Escolar Documentos
Profissional Documentos
Cultura Documentos
• Three Phase AC
• A Three Phase system is: several single phase
systems, displaced in time phase from one
another.
• The single phase systems are interconnected
in some way.
• All modern generators are three phase
• Advantage:
– Three phase apparatus is more efficient in the
sense it uses less material (iron and copper) for a
given capacity (power)
– Costs less than single phase apparatus which
handles the same power
• Called Three phase as there are three
sinusoidal waves of different time phase.
• Any no of phases can be developed by
properly spacing the coils on the stator
• Mercury arc Rectifiers are 6-12 phase
• Rotary converters are 6 phase
• For a fixed amount of power to be transmitted
over a fixed distance at a fixed iron loss with a
fixed voltage between the conductors –
Three phase system is more economical in the
use of copper than any other no of phases
• Three Phase AC : Balanced Three Phase Supply
3
the periphery of the stator
• Alternators (AC Synchronous generators)
generate three phase AC
• At this position, for Generator, Fleming’s right
hand rule- e.m.f. induced in coil A maxm. And
a conductor placed at position A will have
e.m.f. directions outwards.
• A conductor at position B will experience max
e.m.f. outwards, 1200 later than when the pole
axis was at along position A.
• Similarly max e.m.f. will occur outwards in coil
C, 1200 later than that at B and 2400 later than
that at A.
• Hence e.m.f.s in coils A, B and C will be 1200
out of ‘time’ phase.
• Phase sequence (of supply): CCW rotation
here gives phase ‘B’ (Yellow) lagging ‘A’ (Red)
and phase ‘C’ (Blue) lagging ‘B’ by 1200 each.
• The order in which phase Red, Yellow and Blue
attain their max values is R-Y-B. This is called
the phase sequence.
• If rotation of Field (rotor) is reversed, the
order in which the phase will attain maximum
will also be reversed. The phase sequence will
be R-B-Y.
• Phase sequence of applied voltages to a load:
is fixed by the sequence of the supply lines
• The phase sequence of the load may be
reversed by interchanging any pair of the
supply lines.
• Balanced Three Phase Supply
• 3 phase 4 wire system: Star/Wye connection
common connection at one end of the three
coils – Neutral point (N).
• VRN, VYN and VBN are Phase voltages or Line-to-
neutral voltages.
• Voltages between terminals R, Y and B are called
Line or Terminal voltages: VRY , VYB , VBR
• Phase voltages: VRN , VYN , VBN
• For a balanced three phase supply (Same
amplitude, 1200 time phase apart):
Let, V V00
RN
VYN V 120 0
VBN V 240 0
Then
VRY VRN VNY VRN VYN
V00 V 1200
3 V300
• Delta Connection
Phase voltages =
Line voltages
• Since at any instant, VRY VYB VBR 0 , no current flows
around the series circuit of the three coils.
• Line and Phase voltages are equal
• Line Currents:
• Let, I R I L , IY I L 120 , I B I L 240
0 0 0
• Phase Currents:
I
• Let, RY I 0 0
, I YB I 120 0
, I BR I 240 0
• Then I R I RY I BR
I00 I 2400
•
3 I 30 0
I Y I YB I RY
•
I B I BR I YB
• Balanced Three Phase supply connected to star
connected LOAD:
• Identical impedances connected to a common point
constitute a three phase Balanced Wye/Star Load
• A balanced three phase supply connected to a
balanced three phase load (star/delta) constitutes a
balanced three phase system
• When system is balanced, the three phase
currents (supply as well as load) are equal in
magnitude (RMS) and differ in phase by 1200.
• The phase difference between each phase
voltage and current is defined by the Load (R,
L, C) parameters – LOAD POWER FACTOR
• For a Star connected load with a balanced four
wire supply (star connected) line and phase
currents are equal
I R I 0 , IY I 1200 , I B I 2400
• Neutral wire current is zero:
I N I R IY I B 0
• When balanced three phase voltages are
impressed on this load, all impedances have
equal voltages (RMS value) across them.
• The ratio of the load line and load phase
voltages are same as the supply line and
phase voltages resp.
• The current, power, etc, may then be found by
considering each circuit as a single phase only
• Not to confuse PHASE quantities with LINE
quantitites.
• Problem: In figure below 220 V balanced 3 ø
line voltages are applied to a STAR/WYE load
with R = 6 Ω and X = 8 Ω, inductive, Find phase
currents line currents, power per phase and
total real and reactive power. Draw phasor
diagram
• Solution:
220 00
VR 3
?; Z R 6 j8 ?;
VR
I RN ?; Per phase power VR I *RN P jQ ?
ZR
PR VR I RN Cosφ ?; QR VR I RN Sinφ ?
Total Power, P 3PR ?
Assuming phase sequence to be R - Y - B, finally
Phase voltages :
VR ? ; VY ? ; VB ? ;
Phase currents Line Currents :
I RN ? ; I YN ? ; I BN ? ;
PRN ? ; PYN ? ; PBN ? ; Total power ?
• Problem: Solve previous problem for Delta
connected load and same 220 V balanced 3 ø
line voltages are applied to a delta connected
load with R = 6 Ω and X = 8 Ω, inductive, Find
phase currents line currents, power per phase
and total real and reactive power. Draw
phasor diagram
Three Phase Three Wattmeter method of measuring power