Project Name Employer Project Manager RFI Ref. No.
City Walk Kids Chalhoub Group Muhammad Anwar RFI/HVAC/01
Consultant / Engineer Main Contractor Sub Contractor Date
Bluehaus Group Deco Emirates Gulf Engineering LLC 8/15/2015
Request for Information (RFI)
To: Bluehaus From: Deco Emirates LLC Subject: Server Room AC 1 Both AC Units (CCU & DX) are duty units or 1 duty 1 standby? 2 Capacity of DX floor standing type unit is given 39.0Kw (11.11Tons). We have concern that we may not get this capacity with single unit.
Enclosure: 1) Schedule of Equipment
Requested by : Imteyaz Ahmad Signature :
Reply from Authorized Representative Date: 8/15/2015