


and eight of hard broken stone) using 40mm size 3
3 1M
46 488 M broken stone jelly inclusive of shoring, strutting,
bailing out water wherever necessary ramming, curing, etc. complete
as directed by the departmental officers.

Supplying, fabricating and placing in position the following kinds of


steel grills for reinforcement for all RCC works and other civil works
1 MT
47 140 MT etc., including the cost of steel, binding wire and fabrication of
reinforcement grills etc., complete complying with relevant standard
specification.

Providing form work for centering, shuttering etc.,


for all reinforced concrete slab, beams, lintels, loft etc., including
shuttering, upto 3.00m high using MS sheet of size 90cm x 60cm
and BG 10, stiffened with MS angle of size 25mm x 25mm x 3mm
2
2 laid over silver oak (Country wood) joists of size 10cm x 6.5 cm 1M
48 329 M
(Spaced about 91cm center to center) distance and supported by
casurina props of size 10cm-13cm dia (spaced at 75 cm center to
center) and removing the same after a specified period without
damaging RCC works in all floors etc., complete as directed by the
departmental officer. (Slabs, Lintels & Lofts)

CONTRACTOR No.OF CORRECTIONS


Page 23

Providing form work for centering, shuttering etc., for


all walls. including shuttering, upto 3.00m high
using MS sheet of size 90cm x 60cm and BG 10, stiffened with MS
angle of size 25mm x 25mm x 3mm laid over silver oak (Country 2
2 1M
49 330 M wood) joist of size 10 cm x 6.5 cm (spaced about 91cm centre to
centre) distance and supported by casurina props of size 10cm to
13cm dia (spaced at 75cm centre to centre) and removing the same
after a specified period without damaging RCC works in all floors etc
complete as directed by the departmental officer.

Plastering wall with Cement mortar 1:5 (One of


2
2 cement and five of sand) 12mm thick including providing band 1M
50 252 M
cornice, curing, finishing, etc., complete as directed by the
departmental officers

Special ceiling plastering for all RCC works in


cement mortar 1:3 (One of cement and three of sand) 10mm thick
2
2 including hacking the RCC surface, providing necessary water band 1M
51 49 M
using the same mix of mortar wherever necessary proper finishing,
curing, scaffolding etc., complete with relevant standard
specification.

CONTRACTOR No.OF CORRECTIONS


Page 24

Providing Ellis Pattern flooring 20mm thick (Ellis


pattern) with layer of cement concrete 1:3 (one of cement and three
2
2 of hard broken stone) (No sand) using hard blue granite chips of size 1M
52 49 M
3mm to 10mm and surface rendered smooth over RCC slab
including supplying and fixing 20mm dia GI pipe outlet etc., complete
in all respects. (other than GF)

Painting the walls with two coats of cement paint of


2
2 approved quality over one coat of white cement paint primer 1M
53 105 M
including the cost of cement paint, brushes scaffolding curing etc. all
complete as directed by the departmental officers

White washing two coats using clean shell lime


2
2 including the cost of lime, gum, brushes and scaffolding etc., 1M
54 105 M
complete in all respects as directed by the departmental officers in
all floors

CONTRACTOR No.OF CORRECTIONS


Page 1

EQUITAS HOSPITAL AT CHENNAI

BOQ FOR SANITARY FITTINGS, WATER SUPPLY & DRAINAGE WORKS

AMOUNT
SECTION DESCRIPTION
SUPPLY FIXING

A SANITARY FIXTURES AND FITTINGS

B WATER SUPPLY - PIPES AND FITTINGS

C SOIL & WASTE PIPING

D RAIN WATER PIPES AND FITTINGS

E PUMPS & HEATERS

F MISCELLANEOUS

SUB TOTAL

GRAND TOTAL

AMOUNT IN
WORDS:

DATE:

REVISION:

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
1.0 Supply and fixing of vitreous China clay European Water Closet - wall Nos. 52
hung type with extended 'P' / 'S' trap, with matching soft closing solid
plastic seat and lid with C P brass hinges, rubber buffers, C.I / M.S
Brackets, with concealed flush tank, 40 mm diameter flush bend with
fittings and clamps, overflow arrangements with specials and 25 mm
dia mosquito proof coupling of approved design. The cost shall
include extension piece, sealant, painting of fittings and brackets,
cutting and making good the wall and floor wherever required,
including cost of materials, labour including lead and lift charges, all
complete as per specifications.

2.0 Supply and fixing of white colour vitreous China clay European Nos. RO
Water Closet - (Type-1 / Standard or Basic model) wall hung type
with extended 'P' trap,with exposed flush tank with matching colour
soft closing solid plastic seat and lid with C P brass hinges, rubber
buffers, C.I / M.S Brackets, 40 mm diameter flush bend with fittings
and clamps, overflow arrangements with specials and 25 mm dia
mosquito proof coupling of approved design, 15mm dia C.P angle
stop cock with wall flange, 15mm dia cold water connection pipe etc.
The cost shall include extension piece, sealant, painting of fittings
and brackets, cutting and making good the wall and floor wherever
required, including cost of materials, labour including lead and lift
charges, all complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 3

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.0 Supply and fixing of white colour vitreous China clay Indian Water Nos. RO
Closet - premiun type with 'S' trap,with exposed dual flow flush tank
with C.I / M.S Brackets, 40 mm diameter flush bend with fittings and
clamps, overflow arrangements with specials and 25 mm dia
mosquito proof coupling of approved design, 15mm dia C.P angle
stop cock with wall flange, 15mm dia cold water connection pipe etc.
The cost shall include extension piece, sealant, painting of fittings
and brackets, cutting and making good the wall and floor wherever
required, including cost of materials, labour including lead and lift
charges, all complete as per specifications.

4.0 Supply and fixing of white colour vitreous china wash basin, installed Nos. 17
with specially fabricated MS brackets with adjustable screws and nuts
to suit the wash basin, 15mm dia mixer pillar cock provision, 32mm
dia CP waste coupling, 32mm dia CP brass bottle trap, 2 nos of
15mm dia CP angle stop cocks for cold & hot water supply lines with
wall flanges etc,. The work shall include cutting and making good the
wall and floor wherever required, necessary extension piece, sealant,
including cost of materials, labour including lead and lift charges, all
complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 4

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
5.0 Supply and fixing of white vitreous China large flat back lipped Nos. 6
Urinals suitably supported by CI/ MS brackets duly painted including
, CP brass flush pipe, CP brass spreader and automatic sensor
based flushing system (battery operated) along with C P brass waste
with doom type grating and bottle trap etc. The work shall include
cutting and making good the wall and floor wherever required,
including cost of materials, labour including lead and lift charges, all
complete as per specifications.

6.0 Supply and fixing and commissioning of Ceramic Urinal Partition - Nos. 6
Large. The cost shall include cutting and making good the wall
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications

7.0 Supply and fixing of Ceramic lab sink ,15mm dia sink cock with Nos. 1
regular swinging spout for cold water supply lines with flanges,
40mm dia waste coupling, 15mm dia C P angle stop cock for cold
water supply lines with wall flanges.The cost shall include cutting and
making good the wall wherever required, including cost of materials,
labour including lead and lift charges, all complete as per
specifications

CONTRACTOR No.OF CORRECTIONS


Page 5

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
8.0 Supply and fixing of superior quality, white colour, wall mounted Nos. 14
inverted L grab bar (Model: Cera - Crane - 2503) with flanges,
countersunk screws etc. The cost shall include cutting and making
good the wall wherever required, including cost of materials, labour
including lead and lift charges, all complete as per specifications.

9.0 Supply and fixing of vitreous china Under counter fixed wash basin, Nos. 17
installed below granite counter provided by the civil contractor, with
15mm dia mixer pillar cock fitting, 32mm dia C P waste coupling,
32mm dia C P brass bottle trap, two 15mm dia C P angle stop cocks -
one each for hot & cold water supply lines with wall flanges etc,. The
work shall include cutting and making good the wall and floor
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

10.0 Supply and fixing of vitreous china Above counter fixed wash basin, Nos. RO
installed above granite counter provided by the civil contractor, with
15mm dia mixer pillar cock fitting, 32mm dia C P waste coupling,
32mm dia C P brass bottle trap, two 15mm dia C P angle stop cocks -
one each for hot & cold water supply lines with wall flanges etc,. The
work shall include cutting and making good the wall and floor
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 6

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
11.0 Supply and fixing of vitreous china Full Pedestal fixed wash basin, Nos. RO
with 15mm dia mixer pillar cock fitting, 32mm dia C P waste coupling,
32mm dia C P brass bottle trap, two 15mm dia C P angle stop cocks
one each for hot & cold water supply lines with wall flanges etc,. The
work shall include cutting and making good the wall and floor
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

12.0 Supply and fixing of 15mm dia CP pillar cock for wash basins with Nos. 34
pipe nipples, teflon tape, all accessories required etc. The cost shall
include cutting and making good the wall wherever required, including
cost of materials, labour, all complete as per specifications

13.0 Supply and fixing of CP brass body bib cock and CP Hand shower Nos. 52
(Health faucet) of 8mm dia outlet, 1.0 m long Flexible tube and wall
hook and clamp with 15mm CP angle cock with wall flange. The cost
shall include cutting and making good the wall wherever required,
including cost of materials, labour (including lead and lift charges), all
complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 7

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
14.0 Supply and fixing of standard size stainless steel kitchen sink of Nos. 2
overall Size - 915 x 460 mm with bowl size of 470 x 410 x 230 mm
deep with drain board, two numbers of 15mm dia sink cocks, with
sink mixer and spout for cold and hot water supply lines with flanges,
40mm dia waste coupling, 15mm dia C P angle stop cocks for hot
and cold water supply lines with wall flanges.The cost shall include
cutting and making good the wall wherever required, including cost
of materials, labour including lead and lift charges, all complete as
per specifications

15.0 Supply and fixing of standard size stainless steel kitchen sink without Nos. 2
drain board, two numbers of 15mm dia sink cocks, with sink mixer
and spout for cold and hot water supply lines with flanges, 40mm dia
waste coupling, 15mm dia C P angle stop cocks for hot and cold
water supply lines with wall flanges.The cost shall include cutting and
making good the wall wherever required, including cost of materials,
labour including lead and lift charges, all complete as per
specifications

16.0 Supply and fixing of Concealed Wall Diverter assembly consisting of Nos. RO
built-in non return valve for spout and over head shower rose . The
cost shall also include the fixing one number C.P brass spout. The
work shall include cutting and making good the wall and floor
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 8

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
17.0 Supply and fixing of Wall Mixer assembly with bend pipe on upper Nos. 19
side for shower with built-in non return valve for spout and over head
shower rose . The cost shall also include One number C.P brass
spout inbuilt or seperate. The work shall include cutting and making
good the wall and floor wherever required, including cost of materials,
labour including lead and lift charges, all complete as per
specifications.

18.0 Supply and fixing of Wall mounted Rain Shower assembly with a Nos. 19
bend shower arm assembly from the wall. The work shall include
cutting and making good the wall wherever required, including cost of
materials, labour including lead and lift charges, all complete as per
specifications.

19.0 Supply and fixing of Ceiling mounted Rain Shower assembly with Nos. RO
clampings from ceiling. The work shall include cutting and making
good the wall and ceiling wherever required, including cost of
materials, labour including lead and lift charges, all complete as per
specifications.

20.0 Supply and fixing of 15mm dia CP Short body bib cock for Washing Nos. RO
Machine with pipe nipples, teflon tape, all accessories required etc.
The cost shall include cutting and making good the wall wherever
required, including cost of materials, labour, all complete as per
specifications

CONTRACTOR No.OF CORRECTIONS


Page 9

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
21.0 Supply and fixing of 15mm dia CP Short body bib cock with pipe Nos. 5
nipples, teflon tape, all accessories required etc. The cost shall
include cutting and making good the wall wherever required,
including cost of materials, labour, all complete as per specifications

22.0 Supply and fixing of 15mm dia CP Long body bib cock with pipe Nos. 10
nipples, teflon tape, all accessories required etc. The cost shall
include cutting and making good the wall wherever required,
including cost of materials, labour, all complete as per specifications

23.0 Supply and fixing of 15mm dia wall mounting CP long body sink cock Nos. 4
with swivel type spout for sinks with pipe nipples, teflon tape, all
accessories required etc. The cost shall include cutting and making
good the wall wherever required, including cost of materials, labour,
all complete as per specifications

24.0 Supply and fixing of 15mm dia C.P brass angle stop cock with wall Nos. 10
flange and 15mm dia PVC connecting pipe, for Water Dispensors and
geyser. The cost shall include cutting and making good the wall
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

CONTRACTOR No.OF CORRECTIONS


Page 10

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
25.0 Supply and fixing of 20mm dia C.P brass concealed stop cock with Nos. 5
wall flange. The cost shall include cutting and making good the wall
wherever required, including cost of materials, labour including lead
and lift charges, all complete as per specifications.

26.0 Supply and fixing of CP Coat hook with flanges, countersunk screws Nos. 52
etc. The cost shall include cutting and making good the wall
wherever required, including cost of materials, labour, all complete as
per specifications.

27.0 Supply and fixing of CP toilet paper holder flap recessed type Nos. 52
including fixing screws, cutting of required sizes and making good.

28.0 Supply and fixing of CP Soap Dish flap recessed type including fixing Nos. 50
screws, cutting of required sizes and making good.

29.0 Supply and fixing of Auto Soap Dispensor flap recessed type Nos. 34
including fixing screws, cutting of required sizes and making good.

30.0 Supply and fixing of 20mm dia brass lawn hydrant valves with brass Nos. RO
wheels.

CONTRACTOR No.OF CORRECTIONS


Page 11

RATE AMOUNT
A SANITARY FIXTURES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
31.0 Supply and fixing of superior quality plastic Hand towel dispensor Nos. RO
(Model: Kimberly Clark - 4630) The paper dispensor shall be surface
mounted with lockable arrangement and capable of holding
approximately 300 folded tissue papers. The cost shall include any
mounting arrangement needed along with necessary accessories
including cost of materials, labour including lead and lift charges, all
complete as per specifications

32.0 Supply and fixing of C.P superior quality towel ring with flanges, Nos. 17
ountersunk screws etc. The cost shall include cutting and making
good the wall wherever required, including cost of materials, labour
including lead and lift charges, all complete as per specifications.

33.0 Supply and fixing of C.P superior quality towel rail with flanges, Nos. 19
countersunk screws etc. The cost shall include cutting and making
good the wall wherever required, including cost of materials, labour
including lead and lift charges, all complete as per specifications.

TOTAL - SECTION A

CONTRACTOR No.OF CORRECTIONS


Page 12

RATE AMOUNT
B WATER SUPPLY - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supply, fixing, testing and commsisioning of CPVC pipes (SDR 11)
conforming to ASTM D-2846 standard including all CPVC fittings like
tees, elbows, bends, unions, coupling, reducer tees, collars etc. The
work shall include cutting jointing with solvent cement, pressure
testing the joints / pipeline for 10 kg/sq.cm hydraulic pressure, for
2 hours etc. making holes, including chasing in solid block masonry
walls with groove cutting machine to required width and depth,
making bores / core cutting in walls / beams / foundations and RCC
slabs, making good the walls and bores in CC or CM 1:3 as
applicable clearing the debris, wrapping of concealed pipes with
chicken wire mesh, MS hooks / angle supports (all MS angle
supports / frames to be painted with two coats of primer) for fixing
pipes and making good the walls and floors.

Note:
(1) Strictly use SDR-11 grade CPVC pipe and fittings for internal cold
water and hot water supply up to 54 mm dia.
(2) Rate Quoted shall be inclusive of cost of other consumables like
hacksaw blade, solvent for CPVC pipe up to 54 mm dia etc.

1.1 15 mm dia Mtrs. 30


1.2 20 mm dia Mtrs. 575
1.3 25 mm dia Mtrs. 530
1.4 32 mm dia Mtrs. 240
1.5 40 mm dia Mtrs. 135
1.6 50 mm dia Mtrs. 85

CONTRACTOR No.OF CORRECTIONS


Page 13

RATE AMOUNT
B WATER SUPPLY - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
2.0 Supply, fixing, testing and commsisioning of Medium duty
Galvanized Pipes (GI) pipes conforming to IS:1239 standard
including all fittings like tees, elbows, bends, unions, coupling,
reducer tees, collars etc. The work shall include cutting, screwing,
threading and jointing, pressure testing the joints / pipeline for 20
kg/sq.cm hydraulic pressure etc. making holes, including chasing in
solid block masonry walls with groove cutting machine to required
width and depth, making bores / core cutting in walls / beams /
foundations and RCC slabs, making good the walls and bores in CC
or CM 1:3 as applicable clearing the debris, wrapping of concealed
pipes with chicken wire mesh, MS hooks / angle supports (all MS
angle supports / frames to be painted with two coats of primer) for
fixing pipes and making good the walls and floors.

1.1 15 mm dia Mtrs. RO


1.2 20 mm dia Mtrs. RO
1.3 25 mm dia Mtrs. RO
1.4 32 mm dia Mtrs. RO
1.5 40 mm dia Mtrs. RO

3.0 Supply and Fixing of Nitrile rubber tubular insulation (Armaflex or


equivalent) of 9mm thick over exposed hot water supply pipe . The
cost to include providing PVC (4Kg) pipe over the insulation
(according to the size of the pipe) and sealing it with silicon sealant
for all exposed pipes (ring main). All complete as required.

