Nonlinear Static Pushover Analysis of Existing and CFRP Retrofitted Shear


Wall Building Frame

Conference Paper · September 2013

CITATIONS READS

0 58

4 authors, including:

Muhammad Ajmal Muhammad Rahman


King Fahd University of Petroleum and Minerals King Fahd University of Petroleum and Minerals
9 PUBLICATIONS   5 CITATIONS    67 PUBLICATIONS   334 CITATIONS   

SEE PROFILE SEE PROFILE

Zekai Celep
Istanbul Technical University
90 PUBLICATIONS   789 CITATIONS   

SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Research study View project

Effect of Nanomaterials on cement slurry under HPHT conditions View project

All content following this page was uploaded by Muhammad Ajmal on 16 February 2017.

The user has requested enhancement of the downloaded file.


Nonlinear Static Pushover Analysis of Existing and CFRP
Retrofitted RC Shear Wall Frame

Muhammad Ajmal1, Muhammad K.Rahman2, Mohammed H.Baluch1 and Zekai Celep3


1
Department of Civil Engineering, King Fahd University of Petroleum and Minerals, Dhahran, Saudi
Arabia
2
Research Institute, King Fahd University of Petroleum and Minerals, Dhahran, Saudi Arabia
3
Department of Civil Engineering, Istanbul Technical University, Istanbul, Turkey

ABSTRACT: The seismic events in Saudi Arabia in 2009, in the Western Region, have led to
concerns about safety and vulnerability of reinforced concrete buildings, which were designed
only for gravity loads in the past, devoid of any ductile detailing of joints. In this study, a
nonlinear static pushover analysis of eight-story reinforced concrete shear wall frame of a
building in Madinah was carried out before and after retrofitting of the building. The static
pushover analysis was carried out using SAP2000 incorporating inelastic material behavior of
concrete and steel. Moment curvature and P-M interactions of frame members were obtained by
cross sectional fiber analysis using the software XTRACT. The shear walls were modeled using
shell element and mid-pier approach. The damage modes include a sequence of yielding leading
to failure of the members, and structural levels were obtained for the target displacement under
the expected design earthquake. Retrofitting of the existing frame is done based on the demand
displacement of the existing frame obtained using FEMA356 capacity spectrum method (CSM).
The deficient columns were retrofitted with CFRP jacketing and the length of existing shear
walls was increased to enhance the seismic response capacity of the building. The seismic
displacement response of the retrofitted frame obtained using pushover analysis shows a
significant increase in the lateral load capacity of the building.

1 INTRODUCTION
In the 80’s and 90‘s most of the RC frames in seismically active areas of Saudi Arabia were
designed only for gravity load and therefore, they have limited lateral load resistance and are
susceptible to column-side sway or soft-story mechanisms under earthquake effects. For high-
rise buildings, lateral forces due to wind loads were considered, however. Also non ductile
detailing practice employed in these structures makes them prone to potential damage and
failure during earthquake. The nonlinear static pushover analysis for seismic design and
evaluation is being implemented in many codes and is being used to evaluate the seismic
response of the existing and retrofitted frame.
In this paper, a case study involving seismic evaluation and retrofitting of a typical eight storey
reinforced concrete building in the city of Madinah in Saudi Arabia is presented. The building is
3-D reinforced concrete frame-shear wall structure A typical frame of the building with shear
wall is considered for investigations. The seismic displacement response of the existing and the
retrofitted frame are obtained using the method of pushover analysis. The static pushover
analysis was carried out using SAP2000 incorporating inelastic material behavior for concrete
and steel, and moment curvature and P-M interactions of frame members obtained by cross
sectional fiber analysis using the software XTRACT.

