Complementary Tripping curves

technical information

t The following curves show the total fault current breaking time, depending on its
DB124179

amperage. For example: based on the curve on page 3, an iC60 circuit breaker
of curve C, 20 A rating, will interrupt a current of 100 A (5 times the rated current In)
Thermal tripping limits in:
bb 0.45 seconds at least
bb 6 seconds at most.

The circuit breakers’ tripping curves consist of two parts:


bb tripping of overload protection (thermal tripping device): the higher the current, the
shorter the tripping time
Electromagnetic bb tripping of short-circuit protection (magnetic tripping device): if the current exceeds
tripping limits the threshold of this protection device, the breaking time is less than 10 milliseconds.
For short-circuit currents exceeding 20 times the rated current, the time-current
curves do not give a sufficiently precise representation. The breaking of high short-
circuit currents is characterized by the current limiting curves, in peak current and in
energy. The total breaking time can be estimated at 5 times the value of the ratio
(I2t)/(Î)2.
min. max.
Verification of the discrimination between two
circuit breakers
In By superimposing the curve of a circuit breaker on that of the circuit breaker installed
upstream, one can check whether this combination will be discriminating in cases of
overload (discrimination for all current values, up to the magnetic threshold of the
upstream circuit breaker). This verification is useful when one of the two circuit
breakers has adjustable thresholds; for fixed-threshold devices, this information is
provided directly by the discrimination tables.
To check discrimination on short circuit, the energy characteristics of the two devices
must be compared.

2 Version : 2.9 05/09/2014 CA908024E


Complementary Tripping curves
technical information According to IEC/EN 60898-1 standards

Alternative current 50/60 Hz


iC60a/N/H/L
According to IEC/EN 60898-1 (reference temperature 30°C)

Curves B, C, D rating up to 4 A Curves B, C, D rating 6 A to 63 A


DB124180

DB124185
3600 s for I/In = 1.45 3600 s for I/In = 1.45
3600 s 3600 s
for for
I/In = 1.13 I/In = 1.13
1000 1000

60 s 60 s
100 for I/In = 2.55 100 for I/In = 2.55

10 10
t(s) t(s)

1 1s 1 1s
for for
I/In = 2.55 I/In = 2.55

0,1 0,1
B C D B C D

0,01 0,01
1 3...5 5...10 10...14
1
3...5 5...10 10...14
I / In I / In

C120N/H DPN, DPN N, DPN H (circuit-breaker and residual current device)


According to IEC/EN 60898-1 (reference temperature 30°C) According to IEC/EN 60898-1 (reference temperature 30°C)

Curves B, C, D Curves B, C, D
DB124207

DB124208

3600 s for I/In = 1.45 3600 s for I/In = 1.45


3600 s 3600 s
for for
I/In = 1.13 I/In = 1.13
1000 1000

60 s 60 s
100 for I/In = 2.55 100 for I/In = 2.55

10 10
t(s) t(s)

1 1s 1 1s
for for
I/In = 2.55 I/In = 2.55

0,1 0,1
B C D B C D

0,01 0,01
1 1 3...5 5...10 10...14
3...5 5...10 10...14
I / In I / In

CA908024E Version : 2.9 05/09/2014 3


Complementary Tripping curves
technical information According to IEC/EN 60898-1 standards

Alternative current 50/60 Hz


iK60 C60
According to IEC/EN 60898-1 (reference temperature 30°C) According to IEC/EN 60898-1 (reference temperature 30°C)

Curves B, C Curves B, C, D
DB124209

DB405822
3600 s for I/In = 1.45 3600 s for I/In = 1.45
3600 s 3600 s
for for
I/In = 1.13 I/In = 1.13
1000 1000

60 s 60 s
100 for I/In = 2.55 100 for I/In = 2.55

10 10
t(s) t(s)