3.1 20mm dia. Mtrs. 85


3.2 25mm dia. Mtrs. 150

CONTRACTOR No.OF CORRECTIONS


Page 14

RATE AMOUNT
B WATER SUPPLY - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.3 32mm dia. Mtrs. 15
3.4 40mm dia. Mtrs. RO

4.0 Supplying, fixing and testing of lever operated gun metal Ball
valves with fittings of screwed end type. The cost shall include cost
of materials, labour including lead and lift charges, all complete as
per specifications
4.1 20 mm dia. Nos. 50
4.2 25mm dia. Nos. 25
4.3 32mm dia. Nos. 15
4.4 40mm dia. Nos. 8

5.0 Supplying, fixing, testing and commissioning of Wafer type C.I. Dual
plate Check valve (Non-return) as per IS:5312 with required
flanges, nuts, GI bolts and gaskets etc. all complete as required of
the following sizes. The cost shall include cost of materials, labour
including lead and lift charges, all complete as per specifications

5.1 32 mm dia Nos 1

6.0 Supplying, fixing and commissioning Brass body "Y" type Strainer
with SS mesh,suitable flanges, nuts, bolts, gaskets etc. all complete
as required. The cost shall include cost of materials, labour
including lead and lift charges, all complete as per specifications

6.1 32 mm dia Nos RO


6.2 40 mm dia Nos 4

CONTRACTOR No.OF CORRECTIONS


Page 15

RATE AMOUNT
B WATER SUPPLY - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
7.0 Supplying, fixing and commissioning of Heavy Duty Mechanical type
gunmetal float valve of approved quality tested to withstand
20kg/Sq.cm.
7.1 32 mm dia Nos RO
7.2 40 mm dia Nos RO

8.0 Providing, fixing, testing and commissioning of cast iron lever


operated slim seal type butterfly valves of CI body and spheroidal
graphite iron disc (SG iron),with nitrile rubber seal, tested to 10 kg /
sq.cm Confrming to BS 5155 / MF6 standards and including a set of
GI flanges as per BS-10 table 1 including bolt nuts, and Neoprene
rubber gaskets etc.complete.
8.1 50 mm dia Nos 8
8.2 65 mm dia Nos 5

9.0 Suppling, fixing, testing and commissioning of water meter with


direct reading dia in KL with all integral parts of gun metal or brass
with neccesary fitting such as threaded pieces, unions, check
nuts,ball valve, y stainer, NRV complete.
9.1 32 mm dia Nos RO

10.0 Supplying, fixing, testing and commissioning of brass body nickel


plated automatic air release valves with brass splindle, NBR, ball
valve and joinfranite elastomer,staniless steel spring
polypropylenic float at the top most points of watersupply
distribution ringmain.
10.1 20 mm dia Nos 4

CONTRACTOR No.OF CORRECTIONS


Page 16

RATE AMOUNT
B WATER SUPPLY - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
11.0 Construction of valve chamber with burnt bricks in CM (1:4) and
plastering including excavation and providing heavy duty C.I cover
with frame as required.
11.1 600 X 600 X 750mm deep for supply Nos 1

12.0 Supply and fixing of Cast Iron, Medium duty OHT cover with
frames of the following sizes.
12.1 450 x 450mm Nos RO
12.2 600 x 600mm Nos 12

TOTAL - SECTION B

CONTRACTOR No.OF CORRECTIONS


Page 17

RATE AMOUNT
C SOIL & WASTE - PIPES & FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supply, fixing, testing and commsisioning uPVC Pressure pipe


(Ring-fit) soil waste vent pipe of Class 3 (6 Kgf/cm2) conforming to
IS 4985-2000 including all fittings (IS 7834 for moulded fittings and
IS 10124 for fabricated fittings), Eg: Bends, tees, elbows collars,
juction, inspection doors, cowls, offset acess pipes, jointing with
PVC solvent, running of pipes suspended from the ceiling with
brackets and fasteners, chasing / chipping walls using groove
cutting machine, making bores / core cutting in slab / beam / wall
and making good of the same, cost shall include providing steel
brackets, MS angle supports, Pipe supports (all MS angle supports /
frames to be painted with two coats of primer) and fasterners. The
cost shall include transportation, lead and lift all complete as
required

1.1 25 mm dia (For AC Drain) Mtrs. 50


1.2 40 mm dia (For wash basin) Mtrs. 90
1.3 50 mm dia (For sink) Mtrs. 20

CONTRACTOR No.OF CORRECTIONS


Page 18

RATE AMOUNT
C SOIL & WASTE - PIPES & FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
2.0 Supply, fixing, testing and commsisioning uPVC SWR (Type B, Ring
fit) soil waste vent pipe conforming to IS 13592-1992 pressure
rated to 6kg/sq.cm including all fittings (IS 14735-1999), Eg: Bends,
tees, elbows collars, juction, inspection doors, cowls, offset acess
pipes, jointing with PVC solvent, running of pipes suspended from
the ceiling with brackets and fasteners, chasing / chipping walls
using groove cutting machine, making bores / core cutting in slab /
beam / wall and making good of the same, cost shall include
providing steel brackets, MS angle supports, Pipe supports (all MS
angle supports / frames to be painted with two coats of primer)
and fasterners. The cost shall include transportation, lead and lift
all complete as required.

2.1 75mm dia Mtrs. 425


2.2 110mm dia Mtrs. 400

3.0 Supply, fixing, testing and commsisioning uPVC Pressure pipe


(Ring-fit) soil waste vent pipe of Class 5 (10 Kgf/cm2) conforming
to IS 4985-2000 including all fittings (IS 7834 for moulded fittings
and IS 10124 for fabricated fittings), for pipes buried below ground,
jointing with PVC solvent, encasing the pipe with 150mm thick 1 : 4
: 8 PCC (in locations as indicated in the drawing ). Pipe shall be
layed on consolidated surface / pedastals with pre determined
slope. The cost shall include transportation, lead and lift all
complete as required. Cost to include for excavation, back filling the
earth and consolidating the same

3.1 110mm dia Mtrs. 105

CONTRACTOR No.OF CORRECTIONS


Page 19

RATE AMOUNT
C SOIL & WASTE - PIPES & FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.2 160mm dia Mtrs. RO

4.0 Supply and fixing PVC ' P ' or ' S ' of multi port, deep seal floor trap Nos. 80
with self cleansing design.The cost shall include cutting and making
good the floor wherever required, including cost of materials,
labour including lead and lift, all complete as per specifications.
(100mm dia inlet and 50 mm / 75mm outlet )

5.0 Supply and fixing C.P hinged trap cover with roach trap (Chilly or
equivalent) of 6mm thick and having perforations with rim
including setting in floor with cement mortar or white cement
5.1 125mm dia. Nos. 70

6.0 Supply and fixing C.P hinged trap cover with roach trap (Chilly or
equivalent) of 6mm thick and without perforations with rim
including setting in floor with cement mortar or white cement
6.1 125mm dia. Nos. 10

7.0 Supply and fixing of floor clean out provision for accessing / Nos 10
cleaning the waste pipes with suitable cover plate at floor level
inclusive of all accessories as required

CONTRACTOR No.OF CORRECTIONS


Page 20

RATE AMOUNT
C SOIL & WASTE - PIPES & FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
8.0 Excavating trenches of required depth for UG Drain pipes, Cum 50
manholes, inspection chambers, gully traps etc.,in all kinds of
soil/including excavation for sockets and dressing of sides ramming
of bottoms and taking out the excavated soil and then back filling
the trench as required in layers not exceeding 20cm in depth
including consolidating each deposited layer by ramming watering
etc., as directed

9.0 Providing and fixing square mouth SW gully trap 100mm dia grade '
A' complete with C.I grating burnt brick masonry with CM (1:4) and
plastering with water tight heavy duty double seal C.I cover, frame
of 45x45 cm size The weight of the cover to be not less than 4.52
kg of frame to be not less than 2.75 Kg.

9.1 300 x 300mm size ' P' trap Nos 10


9.2 450 x 450mm size ' P' trap Nos RO

CONTRACTOR No.OF CORRECTIONS


Page 21

RATE AMOUNT
C SOIL & WASTE - PIPES & FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
10.0 Constructing brick masonry for manholes/ inspection chambers
with burnt bricks & cement mortar 1 : 5. Foundation concrete 1: 4:
8, inside plastering 15mm thick with C.M 1:2 finished smooth with
floating coat of cement neatly finished with water proofing to
required grade and making channel in cement concrete 1:3:4 neatly
finished complete as per standard design and as per the drawing.
Each manhole should be provided with CI rungs placed
appropriately conforming to IS standards.
Note:
1. All manholes to be constructed as per IS 4111 (Part1)
specification
2. Manhole covers are separately listed below

10.1 Inside size of 600mm x 600mm and depth not exceeding 800mm Nos 10

10.2 Inside size of 900mm x 900mm and depth not exceeding 1500mm Nos RO

11.0 Supply and fixing of double seal, pre-cast RCC, Medium duty
inspection chamber cover with frames of the following sizes.
Construction of pre-cast RCC cover to be made to withstand atleast
5 metric tonnes of loading of following size
11.1 600 x 600mm Nos 8
11.2 900 x 900mm Nos 2
11.3 900mm Dia Nos RO

TOTAL - SECTION C

CONTRACTOR No.OF CORRECTIONS


Page 22

RATE AMOUNT
D RAIN WATER - PIPES AND FITTINGS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supply, fixing, testing and commsisioning uPVC Pressure pipe (Ring-
fit) soil, waste vent pipe of Class 3 (6 Kgf/cm2) conforming to IS
4985-2000 including all fittings (IS 7834 for moulded fittings and IS
10124 for fabricated fittings), Eg: Bends, tees, elbows collars,
juction, inspection doors, cowls, offset acess pipes, jointing with
PVC solvent, running of pipes in the shafts / ceiling with brackets
and fasteners, chasing / chipping walls using groove cutting
machine, making bores / core cutting in slab / beam / wall and
making good of the same, cost shall include providing steel
brackets, MS angle supports, Pipe supports (all MS angle supports /
frames to be painted with two coats of primer) and fasterners. The
cost shall include transportation, lead and lift all complete as
required

1.1 50 mm dia Mtrs. 20


1.2 110 mm dia Mtrs. 220
1.3 160 mm dia Mtrs. 20

2.0 Making rain water Spouts/ grating with PVC bends, elbows, tees Set 7
etc., 150 X 150mm C.I grating.

3.0 Constructing rain water recharge pit using concentric cement rings Nos RO
and filled with absorbent media including coarse sand, fine sand,
gravel and smooth stones as per standard construction including
chamber cover all complete as required

TOTAL - SECTION D

CONRACTOR No.OF CORRECTIONS


Page 23

RATE AMOUNT
E PUMPS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Transfer pumps:


1.1 Supply, installation, testing and commissioning of Submersible Set 1
pumps of following duty condition. Cost to include necessary
fittings, starters, panel and accessories all complete as required
Duty Condition:
5 Cum/hr at 50m head
Note: One set consists of 1 working and No standby pump

2.0 Supply, installation including unloading, shifting to location, Set 1


coordination with HPNS supplier, testing and commissioning of
Hydro Pneumatic System as supplied by the client and integrating
with the plumbing system. Cost to include necessary fittings and
accessories.

TOTAL - SECTION E

CONTRACTOR No.OF CORRECTIONS


Page 24

RATE AMOUNT
F MISCELLANEOUS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Making of core cutting in RC slab of maximum 150mm thick of


following diameter. Cost to include proper packing including water
proofing
1.1 100 mm dia Nos. 10
1.2 150 mm dia Nos. 8

2.0 Supply and fixing of MS angle supports, channels and other Kgs 250
supporing structure for suspending, mounting pipes and other
fittings

3.0 Providing and fixing in place liquid level controller (Niagara or Nos. 4
Equivalent) with high and low level indicator in the Overhead tanks
along with associated wiring and connections. All complete as
required.

4.0 Supply and grouting of SS rungs made of 20 mm dia SS pipe 150 Nos. 40
mm wide for UG sump, to be fixed as per the detailed drawing

5.0 Provision of puddle flanges with M.S. plate of 6mm thick, the plate
to be welded to GI pipe of following sizes for storage water tanks
(refer drawing for construction). Supply shall be as per site
requirement as plain, single side threaded or double side threaded.

5.1 32 mm dia Nos. 15


5.2 40 mm dia Nos. 6
5.3 50 mm dia Nos. 6
5.4 65 mm dia Nos. 8

CONTRACTORS No.OF CORRECTIONS


Page 25

RATE AMOUNT
F MISCELLANEOUS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

6.0 Supply and fixing on terrace of dual layer PVC tank (of food grade
quality PVC) with manhole lid and suitable locking arrangements,
making holes of suitable diameter for inlet, outlet and over flow
pipes, including cost of all materials, labour (including lead and lift
charges), transport charges and testing complete as per
specifications
6.1 Capacity Nos RO

TOTAL - SECTION F

CONTRACTORS No.OF CORRECTIONS


Page 26

LIST OF APPROVED MAKES (PHE)


S No DESCRIPTION BRAND NAMES
Fixtures & Fittings
1 Vitreous Ceramic Sanitary Ware Client Supply
2 C.P Fittings Client Supply
3 Urinal Partition Client Supply
4 Exposed Cistern Client Supply
5 Health Faucet Client Supply
Toilet Accessories (Towel Ring, Toilet Paper Holder,
6 Client Supply
Robe hooks)
7 Automatic Hand Drier Client Supply
8 Liquid Soap Dispensor / Tissue Paper Dispensor Client Supply
9 Kitchen Sink Client Supply
10 Geyser Client Supply
11 Concealed Stop Cock Client Supply
12 Angle Stop Cock Client Supply

Pipes & Fittings


1 G.I Pipes TATA / Jindal
2 G.I Fittings R' Brand / AVR / HB
3 PVC Pipes ( SWR quality ) Finolex / Prince / Supreme
4 PVC Fittings Finolex / Prince / Supreme
5 CPVC Pipes Flowguard - Astral / Ashirwad / Supreme
6 UPVC Pipes (Schedule - 40) Flowguard - Astral / Ashirwad / Supreme
7 Pipe Bracket / Supports Hi-Tech or MS Fabricated as per drawing
8 Hot water insulation (Nitrile Rubber) Vidoflex / Armaflex
9 PVC Connection Pipes Kohinoor

Valves
1 Butterfly valve (50 Dia and above) Saunders / Advance / Intervalve
2 Ball valves ( Upto 40mm Dia ) Audco / RB / Leader
3 Y Strainer Sant / Zoloto / Leader
4 Non Return Valve Saunders / Advance / Intervalve

Pumps
1 Pressure boosted pump Grundfos / Xylem / CRI

CONTRACTOR No.OF CORRECTIONS


Page 27

LIST OF APPROVED MAKES (PHE)


S No DESCRIPTION BRAND NAMES
2 Sewage cutter pump N/A
3 Dewatering pump N/A

Miscellaneous
1 PVC Tanks (Food Grade) N/A

CONTRACTOR No.OF CORRECTIONS


Page 1

EQUITAS HOSPITAL AT CHENNAI

BILL OF QUANTITIES FIRE PROTECTION SYSTEM - HYDRANT, SPRINKLER, FIRE SUPPRESSION, SMOKE DETECTION
AND VOICE EVACUATION SYSTEM

AMOUNT
SECTION DESCRIPTION
SUPPLY FIXING

A FIRE PUMPS & ALLIED WORKS

B HYDRANT SYSTEM

C SPRINKLER SYSTEM

D SIGNAGES

E FIRE EXTINGUISHERS

F FIRE DETECTION AND ALARM

G PA SYSTEM (FIRE EVACUATION)

SUB TOTAL

GRAND TOTAL

AMOUNT IN
WORDS:

DATE:

REVISION:

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supplying, Installation, Testing an Commissioning of Electric driven Nos 1


main fire pump suitable for automatic operation and consisting of
following: complete in all aspects as required.
(a) Horizontal type, centrifugal, end suction type pump of cast iron
body & bronze impeller with stainless steel shaft, mechanical seal
to ensure a minimum pressure of 3.5 kg/sq. cm at highest and
farthest outlet at specified flow of 2280 lpm at 75 m head
conforming to IS 1520. The pump shall be capable of giving not less
than 150% discharge at a head not less than 65% of the rated head.
Pump to be selected with NPSH available more than 7 m to ensure
proper operation in negative suction condition

(b) Suitable HP SQ cage induction motor, TEFC, synchronous speed


1500 RPM, suitable for operation on 415 Volts, 3 Phase 50 Hz AC
with IP 55 Protection for enclosure, horizontal foot mounted type
with Class 'F' insulation, conforming to IS:325
( c) M.S.fabricated common base plate,coupling, coupling guard,
foundation bolts etc. as required.
(d) Pump to be fixed on suitable cement concrete foundation duly
plastered (done by the civil contractor) with anti vibration pads all
complete as required
For Hydrant System

2.0 Supplying, Installation, Testing and Commissioning of Diesel engine Nos 1


driven main fire pump suitable for automatic operation and
consisting of following : complete in all respect as required.

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
(a) Horizontal type ,centrifugal, end suction type pump of cast iron
body and bronze impeller with stainless steel shaft,mechanial seal
to ensure a minimum pressure of 3.5 kg/sq.cm. at highest and
farthest outlet at specified flow of 2280 lpm at 60m. head
conforming to IS 1520. The pump shall be capable of giving not less
than 150% discharge at a head not less than 65% of the rated head.
Pump to be selected with NPSH available more than 7 m to ensure
proper operation in negative suction condition.

(b) Suitable HP, 1500 RPM water cooled with radiator with associated
piping if required, diesel engine conforming to relevant BS & IS
standard complete with auto starting mechanism, 12 volts/24 Volts
electric starting equipment, Diesel Tank (For 8 hours of operation),
residental silencer, intruments and protection as per
specification,stop solenoid for auto stop in the event of fault with
audio indications, painted with post office red colour etc. as
required.
( c) Batteries & battery leads with stand
(d) M.S.fabricated common base plate,coupling, coupling guard,
foundation bolts etc. as required.
(e) Pump to be fixed on suitable cement concrete foundation duly
plastered (done by the civil contractor) with anti vibration pads all
complete as required
(f) Exhaust pipe of adequate size duly insulated with 50mm thick glass
wool with 1.9mm thick aluminium sheet cladding - Lot (To be
measured from drawing)
(g) Fuel piping from diesel tank to engine - Lot
For Hydrant System

CONTRACTOR No.OF CORRECTIONS


Page 3

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

3.0 Supplying, Installation, Testing and Commissioning of electric driven Nos 1


pressurisation pump (Jockey) suitable for automatic operation and
consisting of following and complete in all respect as required.

(a) Horizontal type, centrifugal pump of cast iron body & bronze
impeller with stainless steel shaft, mechanical seal flow of 180 lpm
and 75m head conforming to IS 1520. Pump to be selected with
NPSH available more than 7 m to ensure proper operation in
negative suction condition.
(b) Suitable HP SQ cage induction motor, TEFC type, synchronous
speed 2900 RPM, suitable for operation on 415 volts, 3 Phase 50
Hz. AC with IP 55 class of Protection for enclosure, horizontal foot
mounted type with Class -'F' insulation, conforming to IS:325.