2 OUTLINE OF BUILDING
The structure is an existing building located in Madinah, Saudi Arabia, constructed in 1996. The
building has eight stories with a typical storey height 3.2 m for five storeys and remaining three
storey heights are 4.2 m, 2.4 m and 5 m, respectively. Plan area of the building is 40 m x 40 m.
The building has a dome at the roof level with reinforced concrete frames, elevator shafts and
ribbed and flat slab systems at different floor levels. From the available design data, the strength
of concrete and steel reinforcement are 30 MPa and 420 MPa, respectively. The loading for the
building includes; self-weight of members, superimposed load of 1.44 KN/m2 for floors and
1.93 KN/m2 for roof. Ad live load of 4.8 KN/m2 for floors and 2.4 KN/m2 for roof. The building
is located in the Seismic Zone 3 as per SBC-301 and Zone 2B as per UBC-1997, with site class
D (stiff soil) and Building Importance Coefficient (I) equal to 1.25.A plan for building and shear
wall frame used in this investigation is shown in Figures 1 and 2. The accidental eccentricity is
ignored in the seismic loading in order to directly observe the lateral load effect on the walls.

Figure 1: Plan of Building

Figure 2: Model of Frame Selected for Investigation


3 MODELING OF THE RC FRAME
Column and beams are modeled using line elements. The shear walls are modeled using
smeared multi-layer shell elements and mid-pier approach. The multi-layer shell element is
based on the principles of composite material mechanics. Mid pier approach is based on line
elements where shear wall is taken as equivalent mid-pier and rigid beams.
To analyze the cross-sections, Mander confined and unconfined concrete model (1988) and
elasto-plastic steel model with strain hardening were used for existing members and Lam &
Teng CFRP confined concrete model were utilized to model retrofitted members. XTRACT
(2007) software is utilized to determine the moment-rotation curves for beams and PMM
interaction curves for columns.

4 PUSHOVER ANALYSIS OF EXISTING RC FRAME


The nonlinear analysis of the building is performed using SAP2000 (CSI, 2009). The nonlinear
properties for columns and beams are assumed to be a plastic P-M-M hinge and one component
plastic moment hinge, respectively. The user defined plastic hinges are utilized. The axial force
for columns, and shear force for beams is considered from a combination of dead and live loads
(D+0.25L).The pushover analysis is carried in both positive and negative x-directions. The
pushover curves for the existing frame with x-directions are shown in Figure 3.

Figure 3: Pushover Curves for Existing Frame in Positive and Negative X-Directions

5 PEROFMANCE EVALUATION OF EXISTING FRAME


Performance point of existing typical frame is obtained using FEMA-356 Capacity Spectrum
Method (CSM). The base shear and displacement performance point of existing frame in
positive and negative x-directions is given in Table 1.
Table 1: Base Shear and Displacement at Performance Point
Directions Base shear (kN) Displacement (m)
Positive x 4076 0.08
Negative x 4228 0.077
From the pushover analysis of the existing frame it was observed that top columns are failing in
tension because of low axial load and high moments acting on columns due to lateral loads
Also, it was observed that at low level of displacement most of the beams yield which is a clear
indication that beams are designed purely for gravity loads. It can also be seen that at demand
displacement shear walls are also failing due to crushing of concrete and yielding of steel.
Figures 4 and 5 show the formation of hinges in the frame from the movement in the positive
and negative x-directions. Figures 6 and 7 shows that the crushing of concrete occurs on the
compression side and yielding of steel occurs on the tension side of shear wall at the demand
displacement.

a) Positive x-direction b) Negative x-direction

Figure 4: Hinges Formation at Demand Displacement for shell element model

a) Positive x-direction b) Negative x-direction

Figure 5: Hinges Formation at Demand Displacement for mid pier approach


a) Positive x-direction b) Negative x-direction

Figure 6: Crushing of Concrete at the Base of Shear Wall at Demand Displacement

a) Positive x-direction b) Negative x-direction

Figure 7: Yielding of Steel at the Base of Shear Wall at Demand Displacement

*Note: Stresses are in MPa

6 RETROFITTING SCHEME
From the pushover analysis of existing frame, it is clear that at performance point the shear
walls are failing due to crushing of concrete and hinges are formed in top storey columns. After
reviewing various options, it was found that retrofitting of shear walls should be done by
increasing the length of shear walls using high strength concrete (HSC) (availability of space is
not a problem) and jacketing top columns with CFRP. Shear walls are extended 1.2 m using
HSC of 45 MPa. Figure 8 shows the retrofitting schemes for shear wall and columns.
Figure 8: Retrofitting Strategy for Existing Frame

7 PUSHOVER ANALYSIS OF RETROFITTED FRAME


Pushover analysis has been carried out following the retrofitting of the frame. Figure 9 shows
the pushover analysis curves for the existing and retrofitted frame. Figure 9 shows the
significant increase in lateral load capacity of the existing frame after retrofitting. The proposed
scheme reduces significantly the lateral displacement. Figures 10 and 11 show the inter-storey
drift ratio (IDR) and total drift of the existing and retrofitted frame.

