CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING

DESIGN OF FOOTING

Isolated Footing

Input Values

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Footing Geomtery

Design Type : Calculate Dimension


Footing Thickness (Ft) : 300.000mm
Footing Length - X (Fl) : 1000.000mm
Footing Width - Z (Fw) : 1000.000mm
Eccentricity along X (Oxd) : 0.000mm
Eccentricity along Z (Ozd) : 0.000mm

Column Dimensions

Column Shape : Rectangular


Column Length - X (Dcol) : 0.300m
Column Width - Z (Bcol) : 0.400m

Design Parameters

Concrete and Rebar Properties

Unit Weight of Concrete : 23.500kN/m3


Strength of Concrete : 15.000N/mm2
Yield Strength of Steel : 276.000N/mm2
Minimum Bar Size : #12
Maximum Bar Size : #16
Pedestal Minimum Bar Size : #12
Pedestal Maximum Bar Size : #32
Minimum Bar Spacing : 50.000mm
Maximum Bar Spacing : 200.000mm
Pedestal Clear Cover (P, CL) : 50.000mm
Bottom Footing Clear Cover (F, CL) : 50.000mm

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Soil Properties

Soil Type : Drained


Unit Weight : 24.500kN/m3
Soil Bearing Capacity : 100.000kN/m2
Soil Bearing Capacity Type: Gross Bearing Capacity
Soil Surcharge : 0.000kN/m2
Depth of Soil above Footing : 0.000mm
Cohesion : 0.000kN/m2

Sliding and Overturning

Coefficient of Friction : 0.500


Factor of Safety Against Sliding : 1.500
Factor of Safety Against Overturning : 1.500

Global Settings

Top Reinforcement Option : Always calculate based on self weight


Concrete Design Option : Gross Pressure
Top Reinforcement Factor : 1.000
------------------------------------------------------

Design Calculations

Footing Size

Initial Length (Lo) = 1.000m


Initial Width (Wo) = 1.000m

Load Combination/s- Service Stress Level


Load Load Soil Self
Combination Load Combination Title Combination Bearing Weight
Number Factor Factor Factor
3 1.2DL + 1.6LL 1.00 1.00 1.00
Load Combination/s- Strength Level

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Load Load Soil Self


Combination Load Combination Title Combination Bearing Weight
Number Factor Factor Factor
3 1.2DL + 1.6LL 1.00 1.00 1.00
Applied Loads - Service Stress Level
Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
3 168.907 2.110 -3.692 -1.666 -0.812

Applied Loads - Strength Level


Axial Shear X Shear Z Moment X Moment Z
LC
(kN) (kN) (kN) (kNm) (kNm)
3 168.907 2.110 -3.692 -1.666 -0.812

Reduction of force due to buoyancy = 0.000kN


Effect due to adhesion = 0.000kN
Area from initial length and width, Ao =Lo X Wo = 1.000m2
Min. area required from bearing pressure, Amin =P / qmax = 1.760m2

Note: Amin is an initial estimation.


P = Critical Factored Axial Load(without self weight/buoyancy/soil).
qmax = Respective Factored Bearing Capacity.

Final Footing Size

Length (L2) = 1.450 m Governing Load Case : #3


Width (W2) = 1.450 m Governing Load Case : #3
Depth (D2) = 0.300 m Governing Load Case : #3
Depth is governed by Ultimate Load Case
(Service check is performed with footing thickness requirements from concrete check)
Area (A2) = 2.103 m2
Final Soil Height = 0.000 m
Footing Self Weight = 14.822 kN
Soil Weight On Top Of Footing
0.000 kN
=

Pressures at Four Corners

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Please note that pressures values displayed in tables below are calculated after
dividing by soil bearing factor

Pressure at
Pressure at Pressure at Pressure at Area of footing
corner 1
Load Case corner 2 (q2) corner 3 (q3) corner 4 (q4) in uplift (Au)
(q1)
(kN/m2) (kN/m2) (kN/m2) (m2)
(kN/m2)
3 90.0013 95.6876 84.7707 79.0845 0.000
3 90.0013 95.6876 84.7707 79.0845 0.000
3 90.0013 95.6876 84.7707 79.0845 0.000
3 90.0013 95.6876 84.7707 79.0845 0.000

If Au is zero, there is no uplift and no pressure adjustment is necessary. Otherwise,


to account for uplift, areas of negative pressure will be set to zero and the pressure
will be redistributed to remaining corners.

