ADHUNIK POWER & NATURAL RESOURCES LIMITED

2 X 270 MW, PADAMPUR

SOP
DOC REF NO APNRL/IMS/SOP/OP/001/ REV 0 DATE OF ISSUE
RESPONSIBILITY MECHANICAL-OPERATION
PURPOSE ROUTINE TRIAL RUN OF ACJOP PAGE 0

Steps for routine trial of ACJOP

1. Make SLC of ACJOP OFF.


2. Make OFF module isolator of ACJOP at EMB.
3. ‘MCC disturbed” appears at DCS.
4. Ask E/I for shorting at module so that MCC disturbed disappears from
DCS.
5. Depute one person at MCC module.
6. Give ON command for ACJOP, ON indication appears at DCS, also DC
contact making sound audible from module.Check the pressure on local
gauge & DCS.
7. Give OFF command for ACJOP, OFF indication appears at DCS, also DC
contact breaking sound audible from module.
8. Ask E/I for removal of shorting at module.
9. Make module isolator ON.
10.Make SLC of ACJOP ON.

DO NOT RUN ACJOP WHEN TURBINE IS ON LOAD.

PREPARED BY CHECKED BY REVIEWED BY APPROVED BY