CONTENTS
1. SYSTEM DESCRIPTION
1.1 General
2. OPERATION PHILOSOPHY
2.1 General
3. NORMAL OPERATION
4. SECURITY INTERLOCK
4.1 Interlock
5. OPERATION OF EQUIPMENTS
6. APPENDIX
1.1 General
This section shows the conceptual process description of the Flue Gas
Desulphurization (FGD) System for Maitree Super Thermal Power Station.
The wet limestone-gypsum process FGD System is applied for Overview of FGD
System is shown in Fig.-1.2.
Boiler Stack
Service Service
(Flue Gas) (Treated Gas)
Air Air
Instrument Instrument
Air Air SO2 Absorption Oxidation System
Process Process
Water Utility Water
System
Cooling
Water Cooling Water Limestone Gypsum
Slurry Slurry
Cooling Cooling Water
Water Return Return
Limestone Preparation Gypsum Dewatering
System Handling System
Sump System
Lump Gypsum
Limestone
The area inside the dotted lines (----)shows the scope of supply.
1-1
1.3 System Description
1-2
1.3.1 SO2 Absorbtion Oxidation System
The purpose of this system is to absorb and oxidize SO2 from flue gas.
This system consists of the following equipment.
1-3
The absorbed SO2 is partially oxidized in the tower by oxygen in the flue gas.
Oxidation of the remained unoxidized SO2 is performed in tank by oxidation
system which is called Jet Air Sparger (JAS). A part of the discharged slurry from
the recirculation pump is distributed to several numbers of JAS nozzles and flown
into the reaction tank of the absorber through the nozzles. There is an orifice
plate where negative pressure is generated at downstream of the plate inside the
JAS nozzle. The oxidation air is induced by oxidation air blower into the air
induction nozzle. By mixing air and slurry in JAS nozzle under the turbulent flow
condition, fine air bubbles are generated and effectively dispersed into the tank to
produce efficient gas-slurry contact and agitation condition. Therefore, oxidation
reaction is carried out efficiently in tank. Further, widespread jet stream from the
nozzles at tank bottom realizes mixing of slurry in the absorber tank. This
phenomenon prevents sedimentation of solids at the absorber bottom without
agitator operation while oxidation reactions promote to generate high-grade
gypsum as a by-product.
1-4
Absorber
SO2 + H2O → H2SO3
H2SO3 → H+ + HSO3-
(H+ + HSO3- + 1/2O2 → 2H+ + SO42-)
(2H+ + SO42- + CaCO3 + Aq → CaSO4・2H2O↓+ CO2↑)
SO2 gets absorbed into H2O, then dissociates from H2SO3 to H+ and HSO3-.
A part of HSO3- is oxidized by O2 contained in the flue gas and gets converted
in to H2SO4. CaCO3 in slurry neutralizes a part of H2SO4 and thus recovers pH
of slurry.
Absorber Tank
H+ + HSO3- + 1/2O2 → 2H+ + SO42-
2H+ + SO42- + CaCO3 + Aq → CaSO4・2H2O↓+ CO2↑
All remained HSO3- in slurry is oxidized by oxidation air to be converted into
H2SO4. Thereafter it gets neutralized with CaCO3 to produce CaSO4・2H2O.
1-5
Fig.-1.3.1 SO2 Absorption Oxidation System
To Stack
Process Water
Absorber Mist
Eliminator
Process Water
Absorber
Spray Pipe
From ID Fan
Wet/Dry Interface
Washing
Process Water M
Oxidation Air
Oxidation Air Quenching Nozzle
Blower
JAS Nozzle Absorber Recirculation Pump
Absorber Agitator
To Primary Hydro-cyclone
1-6
1.3.2 Gypsum Dewatering Handling System
1-7
00 HTP 00 BB 001 Gypsum Emergency Storage Shed 1
1-8
Fig.-1.3.2 Gypsum Dewatering Handling System
Waste
Water Hydrocyclone
Waste Water
M Hydrocyclone Feed
Waste Water Tank Agitator
Hydrocyclone Feed Tank
Dewatering System A
Vacuum
Belt Filter Waste Water
From Gypsum Hydrocyclone Feed
Bleed Pump Tank Pump
ATM
Hopper
Dewatering System B
To WWT
Process M
Water
1-9
1.3.3 Limestone Preparation System
00 HTJ 02 AA 001/002 Dosing Bin Bag Filter Outlet Rotary Vane 1+1
A/B
1-10
00 HTK 01 BB 001/002 Wet Mill Receiver Tank A/B 1+1
1-11
Fig.-1.3.3 Limestone Preparation System
Limestone Handling and Storage System
Limestone
Bucket Elevator
Limestone
Grinding Dosing Bin
System A Silo M M
Shut-off Gate Belt Conveyor
Distribution Box
Mill Gravimetric
Hydro- Feeder
cyclone Wet Ball Mill
M
1-12
1.3.4 Sump System
The purpose of this system is to hold the drain from each system.
This system consists of the following equipment.
10/20 HTT 00 AP 001/002 Absorber Area Drain Sump Pump A/B (1+1)x2
1-13
Slurry in Absorber Area Drain Sump is sent back to the Absorber tank by
Absorber Area Drain Sump Pump after the completion of an inspection in the
absorber.
The Limestone Area Drain Sump is located inside limestone preparation system
area. This sump collects the spillage from limestone preparation system area.
The slurry in this sump is pumped to Wet Mill Receiver Tank.
Gypsum Area Drain Sump is located inside gypsum dewatering system area.
This sump collects the spillage from the gypsum dewatering area. The slurry in
the sump is pumped to Filtrate Water Tank.
1-14
Fig.-1.3.4 Sump System
Limestone Area
Drain Sump
Gypsum Area
Drain Sump
1-15
1.3.5 Utility System
1-16
1.3.6 Emergency Transfer System
Primary Hydrocyclone
Absorber M
Gypsum Bleed
Pump
Auxiliary
Emergency Absorbent Tank
Transfer Pump
M M
Absorber Area
Drain Sump
1-17
2. OPERATION PHILOSOPHY
2.1 General
2-1
2.4 Manual Operation Philosophy
Start and stop of the equipment between normal operation and short-term
stoppage state are carried out remotely from DCS.
Please refer to chapter 2.6. Start and stop procedure for the operation
between normal and short-term stoppage state.
Start and stop of the equipment with local control panel are carried out a
start/stop from the local control panel.
2-2
Table-2.2 Plan for Basic Operation of Pumps (1/2)
Valve
Pump Pump Pump
Item Pump Pump After Pump Stop
Suction Discharge Discharge Line Drain Line Wash
Suction Discharge
Drain Washing Vent
Absorber Recirculation Pump Auto Auto Auto Auto Auto Auto - Washing after drain out
Process Water Pump Manual Manual - - Manual Manual - Hold full water
2-3
Table-2.2 Plan for Basic Operation of Pumps (2/2)
Valve
Pump Pump Pump
Item Pump Pump After Pump Stop
Suction Discharge Discharge Line Drain Line Wash
Suction Discharge
Drain Washing Vent
Hose Hose
Auxiliary Absorbent Pump Manual Manual - Manual Manual Drain out
Connection Connection
If auto, a valve is automatic, and it opens and closes sequentially according to a start/stop of a pump.
A start/stop of pump is operated remortly. A manual valve is opened and closed on the local.
