Você está na página 1de 7

The Optimum Thermal Design of Microchannel Heat Sinks

Wen Zhimin and Choo Kok Fah


DSO National Laboratories
20 Science Park Drive, Singapore 118230

Abstract model to determine the optimum design parameters for such a


A thermal resistance model was set up to analyse the heat sinks. Choquette et al. [6], Sasaki et al. [7],Missaggia
flow and heat transfer in microchannel heat sinks. Laminar, et al. [8] and Landram 191 have also done extensive thermal
turbulent, developed and developing flow and heat transfer optimisation studies for this heat sink. However, it is noted
were considered in the analysis. that, their optimum results were normally obtained under a
Optimum thermal design of the heat sink was then limited geometrical range (for the heat sink) with some
studied using this model and a self-developed software, where parameters fixed on a specific flow and heat transfer regime.
the influences of heat sink's channel aspect ratio, fin width to Contradictions were also found among the conclusions.
channel width ratio and the channel width on the T h s paper documents the optimum thermal design
performance of heat sink under three flow constraints: studies done for the microchannel heat sink using a thermal
constant coolant volume flow rate, constant pressure drop and resistance model and a self-developed software. The studies
constant pumping power, were extensively investigated over were conducted over wide flow and heat transfer regimes
wide flow and heat transfer regimes. using large heat sink's geometrical (or design parameters)
This paper documents the modelling or analysis ranges. Effects of heat sink's channel aspect ratio, fin width
methodologies and the results of the investigation which to channel width ratio and the channel width on the total
include guidelines for the optimum thermal design of thermal resistance of the heat sink under three flow
microchannel heat sinks. constraints: constant coolant volume flow rate, constant
pressure drop and constant pumping power will be presented.
Introduction
The rapid development of electronics packaging Thermal Resistance Model
technology has given rise to the need for innovative, small Fig. 1 shows the schematic drawing of a microchannel
scale and highly effective cooling techniques. There is strong heat sinks comprising of an adiabatic cover plate and an IC
requirement now for these cooling techniques to be able to substrate with microchannels fabricated on the reverse side.
dissipate heat flux in the order of 100 Wlcm' or more (e.g. a The heat generated by the IC chips is dissipated away by the
Photon Source X-Ray radiation is expected to have heat flux coolant flowing within the channels.
exceeding 14,000 W/cm2 [l]).
In the race to extend the capabilities of conventional
cooling techniques to meet these requirements, Tuckerman
and Pease [2] applied the micro-fabrication techniques for
micro-electronic devices to the fabrication of microchannel
heat sinks in 1981. They managed to produce large aspect
ratio heat sinks with channel width in the order of 50 pm on
the back of the IC chips.
Subsequent thermal testing revealed that power
dissipation capability of up to 790 W/cm2 can be achieved
with such a heat sink (with water as coolant), while
maintaining the chip temperature rise at only 71°C. This
innovative cooling technique attracted great attention and
extensive theoretical and experimental studies have since
been conducted by various researchers to further assess its Fig. 1 Schematic drawing of the microchannel heat sinks
performance and potential for actual applications.
Philips [3] in 1990, set up a thermal resistance model to Microchannel heat sinks are defined by its height, H,
assess the performance of the microchannel heat sinks within length, L and width, W and its channel height, H,, channel
the laminar and turbulent regime of hydrodynamically width, W,, and width of the fin wall, W,. The base of the
developed or developing flow. A computer code was heat sinks has a thickness, t and a heat load, Q.
developed for the analysis and results revealed that thermal The thermal resistance between the channel entrance and
resistance smaller than 0. l°C/(W/cm2)can be achieved. the substrate surface is defined as:
Salamn [4] in 1989, implemented a quasi-two-
dimensional differential equation to obtain the optimum fin
thickness and channel width of the heat sinks, while Knight
et al. [SI developed a non-dimensional thermal resistance where Koa is the total thermal resistance, T,d,, is the