( c) M.S.fabricated common base plate,coupling, coupling guard,


foundation bolts etc. as required.
(d) Pump to be fixed on suitable cement concrete foundation duly
plastered (done by the civil contractor) with anti vibration pads all
complete as required
For Hydrant System

4.0 Control Panel for Ground Floor Pumps

CONTRACTOR No.OF CORRECTIONS


Page 4

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
4.1 Fabrication, supply, installation, testing and commissioning of No. 1
electrical pump control panel. The panel shall be of cubical
construction, floor mounted / mounted on pump set, fabricated
out of 2mm thick CRCA sheet with hinged lockable doors, dust and
vermin proof, powder coated of approved shade, cable alley,
interconnection, having swictch gears and accessories mounting
and internal wiring, earth terminals, numbering etc.
Note: Cost shall include supply of switchgear, DOL starters of
suitable rating, necessary interlocking, control wiring, cable
termination, earthing etc. all complete as required

5.0 Fabrication, supply, installation, testing and commissioning of No. 1


diesel engine pump control panel. The panel shall be of cubical
construction, floor mounted / mounted on pump set, fabricated
out of 2mm thick CRCA sheet with hinged lockable doors, dust and
vermin proof, powder coated of approved shade, cable alley,
interconnection, having swictch gears and accessories mounting
and internal wiring, earth terminals, numbering etc.
The panel shall comprise the following as detailed below

(a) 20Amps DPMCB - 2 Nos.


(b) Battery charger with transformer with rectifier resistance DC
ammeter, DC voltmeter, Trickle / booster / off selector switch - 2
Nos.
( c) One set of indicating lamps for the following :
1. Phase indication
2. Battery charger on

CONTRACTOR No.OF CORRECTIONS


Page 5

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3. Over load relay
4. DC supply on
5. Control switch on
6. Engine fails to start
7. Pump on
8. Low oil pressure
9. High water temperature
10. Auto manual selector switch
(d) One sets of push button stations for the following
1. Engine Start
2. Engine Stop
3. Engine - hooter ACK
4. Engine - fault reset
(e) One number Selector switch (Engine control, mode selector)
(f) One set of Auxilary relays / contactors / timer for sequence
operating for starting and stopping of the engine
(g) One number Hooter for audio alarm (Industrial type)
(h) The panel shall have sufficient (min. 6Nos per pumpset) NO/NC
contacts for extending the status of fire pumps to the Fire pump
indication / fire alarm panels.

Supply, installation, testing and commissioning of priming tank with Nos RO


necessary pump and control arrangements all completed as
required as per standards

CONTRACTOR No.OF CORRECTIONS


Page 6

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
9.0 Supplying and laying of FRLS, PVC outer sheath, steel armoured,
aluminium / copper conductor, 1100v grade power cables with
glands etc.The cables shall be laid in cable tray on walls/ floor etc.
as required.The the rate shall include any cable trays if necessary
for the same.The minimum size of the cables shall as mentioned
below,
9.1 3.5C x 120 sq.mm for Main electric pumps Rmt 15
9.2 4 C x 16 Sqmm. Jockey pumps Rmt 15
9.3 12 C x 2.5 Sqmm.Diesel engines Rmt 15
9.4 2 C x 2.5 Sqmm.for Instrumentation Rmt 20

10.0 Providing and fixing pressure switch in MS pipe line (pressure range Nos 2
0 - 10 kg / sq.cm) suitable for 12 volts / 24 volts DC including
connection as required

11.0 Providing and fixing pressure switch in MS pipe line suitable for 12 Nos 1
volts / 24 volts DC including connection as required (For Jockey
Pump/ terrace pump )

12.0 Supplying, installing, testing and commissioning of Siphon tube and Nos 4
bib cock for Pressure Gauge capable of measuring 0 - 21 Kg

CONTRACTOR No.OF CORRECTIONS


Page 7

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
13.0 Supplying, laying, testing and commissioning of Class 'C' heavy duty
MS. Pipes conforming to IS 1239 (up to 150mm dia) and IS 3589
with wall thickness of 6.35mm (for 200mm and above) including
fittings like elbows, tees, flanges, tapers nuts, bolts, (galvanised),
gaskets etc,. The cost shall include cutting, welding, fixing in / on
walls, ceiling by using suitable type of supports, clamps, anchor
fasteners and MS angle supports (All MS supports / clamps to be
painted with two coats of primer) as per drawings. The quoted rate
shall also include for chasing / chipping walls, making bores / core
cutting in walls / slab / beams and making them good with filler
material and finishing with cement mortar etc. complete. The
quoted rate shall also include painting of exposed pipes with one
coat of etching primer and with two coats of synthetic enamel paint
of approved red colour / shade

13.1 200 mm nominal dia (wall thickness 6.35 mm) Rmt 10


13.2 150 mm nominal dia Rmt 25
13.3 100 mm nominal dia Rmt 20
13.4 80 mm nominal dia Rmt 20
13.5 25 mm nominal dia Rmt 10

14.0 Supplying, fixing, testing and commissioning of Slim seal standard


lever operated type Butterfly valve PN 16 with Bronze / Gunmetal
seat duly ISI marked complete with nuts, bolts, washers, gaskets
and flanges conforming to IS 13095, of following sizes all complete
as required
14.1 200 mm nominal dia Nos 2

CONTRACTOR No.OF CORRECTIONS


Page 8

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
14.2 150 mm nominal dia Nos 4
14.3 100 mm nominal dia Nos 2
14.4 80 mm nominal dia Nos 1

15.0 Supplying, fixing, testing and commissioning of Wafer type C.I. Dual
plate Check valve (Non-return) as per IS:5312 with required flanges,
nuts, GI bolts and gaskets etc. all complete as required of the
following sizes
15.1 200 mm nominal dia Nos 1
15.2 150 mm nominal dia Nos 2
15.3 100 mm nominal dia Nos 2
15.4 80 mm nominal dia Nos 1

16.0 Supplying, fixing and commissioning C.I.flanged "Y" type Strainer


with SS mesh,suitable flanges, nuts, bolts, gaskets etc. all complete
as required.
16.1 200mm dia. Nos 2
16.2 150mm dia. Nos 1
16.3 100mm dia. Nos RO

17.0 Supplying, installing, testing and commissioning of Gun metal


chrome finished Ball valves with fittings of screwed end type.
17.1 25 mm dia Nos 6

18.0 Supplying, installing, testing and commissioning of SS Needle valves


with fittings of screwed end type. (For Pressure Switch)

18.1 15 mm dia Nos 4

CONTRACTOR No.OF CORRECTIONS


Page 9

RATE AMOUNT
S No FIRE PUMP AND ALLIED WORKS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

19.0 Supply and fixing of flow switches in 150mm dia M.S Pipe Nos 3

20.0 Supply and fixing of IS approved foot valve with all necessary Nos RO
accessories of size 200mm dia

21.0 Supply, fixing, testing and commissioning of air vessel made of Nos. 1
300mm dia, 8mm thick MS sheet, 1200mm in height, with flanged
connection to riser, drain arrangement with 25mm dia Gun metal
ball valve with required accessories, pressure gauge and painting
with synthetic enamel paint of approved shade as required

TOTAL - SECTION A

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No HYDRANT SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supplying, laying, testing and commissioning of Class 'C' Heavy


duty MS. Pipes conforming to IS 1239 (up to 150mm dia) and IS
3589 with wall thickness of 6.35mm (for 200mm and above)
including fittings like elbows, tees, flanges, tapers nuts, bolts,
(galvanised), gaskets etc,. The cost shall include cutting, welding,
laying in ground, providing cement concrete blocks as supports and
also include anticorrosive treatment by coating with primer and
wrapping 4mm thick polymer corrosion resistant tape as per IS:
10221 with 15mm overlap as per specifications for buried yard
hydrant pipe
1.1 150mm nominal dia Rmt 175

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No HYDRANT SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
2.0 Supplying, laying, testing and commissioning of Class 'C' Heavy
duty MS. Pipes conforming to IS 1239 (up to 150mm dia) and IS
3589 with wall thickness of 6.35mm (for 200mm and above)
including fittings like elbows, tees, flanges, tapers nuts, bolts,
(galvanised), gaskets etc,. The cost shall include cutting, welding,
fixing in / on walls, ceiling by using suitable type of supports,
clamps, anchor fasteners and MS angle supports (All MS supports /
clamps to be painted with two coats of primer) as per drawings,
painting the exposed pipes with one coat of etching primer and two
coats of synthetic enamel paint of approved colour. The quoted
rate shall also include for chasing / chipping walls, making bores /
core cutting in walls / slabs / beams and making them good with
filler material and finishing with cement mortar. All wall crossing of
pipes should be done after placing adequate size PVC sleeve in the
wall opening etc. complete.

2.1 150mm nominal dia Rmt 125


2.2 100mm nominal dia Rmt 50
2.3 80mm nominal dia Rmt 20

3.0 Supplying, fixing, testing and commissioning of Slim seal standard


lever operated type Butterfly valve PN 16 with Bronze / Gunmetal
seat duly ISI marked complete with nuts, bolts, washers, gaskets
and flanges conforming to IS 13095, of following sizes all complete
as required
3.1 150mm nominal dia Nos 2

CONTRACTOR No.OF CORRECTIONS


Page 3

RATE AMOUNT
S No HYDRANT SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
4.0 Supplying and fixing Single headed internal hydrant valve with Nos. 8
instantaneous Gun metal couplings of 63 mm dia with cast iron
wheel ISI marked conforming to IS 5290 (Type - A) with blank
Gunmetal cap and chain as required.

5.0 Supplying and fixing 63 mm dia, one length of 15 mtr. long RRL Nos. 16
hose pipe with 63 mm dia Male and Female Gun metal couplings
duly binded with GI wire, rivets etc. conforming to IS 636 (type-A)
as required.

6.0 Supplying and fixing 63 mm dia Gun metal branch pipe with 20 mm Nos 8
(nominal internal diameter) size Gun Metal nozzle conforming to IS
903, suitable for instantaneous connection to inter-connect hose
pipe coupling as required.

7.0 Supplying and fixing First - Aid Hose Reel with MS construction Nos 10
spray painted in post office Red, conforming to IS 884 compete
with the following as required.
(a) 36m long 20 mm (nominal internal) dia water hose Rubber braided
hose Type -2 as per IS: 12585.
(b) 20 mm (nominal internal) dia gun metal globe valve & nozzle.
( c) Drum and brackets for fixing the equipments on wall.
(d) Connections from riser with 40 mm dia stop valve (gun metal ball
valve) & M.S. pipe.

CONTRACTOR No.OF CORRECTIONS


Page 4

RATE AMOUNT
S No HYDRANT SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
8.0 Providing & fixing angle iron (40 mm X 40 mm X 5 mm)door frame Nos. 8
and M.S sheet (2 mm.thick) cum glass shutter of size 1.0 mtr. X 0.9
mtr. (N.S.) with 25 mm. X 25 mm.X 3 mm. angle frame all around &
stiffened in between including hinges, handle, locking arrangement,
painting with approved synthetic enamel paint including sign
writing on glass at internal hydrant including providing & fixing M.S
Sheet 2 mm.thick on remaining portion above door to close
opening including painting etc. all complete as required for Fire
duct shutter

9.0 Supplying and fixing Single headed external yard hydrant valve with Nos. 6
One no. 63mm dia instantaneous FM Gun Metal coupling and cast
iron wheel, ISI marked, conforming to IS 5290 (Type A) with blank
Gunmetal cap and chain as required. (Standpost shall be measured
under piping item)

10.0 Supplying and fixing of hose cabinet of size 900 mm X 600 mm X Nos. 6
500 mm made of 2 mm thick MS sheet with 6 mm thick glazed glass
doors i/c necessary locking arrangement suitable to accommodate
external hydrant , 2 Nos. 15 mtr. long RRL Hose pipe, 1No. branch
pipe and nozzle, mounted on wall OR raised brick platform & duly
painted externally and internally with synthetic enamel paint of
approved colour complete in all respect, for external hydrant, as
required.

CONTRACTOR No.OF CORRECTIONS


Page 5

RATE AMOUNT
S No HYDRANT SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
11.0 Supplying, fixing, testing and commissioning of fire brigade inlet Nos 1
connection of 4 way conforming to IS 904 with 4 nos. 63 mm dia.
built - in Gun metal Non- return valves instantaneous coupling type
with cap and chain arranged on 150 mm dia. pipe manifold and
connected to wet riser system. Quoted rate shall include C.I.
Butterfly valve, C.I. Non-return valve and M.S. cabinet of suitable
size with mounting supports etc. all complete as required

12.0 Supplying, fixing, testing and commissioning of fire brigade inlet Nos 1
connection of 2 way conforming to IS 904 with 2 nos. 63 mm dia.
built - in Gun metal Non- return valves instantaneous coupling type
with cap and chain arranged on 150 mm dia. pipe manifold and
connected to UG sump for draw off / fill in. Quoted rate shall
include C.I. Butterfly valve, C.I. Non-return valve and M.S. cabinet
of suitable size with mounting supports etc. all complete as
required

14.0 Supplying, fixing, testing and commissioning of approved make 25 Nos. 4


mm dia. automatic air release valve on top of the air vessel with
unions etc. all complete as required

TOTAL - SECTION B

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No SPRINKLER SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supplying, laying, testing and commissioning of Class 'C' Heavy


duty MS. Pipes conforming to IS 1239 and 3589 including fittings
like elbows, tees, flanges, tapers nuts, bolts, (galvanised), gaskets
etc,. The cost shall include cutting, welding, fixing in / on walls,
ceiling by using suitable type of supports, clamps, anchor fasteners
and MS angle supports (All MS supports / clamps to be painted with
two coats of primer) as per drawings, painting the exposed pipes
with one coat of etching primer and two coats of synthetic enamel
paint of approved colour. The quoted rate shall also include for
chasing / chipping walls, making bores / core cutting in walls / slabs
/ beams and making them good with filler material and finishing
with cement mortar. All wall crossing of pipes should be done after
placing adequate size PVC sleeve in the wall opening etc. Cost to
include for rigid droppers for sprinklers in areas as indicated in the
drawings

1.1 150mm nominal dia Rmt 250


1.2 100mm nominal dia Rmt 200
1.3 80mm nominal dia Rmt 250
1.4 65mm nominal dia Rmt 250
1.5 50mm nominal dia Rmt 250
1.6 40mm nominal dia Rmt 120
1.7 32mm nominal dia Rmt 120
1.8 25mm nominal dia Rmt 800

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No SPRINKLER SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
2.0 Supplying, fixing, testing and commissioning of Slim seal standard
lever operated type Butterfly valve PN 1.6 with Bronze / Gunmetal
seat duly ISI marked complete with nuts, bolts, washers, gaskets
and flanges conforming to IS 13095, of following sizes all complete
as required
2.1 80mm dia Nos 12
2.2 65mm dia Nos 8
2.3 50mm dia Nos 30
2.4 25mm dia Nos 4

3.0 Supplying, fixing, testing and commissioning conventional Sprinkler


quartzoid bulb type with 15mm screwed end connection as per
specified rating. Sprinklers shall be UL Listed / FM approved.

3.1 Upright- Temperature rating 68 Deg C, K Factor - 5.6 Nos 25


3.2 Side wall - Temperature rating 68 Deg C, K Factor - 5.6 Nos 120
3.3 Pendent- Temperature rating 68 Deg C, K Factor - 5.6 Nos 600

4.0 Supply & fixing of approved type rosette plates (Two piece, Nos 840
adjustable type) for Sprinklers below false ceiling area.

CONTRACTOR No.OF CORRECTIONS


Page 3

RATE AMOUNT
S No SPRINKLER SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING
5.0 Supply, fixing, testing and commissioning of Installation control
valve of cast iron body and brass / bronze working parts comprising
of water motor alarm, bronze seat clapper, and clapper arm,
hydraulically driven mechanical going bell to sound continuous
alarm when the Sprinkler system activates, pressure gauges,
emergency releases, strainer, pressure switch,cock valve complete
with drain valve, MS pipe of required size, flanges, orifice plate,
gasket etc. of size as required.

5.1 150mm dia. Nos 1

6.0 Supplying, fixing, testing and commissioning flow switch on


sprinkler distribution header on each floor and shall be connected
to Sprinkler Anunciation panel through cable. Cable shall be
measured separately. The size required is as mentioned below

6.1 80mm dia Nos 12


6.2 65mm dia Nos 8
6.3 50mm dia Nos 4

7.0 Supply, fixing, testing and commisioning of Stainless steel Nos 720
corrugated flexible pipe (hose) for dropping sprinklers below false
ceiling, pipe shall be designed for a pressure rating of 16 bars and
shall be 1000 mm long of 25mm dia with union / reducer, collar,
clamps etc as required (To be used only in areas where false ceiling
is being proposed)

TOTAL - SECTION B

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No SIGNAGE UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Providing and fixing in position the following type of sign boards
made out of 3mm thick "Opaque" PVC foam board with computer
cut, PVC non-reflective self adhesive vinyl painted foam board,
complete with mirror fasteners.

1.1 Signage with the following text "IN CASE OF FIRE, USE STAIRS Nos 24
UNLESS INSTRUCTED OTHERWISE" of 1.25cm height letters in red
with white back ground. The size of the board shall be 25cm x 30
cm and shall be fixed at the height of 2 mts. from finished floor
near Manual call points.

1.2 Floor identification signage ( ie, GROUND FLOOR … etc.) at each Nos 16
stair enclosure on every floor, indicating the floor number in words,
lettering size shall be 7.5 cm with contrasting colour from back
ground.Size shall be 15cm x 60cm

1.3 Signage with the following text "FIRE EXIT" at each stair enclosure Nos 16
on every floor, lettering size shall be 7.5 cm with contrasting colour
from back ground.Size shall be 15cm x 60cm.

2.0 Providing and fixing in position the signages of the "FIRE ORDER" Nos 8
with the prescribed text on 3mm thick "Opaque" PVC foam board
of computerized cut, PVC non-reflective self adhesive vinyl painted
foam board of size 3' x 4'.

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No SIGNAGE UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.0 Providing and fixing in each patient room / ward the floor plan Nos 140
drawing with the room location and route to the nearest fire
escape clearly highlighted. The drawing has to be laminated and
provided with frame and hanging arrangement.

TOTAL - SECTION D

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No FIRE EXTINGUISHERS UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supplying, fixing and commissioning Portable Fire extinguishers


with B.I.S marking of following type & capacity

1.2 Carbon-di- oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas Nos. 32
filled in brand new seamless cylinder with powder coated finish,
made out of Manganese steel, with wheel type valve, discharge
nozzle, bend & horn, wall mounting bracket etc. complete,
confirming to IS: 2878.

1.3 ABC type Dry chemical powder fire extinguisher of 5 Kgs. Capacity, Nos. 12
with initial filling in brand new cylinder with powder coated finish,
fitted with Gun metal union, discharge hose, wall mounting bracket
etc. complete, confirming to IS:2171.

