Você está na página 1de 48

GERAN / UTRAN

Power Supply
and Link Equipment
User Manual

Service 1A Rack
A50016-G5100-A461-01-7631
Service 1A Rack

f Important Notice on Product Safety


DANGER - RISK OF ELECTRICAL SHOCK OR DEATH - FOLLOW ALL INSTALLATION INSTRUCTIONS.
The system complies with the standard EN 60950 / IEC 60950. All equipment connected to the system must
comply with the applicable safety standards.
Hazardous voltages are present at the AC power supply lines in this electrical equipment. Some components may
also have high operating temperatures.
Failure to observe and follow all installation and safety instructions can result in serious personal injury
or property damage.
Therefore, only trained and qualified personnel may install and maintain the system.

The same text in German:


Wichtiger Hinweis zur Produktsicherheit
LEBENSGEFAHR - BEACHTEN SIE ALLE INSTALLATIONSHINWEISE.
Das System entspricht den Anforderungen der EN 60950 / IEC 60950. Alle an das System angeschlossenen
Geräte müssen die zutreffenden Sicherheitsbestimmungen erfüllen.
In diesen Anlagen stehen die Netzversorgungsleitungen unter gefährlicher Spannung. Einige Komponenten
können auch eine hohe Betriebstemperatur aufweisen.
Nichtbeachtung der Installations- und Sicherheitshinweise kann zu schweren Körperverletzungen oder
Sachschäden führen.
Deshalb darf nur geschultes und qualifiziertes Personal das System installieren und warten.

Caution:
This equipment has been tested and found to comply with EN 301489. Its class of conformity is defined in table
A30808-X3247-X910-*-7618, which is shipped with each product. This class also corresponds to the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment.
This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accor-
dance with the relevant standards referenced in the manual “Guide to Documentation”, may cause harmful inter-
ference to radio communications.
For system installations it is strictly required to choose all installation sites according to national and local require-
ments concerning construction rules and static load capacities of buildings and roofs.
For all sites, in particular in residential areas it is mandatory to observe all respectively applicable electromagnetic
field / force (EMF) limits. Otherwise harmful personal interference is possible.

Trademarks:
All designations used in this document can be trademarks, the use of which by third parties for their own purposes
could violate the rights of their owners.

Copyright (C) Siemens AG 2006

Issued by the Communications Group


Hofmannstraße 51
D-81359 München

Technical modifications possible.


Technical specifications and features are binding only insofar as
they are specifically and expressly agreed upon in a written contract.

2 Id:0900d805800cc1c4 A50016-G5100-A461-01-7631
Service 1A Rack

Table of Contents
This document has 48 pages.

Reason for Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.1 Purpose of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.2 Installation Prerequisites. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3 Handling of the Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 Position in the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Site Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Construction View of the Service1A Rack . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4 Equipment Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.4.1 Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.2 Unpacking the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.4.3 Devices Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.4 Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.4.5 Setup of Earthquake Mounting Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

3 External Cable Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22


3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.2 Ground and AC- Power Supply Connections . . . . . . . . . . . . . . . . . . . . . . . 24
3.3 Alarm Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

4 Rack Completion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.1 Preparation of the Top Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.2 Installation of Backup Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.2.1 Installation of Backup Batteries Type “Oerlicon”. . . . . . . . . . . . . . . . . . . . . 34
4.2.2 Install Backup Batteries Type “Hawker” . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3 Installation of Link Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.3.1 Installation of Microwave Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3.2 Installation of NTPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.4 Post Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

5 Installation and Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42


5.1 Final Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
5.2 Switch ON of the Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

6 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.1 LED Status Indication at the DCBCTRL . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.2 Checks and Replacement of Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2.1 FAN Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2.2 AC/DC Converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2.3 Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
6.2.4 Check of the Ground Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

7 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
7.1 Disposal of Electrical and Electronic Equipment. . . . . . . . . . . . . . . . . . . . . 47
7.2 Installation Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

A50016-G5100-A461-01-7631 Id:0900d805800cc1c4 3
Service 1A Rack

7.3 Ancillary Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

4 Id:0900d805800cc1c4 A50016-G5100-A461-01-7631
Service 1A Rack

List of Figures
Figure 1 ESD Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Figure 2 ESD press-stud for wrist strap connection. . . . . . . . . . . . . . . . . . . . . . . 10
Figure 3 Position of the Service1A Rack on a Telekommunication Site . . . . . . . 11
Figure 4 Configuration of the Service1A Rack (example) . . . . . . . . . . . . . . . . . . 12
Figure 5 ShockwatchTM-label and TiltwatchTM-label . . . . . . . . . . . . . . . . . . . . . . 13
Figure 6 Removal of the straps, opening of the top cover . . . . . . . . . . . . . . . . . . 14
Figure 7 Removal of the packing material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Figure 8 Opening of the PE-wrap, lifting straps around the rack . . . . . . . . . . . . . 15
Figure 9 Opening of rack door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 10 Removal of top cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 11 Guideline for crane transport . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 12 Required space for installation of the Service1A Rack . . . . . . . . . . . . . 17
Figure 13 Removal of fastening claws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 14 Adjusting of the rack feet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 15 Floor and wall mounting of the racks . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 16 Parts of the earthquake kit S3086-K4119-X . . . . . . . . . . . . . . . . . . . . . 19
Figure 17 Double claw for the rear feet in mounted position . . . . . . . . . . . . . . . . . 20
Figure 18 Claws for the front feet before mounting . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 19 Drilling sketch for the earthquake mounting kit . . . . . . . . . . . . . . . . . . . 21
Figure 20 Top of the Service1A Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Figure 21 External Connections of the Service1A Rack . . . . . . . . . . . . . . . . . . . . 23
Figure 22 Power supply configuration with Service1A Rack . . . . . . . . . . . . . . . . . 24
Figure 23 Preparation of the common ground wire . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 24 Wiring of the MSU terminal block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Figure 25 Preparation of the DC-cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 26 Preparation of the alarm cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 27 Connector arrangement at the ACTC-3 . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 28 Changing of the FAN-plug position . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 29 Alarm cable connection at ACTC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Figure 30 Paint retouch of the top cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Figure 31 Placement of the sealing profile tapes . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Figure 32 Parts for battery fixing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 33 Placement of the spacer strips. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Figure 34 Preparation of the battery tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 35 Connection of backup battery sets (Co. Oerlicon) . . . . . . . . . . . . . . . . . 35
Figure 36 Air vent system for Oerlicon battery sets . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 37 Setup of the backup batteries, fixing of the tray bracket . . . . . . . . . . . . 36
Figure 38 Connection between the batteries, battery cable connection . . . . . . . . 37
Figure 39 Routing of the air vent tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Figure 40 Cabling Overview for Microwave Equipment . . . . . . . . . . . . . . . . . . . . . 38
Figure 41 Interfaces on frame F:NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Figure 42 Cabling Overview for NTPM Installation . . . . . . . . . . . . . . . . . . . . . . . . 40
Figure 43 Breaker arrangement at the AD-Panel. . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 44 Breaker arrangement at the AD-Panel. . . . . . . . . . . . . . . . . . . . . . . . . . 43
Figure 45 LED Status Indication of the DCBCTRL . . . . . . . . . . . . . . . . . . . . . . . . 44