2-4
2.5 Definition of Operation State
2-5
Table-2.5 Operating Status List
2-6
Normal Shut-down Condition
Item No. Service
Operation Short Term Long Term Maintenance
00HTJ01AF001/ Belt Conveyor A/B Running Running*3 Stop Stop
002
10/20HTP00BR Gypsum Diverter A/B Running Running*3 Stop Stop
001/002
00HTJ02AF001/ Bucket Elevator A/B Running Running*3 Stop Stop
002
00HTJ01AA001/ Dosing Bin Shut-off Gate A/B Open Open*3 Close Close
002
00HTJ02AT001/ Dosing Bin Bag Filter A/B Running Running*3 Stop Stop
002
00HTJ00AN001/ Dosing Bin Vent Fan A/B Running Running*3 Stop Stop
002
00HTK00AF001/ Gravimetric Feeder A/B Running Running*3 Stop Stop
002
00HTK00AJ001/ Wet Ball Mill A/B Running Running*3 Stop Stop
002
00HTK00AP001/ H.P Trunnion Lube Oil Pump A/B Stop Running*3 Stop Stop
002
00HTK01AP001/ L.P Trunnion Lube Oil Pump A/B Running Running*3 Stop Stop
002
00HTK00AM001 Wet Mill Receiver Tank Agitator A/B Running Running*3 Stop *1 Stop
/002
00HTK02AP001/ Limestone Suspension Pump A/B Running Running*3 Stop Stop
002
00HTK01AT001/ Distribution Box A/B Feed Feed Recycle Recycle
002
00HTK01AM001 Limestone Slurry Storage Tank Running Running Stop *1 Stop
/002 Agitator
00HTK03AP001/ Limestone Slurry Feed Pump A/B Running Running Stop Stop
002
2-7
Normal Shut-down Condition
Item No. Service
Operation Short Term Long Term Maintenance
10/20HTT00AM Absorber Area Drain Sump Agitator Stop *1 Stop *1 Stop *1 Running
001
10/20HTT00AP0 Absorber Area Drain Sump Pump Stop *1 Stop *1 Stop *1 Running
01/002 A/B
00HTT00AM001 Auxiliary Absorbent Tank Agitator Stop *1 Stop *1 Running Running
00HTT01AM001 Gypsum Area Drain Sump Agitator Stop *1 Stop *1 Stop *1 Running
00HTT01AP001 Gypsum Area Drain Sump Pump Stop *1 Stop *1 Stop *1 Running
00HTT02AM001 Limestone Area Drain Sump Agitator Stop *1 Stop *1 Stop *1 Running
00HTT02AP001 Limestone Area Drain Sump Pump Stop *1 Stop *1 Stop *1 Running
2-8
Fig.-2.5.1 Long-term Stoppage State (1/3)
Gypsum Slurry
(*2) AT (*4)
AT Gypsum Slurry
Boiler Unit-1 ID Fan SO2 SO2
ESP
To Primary Hydrocyclone
Process Water
Belt Filter
(*6) Start/Stop Process Water
Control
From Process Water Pumps
To Unit-2 Absorber
AT (*5) 00 HTQ 01 AP 001/002/003
pH ME Wash & Emergency Quench
Process Water
M 10 HTE 00 AT 001 DC Pump A/B/C
Antifoam Agent Antifoam Agent
Absorber To Limestone Grinding Area
To Unit-1 Absorber From Process Water Pumps Mist Eliminator
M
M 10 HTD 00 AP 001/005 Process Water
M
10 HTS 00 AP 001 Absorber Recirculation
M To Unit-1 Absorber
Antifoam Agent Pump Pump A/E
Process Water
To Unit-2 Absorber
10 HTS 00 BB 001 10 HTG 01/08 BN 001 M
Hold Liquid Equipment
Antifoam Agent Tank 10 HTG 00 AN 001/002 JAS A/H LC
M
Empty Liquid Equipment
10 HTS 00 AM 001 Oxidation Air Blower A/B 10 HTD 00 AM 001/002
Antifoam Agent Tank Agitator Absorber Agitator A/B Draft Flue Gas System
10 HTM 00 AP 001/002
Absorber drain
10 HTD 00 BB 001
Gypsum Bleed
Running System
Absorber Pump A/B Stop System
M
To Auxiliary Absorbent Tank
Absorber drain Filtrate Slurry
Running Equipment
To Auxiliary Absorbent Tank
From Filtrate Water Pumps Stop Equipment
Absorber drain 10 HTT 00 AM 001 10 HTT 01 AP 001 Filtrate Slurry M
M
Absorber Area Drain Sump Emergency Transfer Pump Open Valve Open Damper
To Unit-1 Absorber M Agitator Antifoam Agent
(*1) Limestone
M
Absorber drain (*2) From Antifoam Agent Pump Close Valve Close Damper
Slurry Feed
M (*4) Control
(*5) Process Water
From Process Water Pumps Absorber drain Absorber Drain
10 HTT 00 AP 001/002 10 HTT 00 BB 001 00 HTT 00 AM 001
FC From Gypsum Bleed
Absorber Area Drain Sump Absorber Area Drain Sump Limestone Slurry To Unit-1 Absorber Auxiliary Absorbent
Pumps
Pump A/B From Limestone Slurry Tank Agitator
Feed Pumps Absorber drain Absorber Drain
M
Limestone Slurry To Unit-2 Absorber From Absorber Area
Drain Sump Pumps
2-9
Fig.-2.5.1 Long-term Stoppage State (2/3)
: Battery limit -FGD plant 00 HTM 01 AM 001
Waste Water Hydrocyclone Hold Liquid Equipment
※2 Feed Tank Agitator Empty Liquid Equipment
M
Draft Flue Gas System
Running System
00 HTM 02 BB 001 Stop System
Unit-1 Dewatering System A
(*6) Waste Water Hydrocyclone Running Equipment
Feed Tank
M Stop Equipment
10 HTM 00 AT 001 00 HTM 02 AP 001/002
Gypsum Slurry A
Primary Hydrocyclone A Waste Water Hydrocyclone M
M M
ATM
10 HTP 00 BR 001
Gypsum Diverter A A B Waste Water
10 HTM 00 BB 001
Vacuum 10 HTM 00 AP 001 To FGD Waste Water
Receiver A Vacuum Pump A 00 HTM 00 AT 001 00 HTM 00 AT 002
Treatment Plant
Waste Water Waste Water
Hydrocyclone A Hydrocyclone B
Process Water
Gypsum Slurry Unit-1 Dewatering System B ※1 ※3 M
From Process Water Pumps
LC 00 HTM 03 AP
※3 001/002
Waste Water Pump
00 HTM 03 BB 001 A/B
M
※2 Waste Water
Storage Tank
2-10
Fig.-2.5.1 Long-term Stoppage State (3/3)
: Battery limit -FGD plant
00 HTK 01 AM 002
Limestone Slurry Storage
Limestone Slurry
Tank Agitator B
Hold Liquid Equipment
To Unit-1&2 Absorber 00 HTK 00 AJ 001 00 HTK 00 AJ 002 Empty Liquid Equipment
M
M Wet Ball Mill A M Wet Ball Mill B
Draft Flue Gas System
00 HTK 00 AM 001 00 HTK 00 AM 002
Wet Mill Receiver
Running System
Wet Mill Receiver
Tank Agitator A Tank Agitator B Stop System
Running Equipment
00 HTK 03 AP 002 00 HTK 02 BB 002
Limestone Slurry Limestone Slurry 00 HTK 02 AP 001 00 HTK 01 BB 001 00 HTK 01 BB 002 00 HTK 02 AP 002 Stop Equipment
Feed Pump B Storage Tank B Limestone Suspension Wet Mill Receiver Tank A Wet Mill Receiver Tank B Limestone Suspension M
Pump A Pump B Open Valve Open Damper
M
Close Valve Close Damper
2-11
Fig.-2.5.2 Short-term Stoppage State (1/3)
Gypsum Slurry
(*2) AT (*4)
AT Gypsum Slurry
Boiler Unit-1 ID Fan SO2 SO2
ESP
To Primary Hydrocyclone
Process Water
Belt Filter
(*6) Start/Stop Process Water
Control
From Process Water Pumps
To Unit-2 Absorber
AT (*5) 00 HTQ 01 AP 001/002/003
pH ME Wash & Emergency Quench
Process Water
M 10 HTE 00 AT 001 DC Pump A/B/C
Antifoam Agent Antifoam Agent
Absorber To Limestone Grinding Area
To Unit-1 Absorber From Process Water Pumps Mist Eliminator
M
M 10 HTD 00 AP 001/005 Process Water
M
10 HTS 00 AP 001 Absorber Recirculation
M To Unit-1 Absorber
Antifoam Agent Pump Pump A/E
Process Water
To Unit-2 Absorber
10 HTS 00 BB 001 10 HTG 01/08 BN 001
M
Hold Liquid Equipment
Antifoam Agent Tank 10 HTG 00 AN 001/002 JAS A/H LC
M
Empty Liquid Equipment
10 HTS 00 AM 001 Oxidation Air Blower A/B 10 HTD 00 AM 001/002
Antifoam Agent Tank Agitator Absorber Agitator A/B Draft Flue Gas System
10 HTM 00 AP 001/002
Absorber drain
10 HTD 00 BB 001
Gypsum Bleed
Running System
Absorber Pump A/B Stop System
M
To Auxiliary Absorbent Tank
Absorber drain Filtrate Slurry
Running Equipment
To Auxiliary Absorbent Tank
From Filtrate Water Pumps Stop Equipment
Absorber drain 10 HTT 00 AM 001 10 HTT 01 AP 001 Filtrate Slurry M
M
Absorber Area Drain Sump Emergency Transfer Pump Open Valve Open Damper
To Unit-1 Absorber M Agitator Antifoam Agent
(*1) Limestone
M
Absorber drain (*2) From Antifoam Agent Pump Close Valve Close Damper
Slurry Feed
M (*4) Control
(*5) Process Water
From Process Water Pumps Absorber drain Absorber Drain
10 HTT 00 AP 001/002 10 HTT 00 BB 001 00 HTT 00 AM 001
FC From Gypsum Bleed
Absorber Area Drain Sump Absorber Area Drain Sump Limestone Slurry To Unit-1 Absorber Auxiliary Absorbent
Pumps
Pump A/B From Limestone Slurry Tank Agitator
Feed Pumps Absorber drain Absorber Drain
M
Limestone Slurry To Unit-2 Absorber From Absorber Area
