PHASE 7-A BLOCK 17 LOT 04 ORCHARD & RESIDENTIAL ESTATE, SALITRAN, DASMARIÑAS, CAVITE
Prepared by:
GIL S. BELTRAN
Civil Engineer
Page 1 of 9
PROPOSED TWO-STOREY RESIDENTIAL HOUSE
PHASE 7-A BLOCK 17 LOT 04 ORCHARD & RESIDENTIAL ESTATE, SALITRAN, DASMARIÑAS, CAVITE
Owner: MS. LYDA B. FIX
DESIGN OF SLABS
A. DESIGN OF TWO-WAY SLAB (S-1)
Direct Design Method
Design Specifications
L1 = 2.30 m column size = 0.20m x 0.40m a1 = 1 (short direction)
L2 = 3.35 m beam size = 0.20m x 0.35m a2 = 1.25 (long direction)
Fy = 275 Mpa f'c = 20.7 Mpa cc = 25 mm
2 Slab thickness, t
t = Ln (800 + 0.73Fy) = 78.05 mm
36,000 + 5000b [am - 0.12(1 + 1/b)]
3 Design moments
Dead Load = W slab + W ceiling+finish = 3.35 Kpa L1 = 2.3 m
Live Load = 4.8 Kpa L2 = 3.35 m
f = 0.9
Long Span:
Mu = Wu L1 Ln2 /8 =
2
41.48 KN m; Mn = Mu/f = 46.09 KN m
Page 2 of 9
Column strip positive Mn = 13.61 KN m
Beam positive Mn = 11.57 KN m
Slab positive Mn = 2.04 KN m = 1.02 KN m /half strip
Short Span:
Mu = Wu L2 Ln1 /8 =
2
28.48 KN m; Mn = Mu/f = 31.64 KN m
By interpolation:
L2/L1 a1L2/L1
1 75 x x = 13.70 %
1.46 ? %M = 61.30 %
2 45
Code assigns 85% of the column strip moment to the beam
Column strip negative Mn = -12.61 KN m
Beam negative Mn = -10.72 KN m
Slab negative Mn = -1.89 KN m = -0.95 KN m /half strip
Page 3 of 9
DESIGN OF BEAMS
A. FLOOR BEAM, FB1
1 Design loads
TA = 10.12 m2 Slab Thickness = 100 mm
Beam size: b = 0.20 m Beam span L = 3.35 m
h= 0.35 m LL = 4800 Pa
d= 0.34 m
Dead loads: W slab = 23.82 KN
W c+f = 7.2864 KN
W beam = 5.52
WDL = 36.63 KN = 10.93 KN/m
Live loads: WLL = 48.576 KN = 14.50 KN/m
Wu = 1.4DL + 1.7LL = 39.96 KN/m
2 Design Moments
Assuming fully restrained beam
Max. +Moment = WuL2/24 = 18.68 KN m
Max. -Moment = -WuL2/12 = -37.37 KN m
Max. Shear = WuL/2 = 66.93 KN
3 Reinforcement Design
At Support (Negative Moment)
Mu = -37.37 KN m f'c = 20.7 Mpa
Mn = Mu/0.90 = 41.52 KN m Fy = 275 Mpa
AǾ = 201.06 mm2
r = rmax = 0.75rbal
rbal = [0.85f'c b/Fy][600+(600+Fy)] = 0.037
rmax = 0.75rbal = 0.028
use r = 0.3rbal = 0.011
As1 = rbd = 755.17 mm2
a = As1Fy/(0.85f'cb) = 59.01 mm
M1 = As1Fy(d-a/2) = 63.96 KN m > 37.37 KN m
Treat as singly reinforced beam
No. of bars required (use 16 mmÆ)
n = As/AǾ = 3.8 say 4 pcs
Reinforcement:
4 pcs - 16mmǾ (Top bar)
2 pcs - 16mmǾ (Bottom bar)
4 Stirrup
Vu = 66.93 KN Vcr = Vu - Wu d = 53.44 KN
Shear capacity of beam
Page 4 of 9
Vc = √(f'c)bd/6 = 51.18 KN
Vn = fVc/2 = 21.75 KN < 53.44
Stirrup is needed
Vs = Vcr/f - Vn = 41.12 KN
Using 10mmǾ AǾ = 78.54 mm2
Spacing S = AǾFyd/Vs = 354.53 mm
Max S = d/2 = 168.75 mm
Use 10mmǾ stirrups spaced @: 3 @ 50mm; 2 @ 100mm; 2 rest @ 150mm
2 Design Moments
Assuming fully restrained beam
Max. +Moment = WuL2/24 = 9.73 KN m
Max. -Moment = -WuL2/12 = -19.46 KN m
Max. Shear = WuL/2 = 34.84 KN
3 Reinforcement Design
At Support (Negative Moment)
Mu = -19.46 KN m f'c = 20.7 Mpa
Mn = Mu/0.90 = 21.62 KN m Fy = 275 Mpa
AǾ = 201.06 mm2
r = rmax = 0.75rbal
rbal = [0.85f'c b/Fy][600+(600+Fy)] = 0.037
rmax = 0.75rbal = 0.028
use r = 0.25rbal = 0.009
As1 = rbd = 536.08 mm2
a = As1Fy/(0.85f'cb) = 41.89 mm
M1 = As1Fy(d-a/2) = 39.30 KN m > 19.46 KN m
Treat as singly reinforced beam
No. of bars required (use 16 mmÆ)
n = As/AǾ = 2.7 say 3 pcs
Reinforcement:
3 pcs - 16mmǾ (Top bar)
2 pcs - 16mmǾ (Bottom bar)
Page 5 of 9
Reinforcement:
2 pcs - 16mmǾ (Top bar)
3 pcs - 16mmǾ (Bottom bar)
4 Stirrup
Vu = 34.84 KN Vcr = Vu - Wu d = 28.86 KN
Shear capacity of beam
Vc = √(f'c)bd/6 = 43.60 KN
Vn = fVc/2 = 18.53 KN < 28.86
Stirrup is needed
Vs = Vcr/f - Vn = 15.43 KN
Using 10mmǾ AǾ = 78.54 mm2
Spacing S = AǾFyd/Vs = 805.02 mm
Max S = d/2 = 143.75 mm
Use 10mmǾ stirrups spaced @: 3 @ 50mm; 2 @ 100mm; rest @ 150mm o.c.