A50016-G5100-A461-01-7631 Id:0900d805800cc1c4 5
Service 1A Rack

List of Tables
Table 1 Connection of alarm wires with IDC-connectors . . . . . . . . . . . . . . . . . . . 29
Table 2 Connection of the alarm cable at the ACTC . . . . . . . . . . . . . . . . . . . . . . 30
Table 3 Overview of backup battery sets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 4 Pin Assignments of -48 V interface of frame F:NT . . . . . . . . . . . . . . . . . 39
Table 5 Pin Assignments of PCM-Input and -Output connector of frame F:NT . . 39
Table 6 Checklist for Service1A Rack Installation . . . . . . . . . . . . . . . . . . . . . . . . 42

6 Id:0900d805800cc1c4 A50016-G5100-A461-01-7631
Service 1A Rack Reason for Update

Reason for Update


Issue History

Issue Date Summary


Issue history for this document with order number “A30808-X3247-L461-*-7631”
1 03/2004 First issue for external use
2 05/2004 Second issue for external use
3 09/2005 Third issue for external use
4 04/2006 Fourth issue for external use
Issue history for this document with order number “A50016-G5100-A461-*-7631”
01 11/2006 New document number

Issue 01, release-independent, valid with starting Release BR 6.0

A50016-G5100-A461-01-7631 Id:0900d805800d0fe5 7
Reason for Update Service 1A Rack

8 Id:0900d805800d0fe5 A50016-G5100-A461-01-7631
Service 1A Rack Introduction

1 Introduction

Important!
!

The CE and UL declaration of conformity for the product will be fulfilled if the setup and
cabling is undertaken in accordance with the specification in the manual and the docu-
mentation listed there, such as mounting instructions, cable lists etc. Where necessary,
project-specific documentation should be taken into account.
Deviations from the specifications or independent changes during setup, such as use of
cable types with lower screening values, for example, can lead to the CE requirements
being violated. In such cases the CE declaration of conformity is invalidated and the
responsibility passes to the person who has caused the deviations.

The applying technical standards are listed in the “Guide to Documentation” (Siemens
document number A30808-X3247-K52-*-7635).

1.1 Purpose of the Manual


This document is intended to provide the information necessary for the installation,
commissioning and maintenance of the Service1A Rack.
It contains a description of all the necessary steps to install the Rack on site and inte-
grate it into the required infrastructure.
The document includes information on the following:
– Equipment delivery
– Preliminary checks
– Unpacking the Rack and devices
– Rack installation
– Connection with the 3-phase AC network and DC supplied equipment
– Commissioning Activities
– Maintenance
For installation of equipment not supplied by Siemens (e.g. power distribution panel,
telecommunication equipment) refer to site specific documentation or vendor
instructions provided with other equipment.

1.2 Installation Prerequisites


It is required that the installer pays attention to all relevant national electric standards.
– Use the correct material as described in this manual.
– Installation according to the standards EN 50310 or ETS 300253, EN 50154 and the
hints in this manual.
– The other equipment on site must be CE designated.
The installation staff must have a basic knowledge of the relevant standards.
The manual must be available for the staff on site.

A50016-G5100-A461-01-7631 Id:0900d8058009a5e2 9
Introduction Service 1A Rack

1.3 Handling of the Modules


All boards and modules must be handled with extreme care as any one contains
electrostatically sensitive devices (ESD).
The modules are marked with the ESD-label.

Figure 1 ESD Symbol


These are sensitive to static discharge.
Notice:
– Avoid handling the modules in a high-static environment.
– When handling the modules, do not touch connector contacts.
– An ground high-impedance wrist strap must be worn when handling modules.
– Use the socket at the racks for wrist strap connection.
– The modules must be transported in appropriate packaging.

Figure 2 ESD press-stud for wrist strap connection

10 Id:0900d8058009a5e2 A50016-G5100-A461-01-7631
Service 1A Rack Installation

2 Installation

2.1 Position in the System


The Service1A Rack contains the power supply modules (AC/DC converters) for the
telecommunication equipment on site. In addition the rack can be equipped with a
backup battery set and 19” microwave units or network termination modules (NTPM).

power
distribution AC/DC
panel converters

tele-
Link communication
equipment equipment

battery
backup
AC mains

Figure 3 Position of the Service1A Rack on a Telekommunication Site

2.2 Site Requirements


With regard to explosion hazards, the installation room of the Service1A Rack with
integral battery back-up system must be guarantee a continuous ventilation, to keep the
critical hydrogen concentration below 4% vol..
The cross section of the air inlet / outlet must be calculated in accordance to
IEC/EN50272-2.
Prior to the commencement of installation, the construction of the room in which the
Service1A Rack is to be housed must be complete and the room in good condition and
dry heaters, if necessary, should be put up in the room.
The rack is intended to be installed in an area with restricted access.
– The installing room should be free from possible water ingress, frost and excessive
insect attacks.
– Doors and windows must already have been installed and must be lockable.
– Openings in wall or ceiling of floor - if required - must be complete.
– The floor coverings must have been installed.
– Room lighting and wall outlets must have been installed.
– Heating or air-conditioning systems should be ready for operation.
– Walls and ceilings should have been painted. The room must be clean.
– optional cable runways must be installed first.
– All installation works of 3 phase 230 V AC power supply, including a false current
protection switch must be finished.
To prevent subsequent accumulation of dust and dirt, the parts and equipment units to
be installed should be unpacked outside the room (if possible).

A50016-G5100-A461-01-7631 Id:0900d80580099867 11
Installation Service 1A Rack

2.3 Construction View of the Service1A Rack


The equipment is housed in a rack with the dimensions of 1600 mm x 600 mm x 450 mm
(H x W x D).
It can be equipped with up to 6 AC/DC converters and up to 2 trays of backup batteries,
that guarantees continuous operation for a certain time in case of mains breakdown or
AC/DC failure.
In addition, the rack provides a free space of 6 height units (HU) for the installation of
link equipment. Dependend on the type of link equipment (can be microwave or NTPM),
mounting kits for 2 HU have to be installed for microwave indoor units (max. 3 kits) or
3 HU for NTPM modules (max. 2 kits). Without battery trays, 12 HUs for link equipment
are available.

top cover*
SIEMENS

FAN#0 FAN#1 FAN units*

DCBCTRL*

AC/DC converters*

LE
ACTC Batt01/S2
+-
AD Panel Batt0/S1

- - - +++ ++ - -
AD-panel*
0V -48V

LE Panel (S1A)
LE-panel
HU #0 for LE

HU #1 for LE

HU #2 for LE

HU #3 for LE
link equipment
HU #4 for LE

HU #5 for LE

battery set

adjustable feet* *) mandatory part


Figure 4 Configuration of the Service1A Rack (example)

2.4 Equipment Delivery


The rack is shipped vertically mounted on a wooden pallet, protected with PE-foil (or
horizontally in case of transportation by airplane in a wooden crate).
The crate dimensions are 1800 mm x 800 mm x 650 mm (HxWxD).
The Service1A Rack will be delivered without backup batteries (weight aspects).
An additional crate is used for transporting of the batteries.
4 fastening claws which fixing the rack-feet to the pallet should be used for later floor-
fixing. The claws are also provided in the case of transportation in a crate.

