Direct expansion cooling


for mission-critical applications
Delta
Capacity range:
30-100kW

Fixed speed | Inverter compressors


efficient operation under various heat load conditions

Dual-cool feature
two indepandent cooling sources enable highest reliability

Single | Double refrigerant circuit


more flexilibity, more reliability

Huge array of options and accessories


helps to build tailor-made cooling solutions

Delta precision cooling system


High-efficient precision air conditioning units with fixed speed and inverter compressors

SCROLL INVERTER R410a EC FANS DUAL COOL FREECOOLING DOWNFLOW UPFLOW

68 models | 5 enclosure sizes

November 2015
Superior energy efficiency
Technology Delta DX/DC close control cooling system provides precise and reliable control of indoor temperature, humidity and
airflow for proper operation of IT equipment in the data centers. As the heat density of electronic equipment in
modern data centers continue to grow, the application of Delta DX/DC solution allows the cooling system to remain
efficient and perform at optimal levels even when it is functioning at partial loads.

Compressors
Fixed-speed compressors are perfectly suitable for applications where the heat
load is almost constant. The customers of Delta DX/DC systems with fixed-speed
compressors can benefit from quiet operation, unmatched reliability and low
operating cost.
For cooling systems where the heat load and the operating conditions vary over
a wide range, Delta DX/DC offer scroll compressors with stepless capacity
modulation down to 10% of the nominal capacity, enabling precise temperature
control, quiet operation, and superior energy saving.
Both fixed-speed and modulating compressors are optimized for precision
cooling applications and R410a refrigerant.

EC fans
Delta DX/DC features the new radial fans with unique blade geometry and offers
more airflow by smaller size and wide efficiency range. In combination with
EC-motors with integrated control functionality, communication interface and
overtemperature protection, these fans provide unbeatable energy efficiency,
maximum flexibility, and lowest possible sound emission. The EC motor technol-
ogy provide significant savings at both full-load and part-load operation.
Delta’s EC-motors are maintenance free and have a longer lifetime in compari-
son to brushed motors.

Heat exchanger
Delta DX/DC family features fin-tube heat exchangers with small-diameter inner grooved copper tubes and state-of-the-art aluminium
fins. Inner grooving increases the internal surface space, while the groove’s torsion promotes turbulent flow, better refrigerant mixing,
and eliminate refrigerant mal-distribution, resulting in improved heat exchanger performance. Small tube diameter requires less
refrigerant and can withstand higher pressures. The fin geometry has been optimized to achieve improved heat transfer, while
retaining low airside pressure drops.
The laboratory experiments were showed that heat exchanger coils manufactured using small-diameter tubing reduced tube weight
by 35%, fin weight by 30%, and lowered internal coil volume by 40% compared to previous generation.
The unit construction allows easy access to the heat exchanger for maintenance and cleaning.

Dual-cool feature
Dual-cool feature provides thermal management from two independent cooling sources, with direct expansion and chilled water
technologies, and gives a wide range of cooling solutions with a focus on either energy efficiency or system reliability.
The Delta’s control system manages the system by activating DX or CW cooling circuits in accordance to user settings. Chilled water
circuit features 2-way regulating valve to control the cooling capacity.

www.kaltra.de 1
Features and options
A wide array of options and accessories are available to choose from, giving our customers the possibility to tailor the
Delta DX/DC to create exactly the cooling solution they need. Advanced control software features with network connec-
tivity interfaces provides flexible system management - either local or remote - by connecting the cooling units to the
BMS network.

Features
Unit identification
Delta DX i D 60 / 2 Enclosure Width Depth Height
size mm mm mm

F1 1295 925 1985


Direct expansion (DX) F2 1625 925 1985
Cooling
DX+CW dual-cool (DC) F3 1875 925 1985
F4 2175 925 1985
Fixed speed (-) F5 2495 925 1985
Compressor(s) type
Inverter (i)

Condenser size Downflow (D)


Air discharge
Upflow (U)

Nominal capacity kW

Gas circuits Qty.

Package & options


Features Features
DXi/DCi

DXi/DCi
CW 06

CW 09

CW 12

CW 15

CW 18
DX/DC

DX/DC

General
Electrical heater - standard capacity □ □ Air discharge plenum w/ mesh guards □ □
Electrical heater - high capacity □ □ Air intake plenum □ □
Steam humidification system - standard capacity □ □ High performance filters for air intake plenum □ □
Steam humidification system - high capacity □ □ Sound attenuator for air intake plenum □ □
Dehumidification system □ □ Thermal/noise-reduction insulation □ □
Condensate discharge system □ □ Noise-reduction shells for compressors □ □
Motorized backdraft damper □ □ Leak detection □ □
Floorstand □ □ Air pressure control □
Airside
EC-fans □ ■ Temperature/humidity probe on air intake □ □
Dirty filter alarm switch □ □ Temperature/humidity probe (external) □ □
F5 air filtration □ □ Temperature/humidity probe (remote) □ □
Refrigerant circuits
Electronic expansion valve (EEV) □ ■ Solenoid valve (liquid line) □ □
Fluidside
Dual-cool - chilled water cooling system □ □ 2-way regulating valve □
Heating coil □ □ 3-way regulating valve □ □
Power and controls
Power factor capacitor + phase sequence control □ BMS connectivity □ □
Soft starter □ □ SNMP connectivity □ □
Dual power supply □ □ Dual serial connection □ □
Controller backup power supply □ □ Remote terminal □ □
■ Standard feature
□ Option