1.4 Water CO2 type fire extinguisher 9 lts. Capacity, initial filling in Nos. 12
brand new cylinder of powder coated finish, fitted with Gun metal
union, high pressure CO2 gas cartridge & wall mounting bracket
etc. complete confirming to IS:940.

2.0 Supply and fixing of ceiling mounted extinguisher using a clean Nos. 2
agent (10 kg) with zero ODP as the extinguishing medium complete
with pressure gauge, automatic discharge mechanism to discharge
within 10 seconds based on temperature rise

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No FIRE EXTINGUISHERS UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.0 Supplying and fixing Fire buckets round bottom type enamel Nos. 64
painted, white inside & Red out side and Letter "FIRE" in black out
side and handle with mounting bracket.

4.0 Supply and fixing Fire bucket stand fabricated by MS angles to Nos. 16
install 2 Nos. of buckets.

TOTAL - SECTION E

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No FIRE DETECTION AND ALARM SYSTEM (ADDRESSABLE) UNIT QTY
SUPPLY FIXING SUPPLY FIXING
1.0 Supply,erection,testing and commissioning of analogue addressable Nos 1
mircoprocessor based 2 loop main fire alarm control panel capable
of taking minimum 100 detectors and other devices as
MCP,Hooters ,control modules, response indicators, audio/visual
central processing unit, LCD Display as per the detail specification
complete with battery backup of 24 hours operation and 30
minutes alarm operation with batter charger etc., The system shall
be provided with provision for add on car, necessary colour
graphics software facility, integration of both FA & BMS by
providing NO/NC contacts. The panel shall be UL Listed / FM
Approved or have International certification

2.0 Supply, fixing and commissioning Analog Addressable Photo- Nos 320
electric type, multi-sensor, multi criteria smoke detector with Bi-
colour LED indication, automatic mapping device, electronic
addressing, multiple sensitvity levels, pre-alarm option, non-volatile
memory having provision for self diagnostics and history log, dust
and dirt resistant with drift compensation, plug-in design, with
compatible mounting bases, junction box and other accessories as
required and working on 19 - 24 V DC supply all complete as
required. The detectors shall be UL Listed / FM approved or have
an equivalent international standard certification

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No FIRE DETECTION AND ALARM SYSTEM (ADDRESSABLE) UNIT QTY
SUPPLY FIXING SUPPLY FIXING
3.0 Supply, fixing and commissioning Analog addressable Heat detector Nos 8
with operating temperature of 58 Deg C / 9 Deg C rate of rise of
temperature, with compatible mounting bases, junction box and
other accessories as required and working on 12 - 24 V DC supply
all complete as required. The detectors shall be UL Listed / FM
approved or have an equivalent international standard certification

4.0 Supply, fixing and commissioning Audio annunciation device with. Nos 40
The device shall have a Horn rated at 82 dBA @ 3m for Audible
annunciation
5.0 Supply, fixing and commissioning Addressable Single action Manual Nos 16
pull station having an integrally mounted addressable module that
monitors and reports contact status.
6.0 Supply and fixing of response indicator all complete as required Nos 40

7.0 Supply, fixing and commissioning Analogue Addressable Fault Nos 32


isolator module capable of monitoring shorted loop circuit and
automatically restore communications when shorted conditions are
corrected with plug in arrangement, LED status indication, and
other accessories all complete as required, working on 19 - 24 V
DC. The modules shall be UL Listed / FM approved or have an
equivalent international standard certification

CONTRACTOR No.OF CORRECTIONS


Page 3

RATE AMOUNT
S No FIRE DETECTION AND ALARM SYSTEM (ADDRESSABLE) UNIT QTY
SUPPLY FIXING SUPPLY FIXING
8.0 Supply, fixing and commissioning of Strobe for indication with Nos 16
Audio and flash lighting with specifically setting option and working
at 24v DC and all other accessories all complete as required

9.0 Supply, fixing and commissioning Analogue Addressable Control Nos 64


module for monitoring the output devices with LED indication,
automatic mapping device, electronic addressing and working at
24v DC and all other accessories all complete as required

10.0 Supply, fixing and commissioning Analogue Addressable Monitor Nos 24


module for monitoring the output devices with LED indication,
automatic mapping device, electronic addressing and working at
24v DC and all other accessories all complete as required

11.0 Supplying and fixing approved make armoured twin core 1.5 sq. Rmt 5000
mm, Fire retardant sheathed copper conductor wire conforming to
IS standards and specifications.
12.0 Supplying and fixing approved make twin core 1.5 sq. mm, PVC Rmt RO
sheathed copper conductor wire conforming to IS standards and
specifications.
13.0 Supplying and fixing approved make 19 mm dia. PVC conduits on Rmt RO
ceiling / wall / floor etc. complete with accessories like, Junction
boxes, Collars, Bends etc.
TOTAL - SECTION F

CONTRACTOR No.OF CORRECTIONS


Page 1

RATE AMOUNT
S No PUBLIC ADDRESS SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING

1.0 Supplying, installing, testing and commissioning approved make Nos 1


Multi zone selector call station panel, interface with control desk
fitted with goose neck micro phone, zone selection key pad,
mounting stand, power supply unit with in built battery backup
etc., with facility to integrate with FA panel and provision for voice
evacuation message input. The panel shall be made of not less than
1.6mm thick CRCA sheet powder coated in approved colour with
locking arrangement

2.0 Supply, installation, testing and commissioning approved make Nos 1


Solid state power amplifiers suitable to be mounted in amplifier
rack. Amplifier shall be of 1000 W RMS output, with complete
wiring and controls, accessible from the front and with proper
locking arrangement

3.0 Supplying, fixing, testing and commissioning approved make 6W Nos 150
Ceiling mounted loud speakers suitable for music and voice
application, with inline matching transformer, wide dispersion
angle with suitable mounting clamps etc all complete as required.

4.0 Supplying and fixing 40 strand twin core speaker control cables of Rmt 2400
PVC insulated copper conductor overall armoured, Confirming to IS
1554, as per specification. These wires shall be laid along with
wiring of Hooters / strobes of detection system.

CONTRACTOR No.OF CORRECTIONS


Page 2

RATE AMOUNT
S No PUBLIC ADDRESS SYSTEM UNIT QTY
SUPPLY FIXING SUPPLY FIXING

5.0 Supplying and fixing approved make 19 mm dia. PVC conduits on Rmt 2000
ceiling / wall / floor etc. complete with accessories like, Junction
boxes, Collars, Bends etc.

TOTAL - SECTION G

CONTRACTOR No.OF CORRECTIONS


Page 1

LIST OF APPROVED MAKES

FIRE FIGHTING SYSTEM - HYDRANT, SPRINKLER, FIRE EXTINGUISHERS, SMOKE DETECTION, FIRE ALARM, PA AND
VOICE EVACUATION SYSTEMS

S No DESCRIPTION BRAND NAMES

A Hydrant / Sprinkler Equipments & Fittings


1 Electric Pumps Kirloskar / Grundfos / Beacon
2 Diesel Engine Driven Pumps Kirloskar / Cummins / Ashok Leyland
3 Pressure Gauge H Guru / Fiebig
4 Pressure Switch Indfoss / Danfoss
5 Pressure Transducer Danfoss / Switzer
6 Flow Switch System Sensor / Tyco
7 Flow Meter Belimo / Anergy
8 Air Vessel Factory Fabricated
9 Hydrant Landing valves Minimax / Newage / Winco
10 Fire Hose - RRL Minimax / Newage / CRC
11 Branch Pipe and Nozzle Minimax / Newage / Winco
12 First Aid Rubber Hose Minimax / Newage / Winco
13 Fire Brigade Inlet Connection Winco / Newage / Minimax
14 Sprinkler Bulbs Tyco / Viking / HD
15 Sprinkler Alarm Valve (ICV) HD / UL Listed Brand

B Pipes & Fittings


1 G.I Pipes Jindal / Tata
2 G.I Fittings R' Brand / AVR / HB
3 M.S Pipes Jindal / Tata
4 Sprinkler Flexible Hose Tyco / Degein
5 R.C.C Hume Pipes Indian Hume Pipe / Sudharsan / ISI
6 Pipe Bracket / Supports Hi-Tech or MS Fabricated as per drawing
7 Anchor Fasteners Hilti
8 Wrapping & Coating Pypkote / Rustech

C Valves
1 Butterfly valve (50 Dia and above) Saunders / Advance / Honeywell
2 Gun Metal Ball valves ( Upto 40mm Dia ) Audco / Zolotto / Leader
3 Non Return Valve Saunders / Advance / Honeywell

CONTRACTORS No.OF CORRECTIONS


Page 2

4 Y Strainer Sant / Zoloto / Leader


5 Pressure Reducing Valve Cimberio
6 Globe Valve Advance / Leader
7 Air Release Valve Elems/ RB
7 Foot Valve Kirloskar/ Leader

D FIRE EXTINGUISHERS
1 ABC Type Ceasefire / Safex
2 CO2 Type Ceasefire / Safex
3 Clean Agent Ceasefire / Safex

E Fire Detection System


1 Fire Alarm Control Panel Honeywell - Morley / GST
2 GUI Software Honeywell - Morley / GST
3 Repeater Panel Honeywell - Morley / GST
4 Addressable Detectors Honeywell - Morley / GST
5 Addressable Modules Honeywell - Morley / GST
6 Horn / Strobe Honeywell - Morley / GST
7 Addressable Manual Call Point Honeywell - Morley / GST
8 Power Supply Unit Honeywell - Morley / GST
9 Fire Alarm Control Cable Finecore / Polycab / Varsha
10 PVC Conduits VIP / Avon / ISI Marked

F PA System
1 PA Console Bosch / Honeywell / Philips
2 Amplifier Bosch / Honeywell / Philips
3 Speaker Bosch / Honeywell / Philips
4 40 Strand Finecore / Polycab / Varsha

G Miscellaneous
1 Paint Asian

CONTRACTORS No.OF CORRECTIONS


Page 1

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - A WIRING
Supply, installation, testing and commissioning of surface/concealed type of point wiring with
modular type switches, sockets and all materials as per the point wiring chart. The item including
cost of supply and installation of 19mm(in wall) or 25mm(ceiling/wall) dia PVC conduits,
couplers, junction boxes, bends, ceiling/wall plates, metal boxes, switches, sockets, draw boxes
& top cover plate (3mm hylam sheet), 3 run of 1.5sq.mm FRLS copper wires, bakelite
A1
connectors, crimping type ferrules, copper lugs, brass cup washers & brass screws, clamps &
screws and bolt & nuts etc. All the points shall be terminated with 300mm length of additional
wires along with connector terminal blocks. The item including necessary chipping/cutting the
wall and making good the same in case of recessed conduit as required. All complete as per
specifications, drawings and / or as directed by the Engineer.

One light / exhaust fan / wall mounting fan point controlled by one No. 1-way 6 Amps switch.
a) Nos. 578
(upto 6m)

One fan point (with regulator) controlled by one No. 1-way 6 Amps switch. The item including
b) Nos. 170
cost of fan hook with metal box, top round sheet/plate and 2M stepped regulator etc. (upto 6m)

One fan point (without regulator) controlled by one No. 1-way 6 Amps switch. The item including
c) Nos. 10
cost of fan hook with metal box and top round sheet/plate etc. (upto 6m)

One fan point (with regulator) controlled by two Nos. 2-way 6 Amps switch. The item including
d) Nos. 10
cost of fan hook with metal box, top round sheet/plate and stepped regulator etc. (upto 12m)

One light / exhaust fan / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto
e) Nos. 10
12m)

CONTRACTOR No.OF CORRECTIONS


Page 2

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

f) Two light / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto 12m) Nos. RO

One additional light point extended from the existing light point and controlled by existing switch.
g) (all items are as similar to {A1.a} but excluding of switch boxes, switches and sockets) (upto 3m Nos. 263
length)
One 6A dependent 5-pin socket point controlled by one no of 6A switch. (switch & socket are
h) Nos. 200
mounted in a dependent switch box)
One 6A independent 5-pin socket point controlled by one no of 6A switch. (switch & socket are
i) Nos. 36
mounted in a independent switch box)
One 6A/16A 5-pin socket point controlled by one 16A switch with indicator. (switch & socket are
j) Nos. 190
mounted in a independent switch box)
One 16A 5-pin socket point controlled by one 16A switch with indicator. (switch & socket are
k) Nos. 27
mounted in a seperate switch box)
Two nos 6A/16A 5-pin socket point controlled by two nos 16A switch with indicator. (switch &
l) Nos. 40
socket are mounted in an independent switch box)
Two nos of 6A independent 5-pin socket points controlled by two nos of 6A switches. (white
m) Nos. 134
colour)

Two nos of 6A independent 5-pin socket points controlled by two nos of 6A switches. (Black
n) Nos. 72
colour)

o) One 6A one way dependent/indepenent switch with terminations. Nos. 20

p) One 6A dependent/indepenent 5-pin socket with terminations. Nos. 20

q) One 16A dependent/independent switch (with indicator) with terminations. Nos. 10

CONTRACTOR No.OF CORRECTIONS


Page 3

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
r) One 6/16A dependent/independent socket with terminations. Nos. 10

s) One 20A one way dependent/indepenent switch (with indicator) with terminations. Nos. RO

t) One 32A one way dependent/indepenent switch (with indicator) with terminations. Nos. RO

One number of calling bell receiver controlled by one numbers of calling bell buzzer with
u) Nos. 20
termination

Supply, installation, testing and commissioning of surface type of point wiring with modular
type switches, sockets and all materials as per the point wiring chart. The item including cost of
supply and installation of 19mm(in wall) or 25mm(ceiling/wall) dia MS conduits, couplers,
junction boxes, bends, ceiling/wall plates, metal boxes, switches, sockets, draw boxes & top
cover plate (3mm hylam sheet), 3 run of 1.5sq.mm FRLS copper wires, bakelite connectors,
A2
crimping type ferrules, copper lugs, brass cup washers & brass screws, clamps & screws and
bolt & nuts etc. All the points shall be terminated with 300mm length of additional wires along
with connector terminal blocks. The item including necessary chipping/cutting the wall and
making good the same in case of recessed conduit as required. All complete as per
specifications, drawings and / or as directed by the Engineer.

One light / exhaust fan / wall mounting fan point controlled by one No. 1-way 6 Amps
a) Nos. 20
switch.(upto 6m)

One fan point (with regulator) controlled by one No. 1-way 6 Amps switch. The item including
b) Nos. 10
cost of fan hook with metal box, top round sheet/plate and 2M stepped regulator etc. (upto 6m)

CONTRACTOR No.OF CORRECTIONS


Page 4

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

One fan point (without regulator) controlled by one No. 1-way 6 Amps switch. The item including
c) Nos. 15
cost of fan hook with metal box and top round sheet/plate etc. (upto 6m)

One fan point (with regulator) controlled by two Nos. 2-way 6 Amps switch. The item including
d) Nos. 2
cost of fan hook with metal box, top round sheet/plate and stepped regulator etc. (upto 12m)

e) One light / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto 12m) Nos. 5

Two light / exhaust fan / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto
f) Nos. 3
12m)

One additional light point extended from the existing light point and controlled by existing switch.
g) (all items are as similar to {A2.a} but excluding of switch boxes, switches and sockets) (upto 3m Nos. 20
length)

CONTRACTOR No.OF CORRECTIONS


Page 5

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of surface/concealed type of point wiring with
modular type switches, sockets and all materials as per the point wiring chart. The item
including cost of supply and installation of couplers, junction boxes, bends, ceiling/wall plates,
metal boxes, switches, sockets, draw boxes & top cover plate (3mm hylam sheet), 3 run of
1.5sq.mm FRLS copper wires, bakelite connectors, crimping type ferrules, copper lugs, brass
A3 cup washers & brass screws, clamps & screws and bolt & nuts etc. All the points shall be
terminated with 300mm length of additional wires along with connector terminal blocks. The item
including necessary chipping/cutting the wall and making good the same in case of recessed
conduit as required. All complete as per specifications, drawings and / or as directed by the
Engineer. (The item excluding cost of 19mm/25mm dia PVC/MS conduits i.e, Point wiring
in the existing conduits)

One light / exhaust fan / wall mounting fan point controlled by one No. 1-way 6 Amps
a) Nos. RO
switch.(upto 6m)

One fan point (with regulator) controlled by one No. 1-way 6 Amps switch. The item including
b) Nos. RO
cost of fan hook with metal box, top round sheet/plate and 2M stepped regulator etc. (upto 6m)

One fan point (without regulator) controlled by one No. 1-way 6 Amps switch. The item including
c) Nos. RO
cost of fan hook with metal box and top round sheet/plate etc. (upto 6m)

One fan point (with regulator) controlled by two Nos. 2-way 6 Amps switch. The item including
d) Nos. RO
cost of fan hook with metal box, top round sheet/plate and stepped regulator etc. (upto 12m)

One light / exhaust fan / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto
e) Nos. RO
12m)

CONTRACTOR No.OF CORRECTIONS


Page 6

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

f) Two light / wall mounting point controlled by two Nos. 2-way 6 Amps switch. (upto 12m) Nos. RO

One additional light point extended from the existing light point and controlled by existing switch.
g) (all items are as similar to {A3.a} but excluding of switch boxes, switches and sockets) (upto 3m Nos. RO
length)

Supply, installation, testing and commissioning of surface/concealed type of main circuit wiring
from panel/DB to DB's, DB to switch boxes and switch box to other switch boxes using 1100V
grade PVC insulated multistranded FRLS copper wires, to be drawn through conduits. The items
including cost of supply and installtion of 19mm/25mm PVC/MS conduits, couplers, junction
boxes, bends, ceiling/wall plates, metal boxes, draw boxes & top cover plate (3mm hylam
A4
sheet), 3 or 6 runs of FRLS copper wires, bakelite connectors, crimping type ferrules, copper
lugs, brass cup washers & brass screws, clamps & screws and bolt & nuts etc. The item
including necessary chipping/cutting the wall and making good the same in case of recessed
conduit as required. All complete as per specifications, drawings and / or as directed by the
Engineer.