Drain Sump Pumps
2-12
Fig.-2.5.2 Short-term Stoppage State (2/3)
: Battery limit -FGD plant 00 HTM 01 AM 001
Waste Water Hydrocyclone Hold Liquid Equipment
※2 Feed Tank Agitator Empty Liquid Equipment
M
Draft Flue Gas System
Running System
00 HTM 02 BB 001 Stop System
Unit-1 Dewatering System A
(*6) Waste Water Hydrocyclone Running Equipment
Feed Tank
M Stop Equipment
10 HTM 00 AT 001 00 HTM 02 AP 001/002
Gypsum Slurry A
Primary Hydrocyclone A Waste Water Hydrocyclone M
M M
ATM
10 HTP 00 BR 001
Gypsum Diverter A A B Waste Water
10 HTM 00 BB 001
Vacuum 10 HTM 00 AP 001 To FGD Waste Water
Receiver A Vacuum Pump A 00 HTM 00 AT 001 00 HTM 00 AT 002
Treatment Plant
Waste Water Waste Water
Hydrocyclone A Hydrocyclone B
Process Water
Gypsum Slurry Unit-1 Dewatering System B ※1 ※3 M
※2 Waste Water
Storage Tank
2-13
Fig.-2.5.2 Short-term Stoppage State (3/3)
: Battery limit -FGD plant
00 HTK 01 AM 002
Limestone Slurry Storage
Limestone Slurry
Tank Agitator B
Hold Liquid Equipment
To Unit-1&2 Absorber 00 HTK 00 AJ 001 00 HTK 00 AJ 002 Empty Liquid Equipment
M
Wet Ball Mill A Wet Ball Mill B
M M Draft Flue Gas System
00 HTK 00 AM 001 00 HTK 00 AM 002
Wet Mill Receiver
Running System
Wet Mill Receiver
Tank Agitator A Tank Agitator B Stop System
Running Equipment
00 HTK 03 AP 002 00 HTK 02 BB 002
Limestone Slurry Limestone Slurry 00 HTK 02 AP 001 00 HTK 01 BB 001 00 HTK 01 BB 002 00 HTK 02 AP 002 Stop Equipment
Feed Pump B Storage Tank B Limestone Suspension Wet Mill Receiver Tank A Wet Mill Receiver Tank B Limestone Suspension M
Pump A Pump B Open Valve Open Damper
M
Close Valve Close Damper
2-14
Fig.-2.5.3 Normal Operation (1/3)
Gypsum Slurry
(*2) AT (*4)
AT Gypsum Slurry
Boiler Unit-1 ID Fan SO2 SO2
ESP
To Primary Hydrocyclone
Process Water
Belt Filter
(*6) Start/Stop Process Water
Control
From Process Water Pumps
To Unit-2 Absorber
AT (*5) 00 HTQ 01 AP 001/002/003
pH ME Wash & Emergency Quench
Process Water
M 10 HTE 00 AT 001 DC Pump A/B/C
Antifoam Agent Antifoam Agent
Absorber To Limestone Grinding Area
To Unit-1 Absorber From Process Water Pumps Mist Eliminator
M
M 10 HTD 00 AP 001/005 Process Water
M
10 HTS 00 AP 001 Absorber Recirculation
M To Unit-1 Absorber
Antifoam Agent Pump Pump A/E
Process Water
To Unit-2 Absorber
10 HTS 00 BB 001 10 HTG 01/08 BN 001
M
Hold Liquid Equipment
Antifoam Agent Tank 10 HTG 00 AN 001/002 JAS A/H LC
M
Empty Liquid Equipment
10 HTS 00 AM 001 Oxidation Air Blower A/B 10 HTD 00 AM 001/002
Antifoam Agent Tank Agitator Absorber Agitator A/B Draft Flue Gas System
10 HTM 00 AP 001/002
Absorber drain
10 HTD 00 BB 001
Gypsum Bleed
Running System
Absorber Pump A/B Stop System
M
To Auxiliary Absorbent Tank
Absorber drain Filtrate Slurry
Running Equipment
To Auxiliary Absorbent Tank
From Filtrate Water Pumps Stop Equipment
Absorber drain 10 HTT 00 AM 001 10 HTT 01 AP 001 Filtrate Slurry M
M
Absorber Area Drain Sump Emergency Transfer Pump Open Valve Open Damper
To Unit-1 Absorber M Agitator Antifoam Agent
(*1) Limestone
M
Absorber drain (*2) From Antifoam Agent Pump Close Valve Close Damper
Slurry Feed
M (*4) Control
(*5) Process Water
From Process Water Pumps Absorber drain Absorber Drain
10 HTT 00 AP 001/002 10 HTT 00 BB 001 00 HTT 00 AM 001
FC From Gypsum Bleed
Absorber Area Drain Sump Absorber Area Drain Sump Limestone Slurry To Unit-1 Absorber Auxiliary Absorbent
Pumps
Pump A/B From Limestone Slurry Tank Agitator
Feed Pumps Absorber drain Absorber Drain
M
Limestone Slurry To Unit-2 Absorber From Absorber Area
Drain Sump Pumps
2-15
Fig.-2.5.3 Normal Operation (2/3)
: Battery limit -FGD plant 00 HTM 01 AM 001
Waste Water Hydrocyclone Hold Liquid Equipment
※2 Feed Tank Agitator Empty Liquid Equipment
M
Draft Flue Gas System
Running System
00 HTM 02 BB 001 Stop System
Unit-1 Dewatering System A
(*6) Waste Water Hydrocyclone Running Equipment
Feed Tank
M Stop Equipment
10 HTM 00 AT 001 00 HTM 02 AP 001/002
Gypsum Slurry A
Primary Hydrocyclone A Waste Water Hydrocyclone M
M M
ATM
10 HTP 00 BR 001
Gypsum Diverter A A B Waste Water
10 HTM 00 BB 001
Vacuum 10 HTM 00 AP 001 To FGD Waste Water
Receiver A Vacuum Pump A 00 HTM 00 AT 001 00 HTM 00 AT 002
Treatment Plant
Waste Water Waste Water
Hydrocyclone A Hydrocyclone B
Process Water
Gypsum Slurry Unit-1 Dewatering System B ※1 ※3 M
※2 Waste Water
Storage Tank
2-16
Fig.-2.5.3 Normal Operation (3/3)
: Battery limit -FGD plant
00 HTK 01 AM 002
Limestone Slurry Storage
Limestone Slurry
Tank Agitator B
Hold Liquid Equipment
To Unit-1&2 Absorber 00 HTK 00 AJ 001 00 HTK 00 AJ 002 Empty Liquid Equipment
M
Wet Ball Mill A Wet Ball Mill B
M M Draft Flue Gas System
00 HTK 00 AM 001 00 HTK 00 AM 002
Wet Mill Receiver
Running System
Wet Mill Receiver
Tank Agitator A Tank Agitator B Stop System
Running Equipment
00 HTK 03 AP 002 00 HTK 02 BB 002
Limestone Slurry Limestone Slurry 00 HTK 02 AP 001 00 HTK 01 BB 001 00 HTK 01 BB 002 00 HTK 02 AP 002 Stop Equipment
Feed Pump B Storage Tank B Limestone Suspension Wet Mill Receiver Tank A Wet Mill Receiver Tank B Limestone Suspension M
Pump A Pump B Open Valve Open Damper
M
Close Valve Close Damper
2-17
2.6 Start-up and Shutdown Procedure
2-18
Starting Machinery
・ Gypsum Bleed Pump
・ Filtrate Water Pump
・ Waste Water Hydrocyclone Feed Tank Pump
・ Waste Water Pump
・ Gypsum Reversible Belt Conveyor
・ Limestone Suspension Pump
・ Limestone Slurry Feed Pump
2-19
Starting Limestone Grinding System
・ L.P Trunnion Lube Oil Pump
・ H.P Trunnion Lube Oil Pump
・ Wet Ball Mill
・ Gravimetric Feeder
2-20
(2) Short-term Stoppage State → Normal Operation State
2-21
(3) Normal Operation State → Short-term Stoppage State
2-22
(4) Short-term Stoppage State → Long-term Stoppage State
2-23
Stopping Dosing Bin System
・ Dosing Bin Bag Filter
・ Dosing Bin Vent Fan
・ Dosing Bin Bag Filter Outlet Rotary Valve
Stopping Machinery
・ Gypsum Bleed Pump
・ Filtrate Water Pump
・ Waste Water Hydrocyclone Feed Tank Pump
・ Waste Water Pump
・ Gypsum Reversible Belt Conveyor
・ Limestone Suspension Pump
・ Limestone Slurry Feed Pump
2-24
Stopping utilities and stopping of related equipment (if necessary)
・ Instrument Air and Service Air System
(Air Pressure)
・ Process Water System
(Process Water Pump and ME Wash & Emergency
Quench Pump)
・ Cooling Water System
(Cooling Water Pressure)
2-25
Fig.-2.6.1 Slurry Recirculation Pump Group Start Flow Chart
Start Condition
Absorber Level ≧ CH2
4/5
Absorber Recirculation Pump C : Start Completed
2-26
Fig.-2.6.2 Slurry Recirculation Pump Group Stop Flow Chart
Stop Condition
ID Fan Stop
5/5
Absorber Recirculation Pump C : Stop Completed
2-27
2.7 Start-up and Shutdown Schedule
This section describes the start-up / shutdown schedule for the FGD plant.
Fig.-2.7.1 and Fig.-2.7.2 show the typical FGD plant start-up schedule
Fig.-2.7.3 and Fig.-2.7.4 show the typical FGD plant shutdown schedule
2-28
Fig.-2.7.1 FGD Plant Start-up Schedule
Fuel Change
(Oil → Coal)
Normal Operation
(Load up)
2-29
Fig.-2.7.2 FGD Plant Start-up Schedule
100
Boiler Load
(%)
Boiler Start-up
FGD Gas-introduction
Time
2-30
Fig.-2.7.3 FGD Plant Shutdown Schedule
Load Down
Fuel Change
FGD Stop Permission
(Coal → Oil)
from Boiler
2-31
Fig.-2.7.4 FGD Plant Shutdown Schedule
100
Boiler Load
(%)
2-34
Boiler
Cool Down
Boiler
Fire Out Shutdown
Time
2-32
3. NORMAL OPERATION
(2) The following equipments have an automatic back-up function (Stand-by Auto
Mode) by accident.