1 1s 1 1s
for for
I/In = 2.55 I/In = 2.55

0,1 0,1
B C B C D

0,01 0,01
1 1 3...5 5...10 10...14
3...5 5...10
I / In I / In

4 Version : 2.9 05/09/2014 CA908024E


Complementary Tripping curves
technical information According to IEC/EN 60947-2 standards

Alternative current 50/60 Hz


iC60N/H/L MCB and iC60 RCBO
According to IEC/EN 60947-2 for MCB and IEC/EN 61009-1 for RCBO (reference temperature 50°C)

Curves B, C, D rating up to 4 A Curves Z, K rating up to 4 A


DB124181

DB124182
3600 s for I/In = 1.3
3600 s for I/In= 1.3 3600 s
3600 s for
for I/In = 1.05
I/In = 1.05 1000
1000

100
100

10 10

t(s) t(s)

1
1

0,1 0,1
B C D Z K

0,01 0,01
1 1
4±20% 8±20% 12±20% 3±20% 12±20%
I / In I / In

Curves B, C, D rating 6 A to 63 A Curves Z, K rating 6 A to 63 A


DB124186

DB124187

3600 s for I/In = 1.3


3600 s for I/In = 1.3 3600 s
3600 s for
for I/In = 1.05
I/In = 1.05 1000
1000

100
100

10 10

t(s) t(s)

1
1

0,1 0,1
B C D Z K

0,01 0,01
1 1
4±20% 8±20% 12±20% 3±20% 12±20%
I / In I / In

CA908024E Version : 2.9 05/09/2014 5


Complementary Tripping curves
technical information According to IEC/EN 60947-2 standards

Alternative current 50/60 Hz


Reflex iC60N/H NG125a/N/H/L
According to IEC/EN 60947-2 (reference temperature 50°C) According to IEC/EN 60947-2 (reference temperature 40°C)

Curves B, C, D Curves B, C, D
DB124210

DB124211
3600 s for I/In= 1.3 3600 s for I/In = 1.3
3600 s 3600 s
for for
I/In = 1.05 I/In = 1.05
1000 1000

100 100

10 10
t(s) t(s)

1 1

0,1 0,1
B C D B C D

0,01 0,01
1 1
4±20% 8±20% 12±20% 4±20% 8±20% 12±20%
I / In I / In

C60
According to IEC/EN 60947-2 (reference temperature 50°C)

Curves B, C, D
DB405823

3600 s for I/In= 1.3


3600 s
for
I/In = 1.05
1000

100

10
t(s)

0,1
B C D

0,01
1
4±20% 8.5±20% 12±20%
I / In

6 Version : 2.9 05/09/2014 CA908024E


Complementary Tripping curves
technical information According to IEC/EN 60947-2 standards

Motor curve
iC60L-MA NG125L-MA
According to IEC/EN 60947-2 According to IEC/EN 60947-2

Curve MA Curve MA
DB124190

DB124212
1000 1000

100 100

10 10
t(s) t(s)

1 1

0,1 0,1
MA MA

0,01 0,01
1 1
12±20% 12±20%
I / In I / In

CA908024E Version : 2.9 05/09/2014 7


Complementary Tripping curves
technical information According to IEC/EN 60947-2 standards

Direct current
iC60N/H/L
According to IEC/EN 60947-2 (reference temperature 50°C)

Curves B, C, D rating up to 4 A Curves Z, K rating up to 4 A


DB124184

DB124450
3600 s for I/In = 1.3
3600 s for I/In = 1.3 3600 s
3600 s for
for I/In = 1.05
I/In = 1.05 1000
1000

100 100

10 10

t(s) t(s)

1 1

0,1 0,1
B C D Z K

0,01 0,01
1 1
5.7±20% 11.3±20% 17±20% 4.2±20% 17±20%
I / In I / In

Curves B, C, D rating 6 A to 63 A Curves Z, K rating 6 A to 63 A


DB124188

DB124451

3600 s for I/In = 1.3


3600 s for I/In = 1.3 3600 s
3600 s for
for I/In = 1.05
I/In = 1.05 1000
1000

100 100

10 10

t(s) t(s)