2 www.kaltra.de
Technical specifications
Fixed speed compressors:
inlet air: 24°C 50% rH; cooling media temperature (Dual-cool feature): 7/12°C, 100% water; ambient temperature 35°C

Cooling mode DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC DX/DC
Air discharge D/U D/U D/U D/U D/U D/U D/U D/U D/U D/U D/U D/U
Model 30/1 35/1 40/1 45/1 40/2 50/2 55/2 60/2 75/2 80/2 90/2 100/2

Frame size F1 F1 F1 F1 F2 F2 F3 F3 F4 F4 F5 F5
DX mode
Cooling capacity - total kW 30.2 35.0 38.4 42.5 35.5 44.2 51.5 58.5 71.6 76.9 86.2 98.0
Cooling capacity - sensible kW 28.6 30.8 35.6 37.4 31.8 39.2 49.2 53.7 67.4 70.2 75.2 82.2
EER kW/kW 3.66 3.60 3.46 3.54 3.66 3.14 3.56 3.62 3.90 3.65 3.58 3.44
CW mode (Dual-cool feature)
Cooling capacity - total kW 38.0 38.0 44.0 44.0 45.0 52.0 64.8 64.8 98.6 98.6 109.0 109.0
Cooling capacity - sensible kW 33.8 33.8 40.2 40.2 38.2 45.2 58.8 58.8 82.5 82.5 89.5 89.5
EER kW/kW 32.76 21.71 25.88 25.88 29.80 27.66 34.84 31.15 43.25 43.25 31.32 31.32
Compressors scroll/1 scroll/1 scroll/1 scroll/1 scroll/2 scroll/2 scroll/2 scroll/2 scroll/2 scroll/2 scroll/2 scroll/2
Power input kW 7.10 7.98 9.40 10.30 8.20 12.20 12.60 14.10 16.10 18.80 20.60 25.00
Electric absorption A 13.2 14.9 16.7 18.8 14.6 22.5 22.7 26.2 29.8 33.4 37.6 47.6
Refrigerant circuit 1 1 1 1 2 2 2 2 2 2 2 2
Chilled water circuit (Dual-cool feature)
Water flow m³/h 6.5 6.5 7.6 7.6 7.7 8.9 11.1 11.1 16.9 16.9 18.6 18.6
Pressure drop kPa 30 30 41 41 33 43 36 36 84 84 74 74
EC Fans 1 1 1 1 1 1 2 2 2 2 2 2
Airflow m³/h 8700 10000 10800 10800 10000 12000 15000 15500 20000 20000 22000 22000
ESP (nominal/maximal) Pa 20/500 20/200 20/350 20/350 20/275 20/235 20/625 20/575 20/425 20/425 20/325 20/325
Power input kW 1.16 1.75 1.70 1.70 1.51 1.88 1.86 2.08 2.28 2.28 3.48 3.48
Operating current A 1.77 2.66 2.53 2.53 2.33 2.83 2.81 3.13 3.43 3.43 5.22 5.22
Remote condensers 1 1 1 1 2 2 2 2 2 2 2 2
Inverter compressors:
inlet air: 24°C 50% rH; cooling media temperature (Dual-cool feature): 7/12°C, 100% water; ambient temperature 35°C

Cooling mode DXi/DCi DXi/DCi DXi/DCi DXi/DCi DXi/DCi


Air discharge D/U D/U D/U D/U D/U
Model 30/1 45/1 40/2 60/2 90/2

Frame size F1 F2 F2 F4 F5
DX mode
Cooling capacity - total kW 28.0 44.8 40.5 61.4 88.0
Cooling capacity - sensible kW 26.8 42.4 40.0 60.4 79.8
EER kW/kW 3.24 3.12 3.17 3.02 3.16
CW mode (Dual-cool feature)
Cooling capacity - total kW 34.6 56.0 56.0 89.0 112.8
Cooling capacity - sensible kW 30.6 49.5 49.5 73.8 93.2
EER kW/kW 38.44 24.67 24.67 38.03 30.32
Compressors scroll/1 scroll/1 scroll/2 scroll/2 scroll/2
Power input kW 7.74 12.10 10.50 18.00 24.10
Electric absorption A 12.3 19.1 16.7 28.7 38.1
Refrigerant circuit 1 1 2 2 2
Chilled water circuit (Dual-cool feature)
Water flow m³/h 5.9 9.6 9.6 15.2 19.4
Pressure drop kPa 26 50 50 70 80
EC Fans 1 1 1 2 2
Airflow m³/h 7500 12000 12000 17500 22000
ESP (nominal/maximal) Pa 20/700 20/235 20/235 20/600 20/325
Power input kW 0.90 2.27 2.27 2.34 3.72
Operating current A 1.40 3.45 3.45 3.56 5.65
Remote condensers 1 1 2 2 2

The development of Kaltra products and services is continuous and the information in this document may not be up to date.
It is important to check the current position with Kaltra at the address stated below: