Você está na página 1de 4

The centrifugal governor is an early proportional control mechanism.

A control system manages, commands, directs, or regulates the behavior of other


devices or systems using control loops. It can range from a single home heating
controller using a thermostat controlling a domestic boiler to large Industrial
control systems which are used for controlling processes or machines.

For continuously modulated control, a feedback controller is used to automatically


control a process or operation. The control system compares the value or status of
the process variable (PV) being controlled with the desired value or setpoint (SP),
and applies the difference as a control signal to bring the process variable output
of the plant to the same value as the setpoint.

For sequential and combinational logic, software logic, such as in a programmable


logic controller, is used.

Contents
1 Open-loop and closed-loop control
2 Feedback control systems
3 Logic control
4 On�off control
5 Linear control
5.1 Proportional control
5.1.1 Furnace example
5.1.1.1 Underdamped
5.1.1.2 Overdamped
5.2 PID control
5.2.1 Derivative action
5.2.2 Integral action
5.2.3 Ramp up % per minute
5.3 Other techniques
6 Fuzzy logic
7 Physical implementation
8 See also
9 References
10 External links
Open-loop and closed-loop control
There are two common classes of control action: open loop and closed loop. In an
open-loop control system, the control action from the controller is independent of
the process variable. An example of this is a central heating boiler controlled
only by a timer. The control action is the switching on or off of the boiler. The
process variable is the building temperature.This controller applies heat for a
constant time regardless of the temperature of the building.

In a closed-loop control system, the control action from the controller is


dependent on the desired and actual process variable. In the case of the boiler
analogy, this would utilise a thermostat to monitor the building temperature, and
feed back a signal to ensure the controller output maintains the building
temperature to that set on the thermostat. A closed loop controller has a feedback
loop which ensures the controller exerts a control action to control a process
variable at the same value as the setpoint. For this reason, closed-loop
controllers are also called feedback controllers.[1]

Feedback control systems

Example of a single industrial control loop; showing continuously modulated control


of process flow.
A basic feedback loop
In the case of linear feedback systems, a control loop including sensors, control
algorithms, and actuators is arranged in an attempt to regulate a variable at a
setpoint (SP). An everyday example is the cruise control on a road vehicle; where
external influences such as gradients would cause speed changes, and the driver has
the ability to alter the desired set speed. The PID algorithm in the controller
restores the actual speed to the desired speed in the optimum way, without delay or
overshoot, by controlling the power output of the vehicle's engine.

Control systems that include some sensing of the results they are trying to achieve
are making use of feedback and can adapt to varying circumstances to some extent.
Open-loop control systems do not make use of feedback, and run only in pre-arranged
ways.

Logic control
Main article: Programmable logic controller
Logic control systems for industrial and commercial machinery were historically
implemented by interconnected electrical relays and cam timers using ladder logic.
Today, most such systems are constructed with microcontrollers or more specialized
programmable logic controllers (PLCs). The notation of ladder logic is still in use
as a programming method for PLCs.[2]

Logic controllers may respond to switches, light sensors, pressure switches, etc.,
and can cause the machinery to start and stop various operations. Logic systems are
used to sequence mechanical operations in many applications. PLC software can be
written in many different ways � ladder diagrams, SFC (sequential function charts)
or statement lists.[3]

Examples include elevators, washing machines and other systems with interrelated
stop-go operations. An automatic sequential control system may trigger a series of
mechanical actuators in the correct sequence to perform a task. For example,
various electric and pneumatic transducers may fold and glue a cardboard box, fill
it with product and then seal it in an automatic packaging machine. Programmable
logic controllers are used in many cases such as this, but several alternative
technologies exist.

On�off control
Main article: Bang�bang control
A thermostat can be described as a bang-bang controller. When the temperature, PV,
goes below a SP, the heater is switched on. Another example could be a pressure
switch on an air compressor. When the pressure, PV, drops below the threshold, SP,
the pump is powered. Refrigerators and vacuum pumps contain similar mechanisms.

Simple on�off control systems like these are cheap and effective.

Linear control
Linear control systems use linear negative feedback to produce a control signal to
maintain the controlled process variable (PV) at the desired setpoint (SP).

Proportional control
Main article: Proportional control

Step responses for a second order system defined by the transfer function
{\displaystyle H(s)={\frac {\omega _{n}^{2}}{s^{2}+2\zeta \omega _{n}s+\omega
_{n}^{2}}}} {\displaystyle H(s)={\frac {\omega _{n}^{2}}{s^{2}+2\zeta \omega
_{n}s+\omega _{n}^{2}}}}, where {\displaystyle \zeta } \zeta is the damping ratio
and {\displaystyle \omega _{n}} \omega _{n} is the undamped natural frequency.
Proportional control is a type of linear feedback control system in which a
correction is applied to the controlled variable which is proportional to the
difference between the desired value (setpoint - SP) and the measured value
(Process Value - PV). Two classic mechanical examples are the toilet bowl float
proportioning valve and the fly-ball governor.

