Você está na página 1de 68

AIRCON T

JOB NAME: SATYAM PROPERTIES


SPACE FOR: Bed room-1 +dress room (12.6 X 15.7)
SIZE: 174.24
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 18.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 118.8 22
NE - Wall 0.0 28
E - Wall 118.8 36
SE - Wall 0.0 36
S - Wall 100.8 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 174.24 48
Roof Ins. 36
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)

All Glass 18 23
Partition 118.8 13
Ceiling 13
Floor 174 13
INTERNAL HEAT GAIN
People 2 Nos X
Light 35 WX
Eq. Load 300 WX

OUTSIDE AIR
CFM °F BF

10 23 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 2 Nos X
OUTSIDE AIR
CFM GR/LB BF
10 176.09655 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
10 23 0.85
OUTSIDE AIR HEAT (LATENT)

CFM GR/LB 1 - BF

10 176.09655 0.85
Return duct HP Pump Dehum. & Pipe
heat gain & + loss (%)
leak. loss + GRAND TOTAL
TR 1.16 HEAT

AIRCON T

JOB NAME: SATYAM PROPERTIES

SPACE FOR: Master Bed Room+Dress Room

SIZE: 409.6
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 151.2 12
SW - Glass 0.0 100
W - Glass 75.6 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 156.0 34
SW - Wall 0.0 32
W - Wall 116.4 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 409.6 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 226.8 41.4
Partition 805.2 31.4
Ceiling 410 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 2 Nos X
Light 205 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)
EFFECTIVE ROOM SENSIBLE HEAT (ERSH)
LATENT HEAT
People 2 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 3.96 GRAND TOTAL HEAT

AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Kitchen
SIZE: 156.009
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 25.2 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 132.1 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 156.009 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 25.2 41.4
Partition 442.92 31.4
Ceiling 156 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 2 Nos X
Light 78 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 2 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 1.47 GRAND TOTAL HEAT

AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Dining Room
SIZE: 199.42
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 199.42 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 0 41.4
Partition 688.8 31.4
Ceiling 199 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 8 Nos X
Light 100 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 8 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 1.64 GRAND TOTAL HEAT

AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Ent. Lobby
SIZE: 50.22
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 50.22 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 0 41.4
Partition 343.2 31.4
Ceiling 50 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 1 Nos X
Light 25 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 1 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 0.66 GRAND TOTAL HEAT

AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Drawing room
SIZE: 268.71
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 75.6 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 127.2 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 268.71 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 75.6 41.4
Partition 584.4 31.4
Ceiling 269 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 2 Nos X
Light 403 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 2 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85
Return duct HP Pump Dehum. & Pipe
heat gain & + loss (%)
leak. loss +
TR 2.00 GRAND TOTAL HEAT

AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Bed room-2+dress room (16X 11.10)
SIZE: 216.66
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 50.4 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 141.6 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 216.66 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 50.4 41.4
Partition 682.8 31.4
Ceiling 217 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 2 Nos X
Light 108 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 2 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 1.83 GRAND TOTAL HEAT
AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Family Lounge
SIZE: 259.96
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 259.96 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 0 41.4
Partition 787.2 31.4
Ceiling 260 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 4 Nos X
Light 130 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
20 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 4 Nos X
OUTSIDE AIR
CFM GR/LB BF
20 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
20 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
20 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 1.69 GRAND TOTAL HEAT
AIRCON T
JOB NAME: SATYAM PROPERTIES
SPACE FOR: Puja Room
SIZE: 25.76
SOLAR GAIN GLASS
ITEM Area Sun Gain
(Sq ft) (Btu/h.sq ft)
N - Glass 0.0 14
NE - Glass 0.0 12
E - Glass 0.0 12
SE - Glass 0.0 12
S - Glass 0.0 12
SW - Glass 0.0 100
W - Glass 0.0 164
NW - Glass 0.0 123
Sky light
SOLAR & TRANS. GAIN WALLS & ROOF
ITEM Area Eq. temp. diff.
(Sq ft) (°F)
N - Wall 0.0 22
NE - Wall 0.0 28
E - Wall 0.0 36
SE - Wall 0.0 36
S - Wall 0.0 34
SW - Wall 0.0 32
W - Wall 0.0 30
NW - Wall 0.0 24
Roof Sun 53
Roof Ins. 25.76 39.75
TRANS. GAIN EXCEPT WALLS & ROOF
ITEM Area Temp. diff.
(Sq ft) (°F)
All Glass 0 41.4
Partition 244.8 31.4
Ceiling 26 31.4
Floor 31.4
INTERNAL HEAT GAIN
People 1 Nos X
Light 13 WX
Eq. Load 0 WX