1 1

0,1 0,1
B C D Z K

0,01 0,01
1 1
5.7±20% 11.3±20% 17±20% 4.2±20% 17±20%
I / In I / In

8 Version : 2.9 05/09/2014 CA908024E


Complementary Tripping curves
technical information According to IEC/EN 60947-2 standards

Direct current
C60H-DC C60
According to IEC/EN 60947-2 (reference temperature 25°C) According to IEC/EN 60947-2 (reference temperature 50°C)

Curves B, C, K Curves B, C, D
DB406178

DB405840
3600 s for I/In = 1.3 3600 s for I/In = 1.3
3600 s 3600 s
for for
I/In = 1.05 I/In = 1.05
1000 1000

100 100

10 10

t(s) t(s)

1 1

0.1 0.1
B C D
B C K

0.01 0.01
1 1
3...7 10...14 5.7±20% 12±20%
7...10 17±20%
I / In I / In

NG125a/N/H/L
According to IEC/EN 60947-2 (reference temperature 40°C)

Curves B, C, D
DB124184

3600 s for I/In = 1.3


3600 s
for
I/In = 1.05
1000

100

10
t(s)

0,1
B C D

0,01 1
5.7±20% 11.3±20% 17±20%
I / In

CA908024E Version : 2.9 05/09/2014 9


Complementary Tripping curves
technical information Coordination with loads

The circuit-breaker characteristics chosen depend on the type of load downstream of


the installation.
The rating depends on the size of the cables to be protected and the curves depend
on the load inrush current.
Product selection according to the load inrush current
When certain "capacitive" loads are switched on, very high inrush currents appear
during the first milliseconds of operation. The following graphs show the average
non-tripping curves of our products for this time range (50 μs to 10 ms).

iC60
DB124249 10

Curve D
Curve B
1

t(ms)

0,1

Curve C

0,01
1 10 100 1000
Ipeak/In

NG125 / C120
10
DB124250

Curve D
Curve B

t(ms)

0,1

Curve C

0,01
1 10 100 1000
Ipeak/In

This information allows us to select the most appropriate product, according to the
load specifications: curve and rating.

Example
10
When an iC60 is used with a load with current peaks in the order of 200 In during the
DB124249

Curve D
first 0.1 millisecond, a curve C or D product must be installed.
Curve B
1

t(ms)
DB124251

0,1

Curve C

0,1
0,01
1 10 100 1000
Ipeak/In

200

0,1

10 Version
100 : 2.9
200 05/09/2014
1000 CA908024E
Complementary Tripping curves
technical information

l u t i o n s
Evo

ng
li s

hi
ub
ep
his efor

T
p age ed b
must be remov

2.9 5/10/2014 Add DPN H page 3 JPM


2.8 3/09/2013 Add RCBO in iC60 AC table page 5 Sedoc
2.7 25/04/2013 Change IIn/ C60, (curve C60H-DC, C60) JPM
2.6 11/03/2013 Changed C60H-DC curves page 9 Sedoc
2.5 24/01/2013 Add page 10 "Coordination with loads" Sedoc
2.4 13/07/2012 Add C60 curves Sedoc
2.3 4/07/2012 Deleted C60 curves Sedoc
2.2 06/06/2012 Change texts and add C60 curves Sedoc
2.1 24/08/2011 Change Z, K curves pages 8 Sedoc
2.0 23/05/2011 InDesign CS5 Sedoc
1.2 16/04/2011 Add new curves C120, DPN, iK60, NG125, C60H-DC Sedoc
1.1 25/03/2011 New curves Sedoc
1.0 14/10/2009 Creation Sedoc
Indice Date Modification Name

CA908024E Version : 2.9 05/09/2014 11