MEDIDA DE PERDIDAS DIELECTRICAS PARARRAYOS

TRANSFORMADOR T-16700

SUBESTACION : TEMUCO INFORME Nº : 1

SERVICIO : TRANSORMADOR T-16700 FECHA : 14/02/2006

PARARRAYOS 220 kV

MEDIDA PÉRDIDAS DIELÉCTRICAS

CORRIENTE WATTS
CAPACIDAD
FASE Nº SERIE KV PRUEBA Pol.
pF
LECTURA MULTIPLIC. TOTAL LECTURA MULTIPLIC. TOTAL

42.5 13.1 10 µA 5.9 0.002 +


10 Super. 135.5 0.0512
42.1 14.0 10 µA 45.3 0.002 +
36.0 11.0 10 µA 19.2 0.002 +
990804701 10 Infer. 110.5 0.0429
1 36.3 11.1 10 µA 23.7 0.002 +
16.0 4.7 10 µA 5.8 0.002 +
10 Tot. 48.5 0.0215
16.7 5.0 10 µA 15.7 0.002 +
42.7 13.2 10 µA 88.2 0.002 +
10 Super. 135 0.0445
44.7 13.8 10 µA 43.7 0.002 -
35.1 10.8 10 µA 30.4 0.002 +
2 990804704 10 Infer. 108 0.0355
35.2 10.8 10 µA 5.1 0.002 +
16.1 4.9 10 µA 39.1 0.002 +
10 Tot. 49.5 0.0195
16.5 5.0 10 µA 19.6 0.002 -
40.9 13.3 10 µA 42 0.01 +
10 Super. 141 0.0485
45.9 14.9 10 µA 32.3 0.01 -
35.0 10.7 10 µA 56.6 0.002 +
3 990804705 10 Infer. 108.5 0.0411
36.5 11.0 10 µA 155 0.002 -
17.2 4.8 10 µA 73.0 0.002 -
10 Tot. 50.5 0.0226
16 5.3 10 µA 95.6 0.002 +

RESISTENCIA BASE AISLANTE

Voltaje Prueba: 5kV

H1 326 GΩ

H2 424 GΩ

H3 404 GΩ

Mantenimiento Zona Araucanía


PARARRAYOS 66 kV

MEDIDA PÉRDIDAS DIELÉCTRICAS

CORRIENTE WATTS
CAPACIDAD
FASE Nº SERIE KV PRUEBA
pF
LECTURA MULTIPLIC. TOTAL LECTURA MULTIPLIC. TOTAL Pol.

10 38.2 11.9 10 µA 220 0.002 +


1 J 65604 119.5 0.0288
10 38.3 12.0 10 µA 6.8 0.002 +

10 38.8 12.1 10 µA 24.8 0.002 +


2 J 65607 121.0 0.0323
10 39.1 12.1 10 µA 7.5 0.002 +

10 37.8 12.7 10 µA 28.2 0.002 +


3 J 65605 117.5 0.0291
10 38.0 11.8 10 µA 0.9 0.002 +

ESTADO TIEMPO :
Despejado TEMP. AMBIENTE : 21.7 ºC HUMEDAD RELAT.: 56 %

INSTRUMENTO : Doble M2H

REALIZADO POR : Néstor Espinoza REVISADO POR :

FECHA : 14-02-2006 FECHA :

OBSERVACIONES

Fotografías placas características:

Pararrayos 220kV Pararrayos 66kV