OUTSIDE AIR
CFM °F BF
10 41.4 0.15
ROOM SENSIBLE HEAT (RSH)
Supply duct Supply Heat gain from
heat gain + duct leak. fan HP(%)
loss +
Safety factor (%)

EFFECTIVE ROOM SENSIBLE HEAT (ERSH)


LATENT HEAT
People 1 Nos X
OUTSIDE AIR
CFM GR/LB BF
10 21 0.15

Supply duct leakage Safety


loss + factor %
EFFECTIVE ROOM LATENT HEAT
EFFECTIVE ROOM TOTAL HEAT (
OUTSIDE AIR HEAT (SENSIBLE)
CFM °F 1 - BF
10 41.4 0.85
OUTSIDE AIR HEAT (LATENT)
CFM GR/LB 1 - BF
10 21 0.85

Return duct HP Pump Dehum. & Pipe


heat gain & + loss (%)
leak. loss +
TR 0.44 GRAND TOTAL HEAT
Heat Load Sheet -1
AIRCON TECHNIQUE PVT. LTD. NEW DELHI
ALTURA MTS AREA DEL RECINTO MTS
s room (12.6 X 15.7) 750 13.2 13.2
1568 Cu ft ESTIMATE FOR : SUMMER
AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 95 90.99
ROOM 72 59.69
0.56 0 DIFFERENCE 23 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 2 People X 5
0.56 121 1568 Cu ft X 1
0.56 0 CFM VENTILATION
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 889 NOTES
0.34 0 Occupancy = 2 Nos
0.34 1454 Lighting = 0.2 W/Sq ft
0.34 0 Eq. Load = 0.3 KW
0.34 1165 Height = 9 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.38 3178 TR =
0.12 0 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)

1.13 468 AREA PARED A. VIDRIO


0.41 633 N - Wall
0.36 0 NE - Wall
0.36 815 E - Wall
HEAT GAIN SE - Wall
245 490 S - Wall 118.8 18
3.41 119 SW - Wall
3.41 1023 W - Wall
10355 NW - Wall
PARTITION
FACTOR ACTIVIDAD
"Trabajo de
1.08 37 Oficina"
ROOM SENSIBLE HEAT (RSH) 10393
0

CHECK FIGURES
10.0 1039 Derived Average
CFM/SQFT 3.97 3
ROOM SENSIBLE HEAT (ERSH) 11432 SQFT/TR 130.42 130
T HEAT SQFT/PER 87.12 65
205 410 BASEMENT NO/YES check

FACTOR
0.67 177
587
5.0 29
EFFECTIVE ROOM LATENT HEAT (ERLH)
616
EFFECTIVE ROOM TOTAL HEAT (ERTH)
12048
)
FACTOR
1.08 211

FACTOR

0.68 1018
HEAT SUB TOTAL 13277
5.0 664

13941 BTU/NR

Heat Load Sheet -2

AIRCON TECHNIQUE PVT. LTD. NEW DELHI

+Dress Room

4915 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 2 People X 10
0.56 1016 4915 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 6943
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 2 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 1803 Height = 12 FT
0.34 0 Load Summary
0.34 1187
0.34 0 Summer Load:
0.48 0 TR =
0.12 1954 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 10610 TA GA
0.41 10366 N - Wall
0.36 4630 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 490 S - Wall 307.2 151
3.41 698 SW - Wall
3.41 0 W - Wall 192 76
39698 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 39833
0

CHECK FIGURES
10.0 3983 Derived Average
CFM/SQFT 6.62 3
ROOM SENSIBLE HEAT (ERSH) 43816 SQFT/TR 89.87 130
T HEAT SQFT/PER 204.80 65
205 410 BASEMENT NO/YES check

FACTOR
0.67 42
452
5.0 23
EFFECTIVE ROOM LATENT HEAT (ERLH)
475
EFFECTIVE ROOM TOTAL HEAT (ERTH)
44291
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 45293
5.0 2265

