Você está na página 1de 8

148 Electric Machines

3.1 The emf per turn for a single-phase 2200/220- 3.5 A transformer has 200 primary and 400
V, 50-Hz transformer is approximately 12 V. secondary turns. The primary draws a current
Calculate of (44.68 + j 2.37) A when the secondary
(a) the number of primary and secondary supplies a load current of (21.62 + j0) A. (a)
turns, and Find the exciting current. (b) If the core has a
(b) the net cross-sectional area of core of a permeance of 7.69 ¥ 10–5 H/T2, find the peak
maximum flux density of 1.5 T. value of core flux. (c) Find the primary and
secondary induced emfs if the frequency is
3.2 A transformer has primary and secondary
50 Hz. (d) Find the core loss.
turns of 1250 and 125 respectively. It has
core cross-section of 36 cm2 and its rms flux Remark: This is a learning exercise. This is
density is to be limited to 1.4 T (to prevent not how the exciting current is measured in a
transformer because this needs differentiating
core saturation). What maximum 50 Hz
of two nearly equal quantities which introduces
voltage can be applied on the primary side
large measurement error. As elaborated in this
and the corresponding open-circuit secondary
chapter the exciting current is measured by a
voltage?
no-load test.
The core has a mean length of 150 cm and
3.6 A 23 kVA, 50 Hz, 2300/230 V transformer
its relative permeability can be assumed to be
has primary and secondary turns of 200/20.
8000. What would be the rms exciting current
When rated voltage is applied, calculate
when the transformer’s primary winding is
the mutual core flux neglecting the winding
excited at a voltage as calculated above? Also
voltage drops. At full load the leakage flux
calculate the magnetizing susceptance as seen
linking each winding is 1% of the mutual flux.
from primary and secondary sides.
Calculate the primary and secondary leakage
If the transformer were to be excited at 60 reactances and the total reactance as referred
Hz, what should be the maximum primary to either side.
voltage for the core flux density limit not to Hint: fl1 is caused by I1N1 and by I1N2, while
be exceeded? What would be the magnetizing the mutual flux is caused by (I1N1 – I2N2).
susceptance as seen on each side in this case? Refer Fig. 3.11.
3.3 A single-phase transformer is rated 600/200 V, 3.7 A 100 kVA, 1100/230 V, 50-Hz transformer
25 kVA, 50 Hz. The transformer is supplying has an HV winding resistance of 0.1 W and a
full load on secondary side at 0.707 pf lagging. leakage reactance of 0.4 W. The LV winding
What is the load impedance? Assuming the has a resistance of 0.006 W and a leakage
transformer to be ideal what impedance is reactance of 0.01 W. Find the equivalent
seen on the primary side; also the primary winding resistance, reactance and impedance
current and its pf. referred to the HV and LV sides. Convert
3.4 A single-phase 50 Hz transformer has a these to pu values.
voltage ratio of 230/2300 V. A capacitor rated 3.8 A 50 kVA, 2200/110 V transformer when
30 kVAR is connected on the 2300 V side. tested gave the following results:
Calculate the value of this capacitor. What is OC test, measurements on the LV side: 400 W,
the kVAR of the capacitor and the value of its 10 A, 110 V
capacitance as seen on 230-V side. Assume SC test, measurements on the HV side; 808 W,
the transformer to be ideal. 20.5 A, 90 V
Transformers 149