07803-4157-0/97 $10.00 01997 IEEE


123 1997 IEEUCPMTElectronic Packaging Technology Conference
hottest temperature on the surface of the heat sink and Th is
the temperature of the coolant at the inlet. Due to the single m=:
direction coolant flow, the hottest temperature should be
located at the end of the channel. where k,is the conductivity of the heat sink.
Assuming that the heat load is applied uniformly on the By introducing Nusselt number Nu,
base of the heat sink, the total thermal resistance, hodwould hD
thus be the sum of the bulk-temperature-rise, convective, NU=-
constriction and conduction thermal resistances, expressed as: Kf
where Kf is tlhe conductivity of the coolant, the convective
Rtotal = Rbulk + Rconv + Rconstr Rcond (2) thermal resistance can now be written as:
To simpllfy the expressions to be defined, two 1 1 + p- 2a
geometrical ratios are now introduced: aspect ratio, a and fin Rconv = NuKf(WL) - 1+2aq l + aWC
(14)
width to channel width ratio, f3 where, The constriction thermal resistance, RONis due to the
need to funnell the heat from the base to the fin of the heat
(3) sink. It can be:obtained using [3],
The bulk-temperature-rise thermal resistance, is the
resistance between the channel entrance and the exit defined
r
as:
m m
‘bulk,out - ‘in - 1
Rhulk = (4)
Q Pf CPf G
where pf and Cp, are the density and specific heat of the r 1
coolant respectively and G is the coolant’s volume flow rate
given as:
G = nH,WcV (5)
The conduction thermal resistance, Rondthrough the
where n is the total channel number given as n=W/(Ww+Wc) heat sink can be obtained simply by using,
and V is the velocity of the coolant inside the channel.
1
Introducing the hydraulic diameter, D and Reynolds
number, Re,

D= 4HcWc - kc wc Careful observation of the equations above would reveal


2(Hc+Wc) l + a that all four components of the total thermal resistance have
the area term, WL. Redefining the total thermal resistance as
Re=- P f W (7) the temperature difference against unit area heat flux, Rl(tota~,
Pf m m

where pf is the viscosity of working fluid. Thus, the bulk-


temperature-rise thermal resistance can be written as:
WL
L - 2- 1+p The total thernnal resistance can then be summarised as:
Rhulk = (8)
CP, Pf (WRe 1+ a L 2 1+p
The convective thermal resistance, KO,,is defined as: Rtotal = ___--
Cpfpf Re l + a
1 +- 1 1 + p 2a
Rconv =- (9) W
C
Ueff
where h is the convective heat transfer coefficient and A e is~
the effective area available for the convective heat transfer.
According to the fin (or extended surfaces) theory, &E can be WC

written as:
A,, = mwc+ 2@c) (10)
+- t
where q is the fin efficiency. And for fin with insulated tip, kS
This total thermal resistance is a function of the coolant
and heat sink material properties, the flow and heat transfer
status and the heat sink’s geometry.
and For a given heat sink, where the coolant, the heat sink’s

124 1997 IEEUCPMT ElectronicPackagingTechnology Conference


dimension (t, L and w>
and the material are specified, its Nusselt Number
optimum thermal design is achieved by minimising the total For laminar thermally developing and hydrodynamically
thermal resistance by varying the geometrical parameters (a, fully developed flow, Nusselt number in rectangular channel
and WJ and determining the ideal flow and heat transfer with four walls subjected to a constant heat flux is obtained
status within specified constant inlet flow constraints (i.e. by the polynomial curve fits written as following:
coolant volume flow rate, pressure drop or pumping power).
Friction factor, f and Nusselt number, Nu required during Nu = Bo + B, lnx' + B, ln2x' + B, ln3 X' + B, ln4'X (22)
the calculation of flow conditions are determined by using the where x' is the thermodynamic entrance length given by
method shown below ([3] and [6]). x'=(L/D)/(RePrf), and Prf is the Prandtl number of the
coolant. The coefficient B; are shown in Table 3.
Friction Factor Table 3 Coefficients for developing laminar Nusselt number
For laminar developing flow, the friction factor, f
satisfies the following polynomial fit, I al0.l I a=1.0 I a=2.0
Bn I 5.3570 I 3.5887 I 4.1289
f Re = A, + A, lnx' + A, ln2x' + A, ln3x' + A, in4 x" (19) B1 I -0.0812 I 0.0441 I 0.2150
where x' is the hydrodynamic entrance length given by B2 I -0.1337 I -0.0417 I 0.02514
x+=(L/D)/Re. The coefficients, A; are shown in Table 1. I Bq I -0.0471 I -0.0326 I -0.0248 I
Table 1 Coefficients for developing flow friction factor
I I a=1.0 I a=2.0 I a4.0 I a210.10.1 I
A0 14.206 15.510 19.099 23.920
B2 -0.0505 -0.0289 -0.2952
Ai 0.1725 0.2265 -0.445 -1.743
B3 -0.0353 -0.0327 -0.0588
I A2 I 0.1366 I 0.1539 I 0.00786 I -0.0562 I To simulate the real case, in which three walls are
I&I 0.456 I 0.0479 I 0.0393 I 0.0401 I heated, Phillips [3] suggests that the Nusselt number be
calculated using:
For fully developed laminar flow which occurs when x"
is greater than 1, the friction factor, f can be obtained through
[31,
where, x'=w denotes fully-developed heat transfer.
f Re = 24(1- 1.3553~-'+ 1.9467a-' - 1.70126, The Nusselt numbers for 3-side heated wall for various
(20) aspect ratios have been calculated and are listed in Table 4
+0.9564a-, - 0.2537cC5)
[lo].
For rectangular turbulent flow, the friction factor, f is
Table 4 Nusselt number of 3-sides heated channel
obtained based on that of circular channel as follows:
f = A(Re,,)B
where,
1.01612
A = 0.0929 + ~
6.072 3.169
x/D 5.393
0.31930 0.4 4.885 5.0 3.636
B = -0.26800 - ~