GRAND TOTAL HEAT 47558

Heat Load Sheet -3


AIRCON TECHNIQUE PVT. LTD. NEW DELHI

1872 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 2 People X 10
0.56 0 1872 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 2314
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 2 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 1348
0.34 0 Summer Load:
0.48 0 TR =
0.12 744 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 1179 TA GA
0.41 5702 N - Wall
0.36 1764 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 490 S - Wall
3.41 266 SW - Wall
3.41 0 W - Wall 157 25
13807 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 13941
0

CHECK FIGURES
10.0 1394 Derived Average
CFM/SQFT 6.08 3
ROOM SENSIBLE HEAT (ERSH) 15335 SQFT/TR 92.22 130
T HEAT SQFT/PER 78.00 65
205 410 BASEMENT NO/YES check
FACTOR
0.67 42
452
5.0 23
EFFECTIVE ROOM LATENT HEAT (ERLH)
475
EFFECTIVE ROOM TOTAL HEAT (ERTH)
15810
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 16813
5.0 841

GRAND TOTAL HEAT 17653

Heat Load Sheet -4


AIRCON TECHNIQUE PVT. LTD. NEW DELHI

2393 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 8 People X 10
0.56 0 2393 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 8 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 951 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 0 TA GA
0.41 8868 N - Wall
0.36 2254 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 1960 S - Wall
3.41 340 SW - Wall
3.41 0 W - Wall
14373 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 14507
0

CHECK FIGURES
10.0 1451 Derived Average
CFM/SQFT 4.95 3
ROOM SENSIBLE HEAT (ERSH) 15958 SQFT/TR 105.83 130
T HEAT SQFT/PER 24.93 65
205 1640 BASEMENT NO/YES check

FACTOR
0.67 42
1682
5.0 84
EFFECTIVE ROOM LATENT HEAT (ERLH)
1766
EFFECTIVE ROOM TOTAL HEAT (ERTH)
17724
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 18727
5.0 936

GRAND TOTAL HEAT 19664

Heat Load Sheet -5


AIRCON TECHNIQUE PVT. LTD. NEW DELHI

603 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 1 People X 10
0.56 0 603 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 1 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 240 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 0 TA GA
0.41 4418 N - Wall
0.36 568 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 245 S - Wall
3.41 86 SW - Wall
3.41 0 W - Wall
5556 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 5690
0

CHECK FIGURES
10.0 569 Derived Average
CFM/SQFT 7.71 3
ROOM SENSIBLE HEAT (ERSH) 6259 SQFT/TR 66.35 130
T HEAT SQFT/PER 50.22 65
205 205 BASEMENT NO/YES check

FACTOR
0.67 42
247
5.0 12
EFFECTIVE ROOM LATENT HEAT (ERLH)
260
EFFECTIVE ROOM TOTAL HEAT (ERTH)
6519
)
FACTOR
1.08 760
FACTOR
0.68 243
HEAT SUB TOTAL 7522
5.0 376

GRAND TOTAL HEAT 7898

Heat Load Sheet -6


AIRCON TECHNIQUE PVT. LTD. NEW DELHI

3225 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 508 OUTSIDE AIR (VENTILATION)
0.56 0 2 People X 10
0.56 0 3225 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 2 Nos
0.34 1557 Lighting = 1.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 1282 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 3537 TA GA
0.41 7524 N - Wall
0.36 3037 NE - Wall
0.36 0 E - Wall 202.8 75.6
HEAT GAIN SE - Wall
245 490 S - Wall
3.41 1374 SW - Wall
3.41 0 W - Wall
19309 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 19443
0

CHECK FIGURES
10.0 1944 Derived Average
CFM/SQFT 4.93 3
ROOM SENSIBLE HEAT (ERSH) 21387 SQFT/TR 116.79 130
T HEAT SQFT/PER 134.36 65
205 410 BASEMENT NO/YES check

FACTOR
0.67 42
452
5.0 23
EFFECTIVE ROOM LATENT HEAT (ERLH)
475
EFFECTIVE ROOM TOTAL HEAT (ERTH)
21862
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 22865
5.0 1143

GRAND TOTAL HEAT 24008

Heat Load Sheet -7


AIRCON TECHNIQUE PVT. LTD. NEW DELHI

s room (16X 11.10)


2600 Cu ft ESTIMATE FOR : SUMMER
AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 339 OUTSIDE AIR (VENTILATION)
0.56 0 2 People X 10
0.56 0 2600 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 2 Nos
0.34 1733 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 1033 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 2358 TA GA
0.41 8790 N - Wall
0.36 2449 NE - Wall
0.36 0 E - Wall 192 50.4
HEAT GAIN SE - Wall
245 490 S - Wall
3.41 369 SW - Wall
3.41 0 W - Wall
17562 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 17696
0