Compute all the parameters of the equivalent the load and source impedances (i.e. by
circuit referred to the HV and LV sides of making the 60 W secondary impedance to
the transformer. Also calculate % voltage 2400 W when referred to the primary).
regulation and efficiency at full load and (b) Find the load current, voltage and power
0.8 pf lagging. under the conditions of maximum power
3.9 A 22/127 kV, 125 MVA transformer has transfer.
primary and secondary impedances of 0.015 3.13 Draw a clear phasor diagram of a transformer
+ j 0.06 pu each. Its magnetizing reactance is operating at rated values. Refer to Fig. 3.14(a)
j 120 pu. The pu values are expressed on the and assume N1/N2 = 1.5 and I1R1 = 0.15 E1,
base of the transformer rating. Calculate the I2R2 = 0.15 V2, I1X1 = 0.3 E1, I2 X2 = 0.25 V2,
primary and secondary impedances in ohms Ii = 0.1 I 2¢ , Im = 0.25 I 2¢
and also the magnetizing reactance in ohms Consider the load power factor to be (a)
on the LV side. 0.8 lagging (b) 0.8 leading. Use V2 as the
3.10 A 20 kVA, 2000/200 V, 50 Hz transformer is reference phasor.
operated at no-load on rated voltage, the input 3.14 An ideal transformer has a primary winding
being 150 W at 0.12 power factor. When it is of 200 turns. On the secondary side the
operating at rated load, the voltage drops in the number of turns between A and B is 600 and
total leakage reactance and the total resistance between B and C is 400 turns, that between A
are, respectively, 2 and 1 per cent of the rated and C being 1000. The transformer supplies
voltage. Determine the input power and power a resistor connected between A and C which
factor when the transformer delivers 10 kW draws 10 kW. Further, a load of 2000 –45° W
at 200 V at 0.8 pf lagging to a load on the LV is connected between A and B. The primary
side. voltage is 2 kV. Find the primary current.
3.11 A single-phase load is fed through a 66-kV 3.15 A 5-kVA, 400/80-V transformer has Req (HV)
feeder whose impedance is 120 + j 400 W and = 0.25 W and Xeq (HV) = 5 W and a lagging
a 66/6.6 kV transformer whose equivalent load is being supplied by it resulting in the
impedance (referred to LV) is 0.4 + j 1.5 W. following meter readings (meters are placed
The load is 250 kW at 0.8 leading power on the HV side).
factor and 6 kV. I1 = 16 A, V1 = 400 V, P1 = 5 kW
(a) Compute the voltage at the sending-end of For this condition calculate what a voltmeter
the feeder. would read if connected across the load
(b) Compute the voltage at the primary terminals. Assume the exciting current to be
terminals of the transformer. zero.
(c) Compute the complex power input at the 3.16 A 25-kVA, 230/115-V, 50-Hz transformer has
sending-end of the feeder. the following data
3.12 An audio-frequency ideal transformer is R1 = 0.12 W R2 = 0.04 W
employed to couple a 60-W resistance load X1 = 0.2 W X2 = 0.05 W
to an electric source which is represented by
Find the transformer loading which will make
a constant voltage of 6 V in series with an
the primary induced emf equal in magnitude
internal resistance of 2400 W.
to the primary terminal voltage when the
(a) Determine the turn-ratio required to ensure transformer is carrying the full load current.
maximum power transfer by matching Neglect the magnetizing current.
150 Electric Machines

3.17 The resistances and leakage reactances of 3.20 The approximate equivalent circuit of a
a 10 kVA, 50 Hz, 2200/220 V distribution 4 kVA, 200/400 V single-phase transformer,
transformer are as follows: referred to the LV side, is shown in Fig. P3.20.
(a) An open-circuit test is conducted by
R1 = 4 W R2 = 0.04 W
applying 200 V to the LV side, keeping
X1 = 5 W X2 = 0.05 W
the HV side open. Calculate the power
Each quantity is referred to its own side of the input, power factor and current drawn by
transformer. (Suffix ‘1’ stands for HV and ‘2’ the transformer.
for LV). (b) A short-circuit test is conducted by passing
(a) Find the total leakage impedance referred full-load current from the HV side keeping
to (i) HV side (ii) LV side. the LV side shorted. Calculate the voltage
required to be applied to the transformer
(b) Consider the transformer to give its rated
and the power input and power factor.
kVA at 0.8 pf lagging to a load at rated
voltage. Find the HV terminal voltage and
% voltage regulation. 0.15 W 0.4 W
+ +
(c) Repeat (b) for a pf of 0.8 leading.
(d) Consider the core-loss to be 80 W. Find
V1 800 W 400 W V¢2
the efficiency under the conditions of part
(b). Will it be different for the conditions
– –
under part (c)?
(e) If the load in part (b) gets short-circuited, Fig. P 3.20
find the steady-state current in the HV
lines, assuming that the voltage applied to
3.21 A 20 kV A, 2000/200 V transformer has name
the transformer remains unchanged.
plate leakage impedance of 8%. What voltage
3.18 For Problem 3.10, assume that the load power must be applied on the HV side to circulate
factor is varied while the load current and full-load current with the LV shorted?
secondary terminal voltage are held fixed. 3.22 Derive the condition for zero voltage
With the help of a phasor diagram, find the regulation. Also show that the magnitude of
load power factor for which the voltage maximum voltage regulation equals the pu
regulation is zero. value of equivalent leakage impedance.
3.19 A 20 kVA, 2000/200 V, single-phase 3.23 The following test results were obtained for
transformer has the following parameters: a 20 kVA, 50 Hz, 2400/240 V distribution
HV winding: R1 = 3 W X1 = 5.3 W transformer:
L V winding: R2 = 0.05 W X2 = 0.05 W Open-circuit test (LV): 240 V, 1.066 A, 126.6 W
Short-circuit test (HV): 57.5 V, 8.34 A, 284 W
(a) Find the voltage regulation at (i) 0.8 pf
(a) When the transformer is operated as a step-
lagging (ii) upf (iii) 0.707 pf leading.
down transformer with the output voltage
(b) Calculate the secondary terminal voltage
equal to 240 V, supplying a load at unity
at (i) 0.8 pf lagging (ii) upf (iii) 0.707 pf
power factor, determine the maximum
leading when delivering full-load current
efficiency and the unity power factor load
with the primary voltage held fixed at
at which it occurs.
2 kV.
Transformers 151