The proportional control system is more complex than an on-off control system like
a bi-metallic domestic thermostat, but simpler than a proportional-integral-
derivative (PID) control system used in something like an automobile cruise
control. On-off control will work where the overall system has a relatively long
response time, but can result in instability if the system being controlled has a
rapid response time. Proportional control overcomes this by modulating the output
to the controlling device, such as a control valve at a level which avoids
instability, but applies correction as fast as practicable by applying the optimum
quantity of proportional gain.

A drawback of proportional control is that it cannot eliminate the residual SP-PV


error, as it requires an error to generate a proportional output. To overcome this
the PI controller was devised, which uses a proportional term (P) to remove the
gross error, and an integral term (I) to eliminate the residual offset error by
integrating the error over time to produce an "I" component for the controller
output.

In some systems there are practical limits to the range of the manipulated variable
(MV). For example, a heater can be off or fully on, or a valve can be closed or
fully open. Adjustments to the gain simultaneously alter the range of error values
over which the MV is between these limits. The width of this range, in units of the
error variable and therefore of the PV, is called the proportional band (PB) which
is the inverse of the proportional gain. While the gain is useful in mathematical
treatments, the proportional band is often used in practical situations.

Furnace example
When controlling the temperature of an industrial furnace, it is usually better to
control the opening of the fuel valve in proportion to the current needs of the
furnace. This helps avoid thermal shocks and applies heat more effectively.

At low gains, only a small corrective action is applied when errors are detected.
The system may be safe and stable, but may be sluggish in response to changing
conditions. Errors will remain uncorrected for relatively long periods of time and
the system is overdamped. If the proportional gain is increased, such systems
become more responsive and errors are dealt with more quickly. There is an optimal
value for the gain setting when the overall system is said to be critically damped.
Increases in loop gain beyond this point lead to oscillations in the PV and such a
system is underdamped.

Underdamped
In the furnace example, suppose the temperature is increasing towards a setpoint at
which, say, 50% of the available power will be required for steady-state. At low
temperatures, 100% of available power is applied. When the process value (PV) is
within, say 10� of the SP the heat input begins to be reduced by the proportional
controller. This implies a 20� proportional band (PB) from full to no power input,
evenly spread around the setpoint value. At the setpoint the controller will be
applying 50% power as required, but stray stored heat within the heater sub-system
and in the walls of the furnace will keep the measured temperature rising beyond
what is required. At 10� above SP, we reach the top of the proportional band (PB)
and no power is applied, but the temperature may continue to rise even further
before beginning to fall back. Eventually as the PV falls back into the PB, heat is
applied again, but now the heater and the furnace walls are too cool and the
temperature falls too low before its fall is arrested, so that the oscillations
continue.
The temperature oscillations that an underdamped furnace control system produces
are unacceptable for many reasons, including the waste of fuel and time (each
oscillation cycle may take many minutes), as well as the likelihood of seriously
overheating both the furnace and its contents.

Overdamped
Suppose that the gain of the control system is reduced drastically and it is
restarted. As the temperature approaches, say 30� below SP (A 60� proportional band
(PB) this time), the heat input begins to be reduced, the rate of heating of the
furnace has time to slow and, as the heat is still further reduced, it eventually
is brought up to setpoint, just as 50% power input is reached and the furnace is
operating as required. There was some wasted time while the furnace crept to its
final temperature using only 52% then 51% of available power, but at least no harm
was done. By carefully increasing the gain (i.e. reducing the width of the PB) this
overdamped and sluggish behavior can be improved until the system is critically
damped for this SP temperature. Doing this is known as 'tuning' the control system.
A well-tuned proportional furnace temperature control system will usually be more
effective than on-off control, but will still respond more slowly than the furnace
could under skillful manual control.

PID control

A block diagram of a PID controller

Effects of varying PID parameters (Kp,Ki,Kd) on the step response of a system.


Main article: PID controller
Apart from sluggish performance to avoid oscillations, another problem with
proportional-only control is that power application is always in direct proportion
to the error. In the example above we assumed that the set temperature could be
maintained with 50% power. What happens if the furnace is required in a different
application where a higher set temperature will require 80% power to maintain it?
If the gain was finally set to a 50� PB, then 80% power will not be applied unless
the furnace is 15� below setpoint, so for this other application the operators will
have to remember always to set the setpoint temperature 15� higher than actually
needed. This 15� figure is not completely constant either: it will depend on the
surrounding ambient temperature, as well as other factors that affect heat loss
from or absorption within the furnace.

To resolve these two problems, many feedback control schemes include mathematical
extensions to improve performance. The most common extensions lead to proportional-
integral-derivative control, or PID control.

Derivative action
The derivative part is concerned with the rate-of-change of the error with time: If
the measured variable approaches the setpoint rapidly, then the actuator is backed
off early to allow it to coast to the required level; conversely if the measured
value begins to move rapidly away from the setpoint, extra effort is applied�in
proportion to that rapidity�to try to maintain it.

Você também pode gostar