12 Id:0900d80580099867 A50016-G5100-A461-01-7631
Service 1A Rack Installation

The following information is given for identification of delivery:


– customer order number
– serial number of the rack or other supplied equipment
– destination
– gross and net weight
– overall dimensions (cm)
– symbol or imprint to identify the "Top" and the "Bottom"
– delivery papers
For transportation of the crate / pallet from the unloading area into the construction room
use handling aids (for example: fork-lift truck, goods elevator), a second person is
needed for help.

2.4.1 Preliminary Checks


A ShockwatchTM -label and a TIP (N) TELLTM-label are fixed at the rack surface in the
case of pallet transportation or at the crate for indication of fallover or strong shocks
during the transport from the factory to the site.
If the TIP (N) TELLTM-label arrow is blue, the package has been on the side or tipped
over in transit. If the ShockwatchTM -label is red, the package has been shocked during
transport.
Check that the crate or the pallet is not damaged. In case of evident damage due to
transport, unpack the equipment in presence of an insurance company representative
and promptly claim any damage and inform the shipper for specifying the damage.
Check whether that the package is actually addressed to the site and complete.

ShockwatchTM - label

TIP (N) TELLTM - label

Figure 5 ShockwatchTM-label and TiltwatchTM-label

2.4.2 Unpacking the Rack


During the unpacking steps, great care must be taken to ensure that the rack is not
scratched or damaged in any way. Unpack the rack according to the following figures.

A50016-G5100-A461-01-7631 Id:0900d80580099867 13
Installation Service 1A Rack

unscrew

cut

Figure 6 Removal of the straps, opening of the top cover

WARNING
!

Safety gloves and goggles must be worn when cutting the straps.
Pay attention to the tension of the straps. Use only plate shears.

– Cut the three straps (see Figure 6).


– Unscrew the 10 M4 screws on the top of the crate (see Figure 6).
– Remove the crates top cover.
– Take out the packing material protecting the rack (see Figure 7).
– Remove the protection to the head and to the base of the rack.
– Open and remove the tubular PE-wrap protecting the rack (see Figure 8).
– Take out the rack from the crate. Use the straps around the rack.
– Lift the rack in vertical position.

Figure 7 Removal of the packing material

WARNING
!

The burning of packing material should be avoided, as packaging may give off toxic
gases.

14 Id:0900d80580099867 A50016-G5100-A461-01-7631
Service 1A Rack Installation

cut

Figure 8 Opening of the PE-wrap, lifting straps around the rack


Immediately after unpacking the rack, inspect it for damage and report the extent of any
damage to the transportation company.
If the rack is shipped on a wooden pallet, cut the PE-foil top-down with a suitable knife
at the carton profiles, that protects the rack edges.
Remove the foil and the carton profiles. Unscrew the 4 fixing claws at the rack feet.
Slide or shift the rack from the pallet.
Pay attention to prevent the fallover of the rack.

2.4.3 Devices Unpacking


Proceed as follows:
– Open the PVC wrap protecting the carton and withdraw it.
– Remove the dehydrating material bag from the box.
– Cut with a suitable knife the adhesive tape sealing the box.
– Take the device out.
– Open the PVC wrap protecting the device/board and withdraw it.
The packing material should be preserved for possible future re-packing. For this
purpose, reverse the procedure described above, taking into account the warnings
specified for packing.
If the packing material is supplied by the customer, special care should be taken to avoid
damage during the transport and storage of the devices.

2.4.4 Rack Installation


Prior to the commencement of the installation works, consult the site documentation to
locate the installation point of the Service1A Rack, the telekommunication equipment
and the AC distribution panel.
After that check the proper installation of the earthing bar and the provided cable
runways.

WARNING
!

Before opening the rack-door take measures to prevent the rack from falling over!

If the rack must be moved to the final installation position by crane and for later
connection works, it is necessary to remove the top cover of the rack.

A50016-G5100-A461-01-7631 Id:0900d80580099867 15
Installation Service 1A Rack

For the removal of the top cover proceed in steps as follows:


– Open the rack-door: Slide down the protection cover (1), push the button behind the
cover (2) and flap out the handle (3).
– Turn the handle counterclockwise 45° (4).
– Slide the top cover 20 mm in front direction and lift it up.
– Disconnect the green/yellow ground wire from the pin inside the top cover.
– Remove the top cover completely.

3
4

2
1

Figure 9 Opening of rack door

Figure 10 Removal of top cover

WARNING
!

Do not stay or run below suspended loads!


Note the accident prevention regulations when working with a fork lift truck or crane!

WARNING
!

The total weight of rack must not exceed 360 kg when being lifted.
Under no circumstances must the sets of batteries be inserted into the Rack during
transportation on site.
The doors must be kept closed during transportation.

16 Id:0900d80580099867 A50016-G5100-A461-01-7631
Service 1A Rack Installation

60°

Figure 11 Guideline for crane transport

g NOTE
To prevent the Rack from tipping over (product safety) it must be fixed either to a
wall or the floor. It is recommended to prepare the fixings before moving the rack to
its final position.

1900 mm
minimum

*) distance
to wall
450 mm
1600 mm

750 mm

600 mm 500 mm

1100 mm

*) minimum clearance to the wall: 50 mm,


150 mm with earthquake kit S30861-K4119 -X
450 mm
Figure 12 Required space for installation of the Service1A Rack
Four fastening claws fixing the adjustable rack-feet to the base of the crate.
The claws can be later used for floor fixing of the racks, excepted in earthquake zones
(see Figure 13).

A50016-G5100-A461-01-7631 Id:0900d80580099867 17
Installation Service 1A Rack

Figure 13 Removal of fastening claws

3
1
2

Figure 14 Adjusting of the rack feet


Proceed as described in the list below:
– Remove the 4 fastening claws from the crates base as shown in Figure 13 and move
the rack carefully to the final installation position.
– Check the correct vertical rack position, using the spirit level. In case, the position is
incorrect, equalize the differences in the floor height by adjusting the rack feet. (see
Figure 14).
– Loosen the lock nut (1) and adjust the rack feet (2) for proper floor contact by using
the adjuster feet wrench M42.
– Tighten the lock nut as far as possible to avoid a gap between the bottom section
(3) and the rack frame (4)
– Push a claw on each of the 4 rack feet and mark the drilling point on the floor.
– Remove the clamps and drill the 4 holes and insert the 4 wall plugs (e.g. Fischer
S8GK) into the holes.
– Push the claws on the rack feet and fix them. Use a ratchet with a M10 nut. (see
Figure 15, left side)
The rack can alternatively fixed to the wall. The rack has two right angle brackets on its
top rear for wall fixing (Figure 15, right side).

18 Id:0900d80580099867 A50016-G5100-A461-01-7631
Service 1A Rack Installation

Figure 15 Floor and wall mounting of the racks

WARNING
!

In earthquake zones, the fastening to the wall is prohibited.Use the earthquake


mounting kit for securing to the floor.

2.4.5 Setup of Earthquake Mounting Kit


In areas with the possibility of earthquake use the mounting kit for Earthquake Zone 4
(MK:EQ4RV2, S30861-K4119-X). The additional brackets improve the robustness of
the rack against earthquake shocks.
The mounting kit consists of the mechanical parts as shown in the figure below.

3 3

Figure 16 Parts of the earthquake kit S3086-K4119-X


Fix the rack to the floor in accordance with Figure 19 in steps as follows:
– Mark the positions of the drilling holes on the floor.
– Drill the holes with 18 mm in diameter and a depth of 98 mm. Don‘t pre-drill the
holes!

A50016-G5100-A461-01-7631 Id:0900d80580099867 19
Installation Service 1A Rack

– Produce an undercut of the drilling holes: drill the hole to stop and swivel the jack
hammer 3-5 times keeping stop to concrete.
– Clean out the drilling holes with a vacuum cleaner.
– Insert dowels (3) (e.g. HILTI - M12*73 / 20) into the drilling holes and hammer them
into each hole until the sleeve is flush with surface (use an inserting tool, if available).
– Fix the double claw (1) at the rear dowels and tighten the bolts to a torque of 60 Nm
(see Figure 17).
– Shift the rack to the appropriate position, so that each of the rear rack feet is placed
in the cut-out of the double claw (Figure 17).
– Open the rack door.
– Push a claw (2) on each of the front feet and affix them with the M12 bolts to the
steel plugs in front of the rack (see Figure 18).
– Tighten the connection with a torque of 60 Nm.

Figure 17 Double claw for the rear feet in mounted position

Figure 18 Claws for the front feet before mounting

20 Id:0900d80580099867 A50016-G5100-A461-01-7631
Service 1A Rack Installation

wall

142.5
600

465
450
485
57.5
(sketch without scale, all measures in mm)
front side

Figure 19 Drilling sketch for the earthquake mounting kit

A50016-G5100-A461-01-7631 Id:0900d80580099867 21
External Cable Connections Service 1A Rack

3 External Cable Connections

3.1 Overview
This chapter provides the information required for installing the cables between the
Service1A Rack, the power distribution panel and the telecommunication equipment on
site.
The rack cannot function without the following cable connections:
– power distribution panel of 230 VAC, 3-phase supply -> AC mains 5 pole terminal
block 5 pole of the MSU (location: top of rack)
– ground bar -> ground bolt (location: top of rack)
– ground bolt - ground connector DC supplied telecommunication equipment
– -48 VDC power output terminals -> DC power input of telecommunication equipment
optional:
– alarm collection terminal ACTC (location: AD-panel)- alarm collection terminal of the
telecommunication equipment
– if installed: link equipment (can be NTPM or microwave)- telecommunication equip-
ment
– if installed: link equipment - directly to the PSTN (NTPM will be used) or in case of
microwave equipment to the microwave outdoor units
For the AC supply cable connection, the top cover has to be removed. For opening and
removal refer to section 2.4.4 of this manual.

clamp for AC supply cable

ground bolts
AC supply terminals

air vent tube

Figure 20 Top of the Service1A Rack

22 Id:0900d8058009a699 A50016-G5100-A461-01-7631
Service 1A Rack External Cable Connections

Some additional hints for the installation of external cabling:


– The first cable that has to be installed is the ground cable between the main ground
bolt M8 on the top of the rack and the nearest ground bar on site.
– The second installation step is to connect the ground bolt M8 of the Service1A Rack
with the ground connector of the telecommunication equipment
– After that all other cables e.g. AC mains, DC cables or the alarm lines can be
installed.
– If microwave antenna cables are fed through the cable feeding module located at
the top of the rack front, the outer isolation has to be stripped back, so that a proper
ground contact of the outer conductorto the metal mesh of the rubber profiles is
guaranteed.
– Cut also back the outer insulation of all other screened cables in this area.

ground connection
alarm lines
3 phase AC mains max. 3 x -48V
from max. 3 x +0V
power distribution panel from / to
SIEMENS
telecommunication
FAN#0 FAN#1 equipment

LE
ACTC Batt01/S2
+-
AD Panel Batt0/S1

- - - +++ ++ - -

0V -48V

LE Panel (S1A)
to LE#0
ground bar LE#1
LE#2
LE#3
LE#4
LE#5

Figure 21 External Connections of the Service1A Rack

g NOTE
Use only screened cables for connections between the Service1A Rack and the
telecommunication equipment on site.

A50016-G5100-A461-01-7631 Id:0900d8058009a699 23
External Cable Connections Service 1A Rack

3.2 Ground and AC- Power Supply Connections


The Service1A Rack has to be connected to the site specific ground system before
starting the connection of the AC power supply cable.
An external ground wire (16 mm2, copper conductor) has to be connected on the upper
left side grounding bolt of the rack that must be attached to the ground bar on site.
In addition a ground wire (16 mm2, copper conductor) between the rack and the ground
connector of the telecommunication equipment has to be installed.
If on site a main ground wire (50 mm2, copper conductor) is installed, it is possible to
connect the rack and the telecommunication equipment on the shortest way to the main
ground using 16 mm2 copper wires.
Connect the rack to the ground system as follows:
– Use the nearest ground bar on site.
– Measure the distance between the connection points of the ground system and the
ground bolt of the rack.
– Cut the wire to the required length.
– Remove the insulation at the end that has to be connected at the ground bolt (length
approx. 10 mm) and equip it with a crimp cable lug M8.
– Attach the wire end to the ground bolt and firmly tighten the nut.
– Route the wire to the ground bar. The connection procedure depends on the type
and the manufacturer of the ground bar.

main ground wire 50 mm2


ground wire 50 mm2 H07-RN F 5 G4 * H 07 V-R 16 mm2 *

ground wire ground wire - 48 VDC


16 mm2
16 mm2

3 x 25 A
circuit
breaker
3 x 230 V AC telecommunication
equipment
ground bar

Service1A Rack

*) cross section needed depends on the cable length between


the external breakers and the MSU
Figure 22 Power supply configuration with Service1A Rack
The figure above shows the recommended cabling for the power supply and ground
connection. The recommended cable types guarantees the proper function of the
Service1A Rack.
The second ground connection has to be installed between the Service1A Rack and the
ground connection point of the telecommunication equipment (common ground wire). If
the equipment and the Service1A Rack stand close together, the prefabricated wire
(part of the cable kit S30864-X211-A140, cable no. 446) can be used.

24 Id:0900d8058009a699 A50016-G5100-A461-01-7631
Service 1A Rack External Cable Connections

If the distance not exceed 5 m, the common ground wire provided with the cable kit
S30864-X211-A141 (cable no. 446) can be installed.
If the distance is longer than 5 m, the ground wire has to be prepared on side as shown
in the scetch.

10 mm heat shrinking sleeve 10 mm


further preparation depends
on the equipment that has to be
connected
crimp cable lug M8 recommended wire type: S07V-K 16 mm2

Figure 23 Preparation of the common ground wire


An easily accessible disconnect device is incorporated into the AC mains supply wiring.
To isolate the mains supply 3 x 25 A circuit breakers are used (one per phase). They
have to be installed in the AC distribution panel nearby the rack.
The disconnect device shall simultaneously interrupt all phase conductors.
The 5-pole terminal block of the MSU, located in the top of Service1A Rack, is the con-
nection point for the AC power supply cable.
The rack will be powered by 3 x 230 VAC, 50 Hz, 20 A per phase.

N
L1
L2
L3
PE

Figure 24 Wiring of the MSU terminal block

A50016-G5100-A461-01-7631 Id:0900d8058009a699 25
External Cable Connections Service 1A Rack

This warning must appear in the original German text:

WARNING
!