(b) Determine the power-factor of the rated 3.28 A 20 kVA, 200/500 V, 50 Hz, single-phase
load, supplied at 240 V, such that the transformer is connected as an auto-trans-
terminal voltage observed on reducing the former as shown in Fig. P3.28. Determine its
load to zero is still 240 V. voltage-ratio and the kVA rating. Mark on the
3.24 In a 25 kVA, 2000/200 V transformer, the diagram, the magnitudes and relative direc-
iron and copper losses are 300 and 400 W tions of the currents in the winding as well as
respectively. in the input and output lines when delivering
the rated kVA to load.
(a) Calculate the efficiency on unity power-
factor at (i) full-load (ii) half-load.
(b) Determine the load for maximum
efficiency and the iron-and the copper-loss 500 V
in this case. Load
3.25 The efficiency of a 1000 kVA, 110/220 V,
50 Hz, single-phase transformer is 98.5% at

200V
half full-load at 0.8 pf leading and 98.8% at Input
full-load upf.
Determine: (a) iron-loss, (b) full-load copper- Fig. P3.28
loss, and (c) maximum efficiency at upf.
3.26 Open and short-circuit tests performed on a 3.29 A 400/100 V, 10 kVA, 2-winding transformer
500 kVA, 6600/2300 V, 50 Hz transformer is to be employed as an autotransformer to
yielded the following data: supply a 400 V circuit from a 500 V source.
No-load loss = 3 kW When tested as a 2-winding transformer at
Full-load short circuit loss = 4 kW rated load, 0.85 pf lagging, its efficiency is
0.97%.
(a) Calculate the load (kVA) at which the (a) Determine its kVA rating as an autotrans-
transformer efficiency would be maximum former.
for a given power factor. Calculate this
(b) Find its efficiency as an autotransformer.
efficiency for a pf of 0.85.
3.30 A 20 kVA, 2000/200 V, two-winding trans-
(b) The transformer supplies the following
former is to be used as an autotransformer,
load cycle.
with a constant source voltage of 2000 V.
12 hours, full load 0.8 pf. At full-load of unity power factor, calculate
12 hours, half full load 0.9 pf. the power output, power transformed and
Calculate the energy efficiency of the power conducted. If the efficiency of the two-
transformer. winding transformer at 0.7 pf is 97%, find the
3.27 A transformer has its maximum efficiency of efficiency of the autotransformer.
0.98 at 20-kVA at unity power factor. During 3.31 A 200/400 V, 20 kVA, and 50 Hz transformer is
the day it is loaded as follows: connected as an autotransformer to transform
12 hours; 2 kW at power factor 0.6 600 V to 200 V.
6 hours; 10 kW at power factor 0.8 (a) Determine the autotransformer ratio a¢.
6 hours; 20 kW at power factor 0.9 (b) Determine the kVA rating of the auto-
Find the ‘all-day’ efficiency of the transformer. transformer.
152 Electric Machines