x/D 0.5 4.505 10 4.252


PfVD.5, 0.7 3.991 00 5.385
Re,, =-
Pf 1.0 3.556
2 111 1 For laminar thermally fully developed flow which occurs
D = [- + --(2 - -)ID
3 24a a when the thermodynamic entrance length, x' is larger than
0.2, the Nusselt number is obtained by using [lo]:
Laminar or turbulent flow regimes are distinguished by
the critical Reynolds number determined from Table 2 [3]. NU = 8.235 (1- 2.04216' + 3.0853a-' - 2 . 4 7 6 5 ~ ~
Table 2 Critical Reynolds number +1.0578a4 - 0.1861~~-~) (24)

Aspect ratio Critical Reynolds number For turbulent flow condition, Nusselt number can be
a=1.0 2200 obtained by [111,
a10.2 or a250 2500
other a Linear interpolation Nu = 0.012[1.0 + (D / L)2'3](Reo.87-280)Pr0.4 (25)

125 1997 IEEVCPMTElectronic PackagingTechnologyConference


Total Thermal Resistance And Flow Constraints Comparison of the results obtained show close
Three different flow constraints were considered during agreement. (Trends of components of the total resistance
the calculation of the total thermal resistance. They were: against increasing channel width are also shown in Fig. 2.)
constant coolant volume flow rate, G, constant pressure drop,
AP and constant pumping power, POW. Optimum Design of Microchannel Heat Sink
For a constant coolant volume flow rate flow constraints In order to detennine the optimum thermal design
where: parameters for microchannel heat sink, the three different
G = nHcWcV (26) flow constraints were studied separately using the same heat
sinks and cooldantmentioned above. In addition, three main
velocity is known and thus the pressure drop, pumping power variables a,f3 and W, which when varied will influence the
and total thermal resistance can be easily determined from heat sinks’ performances were also studied separately. The
the equations defined. default values of these variables when anyone of them is
For a constant pressure drop flow constraints where: varied are a4.0,p=l.O and Wc=lOOpm.
L pv2
AP = 4f -(-) (27) Constant Voluime Flow Rate
D 2 Effects of the aspect ratio, fin width to channel width
Velocity, V was iterated from equations (7), (19)-(21) and ratio and channel width on the total thermal resistance when
(27) using Newton iteration method with the aid of a self the volume flow rate was fixed at G=3.0e-5m3/s, are shown in
developed computer program. Fig. 3(a), (b) and (c).
For a constant pumping power flow constraints where:
POW = APG (28)
Velocity7 V was iterated from equations (7), (19)-(21)’ (26)’ I \\
\‘ Pumaina Power I
I

(27) and (28).


In both constant pressure drop and constant pumping
power flow constraints, once the velocity, V is known, the
pressure drop, pumping power and total thermal resistance
can be easily determined.