Vor Anschluß des 3 x 230 V Einspeisungskabels ist sicherzustellen, daß das Kabel
spannungsfrei ist. Die Hauptsicherungen sind zu unterbrechen. Es sind geeignete
Maßnahmen gegen unbefugtes Einschalten der Netzspannung zu treffen.

An imprint, located on the front of the AD-panel gives instruction how to deenergize the
Service1A Rack.
To deenergize entire unit:
1. “Switch OFF BATT 0 + BATT 1(BR:33) to deenergize DC circuit”
2. “Switch OFF breakers (BR: L1-L3) to deenergize AC circuit”
To connect the rack with the AC distribution panel proceed the following steps:
– Remove the top cover of the rack carefully, avoid damages to the paint work.
– Refer to the site documentation for the required information about type and location
of the AC distribution panel.
– Check the actual distance between terminal block of the MSU and AC distribution.
– Cut the cable to the required length. Note: The protection earth wire (PE) must be
approx. 2 cm longer as the L1, L2, L3 and the N wires.
– Remove the outer insulation of the cable (approx. 150 mm) and cut back the wire
insulation (15 mm) at the end that is to be connected to the MSU terminal block.
– Equip each wire with a crimp wire end sleeve.
– Fit the wires into the terminals. Use a screwdriver for opening the terminal springs.
Check that all wires are proper fixed.
– Fix the cable with the clamp provided at rear of top of the rack.
The connection procedure of the power supply cable at the AC distribution panel
depends on the type and the manufacturer of the panel.
The Service1A Rack has to be connected with up to 3 -48 VDC lines to the tele- com-
munication equipment on site. The maximum current of each line is limited to 80 A.
If the equipment and the Service1A Rack stand close together, a prefabricated cable
(part of the cable kit S30864-X211-A140, cable no.443-1 / 443-2) can be used.
If the distance not exceed 5 m, the DC cables of the cable kit S30864-X211-A141 (cable
no. 443-1 / 443-2) can be installed. If the distance is longer than 5 m, the DC cables must
be prepared on side as shown in the scetch.

26 Id:0900d8058009a699 A50016-G5100-A461-01-7631
Service 1A Rack External Cable Connections

60 mm 60 mm*

1 cut back the outer insulation and the braided shield

2 cut back the wire insulation 22 mm*


22 mm

3 fix a wire end sleeve and shrunk on the shrink tube *)

*) preparation depends on the interface of the equipment that should be connected


Figure 25 Preparation of the DC-cables
Install the DC-wires between the Service1A Rack and the equipment that to be supplied
with the following steps:
– Refer to the site documentation for the required information about type and location
of the telecommunication equipment.
– Check the actual distance between DC terminals at the AD-panel of the Service1A
rack and the power supply interfaces of the equipment.
– If necessary, prepare the cables as shown in Fig.2.41.
– Fit the wires into the DC terminals of the AD-panel and firmly tighten the screws.
– Route the cables outside the rack.
– Mark the outer insulation of each cable at the points, where it is passing the metal
mesh of the rubber profiles inside the cable feeding module.
– Strip back the outer insulation between the marked points (approx. 15 mm).
– Fix the cable at the stress relieving bracket of the cable feeding module with ties.
– Route the cables forward to the equipment that to be connected.
Connect the DC cables with the telecommunication equipment in accordance to the
installation rules of the manufacturer.

3.3 Alarm Cabling


The Service1A Rack provides some discrete alarm signals at the 24 -pin terminal block:
– 4 alarm signals can be generated by the AC/DC subsystem: Mains Breakdown,
Battery Breakdown, Battery Charger Fault and DC-Output Voltage on the load out
of specified tolerance
– 2 Fan alarms (FAN0, FAN1)
These alarms can be forwarded to the telecommunication equipment on side for trans-
mission purposes.
The prefabricated alarm cable (cable no. 444) is part of the connection kit S30864-X211-
A140. It should be used, if the Service1A Rack and the telecommunication equipment
is installed closed together.
The connection kit S30864-X211-A141 provides all parts for the preparation of the alarm
cable on side, the length is limited to 5 m. If a longer cable is needed, use a cable type
with 16 wires in twisted pairs (e.g. S-09YS(St)CY 8 x 2 x 0.6/1.2).
For installation of the alarm connection perform the following steps:
– Strip back the outer insulation of the cable (length approx. 110 mm).
– Route the cable temporary from the ACTC module outside the rack.

A50016-G5100-A461-01-7631 Id:0900d8058009a699 27
External Cable Connections Service 1A Rack

– Mark the outer insulation of the cable at the points, where it is passing the metal
mesh of the rubber profiles inside the cable feeding module.
– Strip back the outer insulation between the marked points (approx. 15 mm).
– Fix the cable at the stress relieving bracket of the cable feeding module with ties.

remove wire insulation 10 mm for connection at the ACTC only

110 mm length to be determined 15 mm

Figure 26 Preparation of the alarm cable


– Disconnect the alarm wires from the 24-terminal WAGO block as shown in the figure
below.
– Remove the uninsulated ends of the wires.

MBR BBR BCHF 48OTB

SMOKE RDO

14 13 12 11 4321

24 1

Figure 27 Connector arrangement at the ACTC-3


– Connect the wires of the alarm cable with the wires, removed from the ACTC in
accordance with the table below.
– Insert the matching pair of insulated wire ends completely into IDC connector chan-
nels.
– Press the button down with pliers.
– Bend the connected wire pairs back into parallel to the alarm cable.
– Secure the wire pairs at the alarm cable with cable ties.

28 Id:0900d8058009a699 A50016-G5100-A461-01-7631
Service 1A Rack External Cable Connections

Internal Cabling Service1A Rack Alarm Connection Cable 444


Cable WAGO Color Color Wire Signal
no. terminal of wire of wire bundle name
146 2 blue white 1 48OTB
1 black blue 48OTB
147 4 blue turquoise BCHF
3 black violet BCHF
148 12 blue white 2 BBR
11 black orange BBR
149 14 blue turquoise MBR
13 black violet MBR

Table 1 Connection of alarm wires with IDC-connectors

In addition, the alarm connection cable no. 444 has to be connected with the ACTC
24-pole terminal block. At the terminals as shown in Figure 29 the alarm signals for
Overvoltage Protection and the FAN units are provided.
The fan alarms ALFN0 and ALFN1 are supported after changing of the connection
position of the fan alarm wires at the rear side of the ACTC module only.
The rear side of the ACTC is accessible after the removal of the rear panel of the rack.
Change the connection position of the alarm wires no. 151 and 152 as shown in the
figure.

X3
X41
X5/X6
X4

X27

x44 X20 X7/X8

ACTC rear side


151 151
152 152

Figure 28 Changing of the FAN-plug position

WARNING
!

To avoid the risk of electrical hazards, the Service1A Rack must be disconnected from
power supply sources. The battery breaker BR: 33 must be switched OFF.

A50016-G5100-A461-01-7631 Id:0900d8058009a699 29
External Cable Connections Service 1A Rack

ALFN0 ALFN1 OVP

18 17 16 15 65

Figure 29 Alarm cable connection at ACTC


The following table gives additional information about the connection of the alarm cable
at the WAGO terminals of the ACTC.