(c) With a load of 20 kVA, 0.8 pf lagging 0.07), and (0.025 + j 0.0875) W respectively.
connected to 200 V terminals, determine What is the largest value of the unity power
the currents in the load and the two factor load that can be delivered by the parallel
transformer windings. combination at the rated voltage?
3.32 An audio frequency output transformer 3.35 Two single-phase transformers rated
couples a variable frequency source of output 600 kVA and 500 kVA respectively, are
resistance 4.5 kW to a load of 10 W. The connected in parallel to supply a load of
transformer has a turn ratio of 25.4. On test 1000 kVA at 0.8 lagging power factor.
the following inductance data are measured The resistance and reactance of the first
on the transformer. transformer are 3% and 6.5% respectively,
(i) Inductance seen on the primary side with and of the second transformer 1.5% and 8%
secondary open = 18.7 H. respectively. Calculate the kVA loading and
(ii) Inductance seen on the primary side with the power factor at which each transformer
secondary shorted = 0.215 H. operates.
3.36 An ideal 3-phase step-down transformer,
In terms of the frequency response calculate
connected delta/star delivers power to a
(a) lower corner frequency (b) upper corner
balanced 3-phase load of 120 kVA at 0.8
frequency and (c) voltage gain and phase
power factor. The input line voltage is 11 kV
angle at the geometric mean of the frequencies
and the turn-ratio of the transformer, phase-to-
in parts (a) and (b)
phase is 10. Determine the line voltages, line
Hint: It is sufficiently accurate to assume that
currents, phase voltages and phase currents on
test both the primary and the secondary sides.
(i) yields Lm, the magnetizing inductance and 3.37 A D/Y connected bank of three identical
test 60 kVA 2000/100 V, 50 Hz transformers
(ii) yields the leakage inductance seen on is fed with power through a feeder whose
primary side. Transformer winding resis- impedance is 0.75 + j 0.25 W per phase. The
tance is ignored. voltage at the sending-end of the feeder is held
3.33 A 20 kVA, 4400/220 V transformer with an fixed at 2 kV line-to-line. The shortcircuit test
equivalent impedance of 0.01 W is to operate when conducted on one of the transformers
in parallel with a 15 kVA, 4400/220 V with its LV terminals shortcircuited gave the
transformer with an equivalent impedance of following results:
0.015 W. The two transformers are connected VHV = 40 V f = 50 Hz
in parallel and made to carry a load of 25 kVA. IHV = 35 A P = 800 W
Assume both the impedances to have the same
(a) Find the secondary line-to-line voltage
angle.
when the bank delivers rated current to a
(a) Find the individual load currents. balanced 3-phase upf load.
(b) What per cent of the rated capacity is used (b) Calculate the currents in the transformer
in each transformer? primary and secondary windings and in the
3.34 Two single-phase transformers, rated feeder wires on the occurrence of a solid
1000 kVA and 500 kVA respectively, are 3-phase short-circuit at the secondary line
connected in parallel on both HV and LV sides. terminals.
They have equal voltage ratings of 11 kV/400 3.38 Each phase of 3-phase transformer is rated
V and their per unit impedances are (0.02 + j 6.6 kV/230V, 200 kVA with a series reactance
of 8%.
Transformers 153