CHECK FIGURES
10.0 1770 Derived Average
CFM/SQFT 5.56 3
ROOM SENSIBLE HEAT (ERSH) 19466 SQFT/TR 102.81 130
T HEAT SQFT/PER 108.33 65
205 410 BASEMENT NO/YES check

FACTOR
0.67 42
452
5.0 23
EFFECTIVE ROOM LATENT HEAT (ERLH)
475
EFFECTIVE ROOM TOTAL HEAT (ERTH)
19941
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 20943
5.0 1047

GRAND TOTAL HEAT 21991


Heat Load Sheet -8
AIRCON TECHNIQUE PVT. LTD. NEW DELHI

3120 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 4 People X 10
0.56 0 3120 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 4 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 1240 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 0 TA GA
0.41 10134 N - Wall
0.36 2939 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 980 S - Wall
3.41 443 SW - Wall
3.41 0 W - Wall
15736 NW - Wall
PARTITION
FACTOR
1.08 134
ROOM SENSIBLE HEAT (RSH) 15870
0

CHECK FIGURES
10.0 1587 Derived Average
CFM/SQFT 4.16 3
ROOM SENSIBLE HEAT (ERSH) 17457 SQFT/TR 133.40 130
T HEAT SQFT/PER 64.99 65
205 820 BASEMENT NO/YES check

FACTOR
0.67 42
862
5.0 43
EFFECTIVE ROOM LATENT HEAT (ERLH)
905
EFFECTIVE ROOM TOTAL HEAT (ERTH)
18363
)
FACTOR
1.08 760

FACTOR
0.68 243
HEAT SUB TOTAL 19366
5.0 968

GRAND TOTAL HEAT 20334


Heat Load Sheet -9
AIRCON TECHNIQUE PVT. LTD. NEW DELHI

309 Cu ft ESTIMATE FOR : SUMMER


AIN GLASS HEAT GAIN CONDITION DB (°F) WB (°F)
Factor Btu/hour OUTSIDE 113 75
ROOM 71.6
0.56 0 DIFFERENCE 41.4 XXXX
0.56 0
0.56 0 OUTSIDE AIR (VENTILATION)
0.56 0 1 People X 10
0.56 0 309 Cu ft X 1
0.56 0 CFM VENTILATIO
0.56 0
0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
0 Indicated ADP =
AIN WALLS & ROOF Selected ADP =
U Dehum. temp rise =
(Btu/h.sq ft) DEHUMIDIFIED CFM =
0.34 0 NOTES
0.34 0 Occupancy = 1 Nos
0.34 0 Lighting = 0.5 W/Sq ft
0.34 0 Eq. Load = 0 KW
0.34 0 Height = 12 FT
0.34 0 Load Summary
0.34 0
0.34 0 Summer Load:
0.48 0 TR =
0.12 123 DEH. CFM CONVENTIONAL =
EPT WALLS & ROOF DEH. CFM HIPER DUCTED =
U DEH. CFM HIPER PACKAGE =
(Btu/h.sq ft)
1.13 0 TA GA
0.41 3152 N - Wall
0.36 291 NE - Wall
0.36 0 E - Wall
HEAT GAIN SE - Wall
245 245 S - Wall
3.41 44 SW - Wall
3.41 0 W - Wall
3855 NW - Wall
PARTITION
FACTOR
1.08 67
ROOM SENSIBLE HEAT (RSH) 3922
0

CHECK FIGURES
10.0 392 Derived Average
CFM/SQFT 10.36 3
ROOM SENSIBLE HEAT (ERSH) 4314 SQFT/TR 50.67 130
T HEAT SQFT/PER 25.76 65
205 205 BASEMENT NO/YES check

FACTOR
0.67 21
226
5.0 11
EFFECTIVE ROOM LATENT HEAT (ERLH)
237
EFFECTIVE ROOM TOTAL HEAT (ERTH)
4551
)
FACTOR
1.08 380

FACTOR
0.68 121
HEAT SUB TOTAL 5053
5.0 253

GRAND TOTAL HEAT 5305


DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
86 240.02
50 63.93
36 176.10

R (VENTILATION)
CFM/Person 10
Air change per hour 26
CFM VENTILATION 20

0.95
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 15.30 °F
EHUMIDIFIED CFM = 692 CFM