3-1
3.2 Process Control Method
The control system is designed to provide safe and reliable operation of the
FGD plant.
The FGD plant is designed not to interfere on the boiler operation and to
maintain the specified desulfurization performance regardless of the boiler
load-change by controlling the absorbent feed rate to the absorber.
3-2
3.2.1 Limestone slurry Feed Control
The limestone slurry flow rate is estimated corresponding to the boiler air flow
and FGD plant inlet SO2 concentration as a feed-forward signal, and then is
adjusted by FGD outlet SO2 concentration or the absorber tank pH as a
feed-back signal.
Boiler Air
Flow Signal
FF
FB
FIC
FGD Inlet SO2
AICA
FGD Outlet SO2
FT
FCV
Absorber Limestone
M Slurry
Tank AT AICA
pH
3-3
Control
PV
SV
△
Tr PID (Propotion + Integral Differential Pressure Transmitter
PID FX
+ differential) Control Function for Flow Rate
A/M
Σ Addition
Limestone Amount
PV
a×b
△ a b
△
X1
PID PID
c
A/M A/M
C (SO2 amount)
F1(x)
Neccesary limestone slurry amount is
calculated from the SO2 amount.
FF FF This necessary limestone slurry amount
Σ1 Σ2
signal is the Feedforward signal for this
control.
TITLE
3-4
3.2.2 Slurry Concentration Control (Absorber Density Control)
Vacuum Belt
Filter Local
Control Panel
DICA
CH
CL
M
Primary
Hydrocyclone
DT
Absorber
Tank
3-5
Control
Remarks)
Absorber Slurry Density
K : Calculation
DT
AX
CH/CL
TITLE
3-6
3.2.3 Absorber Tank Level Control
Absorber tank level is controlled to keep operated in the suitable range level.
The absorber tank level is controlled by the quantity of make-up water supply
to absorber tank by the batch operation.
Process Water
LT
CH Absorber
LICA LT
CL Tank
LT
3-7
Control
Remarks)
Absorber Tank Level T1 : Manual Switch
LT LT LT
LX LX LX
T1
CH/CL
Process Water
Absorber
TITLE
3-8
3.2.4 Belt Filter Washing Tank Level Control
Belt filter washing tank level is controlled to keep operated in the suitable
range level.
The belt filter washing tank level is controlled by the quantity of process water
supply to belt filter washing tank by batch operation.
M
CH
LIA
LT
Belt Filter
Washing Tank
3-9
Control
LT
LX
CH/CL
Process Water
TITLE
3-10
3.2.5 Filtrate Water Tank Level Control
Filtrate tank level is controlled to keep operated in the suitable range level.
The filtrate tank level usually is controlled by the filtrate feed to absorber tank
by batch operation.
Unit 1
FGD Inlet SO2
Unit 2
FGD Inlet SO2 FIC
CH
LIA
FT CL
LT
Absorber
Tank
FT
Unit 2
Absorber
Tank
3-11
Control
Unit 2 Unit 1
X1,2 : c=a×b
Unit 2 Unit 2 Unit 1 Unit 1
Filtrate Water Filtrate Water FGD Inlet Filtrate Water FGD Inlet SO2 amount which is to be removed
Boiler Air Boiler Air
Tank Level Flow Rate SO2 Conc. Flow Signal Flow Rate SO2 Conc. Flow Signal by FGD is calculated.
LT FT AT FT AT
F1,2(x)
LX FX AX a×b FX AX a×b
Unit 2
Absorber
Unit 1
Absorber
TITLE
3-12
3.2.6 Waste Water Hydrocyclone Feed Tank Level Control
Waste water hydrocyclone feed tank level is controlled to keep operated in the
suitable range level.
The waste water hydrocyclone feed tank level is controlled by the feed to
Waste water hydrocyclone by batch operation.
M CH
LIA
To Waste Water
CL
Hydrocyclone
LT
Waste Water
3-13
Control
LT
LX
CH/CL
TITLE
3-14
3.2.7 Waste Water Storage Tank Level Control
Waste water storage tank level is controlled to keep operated in the suitable
range level.
If the tank level becomes to CL1, waste water flows to Filtrate Water Tank is
stopped by closing motor valve automatically. When the tank level is increased
to CH1, waste water flow to Filtrate Water Tank starts again.
Waste water flow rate is controlled to keep the constant flow rate by observing
the flow rate with flow meter.
If the tank level becomes to CL2, waste water flow to Waste Water Treatment
System is stopped by closing control valve automatically.
When the tank level is increased to CH2, waste water flow to Waste Water
Treatment System starts again.
FIC
FT
3-15
Control
LT
LX
CH1/CL1
TITLE
3-16
Control
Remarks)
Waste Water Flow Rate T1 : more than CL2 : a→c
less than CL2 : b→c
FT-42010
FX
F1(x)
△ Open
Position
PID
Valve
A/M
0% Close
a 100%
b Valve Input
SG T1 Waste Water Storage Tank Level less than
CL2
c
FCV
TITLE
3-17
3.2.9 Limestone Slurry Storage Tank Level Control
3-18
FIig.-3.2.9 Limestone Slurry Storage Tank Level Control
From Process Water
Pump
FT FIC DT
FCV
FT FIC
Gravimetric FCV
Feeder M
WT
M
LICA
LICA LIA
CH
CL
WIC M LT LT
Oil Reservoir
H.P Trunnion Lube Oil Pump
L.P Trunnion Lube Oil Pump
3-19
Control
LT
LX
CH/CL
Limestone
Grinding
System
TITLE
3-20
3.2.10 Limestone Grinding System Control
3-21
FIig.-3.2.10 Limestone Grinding System Control
Dosing Bin
Mill Hydrocyclone
FT FIC DT
FCV
FT FIC
Gravimetric FCV
Feeder M
WT
LICA LIA
WIC M LT LT
Oil Reservoir
H.P Trunnion Lube Oil Pump
L.P Trunnion Lube Oil Pump
3-22
Control
Remarks)
T1 : Wet Ball Mill is in operation : a→c
Wet Ball Mill stops : b→c
DT F1(x)
WT LT
WX AX LX Open
Position
Valve
△ △
PID PID
Close
A/M A/M 100%
Valve Input
CH/CL
0% a 0 a
b Wet Ball Mill b
SG T1 SG T1 Wet Ball Mill
Operation Operation
c c
Distribution
Box
FCV- FCV- 00 HTK 01 AT 001/002
TITLE
3-23
3.2.11 Process Water Tank Level Control
Process water tank level is controlled to keep the fixed range level.
The process water tank level is controlled by the quantity of process water
supply to process water tank.
CH M
LIA
LT
Process
Water Tank
3-24
Control
Process Water
Tank Level
LT
LX
CH/CL
Process Water
TITLE
3-25
3.3 Set Point List
3-26
Table 3.3 Set Point List
Pressure
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
1 PDIA Mist Eliminator kPa H Later H ANN DCS Unnecessary
Differential Pressure
※This set point list does not include unit equipments. (for example Vacuum Belt Filter, Oxidation Air Blower, etc..) BHEL shall add set point for unit equipment and finalize the list according to the vender information.
3-27
Table 3.3 Set Point List
Temperature
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
Maximum temperature in AH mechanical trip Emergency Spray valve
1 TIA FGD Inlet Temperature deg.C HH Later Interlock DCS Necessary
condition open
Maximum temperature in AH mechanical trip
H Later H ANN DCS Necessary
condition - 10 deg.C
Heat-resistant value of Absorber internal Emergency Spray valve
2 TIA FGD Outlet Temperature deg.C HH Later Interlock DCS Necessary
material open
Heat-resistant value of Absorber internal
H Later H ANN DCS Necessary
material - 10 deg.C
prevention for
△H Later H ANN TT measuring range × 0.05 (5%) DCS Unnecessary
meter deflection
※This set point list does not include unit equipments. (for example Vacuum Belt Filter, Oxidation Air Blower, etc..) BHEL shall add set point for unit equipment and finalize the list according to the vender information.
3-28
Table 3.3 Set Point List
Level
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
1 LICA Absorber Level m HH 6.0 Overflow Normal Level + 1.0 m
CH 5.1 Absorber make-up water supply stop Normal Level + 0.1 m DCS Unnecessary
CL 4.9 Absorber make-up water supply start Normal Level - 0.1 m DCS Unnecessary
3-29
Table 3.3 Set Point List
Level
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
3 LIA Filtrate Water Tank Level m HH Later Over flow
CH1 Later Filtrate Water Tank Feed Valve Open DCS Unnecessary
CH2 Later Filtrate Water Tank Feed Valve Close DCS Unnecessary
3-30
Table 3.3 Set Point List
Level
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
Silo & Bag Filter
7 LIA Wet Mill Receiver Tank Level m HH Later HH ANN DCS Unnecessary
Protection
H Later H ANN DCS Unnecessary
H Later H ANN
3-31
Table 3.3 Set Point List
Level
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
10 LIA Aixiliary Absorbent Tank Level m HH Later Over flow
H Later H ANN
H Later H ANN
※This set point list does not include unit equipments. (for example Vacuum Belt Filter, Oxidation Air Blower, etc..) BHEL shall add set point for unit equipment and finalize the list according to the vender information.