3 runs of 1.5 sq.mm. FRLS copper wiring through PVC conduits. (this item will be considered
a) R. mtr. 500
only where the point wiring exceeds the mentioned length)

b) 2 runs of 2.5 sq.mm. & 1 run of 1.5 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 5100
c) 2 runs of 4.0 sq.mm. & 1 run of 2.5 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 2415
d) 2 runs of 6.0 sq.mm. & 1 run of 4.0 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 50
e) 2 runs of 6.0 sq.mm. & 1 run of 2.5 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 350
f) 4 runs of 6.0 sq.mm. & 2 runs of 4.0 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 20

CONTRACTOR No.OF CORRECTIONS


Page 7

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
g) 4 runs of 6.0 sq.mm. & 2 runs of 2.5 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 100
h) 4 runs of 10.0 sq.mm. & 2 runs of 6.0 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. RO
i) 4 runs of 10.0 sq.mm. & 2 runs of 4.0 sq.mm. FRLS copper wiring through PVC conduits. R. mtr. 75
j) 3 runs of 1.5 sq.mm. FRLS copper wiring through MS conduits. (this item will be considered only R. mtr. 150
where the point wiring exceeds the mentioned length)
k) 2 runs of 2.5 sq.mm. & 1 run of 1.5 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 200
l) 2 runs of 4.0 sq.mm. & 1 run of 2.5 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 125
m) 2 runs of 6.0 sq.mm. & 1 run of 4.0 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 50
n) 2 runs of 6.0 sq.mm. & 1 run of 2.5 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 200
o) 4 runs of 6.0 sq.mm. & 2 runs of 4.0 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 50
p) 4 runs of 6.0 sq.mm. & 2 runs of 2.5 sq.mm. FRLS copper wiring through MS conduits. R. mtr. 75

Supply and installlation of surface/recessed type PVC/MS, rigid/flexible, conduits of the following
sizes with required couplers, junction boxes, bends, ceiling/wall plates, metal boxes, draw boxes
& top cover plate (3mm hylam sheet), clamps, screws, bolt & nuts and necessary fixing
A5
accessories etc. The item including necessary chipping/cutting the wall and making good the
same in case of recessed conduit as required. All complete as per specifications, drawings and /
or as directed by the Engineer:

a) 20mm dia 2mm thick rigid PVC conduits. R. mtr. 15


b) 25mm dia 2mm thick rigid PVC conduits. R. mtr. 20
c) 32mm dia 2mm thick rigid PVC conduits. R. mtr. 15
d) 50mm dia 2mm thick rigid PVC conduits. R. mtr. 15
e) 20mm dia 1.6mm thick rigid PVC conduits. R. mtr. 35

CONTRACTOR No.OF CORRECTIONS


Page 8

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
f) 25mm dia 1.6mm thick rigid PVC conduits. R. mtr. 40
g) 32mm dia 1.6mm thick rigid PVC conduits. R. mtr. 25
h) 50mm dia 1.6mm thick rigid PVC conduits. R. mtr. 15
i) 20mm dia flexible PVC conduits. R. mtr. 35
j) 25mm dia flexible PVC conduits. R. mtr. 25
k) 32mm dia flexible PVC conduits. R. mtr. 20
l) 40mm dia flexible PVC conduits. R. mtr. 15
m) 50mm dia flexible PVC conduits. R. mtr. 15
n) 20mm dia 1.6mm thick rigid MS conduits. R. mtr. 20
o) 25mm dia 1.6mm thick rigid MS conduits. R. mtr. 25
p) 20mm dia flexible MS conduits. R. mtr. 20
q) 25mm dia flexible MS conduits. R. mtr. 15

TOTAL CARRIED OVER TO SUMMARY (Part - A)

PART - B DISTRIBUTION BOARD

CONTRACTOR No.OF CORRECTIONS


Page 9

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of following ways of surface/flush mounting,


phase segregation seven segment type TPN MCB DB's of sheet steel, powder coated, IP42
protection, metal door and cable end box etc. The item including terminal connectors for all
incoming and outgoing circuits, duly pre-wired with suitable size of FRLS PVC copper wires upto
B1 terminal blocks, tinned copper bus bar of suitable rating, neutral links, earth bars, detachable
gland plate, interconnections by using crimping type ferrules & copper lugs, and engraving of
laminated as-built circuit drawings in the door inside etc. The item including necessary
chipping/cutting the wall and making good the same in case of flush mounting as required. All
complete as per specifications, drawings and / or as directed by the Engineer:

a) 4way Nos. 4
b) 6way Nos. 4
c) 8way Nos. 9
d) 12way Nos. RO

Supply, installation, testing and commissioning of following ways of surface/flush mounting,


VTPN MCB DB's of sheet steel, powder coated, IP43 protection, metal door and cable end box
etc. The item including terminal connectors for all incoming and outgoing circuits, duly pre-wired
with suitable size of FRLS PVC copper wires upto terminal blocks, tinned copper bus bar of
B2 suitable rating, neutral links, earth bars, detachable gland plate, interconnections by using
crimping type ferrules & copper lugs, and engraving of laminated as-built circuit drawings in the
door inside etc. The item including necessary chipping/cutting the wall and making good the
same in case of flush mounting as required. All complete as per specifications, drawings and / or
as directed by the Engineer:

a) 4way Nos. 1

CONTRACTOR No.OF CORRECTIONS


Page 10

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
b) 8way Nos. 2
c) 12way Nos. 1

Supply, installation, testing and commissioning of following way of surface/flush mounting, VTPN
MCCB DB's of sheet steel, powder coated, IP42 protection, metal door and cable end box etc.
The item including terminal connectors for all incoming and outgoing circuits, duly prewired with
suitable size of FRLS PVC copper wires upto terminal blocks, tinned copper bus bar of suitable
B3 rating, neutral links, earth bars, detachable gland plate, interconnections, crimping type ferrules,
copper lugs and engraving of laminated as-built circuit drawings in the door inside etc. The item
including necessary chipping/cutting the wall and making good the same in case of flush
mounting as required. All complete as per specifications, drawings and / or as directed by the
Engineer:

a) 4way Nos. RO
b) 8way Nos. RO
c) 12way Nos. RO

CONTRACTOR No.OF CORRECTIONS


Page 11

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of following ways of surface/flush mounting, SPN
MCB DB's of sheet steel, powder coated, IP43 protection, metal door and cable end box etc.
The item including terminal connectors for all incoming and outgoing circuits, duly pre-wired with
suitable size of FRLS PVC copper wires upto terminal blocks, tinned copper bus bar of suitable
B4 rating, neutral links, earth bars, detachable gland plate, interconnections by using crimping type
ferrules & copper lugs, and engraving of laminated as-built circuit drawings in the door inside
etc. The item including necessary chipping/cutting the wall and making good the same in case of
flush mounting as required. All complete as per specifications, drawings and / or as directed by
the Engineer:

a) 4way Nos. RO
b) 8way Nos. 8
c) 12way Nos. 21

Supply, installation, testing and commissioning of following ratings & poles of single phase /
three phase "C" curve, 10KA MCB's to be fixed in the existing MCCB/MCB DB's or enclosures
B5
complete with interconnections by using crimping type ferrules and copper lugs etc. All complete
as per specifications, drawings and / or as directed by the Engineer:

a) 6A to 32A Single Pole MCB Nos. 367


b) 6A to 32A Singl Pole Neutral / Double Pole MCB Nos. 5
c) 40A to 63A Singl Pole Neutral / Double Pole MCB Nos. 2
d) 6A to 32A Triple Pole MCB Nos. 8
e) 40A to 63A Triple Pole MCB Nos. 6

CONTRACTOR No.OF CORRECTIONS


Page 12

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
f) 80A Triple Pole MCB Nos. RO
g) 100A Triple Pole MCB Nos. 1
h) 6A to 32A Triple Pole Neutral MCB Nos. 4
i) 40A to 63A Triple Pole Neutral MCB Nos. 3
j) 6A to 32A Four Pole MCB Nos. RO
k) 40A to 63A Four Pole MCB Nos. 23
l) 80A Four Pole MCB Nos. RO
m) 100A Four Pole MCB Nos. 2

Supply, installation, testing and commissioning of following ratings & poles of three phase 25KA
adjustable thermal magnetic release type MCCB's to be fixed in the existing MCCB DB's or
B6
panels or enclosures complete with interconnections by using crimping type ferrules and copper
lugs etc. All complete as per specifications, drawings and / or as directed by the Engineer:

a) 100A Triple Pole MCCB Nos. RO


b) 125A Triple Pole MCCB Nos. RO
c) 160A Triple Pole MCCB Nos. RO
d) 100A Four Pole MCCB Nos. RO
e) 125A Four Pole MCCB Nos. RO
f) 160A Four Pole MCCB Nos. RO

CONTRACTOR No.OF CORRECTIONS


Page 13

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of following ratings & poles of three phase 36KA
adjustable thermal magnetic type MCCB's to be fixed in the existing MCCB DB's or panels or
B7
enclosures complete with interconnections by using crimping type ferrules and copper lugs etc.
All complete as per specifications, drawings and / or as directed by the Engineer:

a) 200A Four Pole MCCB Nos. RO


b) 250A Four Pole MCCB Nos. RO

Supply, installation, testing and commissioning of following ratings & poles of single phase /
three phase RCCB's to be fixed in the existing MCCB/MCB DB's or enclosures complete with
B8
interconnections by using crimping type ferrules and copper lugs etc. All complete as per
specifications, drawings and / or as directed by the Engineer:

a) 16A to 25A Double Pole RCCB, 30mA Nos. 26


b) 40A Double Pole RCCB, 30mA Nos. RO
c) 63A Double Pole RCCB, 30mA Nos. RO
d) 16A Four Pole RCCB, 30mA Nos. RO
e) 25A Four Pole RCCB, 30mA Nos. RO
f) 40A Four Pole RCCB, 30mA Nos. 33
g) 63A Four Pole RCCB, 30mA Nos. 24

CONTRACTOR No.OF CORRECTIONS


Page 14

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply and installation of blanking plates in the existing MCCB/MCB DB's or enclosures etc. All
B9 Nos. 207
complete as per specifications, drawings and / or as directed by the Engineer:

Supply, installation, testing and commissioning of following type metal one way enclosures
suitable for independent mounting of MCB/MCCB/RCCB's complete with all necessary fixing
B10
accessories etc. All complete as per specifications, drawings and / or as directed by the
Engineer:

a) Single Pole Enclosure for MCB's Nos. 5


b) Double Pole Enclosure for MCB's Nos. 7
c) Triple Pole Enclosure for MCB's Nos. 10
d) Four Pole Enclosure for MCB's Nos. 7
e) Four Pole Enclosure for RCCB's Nos. 6
f) Triple Pole Enclosure for MCCB's Nos. RO
g) Four Pole Enclosure for MCCB's (upto 100A) Nos. RO
h) Four Pole Enclosure for MCCB's (125A to 200A) Nos. RO

Supply and fixing of 32A TP+N+E industrial type switched socket with 32A TPN MCB with IP-66
B11 a) Set. 2
non metallic enclosure with all necessary fixing accessories etc.

CONTRACTOR No.OF CORRECTIONS


Page 15

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply and fixing of 63A TP+N+E industrial type interlocked switched socket with 63A TPN MCB
b) Set. 2
with IP-66 non metallic enclosure with all necessary fixing accessories etc.

Supply and fixing of 125A TP+N+E industrial type interlocked switched socket with 125A TPN
c) Set. 2
MCB with IP-66 non metallic enclosure with all necessary fixing accessories etc.

TOTAL CARRIED OVER TO SUMMARY (Part - B)

CONTRACTOR No.OF CORRECTIONS


Page 16

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - C LUMINAIRES AND FIXTURES

Supply and installation, testing and commissioning of the following luminaires including clamps,
C1 screws, bolt & nuts, down rods, required connector block terminals and necessary fixing
accessories etc.

230V, 1 x 20W, wall/ceiling mounted type 4' length tube light luminaire suitable for 1 x 20W LED
a) Nos. 305
lamp. [Philips make 20W TLED or Equivalent as acceptable to the Client.]

b) 230V, Fluorescent luminarie type UV lamp. Nos. 5

230V, 1 x 22W ceiling mounted square type down light luminarie suitable for 1x22W LED lamp.
c) Nos. 314
[Philips make 22W ENDURALED;6500K or Equivalent as acceptable to the Client.]

230V, 1 x 40W ceiling mounted square type down light luminarie suitable for 1 x 40W LED lamp.
d) [Philips make RC365B LED 33-6500 PSU OD GR D 1xLED/6500 PSU or Equivalent as Nos. 76
acceptable to the Client.]

230V, 1 x 12W ceiling mounted circular type down light luminarie suitable for LED lamp. [Philips
e) Nos. 101
make SM260C LED12S 6500 PSU or Equivalent as acceptable to the Client.]

230V, 1 x 10W ceiling mounted circular type down light luminarie suitable for LED lamp. [Philips
f) make DN192B LED9S-6500 PSU WH S1 Di 1xLED/4000K PSU or Equivalent as acceptable to Nos. RO
the Client.]

230V, 1 x 10W, wall mounted type mirror luminaire suitable for 1 x 10W LED lamp. [Philips make
g) Nos. 20
or Equivalent as acceptable to the Client.]

CONTRACTOR No.OF CORRECTIONS


Page 17

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

230V, Bulk head light type luminaire suitable for LED lamp. [Philips make or Equivalent as
h) Nos. 20
acceptable to the Client.]

230V, Outdoor type Burried light type luminaire suitable for LED lamp. [Philips make LED Uplite
i) Nos. 5
BBP330 or Equivalent as acceptable to the Client.]

230V, Up Down light type luminaire suitable for LED lamp. [Philips make or Equivalent as
j) Nos. 10
acceptable to the Client.]

230V, Outdoor wall bracket type luminaire suitable for LED lamp. [Philips make BR6022 LED20
k) Nos. 10
or Equivalent as acceptable to the Client.]

230V, 70W street light type luminaire (IP 55) suitable for LED lamp. Wipro make Skyline LR02-
l) Nos. 10
102-XXX-57-XX or equivalent.

230V, 50W flood light(IP 55) type LED luminaire, Make: Philips 50W Smart Bright LED Flood
m) Nos. 10
Light (White Light) or equivalent.

n) 230V, 35W compound / Gate light(IP 55) type luminaire suitable for LED. Nos. 4

230V, 45W LED Post top type light(IP 55) (double outrich) metal halide type luminaire of Wipro
o) Nos. 10
make LP02-501-XXX-57-XX or equivalent.

p) 230V, 30W bollard (IP 55) type luminaire suitable for LED. Nos. 5

CONTRACTOR No.OF CORRECTIONS


Page 18

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
q) 230V, 10W outdoor garden light (IP 55) type luminaire suitable for LED. Nos. 5
r) 230V, ding-dong type calling bell with fixing accessories etc. Nos. 10

Supply and installation, testing and commissioning of following sizes of ceiling fan (with required
C2 length of down rod), all complete as per specifications, drawings and / or as directed by the
Engineer.
a) 600mm sweep Nos. 3
b) 900mm sweep Nos. 10
c) 1200mm sweep Nos. 165

Supply and installation, testing and commissioning of light duty type 300mm diameter exhaust
C3 fan, with mounting frame and louvres, all complete as per specifications, drawings and / or as Nos. 60
directed by the Engineer.

Supply, installation, testing and commissioning of automatic timer control unit with suitable
enclosure for street lighting with one no. each 32A single-pole MCB as incomer and outgoing, 1
C4 a) no. of 32A single-pole power contactor, one no. 24-hours modular type analog timer switch with Set. 2
3-position changeover, all complete as per specifications, drawings and / or as directed by the
Engineer-in-charge.

CONTRACTOR No.OF CORRECTIONS


Page 19

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of automatic timer control unit with suitable
enclosure for street lighting/geyser/motor control with one no. each 32A triple-pole MCB as
b) incomer and outgoing, 1 no. of 32A triple-pole power contactor, one no. 24-hours modular type Set. 2
analog timer switch with 3-position changeover, all complete as per specifications, drawings and
/ or as directed by the Engineer-in-charge.

Supply, installation, testing and commissioning of automatic timer control unit with suitable
enclosure for street lighting/geyser/motor control with one no. each 63A triple-pole MCB as
c) incomer and outgoing, 1 no. of 63A triple-pole power contactor, one no. 24-hours modular type Set. 2
analog timer switch with 3-position changeover, all complete as per specifications, drawings and
/ or as directed by the Engineer-in-charge.

Supply, installation, testing and commissioning of astronomical time switch with suitable
enclosure of following configuration to be mounted in feeder pillars / lighting DBs for automatic
switching On & Off of street lights at sun set & sun rise automatic timer control unit for street
d) lighting with one no. each 16A single-pole MCB as incomer and outgoing, 1 no. of 16A single-
pole power contactor, one no. 24-hours modular type analog timer switch with 3-position
changeover, all complete as per specifications, drawings and / or as directed by the Engineer-in-
charge.

i) One output per phase and suitable for single phase supply. Set. 3
ii) Three output (one output per phase) and suitable for single phase supply. Set. 1

CONTRACTOR No.OF CORRECTIONS


Page 20

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of single phase digital metering with necessary
(direct/CT) arrangements, RS232/RS485 port compatibility, suitable metal enclosure and
C5 required fixing accessories etc. The item including necessary chipping/cutting the wall and Nos. 1
making good the same in case of flush mounting as required. All complete as per specifications,
drawings and / or as directed by the Engineer:

Supply, installation, testing and commissioning of microwave technology based occupancy


sensor having high performance, non regulating programmable type, suitable for connected load
C6 upto 10A, for mounting height upto 2.6 mtr and for 5m x 20m coverage area along with Nos. 5
necessary fixing arrangements i/c programming at site etc. all complete as per specifications,
drawings and / or as directed by the Engineer-in-charge.