DERATED
1.16 TR 1.34
691.84 CFM 1.73
691.84 CFM 1.38
691.84 CFM 1.26

VALOR FINAL DE
PARED
118.8
119

101

118.8

S
DATE: 16/10/2010

Estimated By: TAIYAB

FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21
CFM/Person 20
Air change per hour 82
CFM VENTILATION 20

0.99
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 2712 CFM

DERATED
3.96 TR 4.56
2711.91 CFM 6.78
2711.91 CFM 5.42
2711.91 CFM 4.93

MS

156

116

805.2

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 20
Air change per hour 31
CFM VENTILATION 20
0.97
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 949 CFM

DERATED
1.47 TR 1.69
949.13 CFM 2.37
949.13 CFM 1.90
949.13 CFM 1.73

MS

132

442.92

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 80
Air change per hour 40
CFM VENTILATION 20

0.90
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 988 CFM
DERATED
1.64 TR 1.88
987.69 CFM 2.47
987.69 CFM 1.98
987.69 CFM 1.80

MS

688.8

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 10
Air change per hour 10
CFM VENTILATION 20

0.96
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 387 CFM
DERATED
0.66 TR 0.76
387.42 CFM 0.97
387.42 CFM 0.77
387.42 CFM 0.70

MS

343.2

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 20
Air change per hour 54
CFM VENTILATION 20

0.98
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 1324 CFM

DERATED
2.00 TR 2.30
1323.74 CFM 3.31
1323.74 CFM 2.65
1323.74 CFM 2.41

MS

127

584.4

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 20
Air change per hour 43
CFM VENTILATION 20

0.98
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 1205 CFM

DERATED
1.83 TR 2.11
1204.81 CFM 3.01
1204.81 CFM 2.41
1204.81 CFM 2.19

MS

142

682.8

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 40
Air change per hour 52
CFM VENTILATION 20

0.95
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 1080 CFM

DERATED
1.69 TR 1.95
1080.50 CFM 2.70
1080.50 CFM 2.16
1080.50 CFM 1.96

MS
787.2

S
DATE: 16/10/2010
Estimated By: TAIYAB
FOR : SUMMER
% RH DP (°F) GR/LB
20 85
55 64
35 21

CFM/Person 10
Air change per hour 5
CFM VENTILATION 10

0.95
Indicated ADP = 54 °F
Selected ADP = 54 °F
Dehum. temp rise = 14.96 °F
EHUMIDIFIED CFM = 267 CFM

DERATED
0.44 TR 0.51
266.99 CFM 0.67
266.99 CFM 0.53
266.99 CFM 0.49

MS
244.8

S
FOR KNOWING THE SENSIBLE/LATENT HEAT GAIN

DEGREE OTYPICAL
"Sentado
en
Descanso
" THEATER

"Sentado,
muy
ligero
trabajo" HIGH
SCHOOL
"Trabajo OFFICES,
de HOTELS,
Oficina" APTS,CO
DEPT,RE
LLEGE
"De Pie, TAIL,OR
Caminado VARIETY
lento" STORE
"Camiana
do, y DRUG
sentado" STORE
"De Pie,
Caminado
lento" BANK

"Trabajo
Sedentari RESTAU
o" RANT
"Trabjo FACTORY
de Mesa ,LIGHT
suave" WORK

"Baile
Moderad DANCE
"Sentado
en reposo· 360 300 o" HALL

"Caminan
Sentado do, 3 FACTORY
efectuand millas por ,FAIRLY
o un
trabajo hora" HEAVY
ligero 390 410 WORK

Caminand
oo "Trabajo BOWLIN
efectuand Pesado" G ALLEY
o un
trabajo FACTOR
ligero 400 500 Y

Trabajo
sedentario 440 660
Baile
moderno 490 1210
Boliche o
trabajo
pesado 930 1970
82F 80F 78F 75F 70F
SENS LAT SENS LAT SENS LAT SENS