(a) Calculate the reactance in ohm referred to the primary current when the rated current
HV/LV sides. in the 220 V winding is at upf and the rated
(b) The transformer is connected Y/Y. What is current in the 550 V winding is 0.6 pf lagging.
its 3-phase rating (voltage and kVA) and Neglect all leakage impedance drops and
the per unit reactance. magnetizing current.
(c) Calculate the pf of load (rated) at which 3.43 A small industrial unit draws an average load
voltage regulation would be maximum. If of 100 A at 0.8 lagging pf from the secondaries
this load is fed at rated voltage on LV side, of its 2000/200 V, 60 kVA Y/D transformer
what should be the HV side line voltage? bank. Find:
3.39 A 2400/220 V, 300 kVA, 3-phase transformer (a) The power consumed by the unit in kW,
has a core loss of 33 kW at rated voltage. Its (b) the total kVA used,
equivalent resistance is 1.6%. Calculate the (c) the rated line currents available from the
transformer efficiency at 1.8 pf at (i) full load transformer bank,
(ii) at half load. (d) the rated transformer phase currents of the
What is the load at which the transformer D-secondaries,
efficiency would be maximum? Calculate its (e) per cent of rated load on transformers,
value at a pf of 0.8. (f ) primary line and phase currents, and
Hint: Use the pu method. (g) the kVA rating of each individual
3.40 A 3-phase 50 kVA, 6.6/0.4 kV 50 Hz transformer.
transformer is D/Y connected. It yielded the 3.44 The HV terminals of a 3-phase bank of three
following test results: single-phase transformers are connected to a
OC Test SC Test 3-wire, 3-phase, 11 kV (line-to-line) system.
P0 = 520 W PSC = 610 W The LV terminals are connected to a 3-wire,
I0 = 4.21 A ISC = 4.35 A 3-phase load rated of 1000 kVA and 2200 V
V0 = 400 V VSC = 340 V line-to-line. Specify the voltage, current and
Calculate the pu circuit parameters of the kVA ratings of each transformer (both HV and
transformer. Determine its efficiency and LV windings) for the following connections:
voltage regulation at full load 0.8 pf lagging. (a) HV – Y, LV – D (b) HV – D, LV – Y
Calculate also the maximum efficiency and (c) HV – Y, LV – Y (d) HV – D, LV – D.
the load (0.8 pf ) at which it will occur. 3.45 A 3-phase bank consisting of three single-
3.41 A 6.6/0.4 kV, 100 kVA distribution transformer phase 3-winding transformers (Y/D/Y) is
is connected D/Y. The transformer has 1.2% employed to step-down the voltage of a
resistance and 5% reactance. Find the voltage 3-phase, 220 kV transmission line. The data
regulation at full load, 0.8 pf leading. With pertaining to one of the transformers are given
0.4 kV as secondary voltage (on load), what is below:
the primary voltage? Ratings
Hint: Use pu system. Primary 1: 20 MVA, 220 kV
3.42 A single-phase, 50 Hz, three-Winding trans- Secondary 2: 10 MVA, 33 kV
former is rated at 2200 V on the HV side with Tertiary 3: 10 MVA, 11 kV
a total of 250 turns. Of the two secondary Short-circuit reactances on 10 MV A base
windings, each can handle 200 kVA, one is X12 = 0.15 pu
rated at 550 V and the other at 220 V. Compute X23 = 0.1 pu
154 Electric Machines

X13 = 0.2 pu
shown, supply 1000 A at a voltage of 100 2
Resistances are to be ignored. The D-connected to a resistive load. The phase sequence of the
secondaries supply their rated current to a 3-phase supply is ABC.
balanced load at 0.85 power factor lagging,
(a) Calculate the turn-ratio of the teaser
whereas the tertiaries provide the rated current
transformer.
to a balanced load at upf (constant resistance).
(b) Calculate the line current IB and its phase
(a) Compute the primary line-to-line voltage
angle with respect to the voltage of phase
to maintain the rated voltage at the
A to neutral on the 3-phase side.
secondary terminals.
(b) For the conditions of part (a) find the line-
Teaser
to-line voltage at the tertiary terminals.
1000 A
(c) If the primary voltage is held fixed as in A

