Technical Data Sheet for Instrument transformers

CURRENT TRANSFORMERS – 400 KV (SHERWOOD)


Item Particulars Unit Minimum Requirements Guaranteed
Particulars
7.1.1 Service conditions Outdoor Outdoor
7.1.2 Type Oil filled, metallic top tank type Oil filled, metallic top
with Composite bushing. tank type with
Composite bushing.
7.1.3 Standards IEC 44 IEC 60044-1
7.1.4 Rated frequency Hz 50 50
7.1.5 Nominal System Voltage kV rms 330 330
7.1.6 Highest System Voltage kV rms 420 420
7.1.7 System Neutral - Solidly Grounded Solidly Grounded
7.1.8 Rated short time thermal current I (3 sec)kA 31.5 31.5

7.1.9 Rated Load Current A 800 800


7.1.10 Rated peak current kA peak 78 78
7.1.11 Insulation level – primary winding
7.1.11.1 a) Power frequency withstand voltage - one
kV rms Refer to Chpt 2, Section 1 510

7.1.11.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Section 1 1300

7.1.11.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Section 1 950

7.1.11.4 One minute power frequency withstand vkV rms Bidder to Supply 3

7.1.12 Min. Creepage distance mm/kV 31 31


7.1.13 Instrument security factor Bidder to Supply </= 5
7.1.14 Maximum secondary resistance Bidder to Supply </= 5
7.1.15 Radio interference voltage Bidder to Supply < 2500µV
7.1.16 Accuracy limit factor 20 20
7.1.17 Number of cores 5 5
7.1.18 Core Details
7.1.18.1 Protection 800/400/1, 5P20, 20 VA 800/400/1, 5P20, 20 VA
7.1.18.2 Protection 800/400/1, 5P20, 20 VA 800/400/1, 5P20, 20 VA

7.1.18.3 Metering 400/1, 1FS5, 10 VA 400/1, 1FS5, 10 VA

7.1.18.4 Protection 800/400/1, 5P20, 20 VA 800/400/1, 5P20, 20 VA


7.1.18.5 Protection 800/400/1, 5P20, 20 VA 800/400/1, 5P20, 20 VA
7.1.19 Enclosure protection for the secondary terminal box IP 56 IP 55
7.1.20 Secondary terminal box Cast aluminium or Mild steel Mild Steel
* Note: 420kV highest sytem voltage and corresponding BIL is confirmed only after applying Altitude Correction Factor.
Technical Data Sheet for Instrument transformers
CURRENT TRANSFORMERS – 132 KV (SHERWOOD)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.2.1 Service conditions Outdoor Outdoor
7.2.2 Type Oil filled, metallic top tank type Oil filled, metallic top tank type with
with Composite bushing. Composite bushing.

7.2.3 Standards IEC 44 IEC 60044-1


7.2.4 Rated frequency Hz 50 50
7.2.5 Nominal System Voltage kV rms 132 132
7.2.6 Highest System Voltage kV rms 145 145
7.2.7 System Neutral - Solidly Grounded Solidly Grounded
7.2.8 Rated short time thermal current kA 25 25
I (3 sec)

7.2.9 Rated Load Current A 1600 1600


7.2.10 Rated peak current kA peak 63 63
7.2.11 Insulation level – primary winding

7.2.11.1 a) Power frequency withstand kV rms Refer to Chpt 2, Sect 1 275


voltage - one min
7.2.11.2 b) Lightning impulse withstand kV peak Refer to Chpt 2, Sect 1 650
voltage
7.2.11.3 c) Switching impulse withstand kV peak Refer to Chpt 2, Sect 1 Not Applicable
voltage
7.2.11.4 One minute power frequency kV rms Bidder to Supply 3
withstand voltage- secondary
7.2.12 Min. Creepage distance mm/kV 31 31
7.2.13 Instrument security factor Bidder to Supply </=5
7.2.14 Maximum secondary resistance Bidder to Supply </=5