3-32
Table 3.3 Set Point List
Others
Set Point Design Scene
No. Tag no. Service Range Unit Action Basis Remark
Point Value Location Adjustment
1 AICA Absorber pH - H 6.5 H ANN Normal pH + α DCS Necessary
3 FIA Oxidation Air Flow Rate m3N/h H Later H ANN DCS Unnecessary
※This set point list does not include unit equipments. (for example Vacuum Belt Filter, Oxidation Air Blower, etc..) BHEL shall add set point for unit equipment and finalize the list according to the vender information.
3-33
Table 3.3 Set Point List
Timer
Timer. Set Point Scene
No. Equipment Service Action Basis Remark
No. (sec) Adjustment
1 10/20 HTD 00 AP 001~005 T-1 Vent Valve Close after Start PB ON Time for slurry fill to pump suction and Necessary Refer to Section 5
Absorber Recirculation Pump Discharge
A/E
T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
T-3 Pump Washing Valve Open after Suction Valve Close Time for drain out pump Necessary
T-4 Pump Washing Valve Close after Pump Washing Time for enough washing Necessary
Valve Open
T-5 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-6 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
2 10/20 HTM 00 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Gypsum Bleed Pump A/B T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 Line Drain Valve Open Timer Total timer + valve moving time + margin Necessary
T-6 Line Washing Valve Open Timer Total timer + valve moving time + margin Necessary
T-7 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-8 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
3 T-1 1 Valve Open Time Design washing water flow rate Necessary Refer to Section 5
4 10/20 THE 00 AT 001 T-1 1 Valve Open Time Design washing water flow rate Necessary Refer to Section 5
3-34
Table 3.3 Set Point List
Timer
Timer. Set Point Scene
No. Equipment Service Action Basis Remark
No. (sec) Adjustment
5 00 HTM 01 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Filtrate Water Pump A/B T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 Line Drain Valve Open Timer Total timer + valve moving time + margin Necessary
T-6 Line Washing Valve Open Timer Total timer + valve moving time + margin Necessary
T-7 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-8 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
6 00 HTM 02 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Waste Water Hydrocyclone T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
Feed Tank Pump A/B T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 Line Drain Valve Open Timer Total timer + valve moving time + margin Necessary
T-6 Line Washing Valve Open Timer Total timer + valve moving time + margin Necessary
T-7 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-8 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
7 00 HTM 03 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Waste Water Pump A/B T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 Line Drain Valve Open Timer Total timer + valve moving time + margin Necessary
T-6 Line Washing Valve Open Timer Total timer + valve moving time + margin Necessary
T-7 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-8 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
3-35
Table 3.3 Set Point List
Timer
Timer. Set Point Scene
No. Equipment Service Action Basis Remark
No. (sec) Adjustment
8 10/20 HTM 01 AT 001/002 T-1 Vacuum Belt Filter Start after Water Valve Open Time for enough supply of water Necessary Refer to Section 5
Vacuum Belt Filter A/B
T-2 Seal Water Valve Open after Vacuum Belt Filter Start Necessary
T-3 Vacuum Pump Start after Seal Water Valve Open Time for enough supply of water Necessary
T-4 Gypsum Slurry Feed Valve Open after Vacuum Pump Time for enough vacuum pressure Necessary
Start
T-5 Vacuum Pump Stop after Stop PB ON Timer for dewatering Necessary
T-6 Vacuum Belt Filter Stop after Vacuum Pump Stop Timer for washing close Necessary
T-7 Water Valve Close after Vacuum Belt Filter Stop Necessary
9 00 HTK 00 AJ 001/002 T-1 High Pressure Trunnion Lube Oil Pump Start after Time for enough lifting oil pressure Necessary Refer to Section 5
Wet Ball Mill Start PB ON
T-2 Clutch Engage after High Pressure Trunnion Lube Oil Time for enough lifting oil pressure Necessary
Pump Start
T-3 High Pressure Trunnion Lube Oil Pump Stop after Time for trunnion bearing protection Necessary
Clutch Engage
T-4 Gravimetric Feeder Start Time for enough performance of crusher Necessary
T-6 Low Pressure Trunnion Lube Oil Pump Stop after Time for cooling down trunnion bearing
Clutch Disengage
3-36
Table 3.3 Set Point List
Timer
Timer. Set Point Scene
No. Equipment Service Action Basis Remark
No. (sec) Adjustment
10 00 HTK 03 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Limestone Suspension Pump T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
A/B T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-6 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
11 00 HTK 03 AP 001/002 T-1 Pump Start after Suction Valve Open Time for slurry fill to pump suction Necessary Refer to Section 5
Limestone Slurry Feed Pump T-2 Discharge Valve Open after Pump Start Time for enough discharge pressure Necessary
A/B T-3 Open Delay Timer for Pump Flushing Start Total timer + valve moving time + margin Necessary
T-4 Pump Flushing Valve Open Timer Total timer + valve moving time + margin Necessary
T-5 Line Drain Valve Open Timer Total timer + valve moving time + margin Necessary
T-6 Line Washing Valve Open Timer Total timer + valve moving time + margin Necessary
T-7 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-8 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
12 10/20 HTT 00 AP 001/002 T-1 Discharge Valve Open after Start PB ON Time for enough discharge pressure Necessary Refer to Section 5
Absorber Area Drain Sump T-2 Line Washing Valve Open after Stop PB ON Time for drain out line Necessary
Pump T-3 Line Washing Valve Close after Line Washing Valve Time for enough washing Necessary
Open
T-4 No Start Completion after Start PB ON ANN : (Start Sequence Malfunction) Total timer + valve moving time + margin Necessary
T-5 No Stop Completion after Stop PB ON ANN : (Stop Sequence Malfunction) Total timer + valve moving time + margin Necessary
3-37
4. SECURITY INTERLOCK
4.1 Interlock
Boiler : MFT
Boiler : MFT
Note :
For safe shutdown operation, control power can be operated with UPS power supply.
4-1
(2) Protection during Power Failure
In case of power failure, the FGD plant will be stopped. For safe shut
down, emergency power is supplied to the systems as shown in Table-4.1
below.
Table-4.1
4-2
4.2 Countermeasure Plan of Power Failure and Instantaneous Power Failure
Note :
*) Emergency Diesel Generator for supply of emergency electric power is
established at BTG side.
4-3
Table.-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-4
Table.-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-5
Table-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-6
Table-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-7
Table-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-8
Table-4.2 Countermeasure for Power Failure and Instantaneous Power Failure
4-9
5. OPERATION OF EQUIPMENT
5-0
Item Service
10/20 HTD 00 AP 001/002/003/004/005 Absorber Recirculation Pump A/E Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
Absorber Absorber Tank Level : Not LL1 (Master Stop condition)
Electric Fault : Not
Absorber Tank Level : CH2 (for 1st pump start)
6 Start Interlock; Stop Interlock;
5 Stand-by Auto Start due to other pump trip Electric Fault
M 1 Absorber Tank Level : LL1
M
3 Related valves feed back signal missing
Washing 2 (Suction/Discharge valve open)
Water M 7
Absorber M 4
Recirculation
Pump
Open
1 All Pumps All Pumps
Line Drain Valve
Stop Stop
Close
Open
2 Vent Valve
Close T1
Open T3 T3
3 Pump Washing
Valve Close T4 T4
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Start
7 Pump
Stop
T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-1
Item Service
10/20 HTM 00 AP 001/002 Gypsum Bleed Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
1 Absorber Tank Level : Not LL3 N/A
To Primary
Absorber M
Washing Hydrocyclone
Tank Water
Start Interlock; Stop Interlock;
M 5 2 M
Stand-by Auto Start due to another pump trip Electric Fault
M M M
Absorber Tank Level : LL3
M
6 Washing Related valves feed back signal
Water missing
3
M (Suction/Discharge valves open)
4 M 7 Gypsum Bleed Washing
Pump Water
M Gypsum Bleed
Pump
Start/Stop Sequence; Emergency Stop;
Start PB ON Completion Stop PB ON Completion Emergency Stop Completion
Open
1 Line Washing Valve
Close T6 T6
Open
2 Line Drain Valve
Close T5 T5
Open T3 T3
3 Pump Flushing Valve
Close T4 T4
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Start T1
7 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-2
Item Service
10/20 HTS 00 AP 001 Antifoam Agent Pump Sub Function Group
Antifoam
Agent Tank
Open
1 Line Drain Valve
(Manual) Close
Open
2 Discharge Valve
(Manual) Close
Start
3 Pump
Stop
5-3
Item Service
10/20 HTT 01 AP 001 Emergency Transfer Pump Sub Function Group
Emergency
3 6 Transfer
Pump
Open
1 Line Washing Valve
(Manual) Close
Open
2 Line Drain Valve
(Manual) Close
Open
3 Suction Drain Valve
(Manual) Close
Open
4 Discharge Valve
(Manual) Close
Open
5 Suction Valve
(Manual) Close
Start
6 Pump
Stop
5-4
Item Service
00 HTM 00 AP 001/002 Belt Filter Washing Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
Belt Filter Washing Tank Level : Not LL N/A
Belt Filter To Vacuum Belt
Washing Tank Filter
Belt Filter
2 Washing
5 Tank Pump
Belt Filter
Washing
Tank Pump
Open
1 Line Drain Valve
(Manual) Close
Open
2 Suction Drain Valve
(Manual) Close
Open
3 Discharge Valve
(Manual) Close
Open
4 Suction Valve
(Manual) Close
Start
5 Pump
Stop
5-5
Item Service
00 HTM 01 AP 001/002 Filtrate Water Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; To Unit 1 Absorber To Unit 2 Absorber Start Permission; Stop Permission;
1 Filtrate Water Tank Level : Not LL N/A
7 7
Filtrate M
WaterTank Washing To Filtrate
Water Water Tank
Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
M M M 5 2 M M
M
Filtrate Water Tank Level : LL
6 Washing Related valves feed back signal missing
Water
3
M
4 M 8 Washing
Filtrate Water Pump Water
Filtrate Water Pump
M
Open
1 Line Washing Valve
Close T6 T6
Open
2 Line Drain Valve
Close T5 T5
Open T3 T3
Pump Flushing
3
Valve T4 T4
Close
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Start T1
8 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-6
Item Service
00 HTM 02 AP 001/002 Waste Water Hydrocyclone Feed Tank Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; 7 M Start Permission; Stop Permission;
To Waste Water Waste Water Hydrocyclone Feed N/A
Waste Water 1 Hydrocyclone
Hydrocyclone Tank Level : Not LL
Feed Tank Washing
M 7 M To Waste Water
Water Hydrocyclone
Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
M M M 5 2 M M
M
Waste Water Hydrocyclone Feed
6 Tank Level : LL
Washing
3
Water Related valves feed back signal missing
Waste Water M
4 M 8 Hydrocyclone Washing
Feed Tank Pump Water
Waste Water
M Hydrocyclone
Feed Tank Pump
Start/Stop Sequence; Emergency Stop;
Start PB ON Completion Stop PB ON Completion Emergency Stop Completion
Open
1 Line Washing Valve
Close T6 T6
Open
2 Line Drain Valve
Close T5 T5
Open T3 T3
3 Pump Flushing Valve
Close T4 T4
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Start T1
8 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-7
Item Service
00 HTM 03 AP 001/002 Waste Water Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
8 M Waste Water Storage Tank Level : Not LL N/A
1 To Filtrate Water Tank
Waste Water Washing M 7
Storage Tank To WWT
Water
Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
M M M 5 M M
M
Waste Water Storage Tank Level : LL
6 Washing Related valves feed back signal missing
Water
3
Waste Water Pump M
4 M 7 Washing
Water
Waste Water Pump
M
Open
1 Line Washing Valve
Close T6 T6
Open
2 Line Drain Valve
Close T5 T5
Open T3 T3
3 Pump Flushing Valve
Close T4 T4
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Open
Filtrate Water Tank
8
Feed Valve
Close
Start T1
7 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-8
Item Service
00 HTK 00 AP 001/002 H.P Trunnion Lube Oil Pump A/B Sub Function Group
Open
1 Suction Valve
(Manual) Close
Start
2 Pump
Stop
*) This pump is operated by start/stop of Wet Ball Mill A/B Sub Fanction Group (page 5-36).