Summary of Adjusted Pressures at 4 corners Four Corners

Pressure at Pressure at Pressure at Pressure at


corner 1 (q1) corner 2 (q2) corner 3 (q3) corner 4 (q4)
Load Case (kN/m2) (kN/m2) (kN/m2) (kN/m2)
3 90.0013 95.6876 84.7707 79.0845
3 90.0013 95.6876 84.7707 79.0845
3 90.0013 95.6876 84.7707 79.0845
3 90.0013 95.6876 84.7707 79.0845

Check for stability against overturning and sliding

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Factor of safety against


- Factor of safety against sliding
overturning
Load
Along X- Along Z- About X- About Z-
Case Resultant
Direction Direction Direction Direction
No.
3 43.538 24.882 21.603 48.028 92.207

Critical Load Case And The Governing Factor Of Safety For Overturning And
Sliding - X Direction

Critical Load Case for Sliding along X-Direction : 3


Governing Disturbing Force : 2.110kN
Governing Restoring Force : 91.865kN
Minimum Sliding Ratio for the Critical Load Case : 43.538
Critical Load Case for Overturning about X-Direction : 3
Governing Overturning Moment : -2.773kNm
Governing Resisting Moment : 133.201kNm
Minimum Overturning Ratio for the Critical Load Case : 48.028

Critical Load Case And The Governing Factor Of Safety For Overturning And
Sliding - Z Direction

Critical Load Case for Sliding along Z-Direction : 3


Governing Disturbing Force : -3.692kN
Governing Restoring Force : 91.865kN
Minimum Sliding Ratio for the Critical Load Case : 24.882
Critical Load Case for Overturning about Z-Direction : 3
Governing Overturning Moment : -1.445kNm
Governing Resisting Moment : 133.201kNm
Minimum Overturning Ratio for the Critical Load Case : 92.207
Critical Load Case And The Governing Factor Of Safety For Sliding Along Resultant Direction
Critical Load Case for Sliding along Resultant 3
Direction :
Governing Disturbing Force : 4.252kN
Governing Restoring Force : 91.865kN
Minimum Sliding Ratio for the Critical Load Case : 21.603

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Compression Development Length Check


Development length skipped as column reinforcement is not specified in input (Column Dimnesion Task Pane)

Shear Calculation

Punching Shear Check

Total Footing Depth, D = 0.300m


Calculated Effective Depth, deff = D - Ccover - 0.5 * db = 0.244m

For rectangular column, = Bcol / Dcol = 1.333

Effective depth, deff, increased until 0.75XVc Punching Shear Force

Punching Shear Force, Vu = 153.115kN, Load Case # 3

From ACI Cl.11.12.2.1, bo for column= 2.376m

Equation 11-33, Vc1 = 932.205kN

Equation 11-34, Vc2 = 1138.734kN

Equation 11-35, Vc3 = 745.764kN

Punching shear strength, Vc = 0.75 X minimum of (Vc1, Vc2, Vc3) = 559.323kN


0.75 X Vc > Vu hence, OK

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

One-Way Shear Check

Along X Direction

(Shear Plane Parallel to Global X Axis)

From ACI Cl.11.3.1.1, Vc = 227.558kN

Distance along X to design for shear,


0.281m
Dx =

Check that 0.75 X Vc > Vux where Vux is the shear force for the critical load cases at
a distance deff from the face of the column caused by bending about the X axis.

From above calculations, 0.75 X Vc = 170.669 kN


Critical load case for Vux is # 3 37.398 kN
0.75 X Vc > Vux hence, OK

One-Way Shear Check

Along Z Direction

(Shear Plane Parallel to Global Z Axis)

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

From ACI Cl.11.3.1.1, Vc =


227.558 kN

Distance along X to design for shear, Dz = 0.331 m

Check that 0.75 X Vc > Vuz where Vuz is the shear force for the critical load cases at
a distance deff from the face of the column caused by bending about the Z axis.