7.2.15 Radio interference voltage Bidder to Supply < 2500µV


7.2.16 Accuracy limit factor 20 20
7.2.17 Number of cores 5 5
7.2.18 Core Details
7.2.18.1 Protection 1250:1, 5P20, 20 VA 1250:1, 5P20, 20 VA
7.2.18.2 Metering 800:1, 1FS5, 10 VA 800:1, 1FS5, 10 VA
7.2.18.3 Protection 1250:1, 5P20, 20 VA 1250:1, 5P20, 20 VA
7.2.18.4 Protection 1250:1, 5P20, 20 VA 1250:1, 5P20, 20 VA
7.2.18.5 Protection 1250:1, 5P20, 20 VA 1250:1, 5P20, 20 VA
7.2.19 Enclosure protection for the IP 56 IP 55
secondary terminal box
7.2.20 Secondary terminal box Cast aluminium or Mild steel Mild Steel
Technical Data Sheet for Instrument transformers
CURRENT TRANSFORMERS – 132 KV (ORANGE GROVE)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.3.1 Service conditions Outdoor Outdoor
7.3.2 Type Oil filled, metallic top tank type with Oil filled, metallic top tank type with
Composite Composite bushing.
7.3.3 Standards IEC 44 IEC 60044-1
7.3.4 Rated frequency Hz 50 50
7.3.5 Nominal System Voltage kV rms 132 132
7.3.6 Highest System Voltage kV rms 145 145
7.3.7 System Neutral - Solidly Grounded Solidly Grounded
7.3.8 Rated short time thermal current kA 25 25
I (3 sec)
7.3.9 Rated Load Current A 800 800
7.3.10 Rated peak current kA peak 63 63
7.3.11 Insulation level – primary winding
7.3.11.1 a) Power frequency withstand voltage - kV rms Refer to Chpt 2, Sect 1 275
one min
7.3.11.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 650

7.3.11.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 Not Applicable

7.3.11.4 One minute power frequency withstand kV rms Bidder to Supply 3


voltage- secondary
7.3.12 Min. Creepage distance mm/kV 31 31
7.3.13 Instrument security factor Bidder to Supply </=5
7.3.14 Maximum secondary resistance Bidder to Supply </=5
7.3.15 Radio interference voltage Bidder to Supply < 2500µV
7.3.16 Accuracy limit factor 20 20
7.3.17 Number of cores 5 5
7.3.18 Core Details
7.3.18.1 132kV Transformer Diff (87T) 800/400/1; 5P20 20 VA 800/400/1; 5P20 20 VA
7.3.18.2 132kV (OC/EF) Protection 800/400/1; 5P20 20 VA 800/400/1; 5P20 20 VA
7.3.18.3 Metering 800/400/1; 1FS5 10 VA 800/400/1; 1FS5 10 VA
7.3.18.4 Spare 800/400/1; 5P20 20 VA 800/400/1; 5P20 20 VA
7.3.18.5 Spare 800/400/1; 5P20 20 VA 800/400/1; 5P20 20 VA
7.3.19 Enclosure protection for the secondary IP 56 IP 55
terminal box
7.3.20 Secondary terminal box Cast aluminium or Mild steel Mild Steel
Technical Data Sheet for Instrument transformers
CURRENT TRANSFORMERS – 33 KV (ORANGE GROVE)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.4.1 Service conditions Outdoor Outdoor
7.4.2 Type Oil filled, metallic top tank type Oil filled, metallic top tank type with
with Composite bushing. Composite bushing.
7.4.3 Standards IEC 61869-2 IEC 61869-2
7.4.4 Rated frequency Hz 50 50
7.4.5 Nominal System Voltage kV rms 33 33
7.4.6 Highest System Voltage kV rms 36 36
7.4.7 System Neutral - Solidly/Resistively earthed Solidly earthed
7.4.8 Rated short time thermal current I (3 sec) kA 25 25
7.4.9 Rated Load Current A 1600 1600
7.4.10 Rated peak current kA peak 65 65
7.4.11 Insulation level – primary winding
7.4.11.1 a) Power frequency withstand voltage - one kV rms Refer to Chpt 2, Sect 70
min 1
7.4.11.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 170
1
7.4.11.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect N/A
1
7.4.12 One minute power frequency withstand kV rms Bidder to Supply 3
voltage- secondary
7.4.13 Min. Creepage distance mm/kV 31 31
7.4.14 Radio interference voltage Bidder to Supply As per IEC
7.4.15 Number of cores 5 5
7.4.16 Core Details
7.4.16.1 Transformer Differential 1600:1; 1600:1;
5P20 20VA 5P20 20VA
7.4.16.2 Metering 1250:1; 1250:1;
1FS5 10VA 1FS5 10VA
7.4.16.3 OC/EF 1600:1; 1600:1;
5P20 20VA 5P20 20VA
7.4.16.4 Future Core 1600:1; 1600:1;
5P20 20VA 5P20 20VA
7.4.16.5 Future Core 1600:1; 1600:1;
5P20 20VA 5P20 20VA
7.4.17 Enclosure protection for the secondary IP 56 IP 55
terminal box
7.4.18 Secondary terminal box Cast aluminium or Mild Steel
Mild steel
Technical Data Sheet for Instrument transformers
VOLTAGE TRANSFORMERS – 88 KV (SHERWOOD)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.5.1 Service conditions Outdoor Outdoor
7.5.2 Type Oil filled, metallic top tank Oil filled, metallic top
type with silicone tank type with silicone bushing.
bushing.
7.5.3 Standards IEC 44 IEC 60044-1
7.5.4 Rated frequency Hz 50 50
7.5.5 Nominal System Voltage kV rms 88/√3 88/√3
7.5.6 Highest System Voltage kV rms 123/√3 123/√3
7.5.7 Ratio 88/√3 kV: 110/√3 V 88/√3 kV : 110/√3kV
7.5.8 Rated primary voltage 88/√3 kV 88/√3
7.5.9 Rated secondary windings 110/√3 V 110/√3kV
7.5.10 System Neutral - Solidly Grounded Solidly Grounded
7.5.11 Rated short time thermal current kA 25 NA
I (3 sec)
7.5.12 Rated peak current kA peak 63 NA
7.5.13 Insulation level – primary winding
7.5.13.1 a) Power frequency withstand voltage - one min kV rms Refer to Chpt 2, Sect 1 275