5-9
Item Service
00 HTK 01 AP 001/002 L.P Trunnion Lube Oil Pump A/B Sub Function Group
System Flow; Start Permission; Stop Permission;
Oil Reservoir Level : Not LL N/A
Oil Reservoir Tank Oil Temperature : ≧CL
Open
1 Suction Valve
(Manual) Close
Start
2 Pump
Stop
*) This pump is operated by start/stop of Wet Ball Mill A/B Sub Fanction Group (page 5-36).
5-10
Item Service
00 HTK 02 AP 001/002 Limestone Suspension Pump A/B Sub Function Group
Open T3 T3
1 Pump Flushing Valve
Close T4 T4
Open
2 Suction Drain Valve
Close
Open
3 Discharge Valve
Close
Open
4 Suction Valve
Close
Start T1
5 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-11
Item Service
00 HTK 03 AP001/002 Limestone Slurry Feed Pump A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; To Unit 1 AbsorberTo Unit 2 Absorber Start Permission; Stop Permission;
7 7
Limestone Slurry Storage Tank Level : Not LL N/A
1
Limestone Slurry M
Storage Tank Washing To Absorber
Water
Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
M M M 5 2 M M
M
Limestone Slurry Storage Tank Level : LL
6 Related valves feed back signal missing
Washing
3 Water (Suction/Discharge valves open)
M (Suction Drain , Line Drain valves close)
4 M 8 Limestone Slurry Washing
Feed Pump Suction/Discharge valve : close
Water
M
Limestone Slurry
Feed Pump
Open
1 Line Washing Valve
Close T6 T6
Open
2 Line Drain Valve
Close T5 T5
Open T3 T3
3 Pump Flushing
Valve T4 T4
Close
Open
4 Suction Drain Valve
Close
Open
5 Discharge Valve
Close
Open
6 Suction Valve
Close
Start T1
7 Pump
Stop T2
※ If the common header of pump suction is applied, water shall be fed to pump casing and inlet/outlet piping before pump operation.
5-12
Item Service
10/20 HTT 00 AP 001/002 Absorber Area Drain Sump Pump A/B Sub Function Group
M 3 M 1
Start Interlock; Stop Interlock;
M Stand-by Auto Start due to Electric Fault Electric Fault
M 2 Absorber Area Drain Sump Level : LL
Absorber 4 Related valves feed back signal missing
Area Drain
Sump
Pump
Absorber
Area Drain
Sump
Open
2 Line Drain Valve
Close T2 T2
T3 T3
Open
3 Discharge Valve
Close
Start
4 Pump
Stop
T1
5-13
Item Service
00 HTT 00 AP 001 Aixiliary Absorbent Tank Pump Sub Function Group
Open
1 Line Washing Valve
(Hose Connection) Close
Open
2 Line Drain Valve
(Manual) Close
Open
3 Pump Flushing Valve
(Hose Connection) Close
Open
4 Suction Drain Valve
(Manual) Close
Open
5 Discharge Valve
(Manual) Close
Open
6 Suction Valve
(Manual) Close
Start
7 Pump
Stop
5-14
Item Service
00 HTT 01 AP 001 Gypsum Area Drain Sump Pump Sub Function Group
Gypsum Area
Drain Sump
Open
1 Line Washing Valve
Close
Open
2 Line Drain Valve
Close
Open
3 Discharge Valve
Close
Start
4 Pump
Stop
5-15
Item Service
00 HTT 02 AP 001 Limestone Area Drain Sump Pump Sub Function Group
Limestone Area
Drain Sump
Open
1 Line Washing Valve
Close
Open
2 Line Drain Valve
Close
Open
3 Discharge Valve
Close
Start
4 Pump
Stop
5-16
Item Service
00 HTQ 00 AP 001/002/003 Process Water Pump A/B/C Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
Process Water Tank Level : Not LL N/A
Process 1 4
Water Tank Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
2 Process Water Tank Level : LL
5
3 6 Process
Water Pump
Open
1 Line Drain Valve
(Manual) Close
Open
2 Discharge Drain
Valve (Manual) Close
Open
3 Suction Drain Valve
(Manual) Close
Open
4 Discharge Valve
(Manual) Close
Open
5 Suction Valve
Close
(Manual)
Start
6 Pump
Stop
5-17
Item Service
00 HTQ 00 AP 001/002/003 ME Wash & Emergency Quench Pump A/B/C Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
Process Water Tank Level : Not LL N/A
Process 1 4
Water Tank Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
2 Process Water Tank Level : LL
5
Open
1 Line Drain Valve
(Manual) Close
Open
2 Discharge Drain
Valve (Manual) Close
Open
3 Suction Drain Valve
(Manual) Close
Open
4 Discharge Valve
(Manual) Close
Open
5 Suction Valve
Close
(Manual)
Start
6 Pump
Stop
5-18
Item Service
10/20 HTD 00 AM 001/002 Absorber Agitator A/B
Start
1 Absorber Agitator
Stop
5-19
Item Service
10/20 HTS 00 AM 001 Antifoam Agent Tank Agitator
Start
1 Antifoam Agent Tank Agitator
Stop
5-20
Item Service
00 HTM 00 AM 001 Filtrate Water Tank Agitator
Start
1 Filtrate Water Tank Agitator
Stop
5-21
Item Service
00 HTM 01 AM 001 Waste Water Hydrocyclone Feed Tank Agitator
Waste Water
Hydrocyclone Feed Tank
Start
1 Waste Water Hydrocyclone
Feed Tank Agitator
Stop
5-22
Item Service
00 HTM 02 AM 001 Waste Water Storage Tank Agitator
Start
1 Waste Water StorageTank
Agitator
Stop
5-23
Item Service
00 HTK 00 AM 001/002 Wet Mill Receiver Tank Agitator A/B
Start
1 Wet Mill Receiver Tank
Agitator
Stop
5-24
Item Service
00 HTK 01 AM 001/002 Limestone Slurry Storage Tank Agitator A/B
5-25
Item Service
10/20 HTT 00 AM 001 Absorber Area Drain Sump Agitator
Start
1 Absorber Area Drain Sump
Agitator
Stop
5-26
Item Service
00 HTT 00 AM 001 Aixiliary Absorbent Tank Agitator
Start
1 Aixiliary Absorbent Tank
Agitator
Stop
5-27
Item Service
00 HTT 01 AM 001 Gypsum Area Drain Sump Agitator
5-28
Item Service
00 HTT 02 AM 001 Limestone Area Drain Sump Agitator
Start
1 Limestone Area Drain
Sump Agitator
Stop
5-29
Item Service
10/20 HTG 00 AN 001/002 Oxidation Air Blower A/B Sub Function Group Stand-by Auto Mode
(Back-up start)
System Flow; Start Permission; Stop Permission;
N/A N/A
3 4
2
Washing Water
1
Start Interlock; Stop Interlock;
Stand-by Auto Start due to Electric Fault Electric Fault
Jet Air Sparger Lube Oil Temperature : HH
Motor Winding Temperature : HH
Motor Drive Side Bearing Temperature : HH
Motor None Drive Side Bearing Temperature : HH
Oxidation Air
Blower
Open
1 Line Drain Valve
(Manual) Close
Open
2 Discharge Valve
(Manual) Close
Start
3 Blower
Stop
Open
4 Lance Washing Valve
Close
5-30
Item Service
10/20 THE 00 AT 001 Absorber Mist Eliminator Washing Valve Sub Function Group
Second
Stage
First
Stage
Open
Close
Open
Close
Open
Close
1 Upper of Second Stage Open
Close
Open
Close
Open
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
2 Lower of Second Stage
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
3 Close
Upper of First Stage
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
Open Stop
Close
4 Lower of First Stage
Open Stop
Close
Open Stop
Close
Open Stop
Stop
Close
T1 Stop after 1 Cycle
30min. 30min.