Validation of Thermal Resistance Model


The thermal resistance and the analysis methodologies
Total Thermal Resistance +
defined above have been validated against Philips’s [3] and
Choquette’s [6] results (refer to Fig. 2), where a heat sink
having dimensions L=W=lcm, t=lOOpm, a4.0 and p=l.O 0 . O l ~ : I :: : : : : : I : I : : : : c 100
0 5 10 15 20
was analysed at constant pressure drop flow condition of Aspect Ratio
AP=68.9kPa. The heat sink used was made from silicon with
thermal conductivity of 123 W/mK and the coolant used was Fig. 3(a) Effect of Aspect Ratio
water, where, ~ ~ 9 9lkg/m3,
7 . Cp~4179J/kgK,k~0.60W/mK, under Constant Volume Flow Rate
@3.91e-4kg/ms and P r ~ 6 . 2 1 .

A Choquette’s
Philip’s

.-
U) --
% ::
R-Conduction
- lx Total Thermal Resistance

/- R Constriction
0.01 -i+i+tw:: I I:::: I : : : I I : : : : I : : : : I : : : : I : : : : + 100
0 .OOOl -I : : : : I : : : : I : : : : I : : : : I : : : : I 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
0 100 200 300 400 500 Fin Width to Channel Width Ratio
Channel Width (p m)
Fig. 3(b) Effect of Fin Width to Channel Width Ratio
Fig. 2 Validation of the Thermal Resistance Calculation under Constant Volume Flow Rate

126 1997 IEEUCPMT Electronic PackagingTechnology Conference


10000

_ _ _ _ Laminar loo f
t
loooo
-Turbulent

i
i
Pumping Power

Re
L
1000 2 1000

-....---
---- f
0.1

Total Thermal Resistance


- - _ - _- - _
0.014L-i: : I : : : : I : I : : I : : : : : ; : -:-I
100 0.01
0 100 200 300 400 500 0 5 10 15 20
Channel Width (pn) Aspect Ratio

Fig. 3(c) Effect of Channel Width Fig. 4(a) Effect of Aspect Ratio
under Constant Volume Flow Rate under Constant Pressure Drop

Fig. 3(a) shows that under constant volume flow rate, 100 10000
increasing the aspect ratio, increases the flow area which ---- Laminar
decreases the flow velocity and the heat transfer effect (or Power -Turbulent
increases the total thermal resistance) in the turbulent regime.
While in the laminar regime, the total thermal resistance is I
not significantly affected by any increase in the aspect ratio
because convective thermal resistance is no longer a function
of Reynolds Number.
Fig. 3(b) reveals that the fin width to channel width ratio
has little effect on the total thermal resistance.
While analysing the effect of channel width on the total . _ _ _ _ . _ . ..._..__...._---..-_..-
_ . -Resistance
.--.-
I 1000 2

thermal resistance, both a and I3 were fixed, which made


Reynolds number, Re = - PfW-
Pf
--2PfG - l + P a constant. In
PfW l + a ’
order to analyse the effects of channel width in both flow
regimes, another volume flow rate was chosen (G=l.Oe-
o
0.01 0 0.2 0.4 0.6 0.8 I

Fin Width to Channel Width Ratio


1.2 1.4 1.6

5m3/s). Fig. 4 0 ) Effect of Fin Width to Channel Width Ratio


Since both laminar and turbulent flow regime have a under Constant Pressure Drop
constant Nusselt number due to fix aspect ratio or Reynolds
number, increasing W, increases the hydraulic diameter D 10
which decreases the heat transfer coefficient and increases the
total thermal resistance.
It is noted that for the constant volume flow rate :I
constraint, no absolute minimum total thermal resistance
value exists. Although the total thermal resistance within the
turbulent flow regime is lower, the high pumping power 5 g1;:
L 1:

required makes operation in the turbulent flow regime


undesirable. Thus operation in the laminar flow regime is .-
5$ ::.-
recommended under a constant volume flow constraint. In 3 o,l .
. 7
: 1000
addition, heat sink geometry should also satisfy a25.0 and Total Thermal Resistance ii
0.2@<0.6.

