GENERAL NOTES

ELECTRICAL SYMBOLS ABBREVIATIONS

E100
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

KEYED NOTES

STATISTICS

LIGHT DISTRIBUTION NOTES:

ELECTRICAL SITE PLAN


N

E101
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

UP UP

KEYED NOTES
UP UP

MAIN LEVEL POWER & SYSTEMS PLAN MAIN LEVEL LIGHTING PLAN
N N

E201
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

KEYED NOTES

LEVEL 2 POWER & SYSTEMS PLAN LEVEL 2 LIGHTING PLAN


N N

E202
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

KEYED NOTES

LEVEL 3 POWER & SYSTEMS PLAN LEVEL 3 LIGHTING PLAN


N N

E203
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
ROOF POWER PLAN
N

E204
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

MAIN LEVEL UNIT ELECTRICAL PLAN


N

LEVEL 2 UNIT ELECTRICAL PLANS KEYED NOTES


N

E301
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

LEVEL 2 UNIT ELECTRICAL PLANS


N

KEYED NOTES

E302
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

LEVEL 3 UNIT ELECTRICAL PLANS


N
KEYED NOTES

E303
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

LEVEL 3 UNIT ELECTRICAL PLANS


N

KEYED NOTES

E304
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
GENERAL NOTES

FEEDER SCHEDULE

KEYED NOTES

ONE LINE DIAGRAM

FIRE ALARM GENERAL NOTES:

FIRE ALARM RISER DIAGRAM COMMUNICATIONS RISER DIAGRAM


E401
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
E501
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
E502
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
NOTE: KEYED NOTE:

ELECTRICAL DEVICE MOUNTING HEIGHTS INSTALLATION DETAIL TYPICAL ROUGH-IN REQUIREMENTS DETAIL

SERVICE GROUNDING DETAIL

WEATHERPROOF RECEPTACLE MOUNTING DETAIL KEYED NOTES:

GENERAL NOTES:

SERVICE BUS GROUNDING DETAIL

TYPICAL ROUGH-IN REQUIREMENTS DETAIL FOR MC CABLE

TRENCHING DETAIL LIGHTING CONTROL PANEL DETAIL

E601
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
FIRE STOP THRU GYPSUM BOARD WALL DETAIL FIRE BARRIER ELECTRICAL OUTLET INSTALLATION DETAIL

POLE BASE DETAIL


KEYED NOTES

FIRE STOP THRU GYPSUM BOARD WALL DETAIL

FIRE STOP THRU GYPSUM BOARD WALL DETAIL


KEYED NOTES
ENLARGED POLE BASE DETAIL

REGULAR ACCESSIBLE

FIRE STOP THRU MASONARY OR CONCRETE WALL DETAIL ELECTRIC WATER COOLER INSTALLATION DETAIL
FIRE SPRINKLER RISER CONNECTION

E602
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
KEYED NOTES: GENERAL NOTE:

MOTION SENSOR WITH LOW VOLTAGE SWITCH OVERRIDE

BRANCH CIRCUIT VOLTAGE DROP DETAIL

ELECTRICAL EQUIPMENT WORK SPACE CLEARANCES

CONDENSING UNIT CONDUIT DETAIL

DAY LIGHTING ZONE CONNECTION DIAGRAM


EMERGENCY BALLAST OPERATION DETAIL

E603
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
COMMUNICATIONS GROUNDING BUS BAR DETAIL PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).
ELECTRICAL SPECIFICATIONS

E701
ELECTRICAL MECHANICAL
2335 SOUTH STATE, SUITE 100 PROVO, UTAH 84606
PHONE: 801.375.2228 FAX: 801.375.2676

THESE DOCUMENTS ARE INSTRUMENTS OF PROFESSIONAL SERVICE AND THE INFORMATION CONTAINED
HEREIN IS INCOMPLETE UNLESS IN CONJUNCTION WITH ROYAL ENGINEERING'S INTERPRETATIONS,
DECISIONS, OBSERVATIONS AND ADMINISTRATIONS. USE OR REPRODUCTION OF THESE DOCUMENTS IN
WHOLE OR IN PART WITHOUT ROYAL ENGINEERING'S CONSENT IS IN VIOLATION OF COMMON LAW.
COPYRIGHTS, STATUTORY AND OTHER RESERVED RIGHTS. REFER TO ACT 17 U.S.C. PAR. 511 (1991). WHICH
PREEMPTS STATE AND LOCAL PUBLIC RECORD ACTS. REFER TO ACT 17 U.S.C. PAR. 301 (1991).