175 195 155 210 140 230 120 260

SENS-180 195 205 215 185 240 160 275


SENS-180 200 250 215 235 245 205 285

SENS-180 200 250 215 235 245 205 285

SENS-180 200 300 220 280 255 245 290

SENS-180 200 300 220 280 255 245 290

SENS-190 220 330 240 310 280 270 320

SENS-190 220 530 245 505 295 455 365

SENS-220 245 605 275 575 325 525 400

SENS-270 300 700 330 670 380 620 460

SENS-450 465 985 485 965 525 925 605


70F
LAT

90

125
165

165

210

210

230

385

450

540

845
SUMMARY OF HEAT LOAD AND UNIT PROPOSED
AT 71.6 F (220C)
Eqpt Load CFM CFM
S.NO AREA SQ. FEET CFM No.of Peo.
KW REF. TR TR@400 TR@500
CFM CFM

Bed room-1
1 +dress room 174.24 692 2 0.30 1.16 1.73 1.38
(12.6 X 15.7)

Master Bed
2 Room+Dress 409.60 2712 2 0.00 3.96 6.78 5.42
Room

3 Kitchen 156.01 949.13 2.00 0.00 1.47 2.37 1.90

4 Dining Room 199.42 987.69 8.00 0.00 1.64 2.47 1.98

5 Ent. Lobby 50.22 387.42 1.00 0.00 0.66 0.97 0.77

6 Drawing room 268.71 1323.74 2.00 0.00 2.00 3.31 2.65

Bed room-
7 2+dress room 216.66 1204.81 2.00 0.00 1.83 3.01 2.41
(16X 11.10)

8 Family Lounge 259.96 1080.50 4.00 0.00 1.69 2.70 2.16

9 Puja Room 25.76 266.99 1.00 0.00 0.44 0.67 0.53


EQUIPMENT
AT 71.6 F (220C) CONFIGURATION -TR(conventional)
CFM/SQF CFM
Equipment
DTD TR T DELIVER 17 11 8.5 5.5
selected
DERIVED ED

1.34 3.97

4.56 6.62

1.69 6.08

1.88 4.95

0.76 7.71

2.30 4.93

2.11 5.56

1.95 4.16

0.51 10.36
Psychrometric Calculator
inlet temp-> 72.0 °F dry bulb Valid temperature
inlet RH-> 50.0 % range:
outlet temp-> 95.0 °F dry bulb -80° to +211.94°
outlet RH-> 86.0 %
CFM in-> 100.0
altitude (ft.)-> 2,460 750.00 METROS
† Btu/hr = -13,457 total
Btu/hr = -2,264 sensible
*Btu/hr = -11,193 latent
Tons of heating 1.12
SHR = ~
CFM out = 108.5 63.93 gr/lb
moisture added lb/min = 0.17 240.02 gr/lb
moisture added lb/hr = 10.15
mbar 926.23
dewpoint in = 52.36 °F
dewpoint out = 90.14 °F
wet bulb in = 59.69 °F
wet bulb out = 90.99 °F

† negative capacity indicates heating


*assumes water temp = leaving air temp
processes: heating/ cooling/ humidifying/ dehumidifying

Psychrometric formulae extracted from-


2001 ASHRAE HANDBOOK: FUNDAMENTALS
Ch.6, "Psychrometrics"
Enter input to yellow cells only
If you must enter wet bulb or dew point instead of RH,
then simply adjust RH as necessary to obtain the
desired wet bulb or dew point temperature.
deltaT = -23.00 °F 59.60 0.253
deltaH = -33.37 btu/lb 59.61 0.253
H in = 27.26 btu/lb 59.62 0.253
H out = 60.63 btu/lb 59.63 0.253
generated tables-> 59.64 0.253
dry air density in = 0.0672 lb/ft^3 59.65 0.253
dry air density out = 0.0620 lb/ft^3 59.66 0.253
vapor density in = 0.0006 lb/ft^3 59.67 0.253
vapor density out = 0.0021 lb/ft^3 59.68 0.253
moist air density in = 0.0678 lb/ft^3 59.69 0.254
moist air density out = 0.0641 lb/ft^3 59.70 0.254
*t *sat p
humidity ratio in = 0.0091 lb(m)/lb(da) 53.0 0.199
humidity ratio out = 0.0343 lb(m)/lb(da) 54.0 0.206
55.0 0.214
pressure = 13.435 psia 56.0 0.222
sat. vapor pressure in = 0.3888 psia 57.0 0.230
sat. vapor pressure out = 0.8162 psia 58.0 0.239
vapor pressure in = 0.1944 psia 59.0 0.247
vapor pressure out = 0.7020 psia 60.0 0.256
dry air pressure in = 13.2409 psia 61.0 0.266
dry air pressure out = 12.7334 psia 62.0 0.275
63.0 0.285
vapor massflow in = 0.0614 lb/min
vapor massflow out = 0.2305 lb/min -67 0.001
dry air massflow in = 6.7218 lb/min -57 0.001
dry air massflow out = 6.7218 lb/min -47 0.002
-37 0.003
-27 0.006
-17 0.010
-7 0.016
3 0.025
13 0.040