Constant Pressure Drop


Fig. 4(a), (b) and (c) show the effect of varying the aspect O.O1 ’
0 100 200 300 400 500
ratio, fin width to channel width ratio and channel width on Channel Width (pm)
the total thermal resistance under the constant pressure drop
flow constraint. Fig. 4(c) Effect of Channel Width
under Constant Pressure Drop

127 1997 IEEUCPMT ElectrmicPackaging TechnologyConference


Fig. 4(a) shows that when the pressure drop is fixed at achieved when a=15,p=0.5 and Wc=65pm. At this optimum
200kPa, increasing a increases the coolant flow rate through condition, the total thermal resistance was 0.073 OC/W/cm*,
the channels and improves the heat transfer, which reduces the pumping power was 0.986W and the Reynolds number
the total thermal resistance. was 310.3.
Fig. 4 0 ) shows the influence of the fin width to channel
width ratio on the total thermal resistance. Since pressure Constant Pumping Power
drop is a function of velocity and hydraulic diameter, fixing Fig. 6(a), (b) and (c) show the effect of aspect ratio, fin
the aspect ratio and the channel width to analyse the effect of width to channel width ratio and channel width on the total
fin width to channel width ratio resulted in a constant thermal resistance when the pumping power was fixed at
Reynolds number. In order to analyse the effects of both 7.5W.
turbulent and laminar flow regimes, the pressure drop was Fig. 6(a) shows that, as the aspect ratio increases, the
fixed at 68.9 and 4OOkPa instead. total thermal resistance in the laminar and turbulent flow
Results of the analysis show that the fin width to channel regime decreases. However increase in the fin width to
width ratio has little effect on the total thermal resistance and channel width ratio does not affect the total thermal
pumping power because its variation under constant pressure resistance greatly (refer to Fig. 6(b)).
drop only affects the fin efficiency and effective area.
Fig. 4(c) shows the effect of the channel width on the Pumping Power
total thermal resistance when the pressure drop is 68.9kPa. It -
is noted that in the laminar flow regime, there is a "local"
minimum total thermal resistance. However, this value is
larger than the total thermal resistance in the turbulent
regime. Since pumping power required is lower in the d
laminar flow regime, further analysis to determine the loo0

optimum design parameters for microchannel heat sink


operating in the laminar flow regime under constant pressure
drop condition will be meaningful. Total Thermal Resistance
Careful analysis of Fig. 4(a) revealed that when a
increases, the total thermal resistance in the laminar flow
regime decreases more quickly than that in the turbulent
0.01
regime. Thus, there is a possibility of obtaining a minimum 0 5 10 15 20
total thermal resistance in the laminar region by increasing a Aspect Ratio
and decreasing p. Refer to Fig 5. However, due to practical
Fig. 6(a) Effect of Aspect Ratio
limitation, increase in the aspect ratio is limited by the
under Constant Pumping Power
thickness of the heat sink.
1 loo00

Pumping Power

-w
t
s
9
E

.o; 1
0
m
+
.-
a,

Ll
Total Thermal Resistance

0.01 0.01 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6


0 100 200 300 m 500
Channel Width (pn) Fin Width to Channel Width Ratio

Fig. 5 Minimum Resistance in Laminar Region Fig. 6(b) Effect of Fin Width to Channel Width Ratio
under Constant Pumping Power
Effects of the geometrical parameters on the total thermal
resistance for 41a115, O.l<p<l.O and lO<W,l5OOpm were Similar to the constant pressure drop flow condition, Fig.
extensively iterated and compared using the self-developed 6(c) shows that there is a local minimum total thermal
software. The minimum total thermal resistance value was resistance value in the laminar region. However, it is not
possible to make the laminar flow total thermal resistance

128 1997 IEEWCPMT ElectronicPackagingTechnology Conference


smaller than the turbulent one because the turbulent flow 4. Although the total thermal resistance within the turbulent
regime’s total thermal resistance increases nearly at the same flow regime is generally lower than that of the laminar flow
rate as, or even faster than, the laminar one as shown in Fig. regime, the hgher pumping power required makes operation
6(a) and (b). in the turbulent regime undesirable.
5. For constant pressure drop flow constraint, optimum
thermal design can be achieved in the laminar regime by
Pumping Power adjusting the geometrical parameters.
w
-
Results also indicated that in order to derive the optimum
I
thermal design parameters for microchannel heat sinks,
extensive calculation by computer software over wide flow
and heat transfer regimes using large geometrical ranges
should be conducted.