Supply and installation of 76 mm diameter tubular MS street lighting pole of following height pre-
fabricated with a welded MS base plate of 300 x 300 x 6mm size, concealed junction box
incorporating 16A 4-way terminal, 6A MCB and other accessories for loop in and loop out of
cables, set of suitable length 40 mm dia GI pipes at the bottom for cable entry, 3 core 2.5
C7
sq.mm. PVC flexible cable connection to the lighting fixture at top, 8 SWG copper coil earthing,
450 x 450 x 900 mm deep pedestal in cement concrete 1:2:4, complete including excavation
and backfilling, fixing in position with approved hardware, etc., as per as per specifications and /
or directed by the Engineer-in-charge.

a) 3 meter length Nos. 2


b) 4 meter length Nos. 3

CONTRACTOR No.OF CORRECTIONS


Page 21

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
c) 6 meter length Nos. RO

Fabrication, supply and installation of tubular street lighting pole of following length fabricated
out of MS pipes of various diameters and swaged as per standards. A junction box incorporating
16A 4-way terminal, 6A MCB and other accessories shall be fixed to the pole for loop in & loop
out of cable. PVC flexible cable connection to the lighting fixture at top, 8 SWG copper coil
earthing, set of 50mm GI pipe of required length shall be provided at the bottom of the pole for
C8
cable entry to the junction box with the following type outreach curved bracket. The bottom of
the pole will have a base plate of size 350 x 350 x 10mm MS plate welded to the pole. The base
plate shall be fixed on 600 x 600 x 1500 mm deep pedestal in cement concrete 1:2:4, complete
including excavation and backfilling, fixing in position with approved hardware etc., as per as per
specifications and / or directed by the Engineer-in-charge.

a) 7 meter with singlr outreach curved bracket Nos. 10


b) 7 meter with double outreach curved bracket Nos. RO

CONTRACTOR No.OF CORRECTIONS


Page 22

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Fabrication, supply and installation of tubular street lighting pole of following length fabricated
out of MS pipes of various diameters and swaged as per standards. A junction box incorporating
16A 4-way terminal, 6A MCB and other accessories shall be fixed to the pole for loop in & loop
out of cable. PVC flexible cable connection to the lighting fixture at top, 8 SWG copper coil
earthing, set of 50mm GI pipe of required length shall be provided at the bottom of the pole for
C9 Nos. RO
cable entry to the junction box with the following type outreach curved bracket. The bottom of
the pole will have a base plate of size 350 x 350 x 10mm MS plate welded to the pole. The base
plate shall be fixed on 600 x 600 x 1500 mm deep pedestal in cement concrete 1:2:4, complete
including excavation and backfilling, fixing in position with approved hardware etc., as per as per
specifications and / or directed by the Engineer-in-charge.

TOTAL CARRIED OVER TO SUMMARY (Part - C)

PART - D LT PANELS

Supply, installation, testing and commissioning of 415V cubical type, fully compartmenalised,
floor mounted type main switch board fabricated with 14G CRCA sheet, powder coated with
D1
Siemens grey (RAL 7032) after seven tank process and complete with bolted and welded design
and all incoming & outgoing switch gears as per the following.

Suitable aluminuim busbars, bus couplers, control wiring, control fuses, seperate metering
compartment with multi function meter and phase indications.

CONTRACTOR No.OF CORRECTIONS


Page 23

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Electrical and mechanical interlocking facility between DG incomers & bus coupler and between
EB-DG outgoings.

Safety features and items including necessary earthing throughout the bottom length, 6 sq.mm
FRLS copper wire interconnections for compartment earthing, complete copper control wiring
with crimping type ferrules, copper lugs, proper engravation on each compartment etc.

The switch boards shall be CPRI approved of factory assembled and tested.

Current density not more than 0.7 or 0.8A/sq.mm for Aluminium bus bar. Neutral current rating
is half the phase current

All busbars shall be fixed with standard space clearance and with colour coated heat shrinkable
PVC sleeves with DMC/SMC bus bar supports and suitable earth bus (25 x 3mm Cu).

The cable entry shall be from the bottom/top as per site requirement.

The item including cost of MS base frame of 75mm height, 3.15mm sheet steel or 40x40x6mm
MS angle for load bearing members, lifting hooks, steel support structure required for erection
and its painting, minor civil works, vendor drawings, necessary safety clearance from statutory
authorities, panel approval from TNEB/TANGEDCO till obtaining final power supply, all complete
as per specifications, drawings and / or as directed by the Engineer.

CONTRACTOR No.OF CORRECTIONS


Page 24

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

The contractor shall submit general arrangement & control wiring drawings and get approval
from site Engineer/Consultant before commence the fabrication works.

a) MV PANEL

1000A, FP, 50KA, EDO Air Circuit Breaker with O/L,S/C,E/F protections - 1 nos. as EB
i)
incomer

400A, FP, 36KA, MCCB with micro processor releases and rotary handle mechanism &
ii)
spreader - 2 Nos. as DG incomer.

400A, FP, 36KA, MCCB with micro processor releases and rotary handle mechanism &
iii)
spreader - 1 No. as DG Bus coupler.

Phase indication lamps(R,Y,B) - 3 set.

ON/OFF/TRIP Indication lamps - 3 set.

CT ratio 1000/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 1
Set.

CT ratio 400/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 2
Set.

CONTRACTOR No.OF CORRECTIONS


Page 25

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &


Phase sequence. - 3 Set

Busbar:

i) 1000A, TPN, 50KA, for 1 sec Aluminium bus bars - EB bus bar

ii) 400A, TPN, 36KA, for 1 sec Aluminium bus bars - DG bus bar

iii) Phase: current density not more than 0.7A/sq.mm

iv) Neutral: half of the phase current (0.5 x phase)

v) Earth: 25x6mm copper flat

Outgoing:

400A, FP, 36KA, MCCB with micro processor releases and rotary handle mechanism &
i)
spreader - 2 pair.
250A, FP, 36KA, MCCB with micro processor releases and rotary handle mechanism &
ii)
spreader - 4 pair.
200A, FP, 36KA, MCCB with micro processor releases and rotary handle mechanism &
iii)
spreader - 2 pair.
400A, TPN, 36KA, MCCB with micro processor releases and rotary handle mechanism &
iv) Set. 1
spreader - 1 no.

CONTRACTOR No.OF CORRECTIONS


Page 26

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
b) DG PANEL

Incomer -

i) 400A, FP SDF with DIN type fuse links - 2 nos. as DG 1 & 2

ii) 400A, FP SDF with DIN type fuse links - 1 no. as DG Buscoupler.

CT ratio 400/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 2 set.

Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &


Phase sequence. - 2 set.

Busbar:

i) 400A, TPN, 50KA, for 1 sec Aluminium bus bars

Phase: current density not more than 0.8A/sq.mm

Neutral: half of the phase current (0.5 x phase)

Earth: 25x3mm copper flat

Outgoings:-

i) 400A, TPN SDF with DIN type fuse links - 2 nos.

ii) 250A, TPN SDF with DIN type fuse links - 1 no.

iii) 200A, TPN SDF with DIN type fuse links - 1 no.

iv) 100A, TPN SDF with DIN type fuse links - 1 no. Set. 1

CONTRACTOR No.OF CORRECTIONS


Page 27

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

c) ACSB (Outdoor Type Panel)

Incomer:

i) 400A, FP, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 set.

ON/OFF/TRIP Indication lamps - 1 set.

CT ratio 400/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.

Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &


Phase sequence. - 1 set.

Bus bar:

400A, TPN, 36KA, for 1 sec Aluminium bus bar

i) Phase: current density not more than .8A/sq.mm

ii) Neutral: half of the phase current (0.5 x phase)

iii) Earth: 25x3mm copper flat

Outgoing:

250A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader -1 Nos.
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 2 Nos.

CONTRACTOR No.OF CORRECTIONS


Page 28

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iii) Set. 1
spreader - 3 Nos.

d) EQUIPMENTSB

Incomer:

400A, FP, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.

Phase indication lamps(R,Y,B) - 1 set.

ON/OFF/TRIP Indication lamps - 1 set.

CT ratio 400/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.

Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &


Phase sequence. - 1 set.

Bus bar:

400A, TPN, 36KA, for 1 sec Aluminium bus bar

i) Phase: current density not more than .8A/sq.mm

CONTRACTOR No.OF CORRECTIONS


Page 29

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

ii) Neutral: half of the phase current (0.5 x phase)

iii) Earth: 25x3mm copper flat

Outgoing:
250A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader -1 Nos.
200A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader -1 Nos.
160A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iii)
spreader - 1 Nos.
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iv) Set. 1
spreader - 3 Nos.

e) ACSSB (Outdoor Type Panel)


Incomer:
250A, FP, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 250/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Bus bar:

CONTRACTOR No.OF CORRECTIONS


Page 30

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
250A, TPN, 36KA, for 1 sec Aluminium bus bar
i) Phase: current density not more than .8A/sq.mm
ii) Neutral: half of the phase current (0.5 x phase)
iii) Earth: 25x3mm copper flat
Outgoing:

100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i) Set. 1
spreader - 8 Nos.

f) MPSB

Incomer -

250A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.

Phase indication lamps(R,Y,B) - 1 set.

ON/OFF/TRIP Indication lamps - 1 set.

CT ratio 250/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.

Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &


Phase sequence. - 1 set.

Busbar:
i) 250A, TPN, 36KA, for 1 sec Aluminium bus bars
Phase: current density not more than 0.8A/sq.mm

CONTRACTOR No.OF CORRECTIONS


Page 31

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Neutral: half of the phase current (0.5 x phase)
Earth: 25x3mm copper flat
Outgoings:-
200A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 Nos.
160A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 Nos.
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iii)
spreader - 4 Nos.
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iv) Set. 1
spreader - 3 Nos.

g) MLSB
Incomer:
250A, FP, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 250/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Bus bar:
250A, TPN, 36KA, for 1 sec Aluminium bus bar
i) Phase: current density not more than .8A/sq.mm

CONTRACTOR No.OF CORRECTIONS


Page 32

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
ii) Neutral: half of the phase current (0.5 x phase)
iii) Earth: 25x3mm copper flat
Outgoing:
200A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 Nos.
100A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 Nos.
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iii) Set. 1
spreader - 6 Nos.

h) UTILITYSB
Incomer -
200A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 Nos.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 200/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence.
Busbar:
i) 200A, TPN, 36KA, for 1 sec Aluminium bus bars
Phase: current density not more than 0.8A/sq.mm

CONTRACTOR No.OF CORRECTIONS


Page 33

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Neutral: half of the phase current (0.5 x phase)
Earth: 25x3mm copper flat
Outgoings:-
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 4 Nos.
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii) Set. 1
spreader - 3 Nos.

i) PUMPSB
Incomer -
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 100/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Busbar:
i) 100A, TPN, 25KA, for 1 sec Aluminium bus bars
Phase: current density not more than 0.8A/sq.mm
Neutral: half of the phase current (0.5 x phase)
Earth: 25x3mm copper flat

CONTRACTOR No.OF CORRECTIONS


Page 34

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Outgoings:-
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 No.
40A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii) Set. 1
spreader - 5 Nos.

j) ELSB - LIGHTING (wall mounted - compartmentalised DB)


Incomer -
i) 63A, DP, 10KA, MCB 'C' Curve - 1 No.
Outgoings:-
i) 25A, DP, 10KA, MCB 'C' Curve - 9 Nos. Set. 1

k) UPS SB - 1 COMPUTER (wall mounted - compartmentalised DB)


Incomer -
i) 100A, FP, 10KA, MCB 'C' Curve - 1 No.
Outgoings:-
i) 63A, FP, 10KA, MCB 'C' Curve - 3 Nos.
ii) 40A, FP, 10KA, MCB 'C' Curve - 1 Nos.
iii) 25A, DP, 10KA, MCB 'C' Curve - 7 Nos. Set. 1

l) UPS SB - 2 (OT)

CONTRACTOR No.OF CORRECTIONS


Page 35

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Incomer:
63A 4P 18KA on load Auto Transfer Switch with ON delay Timer, Auxillary relay/contactor,
i) single phase preventer, control MCB's, ON/OFF push buttons, MFn meter, phase indications
etc. - 1 No.
63A, FP, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 No.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 63/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Bus bar:
63A, TPN, 18KA, for 1 sec Aluminium bus bar
i) Phase: current density not more than .8A/sq.mm
ii) Neutral: half of the phase current (0.5 x phase)
iii) Earth: 25x3mm copper flat
Outgoing:
i) 32A, TPN, 10KA, MCB 'C' Curve - 6 Nos.
ii) 25A, SPN, 10KA, MCB 'C' Curve - 2 Nos. Set. 1

m) 100KVAR APFC Panel


Incomer -

CONTRACTOR No.OF CORRECTIONS


Page 36

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
400A, TP, SDF with DIN type fuse links - 1 No.
Phase indication lamps(R,Y,B) - 1 set.
CT ratio 400/1A,CL:1.0 tape insulated type with suitable sorting links
Metering:Multifunction meters cl:1.0 measured with following parameters:V,I,PF,KW,KWh.
Outgoing:-
Each bank provide with stage incomers,and on indication lamp
Microprocessor based APFC relay with 8 stages
Type of control:Capcitor duty contactors
Capacitors:Type-cylindrical gas filled and consider upto 5kvar heavy duty type,voltage:440V
i) 25KVAR with 63A TP MCB - 1 Nos.
ii) 20KVAR with 63A TP MCB - 2 Nos.
iii) 10KVAR with 63A TP MCB - 1 Nos.
iv) 7.5KVAR with 63A TP MCB - 2 Nos.
v) 5KVAR with 32A TP MCB - 2 Nos.
vi) APFC controller with 8 stages - 1 No. Set. 1

n) LIFT SB
Incomer:
100A 4P 25KA on load Auto Transfer Switch with ON delay Timer, Auxillary relay/contactor,
i) single phase preventer, control MCB's, ON/OFF push buttons, MFn meter, phase indications
etc. - 1 No.

CONTRACTOR No.OF CORRECTIONS


Page 37

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
100A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 Nos.
Phase indication lamps(R,Y,B) - 1 set.
ON/OFF/TRIP Indication lamps - 1 set.
CT ratio 100/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 1
Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Bus bar:
100A, TPN, 25KA, for 1 sec Aluminium bus bar
i) Phase: current density not more than .8A/sq.mm
ii) Neutral: half of the phase current (0.5 x phase)
iii) Earth: 25x3mm copper flat
Outgoing:
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i) Set. 1
spreader - 5 Nos.

CONTRACTOR No.OF CORRECTIONS


Page 38

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
o) FIRE FIGHTING PANEL
Incomer:
200A 4P 36KA on load Auto Transfer Switch with ON delay Timer, Auxillary relay/contactor,
i) single phase preventer, control MCB's, ON/OFF push buttons, MFn meter, phase indications
etc. - 1 No.
200A, TPN, 36KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 Nos.
Metering:
i) CT ratio 200/5A,CL:1.0 tape insulated type with suitable sorting links..
Multi function meter complete compatible with BMS,EMS & RS485 integration and phase
ii)
indications.
Bus bar:
200A, TPN, 36KA, for 1 sec Aluminium bus bar
i) Phase: current density not more than .8A/sq.mm
ii) Neutral: half of the phase current (0.5 x phase)
iii) Earth: 25x3mm copper flat
Outgoing:
160A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
i)
spreader - 1 Nos.
125A, TPN, 25KA, MCCB with thermal magnetic releases and rotary handle mechanism &
ii)
spreader - 1 Nos.
63A, TPN, 18KA, MCCB with thermal magnetic releases and rotary handle mechanism &
iii) Set. 1
spreader - 2 Nos.

CONTRACTOR No.OF CORRECTIONS


Page 39

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

p) LSB - 6thF & PSB 6thF


Incomer
i) 63A 4P manual change over switch - 1 No.
ii) 63A, FP, 10KA, MCB 'C' Curve - 1 No.
Phase indication lamps(R,Y,B) - 2 set.
ON/OFF/TRIP Indication lamps - 2 set.
CT ratio 63/5A,CL:1.0 tape insulated bar primary type with suitable sorting links. - 3Nos. - 1 Set.
Metering:Multifunction meters cl:1.0 measured with following parameters: V,A,F,PF,KW,KWH &
Phase sequence. - 1 set.
Bus bar:
i) 63A, TPN, 10KA, for 1 sec Aluminium bus bar
ii) Phase: current density not more than 0.8A/sq.mm
Neutral: half of the phase current (0.5 x phase)
Outgoing:
i) 32A FP 10KA MCB 'C' Curve - 4 Nos Set. 2

Supply, installation, testing and commissioning of following ratings of 415V 4P Manual Change
Over Switch panel fabricated with 14G CRCA sheet steel and powder coated. The item including
D2
cost of supply and erection of control wiring, phase indication and necessary supporting
structures (steel frame with painting of required size) & fixing accessories etc.

CONTRACTOR No.OF CORRECTIONS


Page 40

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
i) 63A Set. 10
ii) 200A Set. RO
iii) 250A Set. RO

Supply, installation, testing and commissioning of following ratings of 415V 4P ATS panel
fabricated with 14G CRCA sheet steel and powder coated. The item including cost of supply and
D3
erection of control wiring, phase indication and necessary supporting structures (steel frame with
painting of required size) & fixing accessories etc.

i) 200A Set. RO
ii) 400A Set. RO

Supply and installation of following ratings of DOL staretr with manual start & stop push buttons
D4 and ON/OFF/TRIP indication lamp with metal enclosure and all necessary fixing accessories
etc.
i) 2HP Set. 3
ii) 3HP Set. 3
iii) 5HP Set. 2
iii) 7.5HP Set. 2

TOTAL CARRIED OVER TO SUMMARY (Part - D)

CONTRACTOR No.OF CORRECTIONS


Page 41

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - E RISING MAIN

Supply, installation, testing and commissioning of rising main of standard make, with 433V, 3-
phase, 4-wire, compact airinsulated/sandwich type aluminium bus bars with supports, suitable
for temperature rise of 55 deg over an ambient of 40 deg, jointing of bus bars, spring hanger at
E1 every floor, end cover, fire barriers at each level / floor, MS angle iron frames and brackets
mounted on and grouted into the walls, tap off boxes at each level / floor etc. The item including
two runs of 25x3mm cu earth flat throughout the length. all complete as per specifications,
drawings and / or as directed by the Engineer-in-charge.

Straight Runs: 200A 4P, 4W, indoor, airinsulated/sandwich type aluminium Rising Main with two
runs of copper earthing, Plug in Points & plug outlet cover at every 500mm with Fire Barries,
a) Mts 56
vertical brackets at every 1.5m intervels, Flange end, end cover and copper flexible jumper upto
300mm length at joints etc.

Plug in type Tap Off boxes complete with one number 63A 4P MCCB with thermal magnetic
b) Nos 12
releases, interconnections and required terminal arrangement with all complete.

Plug in type Tap Off boxes complete with Two number of 63A 4P MCCB with thermal magnetic
c) Nos 6
releases, interconnections and required terminal arrangement with all complete.

End feed unit of 200A 4P 36KA MCCB with thermal magnetic releases, interconnections and
d) Nos 3
required terminal arrangement with all complete.

