Você está na página 1de 1

TEST REPORT

Standard as per : BDS 899-3, BS-6500 & IEC 60228 Date : 05.06.2018
Size of Cable : 3X0.75 rm (mm2) Color : Black
Type of Cable : Flexible-FR (Skin Coated) Length : 30000 Meter
Voltage Grade : 300/500 Volts Client : Walton Hi-Tech Industries Ltd.
M/C : Extruder 80 mm B
SL. Description of test Unit Required Value Observed Value
No.
Visual Check - Smooth OK
Nominal cross-sectional area of conductor mm² 0.75 0.75
Number of core’s no. 03 03
Color of core’s - Deep Blue, Light Deep Blue, Light Brown
Brown & Green-Yellow & Green-Yellow
Conductor: (Class-5)
Physical Test Material - Copper Copper
01 Shape of conductor - Stranded Stranded
circular circular
Number of wire no. 26 26
Diameter of Wire 0.193 0.193
Insulation:-
Material - PVC Flame Retardant PVC Flame Retardant
Nominal thickness of insulation mm 0.60 0.61
Minimum Thickness of Insulation mm 0.44 0.59
Sheath:-
Material - PVC Flame Retardant PVC Flame Retardant

Nominal thickness of Sheath mm 0.80 0.81


Minimum Thickness of Sheath mm 0.58 0.79
Approximate overall diameter of cable mm 6.90 6.95-7.05
Max.m D.C resistance of conductor at 20⁰ C Ω/Km 26.0 24.77

Electrical Min. m Insulation resistance constant ki at 20⁰ C MΩ.km 35 105


02
Test A.C Spark Test 6 kv No Break Down Withstood
A.C High Voltage Test for 05 minutes 1.5 kv No Break Down Withstood
Before ageing:
03 Mechanical Min. Tensile strength of PVC FR Insulation N/ mm² 12.5 15.56
Test Min. Elongation of PVC FR Insulation % 150 209
Min. Tensile strength of PVC FR Sheath N/ mm² 12.5 15.75
Min. Elongation of PVC FR Sheath % 150 220
04 Flame Test Unaffected portion from lower edge of the clamp mm 50 389
should be minimum 50 mm
05 Oxygen Minimum Oxygen Index % 29 30.85
Index
Remarks: The above test results are found Passed.

Tested By Checked by Approved by

Você também pode gostar