From above calculations, 0.75 X Vc = 170.669 kN


Critical load case for Vuz is # 3 42.994 kN
0.75 X Vc > Vuz hence, OK

Design for Flexure about Z Axis

(For Reinforcement Parallel to X Axis)

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Calculate the flexural reinforcement along the X direction of the footing. Find the
area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.)
by Salmon and Wang (Ref. 1)

Critical Load Case # 3

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth deff= 0.244 m

Factor from ACI Cl.10.2.7.3 = 0.850

From ACI Cl. 10.3.2, = 0.02689

From ACI Cl. 10.3.3, = 0.02017

From ACI Cl. 7.12.2, = 0.00200


From Ref. 1, Eq. 3.8.4a, constant m = 21.647

Calculate reinforcement ratio for critical load case

Design for flexure about Z axis is


performed at the face of the column at a 0.875 m
distance, Dx =
Ultimate moment, 21.448 kNm

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Nominal moment capacity, Mn = 23.831 kNm

(Based on effective depth) Required = 0.00101

(Based on gross depth) x deff / Depth = 0.00082


Since ρ≤ ρmin ρmin Governs

Area of Steel Required, As = 870.000 mm2

Selected bar Size = #12


Minimum spacing allowed (Smin) = = 50.000mm
Selected spacing (S) = 150.000mm
Smin<= S <= Smax and selected bar size < selected maximum bar size...
The reinforcement is accepted.
According to ACI 318 Clause No- 10.6.4
Max spacing for Cracking Consideration = 446.066mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

#12 @ 150.000mm o.c.

Required development length for bars = =0.305 m

Available development length for bars, DL = 0.525 m


Try bar size # 12 Area of one bar = 113.097 mm2

Number of bars required, Nbar = 9

Because the number of bars is rounded up, make sure new reinforcement
ratio < ρmax

Total reinforcement area, As_total = Nbar X (Area of one bar) = 1017.869 mm2
deff = D - Ccover - 0.5 X (dia. of one bar) = 0.244 m

Reinforcement ratio, = 0.00288

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

From ACI Cl.7.6.1, minimum req'd clear distance between bars


Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 50.000mm
Provided Steel Area / Required Steel Area = 1.170

Check to see if width is sufficient to accomodate bars

Design for Flexure about X axis

(For Reinforcement Parallel to Z Axis)

Calculate the flexural reinforcement along the Z direction of the footing. Find the
area of steel required, A, as per Section 3.8 of Reinforced Concrete Design (5th ed.)
by Salmon and Wang (Ref. 1)

Critical Load Case # 3

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth deff= 0.232 m

Factor from ACI Cl.10.2.7.3 = 0.850

From ACI Cl. 10.3.2, = 0.02689

From ACI Cl. 10.3.3, = 0.02017

From ACI Cl.7.12.2, = 0.00200

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

From Ref. 1, Eq. 3.8.4a, constant m = 21.647

Calculate reinforcement ratio for critical load case

Design for flexure about X axis is


performed at the face of the column at a 0.525 m
distance, Dz =
Ultimate moment, 18.289 kNm

Nominal moment capacity, Mn = 20.321 kNm

(Based on effective depth) Required = 0.00095

(Based on gross depth) x deff / Depth = 0.00074


Since ρ≤ ρmin ρmin Governs

Area of Steel Required, As = 870.000 mm2

Selected Bar Size = #12


Minimum spacing allowed (Smin) = 50.000mm
Selected spacing (S) = 150.000mm
Smin<= S <= Smax and selected bar size < selected maximum bar size...
The reinforcement is accepted.
According to ACI 318 Clause No- 10.6.4
Max spacing for Cracking Consideration = 446.066mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

#12 @ 150.000mm o.c.