ACTC pin no. Wire bundle no. Wire color Signal name
5 3 white OPVP_P
6 green OVP_M
15 turquoise AL_GND
16 violet ALFN1_P
17 4 white AL_GND
18 brown ALFN2_P

Table 2 Connection of the alarm cable at the ACTC

Route the alarm connection cable from the Service1A Rack to the telecommunication
equipment. Connect the alarm connection cable with the telecommunication equipment
in accordance to the installation rules of the manufacturer.

30 Id:0900d8058009a699 A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

4 Rack Completion
The Service1A Rack is shipped including equipment components, pre-installed by the
manufacturer in accordance with the ordered customer configuration mandatory:
– Sub-rack, which holds several boards and modules
– AD-panel
– Backplane (multi-layer PC-board, that is mounted at the rear side of the AC/DC
subrack)
– Rack internal cabling
– FAN units
– AC/DC converters
– AC/DC controller
optional:
– Mounting kit for 19” link equipment (2 or 3 height units)
– Mounting kit for NTPM (2 units with 3 height units, side-by-side)
The (optional) backup batteries are planned for installation after setup of the rack on site.

4.1 Preparation of the Top Cover


After all external cables are installed, prepare the top cover for later setup on the top of
the rack. For this purpose the top cover provides removable pieces for cable routing as
shown in the figure below.
The required number of pieces can be removed in easy manner by cracking out at the
perforation. After that refinish the paint coat at all cracks with the paint retouch kit
(Siemens Serial No. A500-C101-B261).
The sharp edges of the break-outs will be covered with the sealing profile tape (Siemens
Serial No. C42127-Z1-C661). It will be delivered in 100 cm sections and must be cutted
to the required length.

Figure 30 Paint retouch of the top cover

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 31
Rack Completion Service 1A Rack

sealing profile tape

Figure 31 Placement of the sealing profile tapes

4.2 Installation of Backup Batteries


To enable easier transportation and setup of Service1A Rack, it will be delivered without
backup batteries. The battery trays can be equipped with different types of batteries. The
installed battery type depends on the required backup time.
Each battery set consist of 4 batteries always.
If a label relevant to the characteristics of the batteries is delivered, then should be this
label placed on the door of the rack.

Supplier BATTPACK type MK:BATTPACK Capacity


type
Oerlikon, 12CP80 BATTPACKV2 MK:BATTPACKV2 80 Ah
Oerlikon, 12CP100/19” BATTPACKV3 MK:BATTPACKV3 100 Ah
Oerlikon, 12C@2000 BATTPACKV5 MK:BATTPACKV5 55 Ah
Hawker, 12V92F BATTPACKV4 MK:BATTPACKV4 92 Ah

Table 3 Overview of backup battery sets

If the Service1A rack‘s battery trays are equipped with MK:BATTFIXCB, before setup of
the batteries, the spacer strips (1) have to be placed at the rear and the front edge of the
battery tray. Additional spacer blocks (2) are used to provide a distance of 10 mm
between the batteries (see following figure).

32 Id:0900d805800a06ea A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

Figure 32 Parts for battery fixing

bracket

spacer strips

Figure 33 Placement of the spacer strips


The bracket that fix the batteries inside the battery tray has to be removed, before setup
of the battery set.
A second variant of the battery tray will be equipped with fixing plates to provide space
between the batteries. Proceed in accordance with the following figure:
– Remove the MK:BATTERY from the battery tray before fitting of the batteries.
– Mount the battery fixing plates at the bottom section of the battery tray.
– Put on the batteries.

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 33
Rack Completion Service 1A Rack

MK:BATTERY fixing plate

loosen the screws

Figure 34 Preparation of the battery tray

4.2.1 Installation of Backup Batteries Type “Oerlicon”


For installation of an “Oerlicon” battery set proceed in accordance with Figure 35 and
Figure 36 in steps as follows:
– Switch off the circuit breaker at the AD-panel and the mounting kit battery.
– Put on the battery 1,2,3 and 4 into the battery tray.
– Connect the + terminal of battery 1 and the - terminal of battery 2 with the short
metal bridge.
– Connect the following batteries in the same way.
– Connect the blue load-cable to battery 1 (- terminal) and the black load-cable and
the temp-resistor cable to battery 4 (+ terminal)
– Tighten the battery termination fixing screws to a torque of 6 Nm and the cable
termination fixing screws to a torque with 20 Nm.
Fix the batteries with the metal bracket, that is part of the MK:battery

WARNING
!

Only use insulated tools for connecting the cables to the battery terminals in order to
avoid accidental short circuits.

After all electrical connections are complete, setup the air vent system:
– Fix the short clear plastic tubes (1) at the air vent nipples of battery 2 and 3.
– Fix the longer plastic tubes (2) at the air vent nipples of battery 1 and 4.
– Connect the 4 tubes at the collector part (3).
– Connect the long clear plastic tube (4) at the collector part.
– Route the tube along the right side rack frame upwards through the cable feeding
module.
– The tube must be fixed at the rack frame by cable straps.
g NOTE
In order to avoid the accumulation of hydrogen gas, please make sure to install the
ventilation tube parts in a straight line and as short as possible, without any loops in
vertical direction.

34 Id:0900d805800a06ea A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

Temp-resistor cable battery cable +0V

battery cable -48 V

1 2 3 4

_
+ _
+ _
+ _ +

air vent system

Figure 35 Connection of backup battery sets (Co. Oerlicon)

1
4

Figure 36 Air vent system for Oerlicon battery sets

4.2.2 Install Backup Batteries Type “Hawker”


Install and connect the “Hawker” batteries according to Figure 37 and Figure 38 as well
as the following steps:
– Switch off the circuit breaker at the ADP and the mounting kit battery.
– Place batteries 1,2,3 and 4 in the battery tray.
– Mount the bracket of the battery tray for fixing the batteries.
– Connect the battery 1 (+ terminal) and battery 2 (- terminal) with the short metal
bridge and tighten the nuts with a torque of 5 Nm.

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 35
Rack Completion Service 1A Rack

– Connect the following batteries in the same way.


– Fasten the accompanying protecting caps over the battery terminals.
– Connect the blue load cable to battery 1 (- terminal) and connect the black load
cable and the temp-resistor cable to battery 4 (+ terminal).
– Using a wrench set to a torque of 5 Nm, fasten the battery cable nuts.
– Shift the protection cap to the end position to cover the battery cable connectors.

WARNING
!

Use only insulated tools to connect the cables to the battery nuts to avoid accidental
short circuits!

After all electrical connections are complete, setup the air vent system according to
Figure 39:
– Fix the short clear plastic tubes (1) at the air vent connector of batteries 2,3 and 4.
– Fix the longer plastic tubes (2) at the air vent connector of batteries 1.
– Connect the 4 tubes at the T-collector parts (3) and connect them with each other.
– Connect the long clear plastic tube (4) at the T-collector part of battery 4.
– Route the tube along the right side rack frame upwards through the cable feeding
module.
– The air vent tube must be fixed at the rack frame by cable ties.
g NOTE
In order to avoid the accumulation of hydrogen gas, please make sure to install the
ventilation tube parts in a straight line and as short as possible, without any loops in
vertical direction.

bracket
1 2 3 4

Figure 37 Setup of the backup batteries, fixing of the tray bracket

36 Id:0900d805800a06ea A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

blue black

temp-resistor cable

Figure 38 Connection between the batteries, battery cable connection

2
3
4

Figure 39 Routing of the air vent tubes

4.3 Installation of Link Equipment


The link equipment acts as a front end, to provide the Abis interface in case that the
Service1A Rack will be connected with a Base Transceiver Station BTS in mobile net-
works. Different equipment can be used for wire or radio transmission, depending on
customer requirements.
The number of link equipment, which can be installed depends on the height of the units.
g NOTE
For connections between the Abis interface of a BTS and link equipment in the
Service1A Rack pay attention to the recommendation CCITT G.703.
The receive level compared with the transmit level should not be lower than 6 dB.
Mounting kits, designed for 19” units are required for the installation of link equipment.
In total an extra space for 6 height units (HU) is provided in the Service1A Rack. The
fitting of link equipment in the mounting kits must always begin at the top below the fans
without a gap.