TOTAL CARRIED OVER TO SUMMARY - (PART-E)

CONTRACTOR No.OF CORRECTIONS


Page 42

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

PART - F HT & LT CABLING

Supply along with test certificate, laying, testing and commissioning of following sizes of HT
XLPE Aluminium cable, without any cable joint in pre-excavated / pre-formed trenches or drawn
through GI pipe sleeves / hume pipes etc. The item including cost of clamping arrangements,
F1 a)
fixing accessories, cable route markers, cable ties, identification tags etc. all complete as per
specifications, drawings and / or as directed by the Engineer. (All complete as required by
TNEB/TANGEDCO)

i) 11KV, 3C x 120 Sq.mm XLPE Al cable R. mtr. RO


ii) 11KV, 3C x 185 Sq.mm XLPE Al cable R. mtr. 100

Supply, termination, testing and commissioning of following sizes of 11KV outdoor type heat
b) shrinkable trifurcating cable kits with necessary fixing accessories. (All complete as required by
TNEB/TANGEDCO)

i) 11KV, 3C x 120 Sq.mm XLPE Al cable Set. RO


ii) 11KV, 3C x 185 Sq.mm XLPE Al cable Set. 2

Supply, termination, testing and commissioning of following sizes of 11KV indoor type heat
c) shrinkable trifurcating cable kits with necessary fixing accessories. (All complete as required by
TNEB/TANGEDCO)
i) 11KV, 3C x 120 Sq.mm XLPE Al cable Set. RO
ii) 11KV, 3C x 185 Sq.mm XLPE Al cable Set. 2

CONTRACTOR No.OF CORRECTIONS


Page 43

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying, testing and commissioning of following 1.1KV grade multicore aluminium
conductor XLPE/PVC insulated GI round(upto 10sqmm) / flat(16sqmm and above) armoured
PVC sheathed cables (without any cable joint) drawn through tray or steel supports or clamping
F2 on the ceiling/wall or pre-excavated / pre-formed trenches or GI pipe sleeves / hume pipes with
suitable clamping arrangement and fixing accessories, cable route markers, cable ties,
identification tags etc. all complete as per specifications, drawings and / or as directed by the
Engineer.

a) 3.5C x 400 sq.mm Aluminium XLPE cable R. mtr. 320


b) 3.5C x 300 sq.mm Aluminium XLPE cable R. mtr. RO
c) 3.5C x 240 sq.mm Aluminium XLPE cable R. mtr. 55
d) 3.5C x 185 sq.mm Aluminium XLPE cable R. mtr. 15
e) 3.5C x 150 sq.mm Aluminium XLPE cable R. mtr. 35
f) 3.5C x 120 sq.mm Aluminium XLPE cable R. mtr. 75
g) 3.5C x 95 sq.mm Aluminium XLPE cable R. mtr. 20
h) 3.5C x 70 sq.mm Aluminium XLPE cable R. mtr. 20
i) 3.5C x 50 sq.mm Aluminium XLPE cable R. mtr. 125
j) 3.5C x 35 sq.mm Aluminium XLPE cable R. mtr. 75
k) 4C x 35 sq.mm Aluminium XLPE cable R. mtr. RO
l) 3.5C x 25 sq.mm Aluminium XLPE cable R. mtr. 105
m) 4C x 25 sq.mm Aluminium XLPE cable R. mtr. 170
n) 4C x 16 sq.mm Aluminium XLPE cable R. mtr. 450

CONTRACTOR No.OF CORRECTIONS


Page 44

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
o) 4C x 10 sq.mm Aluminium cable R. mtr. 125
p) 4C x 6 sq.mm Aluminium cable R. mtr. 95
q) 4C x 4 sq.mm Aluminium cable R. mtr. 20
r) 4C x 2.5 sq.mm Aluminium cable R. mtr. RO
s) 3C x 10 sq.mm Aluminium cable R. mtr. 15
t) 3C x 6 sq.mm Aluminium cable R. mtr. 455
u) 3C x 2.5 sq.mm Aluminium cable R. mtr. RO

Supply, laying, testing and commissioning of following 1.1KV grade multicore copper conductor
XLPE/PVC insulated GI round(upto 10sqmm) / flat(16sqmm and above) armoured PVC
sheathed cables (without any cable joint) drawn through tray or steel supports or clamping on
F3 the ceiling/wall or pre-excavated / pre-formed trenches or GI pipe sleeves / hume pipes with
suitable clamping arrangement and fixing accessories, cable route markers, cable ties,
identification tags etc. all complete as per specifications, drawings and / or as directed by the
Engineer.

a) 4C x 35 sq.mm copper XLPE cable R. mtr. RO


b) 4C x 25 sq.mm copper XLPE cable R. mtr. RO
c) 4C x 16 sq.mm copper XLPE cable R. mtr. 90
d) 4C x 10 sq.mm copper XLPE cable R. mtr. 25
e) 4C x 6 sq.mm copper XLPE cable R. mtr. 20
f) 4C x 4 sq.mm copper XLPE cable R. mtr. 10
g) 4C x 2.5 sq.mm copper XLPE cable R. mtr. 10

CONTRACTOR No.OF CORRECTIONS


Page 45

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying, testing and commissioning of following 1.1KV grade multicore copper control
cables without any cable joint drawn through tray or on steel supports or clamping on the
F4 ceiling/wall or pre-excavated / pre-formed trenches or GI pipe sleeves / hume pipes with suitable
clamping arrangement and fixing accessories, cable route markers, cable ties, identification tags
etc. all complete as per specifications, drawings and / or as directed by the Engineer.

a) 2C x 2.5 Sqmm cable R. mtr. 20


b) 2C x 4 Sqmm cable R. mtr. 20
c) 4C x 2.5 Sqmm cable R. mtr. 15
d) 12C x 1.5 Sqmm cable R. mtr. 30
e) 16C x 1.5 sq.mm copper armoured cable R. mtr. 40

Supply and termination of the following sizes of 1.1KV XLPE/PVC insulated Al/Cu conductor
cables with single compression brass cable glands and tinned copper lugs including gland earth
F5
clips, adequate size of bare copper wire connecting to the main bus bars etc. all complete as per
specifications, drawings and / or as directed by the Engineer.

a) 3.5C x 400 sq.mm Aluminium XLPE cable Nos. 16


b) 3.5C x 300 sq.mm Aluminium XLPE cable Nos. RO
c) 3.5C x 240 sq.mm Aluminium XLPE cable Nos. 4
d) 3.5C x 185 sq.mm Aluminium XLPE cable Nos. 2
e) 3.5C x 150 sq.mm Aluminium XLPE cable Nos. 4

CONTRACTOR No.OF CORRECTIONS


Page 46

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
f) 3.5C x 120 sq.mm Aluminium XLPE cable Nos. 8
g) 3.5C x 95 sq.mm Aluminium XLPE cable Nos. 2
i) 3.5C x 70 sq.mm Aluminium XLPE cable Nos. 2
j) 3.5C x 50 sq.mm Aluminium XLPE cable Nos. 10
k) 3.5C x 35 sq.mm Aluminium XLPE cable Nos. 8
l) 4C x 35 sq.mm Aluminium XLPE cable Nos. RO
m) 3.5C x 25 sq.mm Aluminium XLPE cable Nos. 14
n) 4C x 25 sq.mm Aluminium XLPE cable Nos. 26
o) 4C x 16 sq.mm Aluminium XLPE cable Nos. 54
p) 4C x 10 sq.mm Aluminium cable Nos. 10
q) 4C x 6 sq.mm Aluminium cable Nos. 10
r) 4C x 4 sq.mm Aluminium cable Nos. 4
s) 4C x 2.5 sq.mm Aluminium cable Nos. 2
t) 3C x 2.5 sq.mm Aluminium cable Nos. RO
u) 3C x 10 sq.mm Aluminium cable Nos. 2
v) 3C x 6 sq.mm Aluminium cable Nos. 32
w) 2C x 2.5 Sqmm cable Nos. 6
x) 2C x 4 Sqmm cable Nos. 4
y) 12C x 1.5 Sqmm cable Nos. 6
z) 16C x 1.5 sq.mm copper armoured cable Nos. 4

CONTRACTOR No.OF CORRECTIONS


Page 47

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Supply and erection of following size of hot dip GI ladder type cable trays including horizontal
and vertical bends, reducers, tees, right angles, cross members and other accessories etc. The
item including cost of steel support structures at every 0.6m/1m intervels as required for
F6
suspend from the ceiling or supported from walls with MS suspenders/brackets and all complete
with painting/powder coating etc. all complete as per the specifications / drawings ad or as
directed by the Engineer.

a) 150 x 50 x 2mm R. mtr. 25


b) 200 x 50 x 2mm R. mtr. 10
c) 300 x 50 x 2mm R. mtr. 100
d) 450 x 75 x 2mm R. mtr. 40
e) 600 x 75 x 2mm R. mtr. 50

Supply and erection of following size of perforated GI cable trays including horizontal and
vertical bends, reducers, tees, right angles, cross members and other accessoriess etc. The
item including cost of steel support structures at every 0.6m/1m intervels as required for
F7
suspend from the ceiling or supported from walls with MS suspenders/brackets and all complete
with painting/powder coating etc. all complete as per the specifications / drawings ad or as
directed by the Engineer.

a) 150 x 50 x 2mm without cover R. mtr. 25


b) 150 x 50 x 2mm with cover R. mtr. 25
c) 200 x 50 x 2mm without cover R. mtr. 25
d) 200 x 50 x 2mm with cover R. mtr. 250

CONTRACTOR No.OF CORRECTIONS


Page 48

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
e) 300 x 50 x 2mm without cover R. mtr. 250
f) 300 x 50 x 2mm with cover R. mtr. 25
g) 450 x 75 x 2mm without cover R. mtr. RO
h) 450 x 75 x 2mm with cover R. mtr. RO
k) 600 x 75 x 2mm without cover R. mtr. RO

Providing earthen cable trenches, including necessary excavation, supply and placing in position
F8 of sand, bricks / PCC protective slabs, cable markers and backfilling in compacted layers, all
complete as per specifications, drawings and /or as directed by the Engineer.

i) 750 mm wide x 1200 mm deep for HT cables R. mtr. 25


ii) 750 mm wide x 800 mm deep for LT cables R. mtr. 50
iii) 450 mm wide x 800 mm deep for LT cables R. mtr. 130

Supply, installation of following sizes of Class-B GI pipe sleeves for cable crossing of drains,
F9 roads, sanitary and water supply lines and the like, all complete as per specifications, drawings
and / or as directed by the Engineer.

i) 50mm dia R. mtr. 20


ii) 100mm dia R. mtr. 15
iii) 150mm dia R. mtr. 15

CONTRACTOR No.OF CORRECTIONS


Page 49

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Supply, installation of following sizes of hume pipes for cable crossing of drains, roads, sanitary
F10 and water supply lines and the like, all complete as per specifications, drawings and / or as
directed by the Engineer.
i) 300mm dia R. mtr. 20
ii) 450mm dia R. mtr. 15
iii) 600mm dia R. mtr. 10

TOTAL CARRIED OVER TO SUMMARY (Part - F)

CONTRACTOR No.OF CORRECTIONS


Page 50

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - G DIESEL GENERATOR

Supply, installation, testing and commissioning of following ratings of DG set with standard
accessories coupled to alternator, 3 phase, 4 wire, 0.8 PF (lag), 415 V mounted on a channel
iron base frame with foot mounting AVM pads, Fuel tank (In Built), Charged battery with leads,
hospital type silencer along with exhaust stack upto 20mtr height with support steel structure &
G1
painting, Composite type acoustic enclosure and standard control panel. The governor shall be
of electronic & mechanical type and the items including auto start (remote) facility with control
panel and complete with necessary control wiring/cabling, metering, indication lamps and fixing
accessories etc.

i) 125KVA Set. RO
ii) 160KVA Set. RO
iii) 200KVA Set. 1
iv) 250KVA Set. 1

TOTAL CARRIED OVER TO SUMMARY (Part - G)

PART - H UNITISED SUB-STATION

CONTRACTOR No.OF CORRECTIONS


Page 51

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of 11KV/433V, 630KVA outdoor type unitised
substation consists of 3 phase, Vector DYN-11, 630KVA cast resin dry type Transformer with
on-load tappings from +5% to -15% in steps of 1.25%, changeable by tap links. The HV side is
H1 connected with 11KV, 630A 25KA draw out type vaccum circuit breaker through wall through
bushing and the LV side is connected 1000A, FP, 50KA, EDO Air Circuit Breaker with
O/L,S/C,E/F protections etc. through copper busbar. The items including necessary fixing
accessories, surge arrester, NCT and with all complete as required.

a) Rated Voltage
HV Windings - 11 KV
LV Windings - 433 V
No load voltage ratio - 11 KV/ 433 V
Rated Frequency - 50 Hz
b) Temperature rise

CONTRACTOR No.OF CORRECTIONS


Page 52

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Winding by resistance - 55 ºC (above ambient temperature)
Number of phases - THREE
c) Winding Connections
HV Windings - DELTA
LV Windings - STAR
Winding - Copper
Vector Group - Dyn 11
d) Terminal arangement
Primary - 11 KV bushing [cable end box]
Secondary - 433V bushing [cable end box]
Core lamination material - Cold Rolled Grain Oriented Core
Type of winding insulation - DPC of class A insulation
e) Tap Changes
Losse - as per energy efficient (level 2)
f) Tap Changes
Type - On-load tap changing
Range - +5% to -15% through RTCC panel
Steps - 17 steps & in steps of 1.25% Set. 1

TOTAL CARRIED OVER TO SUMMARY (Part - H)

CONTRACTOR No.OF CORRECTIONS


Page 53

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - I HT BREAKERS

Design, supply, installation, testing and commissioning of 630A, 350MVA, 11KV, 25KA, outdoor,
RMG panel with copper bus bar consisting two numbers load break switch as incomer and one
number draw out type VCB as outgoing with HT metering arrangement along with necessary CT
I1 Set. 1
& PT arrangements and all complete as required by TNEB. The item including all breaker and
transformer protections and necessary safety accessories etc. All complete as per
specifications, drawing and/or as required by TNEB/TANGEDCO.

CONTRACTOR No.OF CORRECTIONS


Page 54

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Design, supply, installation, testing and commissioningof 630A, 350MVA, 11KV, 25KA, outdoor
type draw out type VCB with HT metering arrangement along with necessary CT & PT
I2 arrangements and all complete as required by TNEB/TANGEDCO. The item including all Set. RO
transformer protections and necessary safety accessories etc. All complete as per
specifications, drawing and/or as required by TNEB.

Design, supply and erection of stand alone outdoor type 11KV HT metering cubicle with CT &
PT arrangements along with provision for fixing one number of digital Trivector Meter for
TNEB/TANGEDCO tariff application. Also the cost inclusive of required control cabling for
I3 Set. RO
protections, civil works and providing necessary support structure/frames with painting as
required for erection. All complete as per specifications, drawing and/or as required by
TNEB/TANGEDCO.

TOTAL CARRIED OVER TO SUMMARY - (PART-I)

PART - J EARTHING

CONTRACTOR No.OF CORRECTIONS


Page 55

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, installation, testing and commissioning of earth station comprising of 50mm outer
diameter and 3 meter length of copper safe earth electrode, including approved clamps, bolts &
nuts, 450m x 450mm brick masonary chamber, heavy duty CI cover, homogeneous layers of
J1 Nos. 6
earth enhancing backfilling materials (bentonite/fly ash) are placed around the earth pipe as per
standards (IS 3043), the items including cost of excavation, backfilling of earth etc. all complete
as per specifications, drawings and / or as directed by the Engineer.

Supply, installation, testing and commissioning of maintenance free-earth station comprising


approved make pointed-end copper-bonded steel-core earthing rods with at least 0.25mm
copper thickness, 23mm diameter and 6 meter length from ground surface, using threaded
couplers for rod lengths, including approved clamps, bolts, nuts, 150mm dia tube well screen
J2 Nos. 20
pipe for total depth, special backfill compound (bentonite/fly ash) within pipe, 450mm x 450mm
brick masonary chamber, heavy duty RCC / CI cover, drilling into all types of earth and rock, any
excavation and backfilling, all complete as per specifications, drawings and / or as directed by
the Engineer.

Supply, laying, testing and commissioning of following sizes of the earth conductors for the
electrical system which including cost of supply and fixing of saddles, insulators, clamps,
J3
screws, bolt & nuts and providing earth work of 2' depth, sleeves wherever required etc., all
complete as per specifications, drawings and/or as directed by the Engineer.

CONTRACTOR No.OF CORRECTIONS


Page 56

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
i) 50x6mm copper flat. R. mtr. 50
ii) 25x3mm copper flat. R. mtr. 150
iii) 25x6mm copper flat. R. mtr. 50
iv) 300mm long 25x3mm copper flat. Nos. 10
v) 300mm long 25x6mm hot dipped GI flat. Nos. 10
vi) 25x3mm hot dip GI flat. R. mtr. 300
vii) 25x6mm hot dip GI flat. R. mtr. 250
viii) 50x6mm hot dip GI flat. R. mtr. RO
ix) 8 SWG copper wire. R. mtr. 450
x) 10 SWG copper wire. R. mtr. 950

TOTAL CARRIED OVER TO SUMMARY (Part - J)

CONTRACTOR No.OF CORRECTIONS


Page 57

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - K LIGHTNING PROTECTION SYSTEM

Design, supply, installation and testing of an advanced Lightning Protection system for multi-
storeyed buildings, including all accessories and consumables, inclusive of all clamping and any
K1 chipping and making good of walls, etc. and PVC / metal conduiting in floor / wall / ceiling etc.
where required, all complete as per specifications, drawings and / or as directed by the Engineer
and comprising the following:

Air Terminal, inclusive of advanced type early streamer mast (5m height with high protcetion
a) lavel ESE 60) with required support structures, adapter & termination lugs and necessary Nos. 1
jointing, painting and clamping accessories.

70 Sq.mm flexible copper cable with suitable conduit for vertical downcomers, inclusive of
b) R. mtr. 50
jointing and clamping.
c) Lightning Event Counter (lightniing strike recorder), inclusive of all accessories. Nos. 1

Maintenance-free tri-polar earth pits made of ground enhancing materials and copper bounded
ground rods, including laying of high-purity copper tape for interconnecting the pits, treating the
d) earth pit (20/25mm dia 3mtr length) with filling materials, clamps, bolts & nuts and its associated Set. 1
accessories as per standard IS, including cost of excavation, backfilling, minor civil works, and
all complete as per specifications, drawings and / or as directed by the Engineer.