part (a), to what value will the tertiary 11 kv, 3-phase


supply Resistive load
voltage increase when the secondary load
is removed?
100 2
3.46 A 500-kVA, 11/0.43-kV, 3-phase delta/star B Volts
M
connected transformer has on rated load HV C
Main
copper-loss of 2.5 kW and LV loss of 2 kW.
The total leakage reactance is 0.06 pu. Find
the ohmic values of the equivalent resistance Fig. P3.49
and leakage reactance on the delta side.
3.47 Two transformers each rated 250-kVA, 3.50 A 15 kVA, 2200/220 V, 50 Hz transformer
11/2-kV and 50-Hz are connected in open- gave the following test results:
delta on both the primary and secondary. OC (LV side) V = 220 V I = 2.72 A
(a) Find the load kVA that can be supplied P = 185 W
from this transformer connection. SC (HV side) V = 112 V I = 6.3 A
(b) A delta connected three-phase load of P = 197 W
250 kVA, 0.8 pf, 2 kV is connected to Compute the following:
the low-voltage terminals of this open- (a) Core loss
voltage transformer. Determine the (b) Full-load copper loss
transformer currents on the 11 kV side of (c) Efficiency at full-load 0.85 lagging of
this connection.
(d) Voltage regulation at full-load 0.8 lagging/
3.48 Two 110-V, single-phase furnaces take loads leading pf
of 500 kW and 800 kW respectively at a 3.51 A transformer of rating 20 kVA, 2000/200 V
power factor of 0.71 lagging and are supplied has the following parameters:
from 6600 V, 3-phase mains through a Scott-
Req(HV side) = 2.65 W
connected transformer combination. Calculate
Zeq(HV side) = 4.23 W
the currents in the 3-phase lines, neglecting
transformer losses. Draw the phasor diagram. Core loss at rated voltage = 95 W
3.49 Figure P3.49 shows a Scott-connected (a) Calculate transformer efficiency when
transformer, supplied from 11 kV, 3-phase, delivering 20 kVA at 200 V at 0.8 pf
50 Hz mains. Secondaries, series connected as lagging.
Transformers 155

(b) What voltage must be applied on the HV tertiary is rated 600 V, 200 kVA and supplies
side for load as in part (a). full-load at 0.6 pf lagging. Determine the
(c) Find the percentage voltage regulation. primary current.
3.52 A 100 kVA, 11 kV/231 V transformer has HV 3.56 An ideal transformer has 200 primary turns
and LV winding resistances of 8.51 W and and 360 secondary turns, the primary being
0.0038 W respectively. It gave the following excited at 600 V. The full secondary has a
test results: resistive load of 8 kW. The secondary is also
tapped at 240 turns which supplies a pure
OC (LV side) 231 V 15.2 A 1.25 kW inductive load of 10 kVA. Find the primary
SC (HV side) 440 V 9A Not current and its pf.
measured 3.57 A 50 kVA, 2300 V/230 V transformer draws
Calculate power of 750 W at 0.5 A at no load when
(a) Equivalent leakage reactance of the 2300 V is applied to the HV side. The HV
transformer winding resistance and leakage reactance are
(b) Full load copper loss 1.8 W and 4 W respectively. Calculate:
(c) Efficiency at full-load and half full-load at (a) the no load pf
0.85 lagging power factor (b) the primary induced emf
3.53 A 100 kVA, 2200 V/220 V transformer has the (c) the magnetizing current and
following circuit parameters. (d) the core loss component of current.
R1 = 0.23 W R2 = 0.0023 W 3.58 Two single-phase transformers operate in
X1 = 1.83 W X2 = 0.013 W parallel to supply a load of 44 + j 18.6 W. The
R1 (HV side) = 5.6 kW transformer A has a secondary emf of 600 V
Xm(HV side) = 1.12 kW on open circuit with an internal impedance
of 1.8 + j 5.6 W referred to the secondary.
The transformer is subjected to the following
The corresponding figures for transformer
daily load cycle = 4 h on no load, 8 h on 1/4th
B are 610 V and 1.8 + j 7.4 W. Calculate the
full-load at 0.8 pf, 8 h on 1/2 full-load at upf,
terminal voltage, current and power factor of
and 4 h on full-load at 0.9 pf.
each transformer.
Determine the all-day energy efficiency of the
3.59 Each phase of a 3-phase transformer is rated
transformer.
6.6 kV/230 V, 200 kVA with a series reactance
3.54 A 400/200 V, 50 Hz transformer has a primary
of 8%
impedance of 1.2 + j 3.2 W and secondary
(a) Calculate the reactance in ohm referred to
impedance of 0.4 + j 1.0 W. A short-circuit
HV/LV sides.
occurs on the secondary side with 400 V
applied to the primary. Calculate the primary (b) The transformer is connected Y/Y. What is
current and its power factor. its 3-phase rating (voltage and kVA) and
3.55 A 50 Hz, 3-winding transformer can be the per unit reactance.
considered as an ideal transformer. The (c) Calculate the pf of load (rated) at which
primary is rated 2400 V and has 300 turns. voltage regulation would be maximum. If
The secondary winding is rated 240 V, this load is fed at rated voltage on LV side,
400 kVA and supplies full-load at upf. The what should be the HV side line voltage?

Você também pode gostar