NO TOCAR ESTA 23
33
0.061
0.092
43 0.137
TABLA 53 0.199
63 0.285
73 0.402
27.1934 <-in out-> 90.90 0.719 60.4890 59.0 0.247
27.2004 90.91 0.719 60.5037 59.1 0.248
27.2074 90.92 0.719 60.5183 59.2 0.249
27.2144 90.93 0.720 60.5330 59.3 0.250
27.2215 90.94 0.720 60.5476 59.4 0.251
27.2285 90.95 0.720 60.5623 59.5 0.252
27.2355 90.96 0.720 60.5770 59.6 0.253
27.2426 90.97 0.720 60.5916 59.7 0.254
27.2496 90.98 0.721 60.6063 59.8 0.255
27.2566 90.99 0.721 60.6210 59.9 0.255
27.2637 91.00 0.721 60.6357 60.0 0.256
*H in wb table *t *sat p *H out *t *sat p
22.8569 <-in out-> 85.0 0.596 52.4348
23.4778 86.0 0.616 53.7209 `t
24.1109 87.0 0.636 55.0381 52.31
24.7568 88.0 0.656 56.3871 52.32
25.4158 89.0 0.677 57.7691 52.33
26.0883 90.0 0.699 59.1850 52.34
26.7747 91.0 0.721 60.6357 52.35
27.4754 <-in out-> 92.0 0.744 62.1223 52.36
28.1908 93.0 0.767 63.6459 52.37
28.9213 94.0 0.791 65.2076 52.38
29.6675 95.0 0.816 66.8085 52.39
52.40
-16.9568 -45 0.002 -13.3333 52.41
-14.4409 -35 0.004 -10.5084
-11.9063 -25 0.006 -7.6303 51.4
-9.3411 -15 0.011 -4.6701 51.5
-6.7272 -5 0.017 -1.5865 51.6
-4.0378 5 0.028 1.6784 51.7
-1.2345 15 0.043 5.2045 51.8
1.7370 25 0.067 9.0999 51.9
4.9517 35 0.100 13.5088 52.0
8.5114 45 0.148 18.6220 52.1
12.5524 55 0.214 24.6895 52.2
17.2553 65 0.306 32.0385 52.3
22.8570 75 0.430 41.0980 52.4
29.6675 85 0.596 52.4348
38.0930 95 0.816 66.8085 41
42
43
44
45
46
47
48
49
50
51
52
53
54
26.7747 <-in out-> 90.0 0.699 59.1849
26.8441 90.1 0.701 59.3284
26.9137 90.2 0.703 59.4723
26.9834 90.3 0.705 59.6165
27.0532 90.4 0.708 59.7610
27.1232 90.5 0.710 59.9059
27.1934 90.6 0.712 60.0511
27.2637 90.7 0.714 60.1967
27.3341 90.8 0.717 60.3427
27.4047 90.9 0.719 60.4890
27.4754 91.0 0.721 60.6357
*H in wb table wb temp wb sat p *H out

`sat p td table `t `sat p


0.194 90.09 0.701
0.194 90.10 0.701
0.194 <-in out-> 90.11 0.701
0.194 90.12 0.702
0.194 90.13 0.702
0.194 90.14 0.702
0.194 90.15 0.702
0.195 90.16 0.702
0.195 90.17 0.703
0.195 90.18 0.703
0.195 90.19 0.703

0.188 90.1 0.701


0.188 90.2 0.703
0.189 90.3 0.705
0.190 90.4 0.707
0.190 90.5 0.710
0.191 90.6 0.712
0.192 90.7 0.714
0.193 90.8 0.716
0.193 90.9 0.719
0.194 91.0 0.721
0.195 91.1 0.723

0.129 79 0.492
0.134 80 0.509
0.139 81 0.526
0.144 82 0.543
0.150 83 0.561
0.156 84 0.579
0.162 85 0.598
0.168 86 0.618
0.174 87 0.638
0.181 <-in out-> 88 0.658
0.188 89 0.679
0.195 90 0.701
0.202 91 0.723
0.210 92 0.746