DESIGN OF COLUMNS
A. EXTERIOR COLUMNS (C1)
Trial Section
b = 200 mm Ag = 80000 mm2
h = 400 mm Ast = 678.58401 mm2
Ǿbar = 12 mm Ǿtie = 10 mm
n = 6 pcs
Design Specifications
f'c = 20.7 MPa ǿ = 0.7
Fy = 275 MPa β = 0.85
1 Axial loads
PDL = 18.31 kN PLL = 24.29 kN
Pu = (1.4DL + 1.7LL)x1.5 = 100.39 kN (for one side only)
PuTotal = Pu x no. of sides x no. of floors = 602.37 kN
4 Lateral ties
s = 16 (Ǿbar) = 192 mm
s = 48 (Ǿtie) = 480 mm
s = least dimension = 200 mm
Thus: Use 6 - 12mm dia bar with 10mm dia lateral ties @ 200mm o.c.
Page 6 of 9
Design Specifications
f'c = 20.7 MPa ǿ = 0.7
Fy = 275 MPa β = 0.85
1 Axial loads
PDL = 18.31 kN PLL = 24.29 kN
Pu = (1.4DL + 1.7LL)x1.5 = 100.39 kN (for one side only)
PuTotal = Pu x no. of sides x no. of floors = 401.58 kN
4 Lateral ties
s = 16 (Ǿbar) = 192 mm
s = 48 (Ǿtie) = 480 mm
s = least dimension = 200 mm
Thus: Use 6 - 16mm dia bar with 10mm dia lateral ties @ 200mm o.c.
DESIGN OF FOOTING
A. INTERIOR FOOTING (F1)
Design Specifications
f'c = 20.7 MPa H = 600 mm
Fy = 275 MPa h = 300 mm
Ǿbar = 16 mm qall = 190 kPa (assume)
σconc = 23.5 kN/m3 σsoil = 15.7 kN/m 3
(assume)
colb = 200 mm cc = 100 mm
colh = 400 mm ǿ = 0.85
1 Service loads
PT = PDL + PLL = 255.62 kN
2 Base dimensions
qnet = qall - [ hσconc + Hσsoil ] = 173.53 kPa
Areqd = PT / qnet = 1.47 m2
B2 = Areqd B = 1.21 m
Trial section:
B = 1.5 m Aact = 2.25 m2
Page 7 of 9
ǿVc = 0.33ǿ bo d √f'c = 510.48 kN
since: ǿVc > Vu → SAFE
6 Design of reinforcement
x2 = (B - colb)/2 = 0.65 m
Mu = qu B x /2
2
2
= 56.555771 kN m
Mu = ǿf'c Bd ω (1-0.59ω)
2
ω2 - 1.69ω + 0.08576 = 0
ω = = 0.052
ρ = ωf'c/Fy = 0.004
n = Ast/AǾ = 7.59
say 8 pcs
Thus: Use 8 16mm dia bar on both sides of footing.
1 Service loads
PT = PDL + PLL = 170.41 kN
2 Base dimensions
qnet = qall - [ hσconc + Hσsoil ] = 175.10 kPa
Areqd = PT / qnet = 0.97 m2
B2 = Areqd B = 0.99 m
Trial section:
B = 1.2 m Aact = 1.44 m2
Page 8 of 9
5 Check beam shear
x1 = (B - colb - 2d)/2 = 0.3 m
Vu = q u B x1 = 66.93 kN
6 Design of reinforcement
x2 = (B - colb)/2 = 0.5 m
Mu = qu B x22/2 = 27.887461 kN m
Mu = ǿf'c Bd2 ω (1-0.59ω)
ω2 - 1.69ω + 0.05286 = 0
ω = = 0.032
ρ = ωf'c/Fy = 0.002
n = Ast/AǾ = 6.08
say 7 pcs
Thus: Use 7 16mm dia bar on both sides of footing.
Page 9 of 9