CONTRACTOR No.OF CORRECTIONS


Page 58

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Supply, laying, testing and commissioning of horizontal network and vertical downcomers for
lightning protection system, inclusive of jointing, clamping, saddles at every one meter intervels,
K2
including of necessary fixing accessories etc., all complete as per specifications, drawings and /
or as directed by the Engineer.
Supplying, erecting, connecting and commissioning solid copper air terminal of 1.2 M height with
proper spike arrangement at top, base plate, jointing, supporting arrangements, clamping and
a) Nos. 1
necessary fixing accessories etc., all complete as per specifications, drawings and / or as
directed by the Engineer.
Supplying, erecting, connecting and commissioning of 25 x 3 mm copper flats for the horizontal
& vertical drops from the terrace level to test link which mounted at 1000mm heigh from the
b) R. mtr. 15
finished ground level. The flats shall be fixed with epoxy resin insulator used as spacer. The
spacer shall be fixed with self threading screws and it shall be fixed at every 1000mm intervels.

Supplying, erecting, connecting and commissioning of 25 x 6 mm GI flats for the horizontal &
vertical drops from the terrace level to test link which mounted at 1000mm heigh from the
c) R. mtr. 10
finished ground level. The flats shall be fixed with epoxy resin insulator used as spacer. The
spacer shall be fixed with self threading screws and it shall be fixed at every 1000mm intervels.

25 x 6 mm copper flats for the vertical drops from the test link to the ground and upto earth
electrodes, including necessary excavation, backfilling, fixing accessories, termination at both
d) R. mtr. 15
ends, etc. The flats shall be fixed with epoxy resin insulator used as spacer. The spacer shall be
fixed with self threading screws and it shall be fixed at every 1000mm intervels.

CONTRACTOR No.OF CORRECTIONS


Page 59

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
40 x 6 mm GI flats for the vertical drops from the test link to the ground and upto earth
electrodes, including necessary excavation, backfilling, fixing accessories, termination at both
e) R. mtr. 10
ends, etc. The flats shall be fixed with epoxy resin insulator used as spacer. The spacer shall be
fixed with self threading screws and it shall be fixed at every 1000mm intervels.

Supply, fixing, testing and commissioning of test links for lightning protection system, inclusive of
f) jointing and clamping, necessary fixing accessories etc., all complete as per specifications, Nos. 1
drawings and / or as directed by the Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - K)

PART - L SAFETY ACCESSORIES


Supply and installation of the following safety accessories to be installed in the Electrical Panel
L1
Room.
i) First aid box. (IS marked - as per standard requirement) Nos. 8
Supply and fixing of 6 Kgs CO2 type (ISI marked) Fire extinguisher complete with all clamps and
ii) Nos. 8
hardwares etc.
iii) Supply and fixing of 11KV danger board as per standard with all fixing accessories etc. Nos. 1
iv) Supply and fixing of 440V danger board as per standard with all fixing accessories etc. Nos. 6

Supply and position of 1.1 KV grade (as per standard) 2Mtr x 1Mtr rubber mat for LT switch
v) Nos. 10
boards to suit the switch board. (ISI marked)

Supply and position of 11 KV grade (as per standard) 2Mtr x 1Mtr rubber mat for HT switch
vi) Nos. 1
boards to suit the switch board. (ISI marked)

CONTRACTOR No.OF CORRECTIONS


Page 60

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
Supply and fixing of shock treatment/First Aid treatment chart in Tamil, Hindi and English,
vii) Nos. 5
complete with necessary fixing accessories etc.
viii) Supply of 11KV Rubber gloves. Pair 2
ix) Supply of 1.1KV Rubber gloves. Pair 2

Supply and fixing of 10Ltr capacity of 4 Nos. Fire Bucket painted as per relevant standard,
x) Nos. 2
complete with necessary clamps, screws etc.

Supply and fixing of 6mm thick MS Chequered Plates as floor separators for covering the shafts
with angle iron supports at floor level around the Rising Mains to form a complete fire barrier
xi) Kg 500
protection between two floors by sealing all gaps around the cable / rising mains etc., in the
duct.

CONTRACTOR No.OF CORRECTIONS


Page 61

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Providing structural steel work riveted, bolted or welded in built up sections, trusses and framed
xii) work, including cutting, hoisting, fixing in position and applying a primer etc. all complete as per Kg 1000
specifications, drawings and / or as directed by the Engineer-in-charge:

Supply and fixing of fire barrier (fire barrier protection) with atleast two hour fire rated by sealing
xiii) Sq. mtr. 50
all gaps around the cable/rising mains, between floors and cutout/shaft etc.

TOTAL CARRIED OVER TO SUMMARY (Part - L)

PART - M TELEPHONE SYSTEM

Supply and fixing of RJ-11 modular type telephone outlet mounted on suitable zinc-passivated
metal
M1 a) box complete with metal box, front plate, screws and fixing accessories etc., The item including Nos. 70
necessary chipping/cutting the wall and making good the same incase of recessed mounting
and all complete as per specifications, drawings and / or as directed by the Engineer.

Supply and fixing of Cat 5e modular type outlet mounted on suitable zinc-passivated metal box
complete with metal box, front plate, screws and fixing accessories etc., The item including
b) Nos. RO
necessary chipping/cutting the wall and making good the same incase of recessed mounting
and all complete as per specifications, drawings and / or as directed by the Engineer.

CONTRACTOR No.OF CORRECTIONS


Page 62

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying and termination of the following sizes of telephone cable laid in 20mm / 25mm dia
&
2mm thick PVC conduit, from EPABX to MDF, MDF to Krone junction box and KJB to various
c)
individual outlets etc. The item including the cost of supply and installation of conduits and all
necessary fixing accessories, all complete as per specifications, drawings and / or as directed
by the Engineer.

i) 2-Pair cable R. mtr. 2100


ii) 10 - Pair cable R. mtr. 45
iii) 20 - Pair cable R. mtr. 50
iv) 100 - Pair cable R. mtr. 10

Supply and fixing of following type of telephone Krone type junction boxes enclosed in MS box
d) with hinged cover with lock & key arrangements etc. The item including minor civil works as
required and all complete as per specifications, drawings and / or as directed by the Engineer.
i) 10-pair Krone type junction box Nos 3
ii) 20-pair Krone type junction box Nos 4
iii) 100-pair Krone type junction box Nos 1

CONTRACTOR No.OF CORRECTIONS


Page 63

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying and termination of high quality CAT-5E Ethernet LAN cable preferably with FR
PVC insulation to be laid in 19mm/25mm dia 1.6mm/2mm thick PVC pipe from individual
telephone/data/CCTV camera outlets to network jack/switch/patch panel/hub located in the
communication room. The items including the cost of supply and installation of conduits,
e) couplers, junction boxes, bends, ceiling/wall plates, draw boxes & top cover plate (3mm hylam R. mtr. RO
sheet), CAT 5E cables, terminations at both ends, ferrules, clamps, screws, bolt & nuts and
necessary fixing accessories etc. The item including necessary chipping/cutting the wall and
making good the same in case of recessed conduit as required. All complete as per
specifications, drawings and / or as directed by the Engineer.

Supply installation and configuration of Matrix ETERNITY IP-PBX with Universal Connectivity
and Mobile Extensions/Universal Slots:12/ Max. IP Users:500/Max. TDM Users:120/Built-in
Ports: 5 IP Users*, AIP, AOP, DIP, DOP, 2 RS232C & Ethernet/Power Supply: Universal SMPS
(100-240V AC, 47-63 Hz) Up to 100 Trunk Line /Expansion Card for T1E1/PRI port for Eternity
f) Nos 1
GE series/Expansion Card for Digital key telephone extensions(DKP) and analog
extensions(SLT) for 4+16 ports for Eternity GE Series/Expansion Card for Analog extensions
(SLT) of 20 ports for Eternity GE series or equivalent type as acceptable to the client, all
complete as per specifications and / or as direcyted by the Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - M)

CONTRACTOR No.OF CORRECTIONS


Page 64

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - N DATA NETWORKING SYSTEM

Supply and fixing of RJ-45 modular type data outlet (CAT-6A) mounted on suitable zinc-
passivated box complete with metal box, front plate, screws and fixing accessories etc. The
N1 a) item including necessary chipping/cutting the wall and making good the same in case of flush Nos. 72
mounting as required. All complete as per specifications, drawings and / or as directed by the
Engineer.

Supply, laying and termination of high quality CAT-6A Ethernet LAN cable preferably with FR
PVC insulation to be laid in 19mm/25mm dia 1.6mm/2mm thick PVC pipe from individual
telephone/data/CCTV camera outlets to network jack/switch/patch panel/hub located in the
communication room. The items including the cost of supply and installation of conduits,
b) couplers, junction boxes, bends, ceiling/wall plates, draw boxes & top cover plate (3mm hylam R. mtr. 2880
sheet), CAT 6A cables, terminations at both ends, ferrules, clamps, screws, bolt & nuts and
necessary fixing accessories etc. The item including necessary chipping/cutting the wall and
making good the same in case of recessed conduit as required. All complete as per
specifications, drawings and / or as directed by the Engineer.

Supply, fixing and termination of high quality wall mounted type patch panel, patch card and
rack with one number of 16 port switch, fixing frames, links and interconnections, necessary
c) Nos. 3
accessories etc., all complete as per specifications, drawings and / or as directed by the
Engineer.

CONTRACTOR No.OF CORRECTIONS


Page 65

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, fixing and termination of high quality wall mounted type patch panel, patch card and
rack with one number of 24 port switch, fixing frames, links and interconnections, necessary
d) Nos. 3
accessories etc., all complete as per specifications, drawings and / or as directed by the
Engineer.

Supply, laying and termination of high quality optical fiber cable laid in PVC pipe. The items
including the cost of supply and installation of conduits, couplers, junction boxes, bends,
ceiling/wall plates, draw boxes & top cover plate (3mm hylam sheet), OFC cables, terminations
e) at both ends, ferrules, clamps, screws, bolt & nuts and necessary fixing accessories etc. The Rmt RO
item including necessary chipping/cutting the wall and making good the same in case of
recessed conduit as required. All complete as per specifications, drawings and / or as directed
by the Engineer.

Fixing of modular type information outlet (for Wi-Fi) with necessary fixing accessories. The item
including necessary chipping/cutting the wall and making good the same in case of flush
f) Nos. RO
mounting as required. All complete as per specifications, drawings and / or as directed by the
Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - N)

CONTRACTOR No.OF CORRECTIONS


Page 66

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - O TELEVISION SYSTEM

Supply and fixing of modular type television socket mounted on suitable zinc passivated metal
box complete with metal box, front plate, screws and required fixing accessories etc. The item
O1 a) including necessary chipping/cutting the wall and making good the same in case of flush Nos. 62
mounting as required. All complete as per specifications, drawings and / or as directed by the
Engineer.

Supply, laying and termination of closed circuit television co-axial RG6 cable laid in
1.6mm/2mm thick 19mm/25mm dia PVC conduit & accessories from
dish/amplifier/communication room to individual TV, items including the cost of supply and
installation of conduits, couplers, junction boxes, bends, ceiling/wall plates, draw boxes & top
b) R. mtr. 2170
cover plate (3mm hylam sheet), 75 ohm RG6 cables, ferrules, clamps, screws, bolt & nuts and
necessary fixing accessories etc. The item including necessary chipping/cutting the wall and
making good the same in case of recessed conduit as required. All complete as per
specifications, drawings and / or as directed by the Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - O)

PART - P CLOSED CIRCUIT TELEVISION SYSTEM


Design, supply and fixing of the following CCTV accessories, all complete as per specifications,
P1 a)
drawings and / or as directed by the Engineer.
Wall/ceiling mounted type Fixed Dome or Bullet type Cameras with 4mm lens, 2MP, 20m IR
i) Nos. 60
distance and with necessary fixing accessories.

CONTRACTOR No.OF CORRECTIONS


Page 67

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying and termination of closed circuit television co-axial camera cable (4+1) laid in
1.6mm/2mm thick 19mm/25mm dia PVC conduit & accessories from individual camera to DVR.
The item including cost of supply and installation of conduits, couplers, junction boxes, bends,
ii) R. mtr. 2750
ceiling/wall plates, clamps, screws, bolt & nuts and necessary fixing accessories etc. Also the
item including minor civil works as required and all complete as per specifications, drawings and
/ or as directed by the Engineer.

Power Supply with Battery backup unit, suitable for 1 nos. 16 channel digital video recorder
iii) Nos. RO
system.
Power Supply with Battery backup unit, suitable for 1 nos. 32 channel digital video recorder
iv) Nos. 2
system.
16 Channel Digital Video Recorder with TCP/IP compatiblity and 2TB Hard Disk storage with
v) Nos. RO
necessary fixing accessories.
16 Channel Network Video Recorder with TCP/IP compatiblity and 2TB Hard Disk storage with
vi) Nos. RO
necessary fixing accessories.
32 Channel Digital Video Recorder with TCP/IP compatiblity and 4TB Hard Disk storage with
vii) Nos. 2
necessary fixing accessories.
32 Channel Network Video Recorder with TCP/IP compatiblity and 4TB Hard Disk storage with
viii) Nos. RO
necessary fixing accessories.
ix) 19" TFT Colour Monitor. Nos. 2

CONTRACTOR No.OF CORRECTIONS


Page 68

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Supply, laying and termination of high quality CAT-6 Ethernet LAN cable preferably with FR PVC
insulation to be laid in 19mm/25mm dia 1.6mm/2mm thick PVC pipe from individual CCTV
camera outlets to network jack/switch/patch panel/hub located in the communication room. The
items including the cost of supply and installation of conduits, couplers, junction boxes, bends,
b) ceiling/wall plates, draw boxes & top cover plate (3mm hylam sheet), CAT 6 cables, terminations R. mtr. RO
at both ends, ferrules, clamps, screws, bolt & nuts and necessary fixing accessories etc. The
item including necessary chipping/cutting the wall and making good the same in case of
recessed conduit as required. All complete as per specifications, drawings and / or as directed
by the Engineer.

Supply, fixing and termination of high quality wall mounted type patch panel, patch card and
rack with one number of 16 port POE switch, fixing frames, links and interconnections,
c) Nos. RO
necessary accessories etc., all complete as per specifications, drawings and / or as directed by
the Engineer.

Supply, fixing and termination of high quality wall mounted type patch panel, patch card and
rack with one number of 32 port POE switch, fixing frames, links and interconnections,
d) Nos. RO
necessary accessories etc., all complete as per specifications, drawings and / or as directed by
the Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - P)

CONTRACTOR No.OF CORRECTIONS


Page 69

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - Q PUBLIC ADDRESS SYSTEM

Q1 Design, supply,installation, testing and commissioning of the following public address system accessories, all complete as per specifications,drawings and / or as directed by the Engineer.

10 Watts, Wall/ceiling mounted type 100V line speaker with built-in line matching
a) Nos. 50
transformer and necessary mounting boxes and fixing accessories.

Supply, laying and termination of 2 core 1 sq.mm flexible copper cable laid in
1.6mm/2mm thick 19mm/20mm dia PVC conduit, from Amplifier to speaker and from speaker to
other speakers. The items including the cost of supply and installation of conduits, couplers,
b) R. mtr. 2250
junction boxes, bends, ceiling/wall plates, clamps, screws, bolt & nuts and necessary fixing
accessories etc. Also the item including minor civil works as required and all complete as per
specifications, drawings and / or as directed by the Engineer.

Supply, installation, testing and commissioning of amplifier rack unit complete with one
no. 750W power amplifier, zone console (upto zone 10) with proper addressing feasibilities for
c) Set. 1
all/individual zone, suitable line matching transformer, power supply unit, connection strip and
mounting rack/desk etc.,

d) Gooseneck Microphone witk desk stand Nos. 1


e) CD / MP3 / DVD Player as per required Nos. 1

TOTAL CARRIED OVER TO SUMMARY (Part - Q)

CONTRACTOR No.OF CORRECTIONS


Page 70

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation
PART - R NURSE CALLING SYSTEM
R1 Design, supply, installation, testing and commissioning of the following nurse calling system accessories, all complete as per specifications, drawings and / or as directed by the Engineer.
Supply & installation of Bed Unit which has Call button, Extra Assistance, Code Blue, House
a) Keeping and Reset, all complete as per specifications, drawings and / or as directed by the Nos. 14
Engineer.

Supply & installation of Nurse station, which receives data from all the bed and store the data in
b) Set. 1
data base all complete as per specifications, drawings and / or as directed by the Engineer.

supply & installation Software, which collects all data and send daily reports / email / SMS
c) ,based on hierachy all complete as per specifications, drawings and / or as directed by the Set. 1
Engineer.

TOTAL CARRIED OVER TO SUMMARY (Part - R)

PART - S MISCELLANEOUS

Preparation of complete set of as-built/schematic drawings, substation layout, physical layout


and the technical documents for submission with Chief Electrical Inspector to Government.
(Liasion with CEA/CEIG for obtaining approval for all drawings) ***** {Complete electrical Lump
S1 1
system all equipments/switchgears including transformer, HT breakers, Rising main, DG Sum
sets, panels, HT/LT cables, Earthing, Lightning protection system, DBs, wiring, luminaires
and fixtures, Elevators and motors & pumps etc.}

CONTRACTOR No.OF CORRECTIONS


Page 71

Rate in Rs. Amount in Rs.


Item No. Description Unit Quantity
Supply Installation Supply Installation

Preparation of completion report, arranging for inspection and attending to defects report and
preparation of final & as-built drawings and obtaining Safety Certificate from CEA / CEIG for Lump
S2 1
commissioning/energisation. (Liasion with the CEA/CEIG for obtaining safety certificate for Sum
energising the substation)

Liasioning with Tamilnadu Electricity Board (TNEB) including submission of application & Lump
S3 1
documents for obtaining required Demand power. (Appx. Cost) Sum

TOTAL CARRIED OVER TO SUMMARY (Part - S)

TOTAL CARRIED OVER TO SUMMARY (Part-A to Part-S)

GRAND TOTAL in Rs. (SUPPLY + INSTALLATION)

CONTRACTOR No.OF CORRECTIONS


GENERAL ABSRACT

Name of Work: "CONSTRUCTION OF BASEMENT FLOOR + GROUND FLOOR + 1st FLOOR TO


6th FLOOR - HOSPITAL BUILDING OF NO : 175, TAMBARAM - VELACHERY MAIN ROAD,
COMPRISED IN SURVEYNO : 81/1B2, AT GOWRIVAKKAM VILLAGE,TAMBARAM TALUK,
KANCHIPURAM DISTRICT. CHENNAI."

SI.No. Description of Works Amount in Rs.

1 Filling low-lying area

2 Providing Rain Water Harvesting

3 Providing pavement and Cement concrete Road

4 Construction of Compound wall with gates

5 Construction of Sump & Pump room

6 Providing external water supply arrangements

7 Providing external sewerage arrangements

8 Providing Electrical Fittings and Conduit works

Grand Total