Figure 9: Pushover Analysis of Existing and Retrofitted Frame


Figure 10: Inter Storey Drift Ratio for Existing and Retrofitted Frame model

Figure 11: Total Storey drift of existing and retrofitted frame at demand displacement
From Figures10 and 11, it can be seen that inter-storey drift ratio and total storey drift of the
existing shear wall frame is high which may cause damage to the structural and nonstructural
components of the frame. Collapse of frame may occur due to excessive inter-storey drift
because excessive inter-storey drift often results from the local concentration of deformation at
a particular “weak storey”. After retrofitting, inter-storey drift and total storey drift reduces
which lowers the seismic vulnerability of the frame under design earthquake.

8 COMPARISON OF HINGE FORMATION IN EXISTING AND RETROFITTED


FRAME AT DEMAND DISPLACEMENT

a) Existing Frame b) Retrofitted Frame


Figure 12: Hinge Formation in the Positive x - direction at Demand Displacement for shell element model
a) Existing Frame b) Retrofitted Frame
Figure 13: Hinge Formation in the Negative x - direction at Demand Displacement for mid-pier model
Figures 12 and 13 clearly show that after strengthening of existing frame there is no flexural
hinge in top storey columns which were failing earlier. Also most of the beams which were
yielded previously are not yielding after retrofitting. It is also observed that after retrofitting,
bottom storey columns start yielding. Figures 14 and 15 clearly show the effect of retrofitting of
existing frame as there is no yielding of steel and crushing of concrete at the base of the shear
wall in contrast to the conditions in the non-retrofitted frame.

a) Existing Frame b) Retrofitted Frame


Figure 14: Stresses in Steel at Base of Shear Wall

a) Existing Frame b) Retrofitted Frame


Figure 15: Stresses in Concrete at Base of Shear Wall

*Note: Stresses are in MPa


9 CONCLUSIONS
Pushover analysis of a typical shear wall frame of building in the city of Madinah shows that the
frame is deficient to resist seismic loading at the expected design earthquake. Formation of
hinges clearly shows that the members of the building are designed purely for gravity loads, and
the building behaves in a non-ductile manner because almost all the seismic load is carried by
the shear walls at very small displacement and hinges start forming in shear walls. Retrofitting
of existing shear wall frame by the extension of shear walls using high strength concrete and
CFRP jacketing of the columns results in significant increase in lateral load capacity of the
frame. No flexural hinges are found in top storey columns which were originally failing at
demand displacement. Inter-storey drift ratio of the retrofitted shear wall frame is significantly,
reduced decreasing the seismic vulnerability.

10 ACKNOWLEDGEMENT
The study is being funded by King Fahd University of Petroleum & Minerals under Project
Number IN101028. The support of the Civil Engineering Department and Center for
Engineering Research Institute at KFUPM is gratefully acknowledged. The authors
acknowledge the support provided by Istanbul Technical University and Earthquake
Engineering Center to the KFUPM graduate students involved in this project.

11 REFERENCES
CSI SAP2000, ‘Static and Dynamic Finite Element Analysis of Structures 14.0’, Computers and
Structures, Inc., (Berkeley, California, 2009).
FEMA 356, ‘Pre-standard and Commentary for the Seismic Rehabilitation of Buildings’, (Reston,
Virginia, 2002).
Lam, L and Teng, JG, ‘Design-oriented Stress-Strain Model for FRP-confined Concrete’, Construction
and Building Materials, (2003).
Mander, JB, Priestley, M.J.N and Park, R, ‘Theoretical Stress–Strain Model for Confined Concrete’,
Journal of the Structural Division, ASCE 114 1804–1826 (1988).
SBC 301, ‘Saudi Building Code for Load and Forces Requirements’, SBC-301, (Saudi Arabia, 2007).
XTRACT, ‘Cross Section Analysis Program for Structural Engineers’, IMBSEN & Associates, Inc.,