Table 12. Utilization Factor for Typical Luminaires of the Five Classifications of Lighting
Systems
Ceil-
70% 50% 30%
ing
Luminaires Type Walls 50% 30% 10% 50% 30% 10% 30% 10%
Room
Utilization Factors
Index
J 0.37 0.31 0.27 0.36 0.31 0.27 0.31 0.27
I 0.45 0.41 0.37 0.45 0.40 0.37 0.40 0.37
H 0.49 0.45 0.42 0.49 0.45 0.42 0.45 0.42
Direct 0 / 79
G 0.53 0.49 0.46 0.53 0.49 0.46 0.48 0.46
Maintenance Factor
F 0.56 0.53 0.49 0.55 0.52 0.49 0.51 0.49
Good.................0.75
E 0.61 0.58 0.53 0.60 0.57 0.55 0.56 0.55
Average............0.65
D 0.66 0.63 0.60 0.64 0.62 0.60 0.61 0.60
Poor..................0.55
C 0.67 0.65 0.62 0.66 0.64 0.62 0.63 0.61
B 0.71 0.68 0.66 0.69 0.67 0.65 0.66 0.64
A 0.72 0.70 0.67 0.71 0.68 0.67 0.67 0.66
J 0.27 0.25 0.19 0.26 0.22 0.16 0.20 0.18
I 0.35 0.29 0.26 0.33 0.28 0.25 0.27 0.24
H 0.37 0.34 0.30 0.36 0.32 0.29 0.30 0.28
Semi-direct 25 / 60 G 0.43 0.38 0.34 0.40 0.36 0.32 0.33 0.31
Maintenance Factor F 0.46 0.41 0.37 0.43 0.39 0.35 0.37 0.33
Good.................0.75 E 0.50 0.46 0.42 0.47 0.43 0.40 0.40 0.38
Average............0.65 D 0.55 0.50 0.46 0.51 0.47 0.44 0.44 0.42
Poor..................0.55 C 0.58 0.53 0.49 0.53 0.49 0.46 0.46 0.44
B 0.62 0.57 0.53 0.57 0.53 0.51 0.50 0.48
âÎÁྨ ÃÐáÇ¡ºéÒ¹ / Utilization Factor for Typical Luminaires of the Five Classifications of Lighting
Systems