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 37
Rack Completion Service 1A Rack

4.3.1 Installation of Microwave Equipment


In case of microwave transmission, the indoor units inside the Service1A Rack must be
connected via the microwave antenna cables with the tower mounted outdoor units.

-48 V / +0 V DC
from Service1A AD Panel

LE breakers 25A
1 8
DC Panel
S30864-X215-A39, (twisted pair, blue: -48 Vdc, black: 0 Vdc)
PCM lines from/to BTSE *
(optional) alarm lines
from/to Microwave Antenna*
cable feeding module

LE0
LE1
LE2
LE3
LE4
LE5
Frame Microwave *) cable has to be prepared on site
Figure 40 Cabling Overview for Microwave Equipment
Additional hints for the connection of the microwave equipment:
– Use mesh screened twisted pair cables only for connections between the BTSE and
the microwave equipment inside the Service1A Rack.
– Strip back the outer insulation of the cables where they pass the cable feeding
module (approx.15 mm).
– Fix the cables at the metal bracket of the cable feeding module with cable ties.
Connect the microwave antenna cables to the indoor units as follows:
– Remove the front part of cable feeding module.
– Feed the microwave cable through the cable feeding module forward to the front
connectors of the microwave indoor units.
– Fix the microwave cables at the connectors.
– Bend the microwave cables into the correct position for easy closing of cable feeding
module.
– Mount the front part of feeding module in its original position.
– Fix each cable at the strain reliefs of the cable feeding module with cable ties.
– Connect the microwave power supply cable at the circuit breakers BR: 01-06 of the
LE-panel.
– Route the cable bundle forward to the link equipment devices.
– Cut the cables for the matching length and equip the end with device-specific con-
nectors.

38 Id:0900d805800a06ea A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

4.3.2 Installation of NTPM


In case of transmission via terrestrial lines, the NTPMs can be placed inside the
Service1A rack, that is equipped with a mounting kit for NTPM, called frame F:NT.
Each frame F:NT includes the equivalent space of 3 HU, allowing the installation of up
to 2 NTPM. The frame F:NT provides 3 interfaces as shown in the figure Figure 41.
The interfaces are:
– subD 9, male with M3 fixings for -48 V output
– subD 25, female with M3 fixings for PCM input
– subD 25, male with M3 fixings for PCM output

- 48 VDC

to OVPT / ABISCON

external PCM lines

Figure 41 Interfaces on frame F:NT


The power supply cable from the frame F:NT to the AD-Panel is part of the F:NT.
The PCM cabling is site specific and depends on customer requirements.

Name F:NT -48 V, subD 9 female pin


0V 1,2,6
-48 V 4,5,9

Table 4 Pin Assignments of -48 V interface of frame F:NT

Signal name F:NT PCM-INPUT subD 25 F:NT PCM-OUTPUT subD 25


female pin male pin
PCM 1 - ULA 1 1
PCM 1 - ULB 14 14
GND/G 3 3
PCM 1 - DLA 2 2
PCM 1 - DLB 15 15
GND/G 16 16
PCM 2 - ULA 4 4
PCM 2 - ULB 17 17

Table 5 Pin Assignments of PCM-Input and -Output connector of frame F:NT

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 39
Rack Completion Service 1A Rack

Signal name F:NT PCM-INPUT subD 25 F:NT PCM-OUTPUT subD 25


female pin male pin
GND/G 6 6
PCM 2 - DLA 5 5
PCM 2 - DLB 18 18
GND/G 19 19

Table 5 Pin Assignments of PCM-Input and -Output connector of frame F:NT

-48 V / +0 V DC
from Service1A AD Panel

LE breakers 25A
1 8
DC Panel
PCM lines from/to BTSE *
S30864-X211-A109
PCM lines from/to PSTN *

cable feeding module

NTPM 0 NTPM 1

Frame F:NT *) cable has to be prepared on site


Figure 42 Cabling Overview for NTPM Installation

g NOTE
Use mesh screened twisted pair cables only for connections between the BTSE and
the PCM-INPUT connector of the frame F:NT and between the PCM-OUTPUT con-
nector and the PSTN.
Strip back the outer insulation of the cables where they pass the cable feeding
module (approx.15 mm).

4.4 Post Installation Notes


The following instructions must carried before leaving the site:
– At the end of the working day enable any alarms that should be active.
– Contact the Network Control Center to announce your departure.
– Close and lock the rack doors.
– Ensure the site is secure or hand over to the person in charge / caretaker
If all installation activities are finished, any garbage must be cleared from site.

40 Id:0900d805800a06ea A50016-G5100-A461-01-7631
Service 1A Rack Rack Completion

Remove all packing material for recycling.

WARNING
!

The burning of rubbish should be avoided, as a burning of packaging material may give
off toxic gases.

g NOTE
For dehydrating the rack during transportation and storage, a bag filled with Silica
Gel is fitted into the rack by the factory. It is recommended to remove the bag,
because after a certain time the bag lost his function.

A50016-G5100-A461-01-7631 Id:0900d805800a06ea 41
Installation and Test Service 1A Rack

5 Installation and Test

5.1 Final Installation Checks


Before SWITCH ON the Service1A Rack check the correct installation of the rack and
all external cable connections.
Use the following table as an checklist

Check Item Yes No


Rack fixed to floor and wall (wall excepted in erthquake zones)
Grounding
Rack connected to ground as described in section “External
Cabling Activities”
Cable screens of all cables connected to ground at the cable
feeding module
Power Supply
Cross section of power supply cable sufficient
power supply connection correspondend to TNS-or TT
Network requirements
Cross section correspondend to cable length
External Alarms
External alarm cables with braided screen
Cable screen contacted to metal lid of cable feeding module
Cable screen contacted to ground at both ends
Overvoltage protection equipment present and correct installed
PCM Cables to Link Equipment
PCM cables with braided screen
Cable screen contacted to ground at both ends
NTPM connector for cable screens correspondend to
EMC requirements
Overvoltage protection equipment correct installed (if present)

Table 6 Checklist for Service1A Rack Installation

42 Id:0900d805800a08e9 A50016-G5100-A461-01-7631
Service 1A Rack Installation and Test

5.2 Switch ON of the Rack


Before the rack will be powered by the external AC mains source, set all circuit breakers
at the AD-Panel and the LE-Panel in switch OFF position.
Switch on the 3 25A circuit breakers at the AC distribution panel on site.
g NOTE
The task of the 25 A circuit breakers in the AC distribution panel is also the function
of a master switch for the Service1A Rack.
Switch ON the circuit breakers at the AD-Panel in the following order:
1. BR: L1-L3 -> The AC/DC converters are switched ON
2. BR: 25 -> ACTC is DC supplied
3. BR: 26 -> FAN units are DC supplied and starts rotating after 7 seconds
4. BR: 27 -> LE-Panel is DC supplied
5. BR: 33 -> Backup batteries are connected
6. BR: 28-30 -> Telecommunication equipment on site is DC supplied