Required development length for bars = 0.305 m

Available development length for bars, DL = 0.475 m


Try bar size # 12 Area of one bar = 113.097 mm2

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Number of bars required, Nbar = 9

Because the number of bars is rounded up, make sure new reinforcement
ratio < ρmax

Total reinforcement area, As_total = Nbar X (Area of one bar) = 1017.869 mm2
deff = D - Ccover - 1.5 X (dia. of one bar) 0.232 m
=

Reinforcement ratio, = 0.00303

From ACI Cl.7.6.1, minimum req'd clear distance between bars


Cd = max (Diameter of one bar, 1.0" (25.4mm), Min. User Spacing) = 50.000mm
Provided Steel Area / Required Steel Area = 1.170

Check to see if width is sufficient to accomodate bars

Bending moment for uplift cases will be calculated based solely on selfweight, soil
depth and surcharge loading.

As the footing size has already been determined based on all servicebility load cases,
and design moment calculation is based on selfweight, soil depth and surcharge
only, top reinforcement value for all pure uplift load cases will be the same.

Design For Top Reinforcement Parallel to Z Axis

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Top reinforcement is calculated based on self weight of footing and soil

Calculate the flexural reinforcement for Mx. Find the area of steel required

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth deff= 0.232 m

Factor from ACI Cl.10.2.7.3 = 0.850

From ACI Cl. 10.3.2, = 0.02689

From ACI Cl. 10.3.3, = 0.02017

From ACI Cl. 7.12.2, = 0.00200

From Ref. 1, Eq. 3.8.4a, constant m = 21.647

Calculate reinforcement ratio for critical load case

Design for flexure about X


axis is performed at the face
0.525 m
of the column at a distance,
Dx =
Ultimate moment, 1.409 kNm

Nominal moment capacity,


1.565 kNm
Mn =

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

(Based on effective depth)


0.00007
Required =

(Based on gross depth) x deff / Depth = 0.00006


Since ρ≤ ρmin ρmin Governs

Area of Steel Required, As = 870.000 mm2


Total reinforcement area,
As_total = Nbar X (Area of one bar) = 904.779 mm2
Provided Steel Area / Required Steel Area = 1.040

Selected bar Size = #12


Minimum spacing allowed (Smin) = 50.000mm
Selected spacing (S) = 150.000mm
Smin<= S <= Smax and selected bar size < selected maximum bar size...
The reinforcement is accepted.
According to ACI 318 Clause No- 10.6.4
Max spacing for Cracking Consideration = 446.066mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

#12 @ 150.000mm o.c.

Design For Top Reinforcement Parallel to X Axis

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

Top reinforcement is calculated based on self weight of footing and soil

Calculate the flexural reinforcement for Mz. Find the area of steel required

The strength values of steel and concrete used in the formulae are in ksi

Bars parallel to X Direction are placed at bottom


Effective Depth deff= 0.244 m

Factor from ACI Cl.10.2.7.3 = 0.850

From ACI Cl. 10.3.2, = 0.02689

From ACI Cl. 10.3.3, = 0.02017

From ACI Cl.7.12.2, = 0.00200

From Ref. 1, Eq. 3.8.4a, constant m = 21.647

Calculate reinforcement ratio for critical load case

Design for flexure about Z


axis is performed at the face
0.575 m
of the column at a distance,
Dx =
Ultimate moment, 1.690 kNm

Nominal moment capacity,


1.878 kNm
Mn =

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER
CONSTRUCTION OF TWO STOREY RESIDENTIAL BUILDING
DESIGN OF FOOTING

(Based on effective
0.000079
depth)Required =

(Based on gross depth) x deff / Depth = 0.000064


Since ρ≤ ρmin ρmin Governs

Area of Steel Required, As = 870.000 mm2


Total reinforcement area,
As_total = Nbar X (Area of one bar) = 904.779 mm2
Provided Steel Area / Required Steel Area = 1.040

Selected bar Size = #12


Minimum spacing allowed (Smin) = 50.000mm
Selected spacing (S) = 150.000mm
Smin<= S <= Smax and selected bar size < selected maximum bar size...
The reinforcement is accepted.
According to ACI 318 Clause No- 10.6.4
Max spacing for Cracking Consideration = 446.066mm

Safe for Cracking Aspect.

Based on spacing reinforcement increment; provided reinforcement is

#12 @ 150.000mm o.c.

PREPARED BY: ENGR. MARK NEIL J. AGBANLOG


CIVIL ENGINEER