Washing
1 Cycle (1hour)
Note : The washing with above mentioned interval (30min.) is initiated when accumulative gas flow rate treated at FGD plant reaches to the preset value.
This value is set to make washing once per 30 minutes at design gas flowrate.
Note 2 : Once ABS level becomes M/E and W/D sequence level (CH2), the M/E wash sequence to be suspended until the level decline to reset level (CH1
5-31
Item Service
Wet/Dry Interface Washing Valve Sub Function Group
System Flow; 1
Start Permission; Stop Permission;
M Absorber level CL1(refer to note 2) N/A
Process
Water
Absorber
1 Open
Wet/Dry Interface Washing
Valve
Stop Stop
Close
T1
T2
Note 2 : Once ABS level becomes M/E and W/D sequence level (CH2), the M/E wash sequence to be suspended until the level decline to reset level (CH1)
5-32
Item Service
10/20 HTM 01 AT 001/002 Vacuum Belt Filter A/B Sub Function Group
Open T2
2 Vacuum Pump Seal
Water Valve Close T3
Start
3 Vacuum Pump
Stop T5
Start T1
5 Vacuum Belt Filter
T6
Stop
Start
6 Belt Filter Vent Fan
Stop
5-33
Item Service
00 HTP 00 BR 001/002 Gypsum Reversible Belt Conveyor
Start
1 Gypsum Reversible Belt
Conveyor
Stop
5-34
Item Service
00 HTJ 02 AT 001/002 Dosing Bin Bag Filter A/B Sub Function Group
Dosing Bin
Start
1 Fan
Stop
Start
2 Rotary Valve
Stop
Start
3 Pulse Air
Stop
T1 *)
5-35
Item Service
00 HTK 00 AJ 001/002 Wet Ball Mill A/B Sub Function Group
Start T4
3 Gravimetric
Feeder
Stop
T2 T5
Engage
4 Clutch System
Disengage
5-36
6. APPENDIX
This section shows Control System Arrangement and Location and Configuration for
Operation switch for each equipment.
6-1
Fig.-6.1 Control System Arrangement
CRT
CPU
Switch Gear
(Control Panel)
LIMESTONE
VACUUM OXIDATION
GRINDING
BELT FILTER AIR BLOWER
SYSTEM
6-2
Table-6.2.1 Location of Operation Switch 1/4 (SO2 Absorption Oxidation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
10 HTD 00 AP 001 Absorber Recirculation pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump A Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump A Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump A Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTD 00 AP 002 Absorber Recirculation pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump B Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump B Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump B Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTD 00 AP 003 Absorber Recirculation pump C - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump C Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump C Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump C Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump C Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump C Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTD 00 AP 004 Absorber Recirculation pump D - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump D Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump D Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump D Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump D Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump D Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTD 00 AP 005 Absorber Recirculation pump E - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump E Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump E Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump E Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump E Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump E Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Absorber Recirculation Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTG 00 AN 001 Oxidation Air Blower A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
10 HTG 00 AN 002 Oxidation Air Blower B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sparger Washing Valve - ** - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
10 HTM 00 AP 001 Gypsum Bleed Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Bleed Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Bleed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
10 HTM 00 AP 002 Gypsum Bleed Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Bleed Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Bleed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Gypsum Bleed Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Gypsum Bleed Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
*marks are indicated the automatically Open/Close valves together with Start/Stop for each pumps. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
**mark is indicated the automatically Open/Close valve together with Start/Stop for Oxidation Air Blower. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-3
Table-6.2.1 Location of Operation Switch 2/4 (SO2 Absorption Oxidation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
10 HTS 00 AM 001 Antifoam Agent Tank Agitator - - - - - Start/Stop - - - - - Motor - - OFF
- Absorber Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- Absorber Inlet Emergency Spray Valve - Open/Close Auto/Manual Open/Close - - - - - - - Actuator / Single Open Remain Stationary Remain Stationary
- Absorber Wet / Dry Spray Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- pH Meter Slurry Feed Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Washing Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Slurry Feed Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Washing Valve - - Motor Open Remain Stationary Remain Stationary
- Limestone Slurry Feed Flow Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Filtrate Return Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Oxidation Air Purge Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
*marks are indicated the automatically Open/Close valves with Absorber Mist Eliminator Switch's Start/Stop. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-4
Table-6.2.1 Location of Operation Switch 3/4 (SO2 Absorption Oxidation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
20 HTD 00 AP 001 Absorber Recirculation pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump A Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump A Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump A Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTD 00 AP 002 Absorber Recirculation pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump B Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump B Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump B Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTD 00 AP 003 Absorber Recirculation pump C - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump C Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump C Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump C Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump C Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump C Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTD 00 AP 004 Absorber Recirculation pump D - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump D Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump D Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump D Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump D Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump D Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTD 00 AP 005 Absorber Recirculation pump E - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Recirculation Pump E Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Recirculation Pump E Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Recirculation Pump E Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump E Vent Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Recirculation Pump E Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Absorber Recirculation Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTG 00 AN 001 Oxidation Air Blower A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
20 HTG 00 AN 002 Oxidation Air Blower B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sparger Washing Valve - ** - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
20 HTM 00 AP 001 Gypsum Bleed Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Bleed Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Bleed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
20 HTM 00 AP 002 Gypsum Bleed Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Bleed Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Bleed Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Bleed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Gypsum Bleed Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Gypsum Bleed Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
*marks are indicated the automatically Open/Close valves together with Start/Stop for each pumps. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
**mark is indicated the automatically Open/Close valve together with Start/Stop for Oxidation Air Blower. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-5
Table-6.2.1 Location of Operation Switch 4/4 (SO2 Absorption Oxidation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
20 HTS 00 AM 001 Antifoam Agent Tank Agitator - - - - - Start/Stop - - - - - Motor - - OFF
- Absorber Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- Absorber Inlet Emergency Spray Valve - Open/Close Auto/Manual Open/Close - - - - - - - Actuator / Single Open Remain Stationary Remain Stationary
- Absorber Wet / Dry Spray Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- pH Meter Slurry Feed Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Washing Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Slurry Feed Valve - - Motor Open Remain Stationary Remain Stationary
- pH Meter Washing Valve - - Motor Open Remain Stationary Remain Stationary
- Limestone Slurry Feed Flow Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Filtrate Return Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
*marks are indicated the automatically Open/Close valves with Absorber Mist Eliminator Switch's Start/Stop. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-6
Table-6.2.2 Location of Operation Switch 1/4 (Gypsum Dewatering Handling System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
- Gypsum Dewatering System A Start/Stop - - Remote/Local Start/Stop - Remote/Local Remote/Local - - - - - - -
10 HTM 01 AT 001 Vacuum Belt Filter A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - OFF OFF
10 HTM 00 AP 001 Vacuum Pump A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - OFF OFF
- Vacuum Pump A Seal Water Valve * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
- Gypsum Slurry Feed Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
- Gypsum Slurry Drain Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Close Remain Stationary Remain Stationary
- Vacuum Belt Filter Feed Water Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
10 HTM 00 AN 001 Belt Filter Vent Fan A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - - OFF
*marks are indicated the automatically Start/Stop equipment with System Switch's ON/OFF under Auto Selection at Local Panel. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-7
Table-6.2.2 Location of Operation Switch 2/4 (Gypsum Dewatering Handling System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
- Gypsum Dewatering System A Start/Stop - - Remote/Local Start/Stop - Remote/Local Remote/Local - - - - - - -
20 HTM 01 AT 001 Vacuum Belt Filter A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - OFF OFF
20 HTM 00 AP 001 Vacuum Pump A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - OFF OFF
- Vacuum Pump A Seal Water Valve * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
- Gypsum Slurry Feed Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
- Gypsum Slurry Drain Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Close Remain Stationary Remain Stationary
- Vacuum Belt Filter Feed Water Valve A * - - Open/Close * Open/Close Auto/Manual Open/Close - - - Motor Open/Close Remain Stationary Remain Stationary
20 HTM 00 AN 001 Belt Filter Vent Fan A * - - Start/Stop/Alarm * Start/Stop Auto/Manual Start/Stop - - - Motor - - OFF
*marks are indicated the automatically Start/Stop equipment with System Switch's ON/OFF under Auto Selection at Local Panel. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-8
Table-6.2.2 Location of Operation Switch 3/4 (Gypsum Dewatering Handling System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