ACTC
180A
BR: 25-27

BR 33

FI BR: 28-30

BR: L1-L3

Figure 43 Breaker arrangement at the AD-Panel


If link equipment is installed inside the Service1A Rack, switch ON the circuit breakers
at the LE-Panel: BR: 01-06 -> Link equipment units 0-5 are DC supplied

0V -48 V
BR01 BR06

Figure 44 Breaker arrangement at the AD-Panel

A50016-G5100-A461-01-7631 Id:0900d805800a08e9 43
Maintenance Service 1A Rack

6 Maintenance

6.1 LED Status Indication at the DCBCTRL


The DC and Battery Controller is the supervision unit for the AC/DC converters. The unit
also manages the battery charging and the battery test.
Two types of the DCBCTRL are available: DCBCTRLA and DCBCTRLD.
Both types are equipped with LEDs for status indication of the AC/DC system. The figure
below gives information about the meaning of the LEDs.

Ethernet connector interface (optional)


RS 232 connector interface to PC
Battery capacity test push button
DCBCTRLD

4 5 6 7 8 9 10 11 12 13
1 2 3

Battery rough test push button System voltage measurement


Manual floating / Equation button Breaker LE
AC OK LED LVDS LED
DC OK LED Major alarm LED
BAT Fail LED Minor alarm LED
Temp alarm LED EQU LED
Reset LED

AC AC OK LED
DC DC OK LED
Batt Fail BAT Fail LED
Temp Temperature alarm LED
Reset Reset LED
V DC
System voltage measurement (VDC)

RS 232 connector interface to PC (Comm Port)

DCBCTRLA
Figure 45 LED Status Indication of the DCBCTRL

g NOTE
A fault of the DCBCTRL modules does not interrupt the function of the power supply
modules.

44 Id:0900d805800a0a3f A50016-G5100-A461-01-7631
Service 1A Rack Maintenance

6.2 Checks and Replacement of Modules

6.2.1 FAN Unit


To replace an internal FAN the locking levers are operated and the FAN is gently pulled
forward.
The metal face plate is the top of the fan unit.

WARNING
!

If power is connected to the system and an internal FAN has to be replaced, first pull it
out to a slight extent so the FAN is disconnected from power. Wait with pulling it out com-
pletely until the fan blades have stopped rotating to avoid injury.

With regard to acceptable failure rates, it is recommended to replace a FAN when its
total operating time exceeds 9 years at an average FAN temperature of 40°C.
Under extreme environmental stress with FANs exposed to an average temperature of
70°C, this time period reduces to 2 1/2 years.
Mark the replaced FAN unit as defective.

6.2.2 AC/DC Converter


Investigate the defective AC/DC converter first by checking the output supply current for
all AC/DC modules inside the Service1A Rack.
This can be done by measuring the indication voltage at the test connector of the
module.
The relationship between the indication voltage and the output current is 100 mV/A.
If no output current is present, the converter module has to be replaced. Select a module
that is compatible to that module which is being replaced.
Loose the fixing screws at the front of the affected AC/DC module and pull it out. Mark
the module as defective.
Plug in the new module and tighten the fixing screws.

6.2.3 Batteries
The AC/DC system supports battery capacity tests at the DCBCTRL (see Figure 45).
It is recommended to make an annual quick battery back-up test by cutting of the base
station from AC power supply. This is to make sure that the batteries are still intact
(quick check only) and the LVD Relais is still making a good electrical contact.
It is recommended to check annually whether any battery nuts have loosened and to re-
tighten them (if necessary) to the recommended torque values given under see section
4.2
Battery service life, operating temperature:
According to EUROBAT, the end of battery service life is reached when the current
battery capacity value has fallen below 80% of nominal battery capacity.
An increase of 10°C in average battery operating temperature effects a 50% reduction
in battery service life.

A50016-G5100-A461-01-7631 Id:0900d805800a0a3f 45
Maintenance Service 1A Rack

That means, that a battery service life of 10 years (20°C), declared by the manufacturer,
the service life will only be 5 years if the average battery operating temperature is
actually about 30°C.
Battery service life is also limited by discharge cycles:
Oerlikon 12CP80, Oerlikon 12C@2000 (1h,100%) " 300 times;
Hawker 12V92F (1h,100%) " 300 times
For replacement of battery sets proceed in accordance to section 4.2.

6.2.4 Check of the Ground Contact


It is recommended to check the connection between the grounding cable (see section
3.2) and the grounding bar of the earth electrode (system) every year (i.e. for corrosion
and loose nuts/screws).

46 Id:0900d805800a0a3f A50016-G5100-A461-01-7631
Service 1A Rack Appendix

7 Appendix

7.1 Disposal of Electrical and Electronic Equipment

The correct disposal and separate collection of your old appliance will help prevent
potential negative consequences for the environment and human health. It is a precon-
dition for reuse and recycling of used electrical and electronic equipment.
For more detailed information about disposal of your old appliance, please contact your
sales representative.
The statements quoted above are only fully valid for equipment which is installed in the
countries of the European Union and is covered by the directive 2002/96/EC.
Countries outside the European Union may have other regulations regarding the
disposal of electrical and electronic equipment.
All electrical and electronic products should be disposed of separately from the
municipal waste stream via designated collection facilities appointed by the government
or the local authorities.

7.2 Installation Tools


The correct installation is carried out with the aid of the following tools:
– Spirit-level
– Plumb bob
– Screw driver for torx screws T8, T10, T20, T25, T30, T40, T50 (length 200 mm)
– Long screw driver for torx screws T30 (length 400 mm)
– Engineer‘s wrenches for M12, M42 (SW 19, 65 mm)
– Ratchet with insets for nuts M4, M5, M6, M8, M10 (SW 7, 8, 10, 13, 17 mm)
– Security torx bit IPR25 (Knürr part no. 4000031 98)
– Insulated torque wrench for Torx T30 (6 Nm) and an open ended 17 mm (20 Nm) for
battery mounting
– Insulated hexagonal socket screw key or ratchet (M6) for connecting DC cables to
AD panel (Service1A) and DC panels (Base and Extension)
– Screw drivers for hexagonal socket screw or hexagonal socket screw key SW 4 mm
– Screw driver for slotted screw M3, M4, M5
– Screw driver for pozi drive screws M3, M4, M5
– A pair of scissors
– 90° offset screw driver for torx screws T20

A50016-G5100-A461-01-7631 Id:0900d805800a0a48 47
Appendix Service 1A Rack

– Adjuster feed wrench M42 (SW65) (Knürr part no. 01.139.965.7)


For installation of third paty eqipment, additional tools may be necessary.

7.3 Ancillary Material


The following ancillary materials are needed:
– plumb line
– colophony
– cable ties with different length
– wire end sleeves for 16 mm² copper wires
– cable lugs M8
– wire end sleeves
– paint retouch kit (Siemens Serial No. A500-C101-B261)

48 Id:0900d805800a0a48 A50016-G5100-A461-01-7631

Você também pode gostar