7.5.13.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 650
7.5.13.2 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 NA
7.5.13.4 d) One minute power frequency withstand kV rms Refer to Chpt 2, Sect 1 3
voltage-
secondary
7.5.14 Min. Creepage distance mm/kV 31 31
7.5.15 Instrument security factor Bidder to Supply </=5
7.5.16 Maximum secondary resistance Bidder to Supply </=5
7.5.17 Radio interference voltage Bidder to Supply < 2500µV
7.5.18 Rated Voltage Factor 1.2 1.2
7.5.19 Number of cores 1 1
7.5.20 Core Details
7.5.20.1 Metering Class 1, 50/100 VA Class 1, 50/100 VA
7.5.4 Enclosure protection for the secondary terminal IP 56 IP 56
box
7.5.5 Secondary terminal box Cast aluminium or Mild Mild Steel
steel
Technical Data Sheet for Instrument transformers
VOLTAGE TRANSFORMERS – 33 KV (ORANGE GROVE)
Item Particulars Unit Minimum Guaranteed
Requirements Particulars
7.6.1 Service conditions Outdoor Outdoor
7.6.2 Type Oil filled, metallic top tank type Oil filled, metallic top tank type
with silicone bushing. with silicone bushing.
7.6.3 Standards IEC 61869-3 IEC 61869-3
7.6.4 Rated frequency Hz 50 50
7.6.5 Nominal System Voltage kV rms 33/√3 33/√3
7.6.6 Highest System Voltage kV rms 36/√3 36/√3
7.6.7 Ratio 33/√3 kV : 33/√3 kV : 110/√3kV
110/√3 V
7.6.8 Rated primary voltage 33/√3 kV 33/√3
7.6.9 Rated secondary voltage 110/√3 V 110/√3kV
7.6.1 System Neutral - Solid
7.6.11 Rated short time thermal current I (3 sec) kA 25 NA
7.6.12 Rated peak current kA peak 65 NA
7.6.13 Insulation level – primary winding
7.6.13.1 a) Power frequency withstand voltage kV rms Refer to Chpt 2, Sect 1 70
- one min
7.6.13.2 b) Lightning impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 170
7.6.13.3 c) Switching impulse withstand voltage kV peak Refer to Chpt 2, Sect 1 NA
7.6.14 One minute power frequency withstand kV rms Refer to Chpt 2, Sect 1 3
voltage- secondary
7.6.15 Min. Creepage distance mm/kV 31 31
7.6.16 Instrument security factor 10 Bidder to Supply </= 5
7.6.17 Radio interference voltage Bidder to Supply </= 5
7.6.18 Rated Voltage Factor 1.9 1.9
7.6.19 Number of cores 2 1
7.6.20 Core Details
7.6.20.1 Protection (star configuration) Class 1, 100 VA Class 1, 100 VA
7.6.20.2 Protection (open delta configuration) Class 1, 100 VA Class 1, 100 VA
7.6.21 Enclosure protection for the secondary IP 56 IP 55
terminal box
7.6.22 Secondary terminal box Cast aluminium or Mild Steel
Mild steel