00 HTM 00 AP 001 Belt Filter Washing Pump B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTM 00 AP 002 Belt Filter Washing Pump A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Belt Filter Washing Tank Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTM 00 AM 001 Filtrate Water Tank Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTM 01 AP 001 Filtrate Water Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Water Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Water Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Water Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Water Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTM 01 AP 002 Filtrate Water Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Water Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Water Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Water Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Water Pump B Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Filtrate Water Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Filtrate Water Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTM 01 AM 001 Waste Water Hydrocyclone Feed Tank Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTM 02 AP 001 Waste Water Hydrocyclone Feed Tank Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Feed Tank Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Feed Tank Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Feed Tank Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Feed Tank Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTM 02 AP 002 Waste Water Hydrocyclone Feed Tank Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Feed Tank Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Feed Tank Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Feed Tank Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Feed Tank Pump B Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Feed Tank Pump Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Feed Tank Pump Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
*marks are indicated the automatically Start/Stop equipment with System Switch's ON/OFF under Auto Selection at Local Panel. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-9
Table-6.2.2 Location of Operation Switch 4/4 (Gypsum Dewatering Handling System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
00 HTM 02 AM 001 Waste Water Storage Tank Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTM 03 AP 001 Waste Water Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Waste Water Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Waste Water Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Waste Water Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Waste Water Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTM 03 AP 002 Waste Water Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Waste Water Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Waste Water Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Waste Water Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Waste Water Pump B Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Waste Water Pump Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Waste Water Pump Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Waste Water Return Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
- Waste Water Flow Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Close Close
00 HTP 00 AF 001 Gypsum Reversible Belt Conveyor A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - OFF OFF
00 HTP 00 AF 002 Gypsum Reversible Belt Conveyor B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - OFF OFF
*marks are indicated the automatically Start/Stop equipment with System Switch's ON/OFF under Auto Selection at Local Panel. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-10
Table-6.2.5 Location of Operation Switch 1/3 (Limestone Preparation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
00 HTJ 00 AA 001 Limestone Intermediate Silo Shut-off Gate A - Open/Close - Open/Close - Open/Close - Open/Close - - - Motor Close Remain Stationary Remain Stationary
00 HTJ 00 AA 002 Limestone Intermediate Silo Shut-off Gate B - Open/Close - Open/Close - Open/Close - Open/Close - - - Motor Close Remain Stationary Remain Stationary
00 HTJ 02 AA 001 Dosing Bin Shut-off Gate A - Open/Close - Open/Close - Open/Close - Open/Close - - - Motor Close Remain Stationary Remain Stationary
00 HTJ 02 AA 002 Dosing Bin Shut-off Gate B - Open/Close - Open/Close - Open/Close - Open/Close - - - Motor Close Remain Stationary Remain Stationary
**marks are indicated the automatically Start/Stop equipment with System Switch's Start/Stop. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-11
Table-6.2.5 Location of Operation Switch 2/3 (Limestone Preparation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
- Limestone Grinding System A Start/Stop - - Start/Stop - - - - - - - - - - -
00 HTK 00 AF 001 Gravimetric Feeder A ** Start/Stop Auto/Manual Start/Stop/Alarm - Start/Stop Remote/Local Start/Stop - - - Motor - - OFF
00 HTK 00 AJ 001 Wet Ball Mill A (Main Motor) ** Start/Stop Auto/Manual Start/Stop/Alarm - Start/Stop Remote/Local - - - - Motor - - OFF
- Wet Ball Mill A Clutch ** Engage/Disengage Auto/Manual Engage/Disengage - Engage/Disengage Remote/Local - - - - Air Clutch - Disengage Disengage
00 HTK 00 AP 001 H.P Trunnion Lube Oil Pump A ** Start/Stop Auto/Manual Start/Stop/Alarm - Start/Stop Remote/Local - - - - Motor - - OFF
00 HTK 01 AP 001 L.P Trunnion Lube Oil Pump A ** Start/Stop Auto/Manual Start/Stop/Alarm - Start/Stop Remote/Local - - - - Motor - - OFF
00 HTK 00 BB 001 Oil Reservoir A Oil Heater - On/Off Auto/Manual On/Off/Alarm - - - - - - - Heater - - OFF
00 HTK 00 AM 001 Wet Mill Receiver Tank Agitator A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTK 00 AM 002 Wet Mill Receiver Tank Agitator B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTK 02 AP 001 Limestone Suspension Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
Suspension Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Suspension Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Suspension Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
Suspension Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTK 02 AP 002 Limestone Suspension Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
Suspension Pump B Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Suspension Pump B Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Suspension Pump B Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
Suspension Pump B Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTK 01 AT 001 Distribution Box A - Disch./Recycle Auto/Manual Discharge/Recycle - - - - - - - Actuator / Double Disch./Recycle Remain Stationary Remain Stationary
00 HTK 01 AT 001 Distribution Box B - Disch./Recycle Auto/Manual Discharge/Recycle - - - - - - - Actuator / Double Disch./Recycle Remain Stationary Remain Stationary
- Wet Mill Receiver Tank A Density Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Wet Ball Mill A Feed Water Flow Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Wet Mill Receiver Tank B Density Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
- Wet Ball Mill B Feed Water Flow Control Valve - Open/Close Auto/Manual Controller - - - - - - - Pneumatic - Lock Lock
*marks are indicated the automatically Open/Close Valves together with Start/Stop for each pumps. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
**marks are indicated the automatically Start/Stop equipment with System Switch's Start/Stop. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-12
Table-6.2.5 Location of Operation Switch 3/3 (Limestone Preparation System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
00 HTK 01 AM 001 Limestone Slurry Storage Tank Agitator A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTK 01 AM 002 Limestone Slurry Storage Tank Agitator B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTK 03 AP 001 Limestone Slurry Feed Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
Feed Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Feed Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Feed Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
Feed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
00 HTK 03 AP 001 Limestone Slurry Feed Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
Feed Pump A Suction Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Feed Pump A Discharge Valve - * - Open/Close - - - - - - - Motor Open/Close Remain Stationary Remain Stationary
Feed Pump A Suction Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
Feed Pump A Flushing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Limestone Feed Line Drain Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Limestone Feed Line Washing Valve - * - Open/Close - - - - - - - Motor Close Remain Stationary Remain Stationary
- Limestone Slurry Return A Valve - * - Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- Limestone Slurry Return B Valve - * - Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
*marks are indicated the automatically Open/Close Valves together with Start/Stop for each pumps. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-13
Table-6.2.4 Location of Operation Switch (Sump System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
10 HTT 00 AM 001 Absorber Area Drain Sump Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
20 HTT 00 AM 001 Absorber Area Drain Sump Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
10 HTT 00 AP 001 Absorber Area Drain Sump Pump A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
10 HTT 00 AP 002 Absorber Area Drain Sump Pump B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Sump Pump Line Washing Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
- Sump Pump Line Drain Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
20 HTT 00 AP 001 Absorber Area Drain Sump Pump A - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
20 HTT 00 AP 002 Absorber Area Drain Sump Pump B - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Sump Pump Line Washing Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
- Sump Pump Line Drain Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
00 HTT 00 AM 001 Auxiliary Absorbent Tank Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTT 01 AM 001 Gypsum Area Drain Sump Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTT 01 AP 001 Gypsum Area Drain Sump Pump - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Sump Pump Line Washing Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
- Sump Pump Line Drain Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
00 HTT 02 AM 001 Limestone Area Drain Sump Agitator - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTT 02 AP 001 Limestone Area Drain Sump Pump - Start/Stop - Start/Stop/Alarm - - - - - - - Motor - - OFF
- Sump Pump Discharge Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
- Sump Pump Line Washing Valve - * - Open/Close - - - - - - - Actuator / Single Close Remain Stationary Remain Stationary
- Sump Pump Line Drain Valve - * - Open/Close - - - - - - - Actuator / Double Open/Close Remain Stationary Remain Stationary
*marks are indicated the automatically Open/Close valves together with Start/Stop for Area Drain Sump Pump. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-14
Table-6.2.5 Location of Operation Switch (Utility System)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
00 HTQ 00 AP 001 Process Water Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTQ 00 AP 002 Process Water Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTQ 00 AP 003 Process Water Pump C - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTQ 01 AP 001 ME Wash & Emergency Quench Pump A - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTQ 01 AP 002 ME Wash & Emergency Quench Pump B - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
00 HTQ 01 AP 003 ME Wash & Emergency Quench Pump C - Start/Stop Auto/Manual Start/Stop/Alarm - - - - - - - Motor - - OFF
- Process Water Tank Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- Emergency Water Tank Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
- Emergency Water Tank Level Control Valve - Open/Close Auto/Manual Open/Close - - - - - - - Motor Open Remain Stationary Remain Stationary
*marks are indicated the automatically Start/Stop equipment with System Switch's ON/OFF. For further details the reader is referred to Item 5. (OPERATION OF EQUIPMENT)
6-15
Table-6.2.6 Location of Operation Switch (Others)
Location and Configuration for Operation Switch Specification
DCS Panel (CRT Operation) Local Panel Local Box Drive Type Limit SW Air Fail Power Fail
Item No. Service Sys. SW Man. SW COS SW Display Sys. SW Man. SW COS SW Display Man. SW COS SW Display
10 HTD 00 AG 001 Absorber Elevator - - - - - - - - Start/Stop - - Motor - - OFF
20 HTD 00 AG 001 Absorber Elevator - - - - - - - - Start/Stop - - Motor - - OFF
*If Auto Mode is selected, the fan is operated with Oxidation Air Blower Start/Stop operation condition.
**If Auto Mode is selected, the fan is operated by inside temperature of the building.
6-16