Escolar Documentos
Profissional Documentos
Cultura Documentos
Using TDS146
Transformer Diagnostic System
A diagnostic tool for on-site diagnosis of power transformers with on-load tap changer
Applicability
On-site testing of power transformers with on-load tap changer, typically in transport and
distribution networks above 25kV. The transformer diagnostic system is suitable to test high-
speed resistor type tap changers, both in-tank and compartment type on-load tap changer,
installed in:
1. Tap Changer:
a. Dynamic resistance measurement (DRM)
Find degradation and defects in the on-load tap changer (contact coking, oil
film layer deposition, arcing contact wear, longer switch times, contact timing
problems, maintenance errors, defect transition resistors, synchronization
problems between phases, etc).
Find problems in the transformer windings that affect the resistance (due to
internal and external faults or vibrations, open circuits, shipping damage,
insulation defects,
defects defect tap changer positions,
positions incorrect connections)
b. Check contactor for switching time control (if equipped)
c. Position measurement on the OLTC drive axis (for rotor-type OLTC’s with
accessible drive axis)
d. Motor power measurement on the OLTC drive mechanism
Detect mechanical friction in the drive mechanism, contact binding, longer
motor operation times.
2. Transformer Windings:
a. Transformer turn ratio measurement
I. Find problems in the transformer windings and magnetic core (due to
internal and external faults or vibrations, open circuits, shipping damage,
insulation defects and incorrect connections)
II. Results should be within 0.5%
b. DC winding resistance measurement
I. Find problems in the transformer windings (due to internal and external
faults or vibrations, open circuits, shipping damage, insulation defects,
defect tap changer positions, incorrect connections)
II. Calculate I2R conductor losses
III. Results should be within 1%
Important standards and recommendations
ANSI/IEEE C57.12.90-1987: American national standard / IEEE Standard Test Code for
Liquid-Immersed Distribution, Power, and Regulating Transformers.
IEEE Std 62-1995: IEEE Guide for Diagnostic Field Testing of Electric Power Apparatus. Part
1: Oil Filled Power Transformers, Regulators, and Reactors.
IEEE Std C57.12.37-2006: IEEE Standard for the Electronic Reporting of Distribution
Transformer Test Data.
IEEE Std C57.140-2006: IEEE Guide for the Evaluation and Reconditioning of Liquid
Immersed Power Transformers.
IEC 60214: Tap-changers - Performance requirements, test methods and application
guide.
IEC 60076-1: Power Transformers - Part 1: General
Typical connection of the TDS146 instrument including the optional hardware features to a
power transformer in case the dynamic resistance of the OLTC is recorded, using additional
sensors to diagnose
di the
h drive
d i system. Kelvin
K l i clamps
l are connectedd to the
h transformer
f
bushings. Drive motor voltage and current are recorded at the motor connections, OLTC
control is performed by bridging OLTC control contacts used for manual OLTC control. A
rotation sensor can be placed at the remote end of the drive axis and an OLTC-in-operation-
contact can be measured to check the excessive switch time protection.
Connect TDS146
Connection of cables
Object Definition
Charging
Measurement
Analysis / Reporting
The TDS146 diagnostic instrument connected to the primary and secondary terminals of a
power transformer and remotely controlled by the notebook
User interface for measurements with the TDS146
Firstly,
Fi tl the
th windings
i di are charged
h d with
ith a DC Secondly, the voltage and current are
Secondly
current. recorded while the tap changer is switched
through its cycle of operation
Detailed close-up DRM graphs are shown of Impedance graphs are calculated based on
each OLTC operation (left) and switch times the measured current and voltage
are calculated (centre). Average values of difference.
current and resistance are shown in graphs
to make small changes visible (right).
Drive analysis option for the TDS146
Typical example of dynamic resistance results of clean tap changer contacts (top) and service-
aged tap changer contacts (bottom) as measured with the TDS146.
Accuracy: ±1W
Driver axis rotation Accuracy: 0.5°
Transformer connection Auto-configuration by relays
OLTC control 2x NO contact, 16A 400V
Operating temperature range 0ºC to 50ºC
Communication with laptop Wireless
Supply voltage 100-250VAC, 50/60Hz
Weight 9.7 kg
Email: info@onsitehv.com
DISTRIBUTOR :