GENERAL INTRODUCTION
The NEW ATI enclosure integrates a new 4-pole
changeover switch including electronics’ control to
meet standard IEC 60947-6-1.
1
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
1
4
2
3
10 6
11
12
13
1 4
3
2
10 6
11
12
13
14 15 16 17 18
2
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
VISUALISATION
> Led
• Sources availability • Test modes
Sources Available Not available On load Off load
Mains
Genset
Led on Led on
• Operating modes
• Fault synthesis
AUTO MANUAL
Active Inactive Blinking
Lightning
protection
(Option)
Led on Led on N/A
• Lamp test
Product error Product OK
> Timers
≤ 1600A ≥ 2000A
2Mt Loss of main validation timer / MAINS (5 sec) Mft Loss of mains validation timer (5 sec)
Failure Timer Once mains has disappeared, Mft is started.
Once mains has disappeared, 2Mt is started. If Mains comes back before Mft ends, the commutation
If Mains comes back before 2Mt ends, the commutation cycle is not started. (Delay on Gen start.)
cycle is not started. (Delay on Gen start.)
dtt Genset stabilisation timer (5 sec)
AT Genset stabilisation timer (5 sec) Generator needs to be stable during dtt to allow transfer
Generator needs to be stable during AT to allow transfer from Mains.
from Mains.
Mrt Mains Return validation timer (1 min)
1Mt Mains Return validation timer (2 min) Once Mains power has returned Mrt is started. If Mains
Once Mains power has returned 1Mt is started. power disappears before Mrt ends, the load is not
If Mains power disappears before 1Mt ends, the load is switched back to the Mains.
not switched back to the Mains.
Cdt Cool down Timer (4 min)
ROT Run on time timer / Cool down timer (4 min) Once the load is switched back from the Generator to the
Once the load is switched back from the Generator to the Mains, Cdt is started and the Generator will stop once Cdt
Mains, ROT is started and the Generator will stop once is finished. (Allows generator cool down).
ROT is finished. (Allows generator cool down).
0Mr/ 0 Main Return timer (5 sec)
Dbt Dead Band timer (5 sec) 0Mf 0 Main Failure timer (5 sec)
This timer is counted down before transferring the load This timer is counted down before transferring the load
from the Mains source to the Generator or vice versa. from the Mains source to the Generator or vice versa.
3
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
OPERATING
> Automatic
In Auto Mode:
• Possible:
- the automatic changeovers.
• Not possible:
- to insert the handle
- to pull the padlocking mechanism.
> Manual
In Manual Mode:
• Possible:
- to insert the handle and to operate manualy.
• Not possible:
- to operate electrically
- to select the auto mode and to padlock if the
handle is housing.
> Padlocking
In Padlocking Mode:
• Possible:
- to padlock in position 0 with a standard
configuration.
• Not possible:
- to operate electrically
- to select the auto mode
- to insert the handle.
4
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
• Led is on
Try to reset the product (see the instructions below).
Then consult your local dealer.
• Reset
Level 1
Level 2
Switch off the power supply during 3 minutes by removing the
power supply. Open site mains breaker and generating set
breaker (position 0).
> POSITIVE
• Go to the next step.
03 > NEGATIVE
Power supply Led is • Led is on:
blinking (≤ 1600A). Try to reset the product (see the instructions above).
Then consult your local dealer.
> POSITIVE
• Go to the next symptoms.
02 01 > NEGATIVE
The mains Mains availability • Check lamp test.
availability. Led is on. • Check that the mains return timer (1MT ≤1600A or Mrt
≥ 2000A) is still counting down.
• Check that the mains protection system (breaker) is on
(Position 1).
• Then consult your local dealer.
> POSITIVE
• Go to the next steps or symptoms.
03 01 > NEGATIVE
The genset Genset availability • Check lamp test.
availability (genset Led is on. • Check that the genset stabilisation timer (AT ≤1600A or dtt
supposed started). ≥ 2000A) is still counting down.
• Check that the genset protection system (breaker) is on
(Position 1).
• Then consult your local dealer.
> POSITIVE
• Go to the next steps or symptoms.
5
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
6
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
7
ATI Transfer Panel
OPERATORS INSTRUCTION MANUAL
CONDITIONS OF USE
Hygrometry: Storage:
• 80% humidity without condensation at 55 °C • Temperature -20 to +40 °C
• 95 % humidity without condensation at 40 °C • Period: 1 year max
Temperature:
• -10 +40 °C without de-rating Power input:
• +40 +65 °C with de-rating* • Vn = 230Vac --> [184 / 276 Vac] ≤ 1600 A
• Vn = 277Vac --> [222 / 332 Vac] ≤ 1600 A
Ingress Protection: • Vn = 277Vac --> [116 / 332 Vac] ≥ 2000 A
Ø 1mm • Enclosed: IP41 ≤ 1600A Ø 1mm
Ø 1mm
Ø 1mm
≤ 1600A ≥ 2000A