References
1. U. S. Choi, C. S. Rogers and D. M. Mills, “High-
performance microchannel heat exchanger for cooling
high-heat-load X-Ray optical elements”, Micromechanical
Systems, ASME DSC-Vol.40, pp 83-89, 1992.
0.01 2. D. B. Tuckerman and R. E W. Pease, “High-performance
0 100 200 300 403 5M)
heat sinking for VLSI”, IEEE Electronic Device Letters,
Channel Width (pn)
Vol. EDL-2, N0.4, pp 126-129, May 1981.
Fig. 6(c) Effect of Channel Width 3. R. J. Phllips, “Microchannel heat sinks”, Advances in
under Constant Pumping Power thermal modelling of electronic components and systems,
(Edited by A. Bar-Cohen and A. D. Kraus), pp 109-184,
However, effects of geometrical parameters on the total ASME, New York, 1990.
thermal resistance were extensively iterated and compared 4. V. J. Salman, “Convective heat transfer in
again between 5lal15, O.llpll.0 and 10IWcllOOpm.The microchannels”, Journal of Electronic Materials, Vol. 18,
minimum laminar total thermal resistance was achieved No.5, pp 611-618, 1989.
when a=15, p=0.65 and Wc=50pm. At this optimum 5. R. W. Knight, J. S. Gooding and D. J. Hall, “ Optimal
condition, the total thermal resistance was 0.054 OC/W/cm2 thermal design of forced convection heat sinks -
and the Reynolds number was 539.13. analytical”, Journal of Electronic Packaging, Vol. 113,
It is further noted that the optimum aspect ratio occurs at No.3, pp 313-321, 1991.
the edge of the analysis limits. This contradicts Choquette’s 6. S. E Choquette, M. Faghri, etc, “Optimum design of
[6] findings where he obtained the minimum total thermal microchannel heat sinks”, Micro-electro-mechanical
resistance when the aspect ratio was at the middle of the systems (MEMS), ASME DSC-Vol.59, pp 115-126, 1996.
analysis limits. 7. S. Sasaki and T. Kishmoto, “Optimal Structure for Micro-
grooved cooling fin for high-powered LSI devices”, Vol.
Conclusion 22, NO.25, pp 1332-1334, 1986.
Optimum thermal design studies were conducted for 8. L. J. Missaggia, J. N. Walpole, Z. L. Liau and R. J.
microchannel heat sink using a thermal resistance model and Phillips, “Microchannel heat sinks for two-dimensional
a self-developed software. Analysis were done over wide flow high power density diode laser arrays”, BEE Journal of
and heat transfer regimes using large geometrical ranges. Quantum Electronics, QE 25, No. 9, pp 1988-1992, 1989.
And the effects of heat sink’s channel aspect ratio, fin width 9. C. S. Landram, “Computational model for optimising
to channel width ratio and the channel width on the total longitudinal fin heat transfer in laminar internal flows”,
thermal resistance of the heat sink under three flow Heat Transfer in Electronic Equipment, ASME HTD-Vol.
constraints: constant coolant volume flow rate, constant 171,1991.
pressure drop and constant pumping power were investigated 10.R. K. Shah and A. L. London, “Laminar flow forced
extensively. Results indicated that: convection in ducts”, Advances in heat transfer, pp 196-
1. The fin width to channel width ratio should satisfy 223, Academic, New York, 1978.
0.51p10.65 in order to achieve low total thermal resistance. 11.VGnielinski, “New equations for heat and mass transfer
2. Aspect ratio should be set as high as possible in the in turbulent pipe and channel flow”, International
laminar flow regime to reduce total thermal resistance. In Chemical Engineering, Vol. 16, pp 359-368, 1976.
addition, setting aspect ratio at a215 should achieve optimum
total thermal resistance especially for constant pressure drop
and constant pumping power flow constraints.
3. Total thermal resistance as low as 0.054°C/W/cm2 is
achievable at a=15, p=0.65 and Wc=50pm under a constant
pumping power of 7.5W.

129 1997 IEEWCPMT ElectronicPackaging Technology Conference

Você também pode gostar