Single busbar or double busbar?


by Bryan Johnson, ABB South Africa

Most switchgear installations used in industry with normal service conditions are based on single busbar arrangements. Compared to double
busbar switchgear, single busbar switchgear is definitely easier to use, readily understood by operators, requires less space, and the total cost of
installation is less (equipment, site procedures, maintenance, spares holding and space).

Typical installations consist of basic cubicle Double busbar switchgear cable connection for the incoming / feeder
types that can be combined together to form cable. Although a very stable system, that
The use of double busbar may be necessary
the required switchboard. Fig. 1 shows typical provides full redundancy, the cost of this
when some of the following features are
cubicles available. system can be prohibitive.
required:
Single busbar switchgear Systems connected to two separate circuit
• Operation of incoming circuit breakers
In a single busbar switchboard the busbar from non-synchronised systems breaker compartments, using a single circuit
can be split into sections, by means of a • Load shedding of feeder circuits with breaker.
bus tie / bus riser (commonly known as a bus a different level of importance during
This arrangement is achieved using the same
section). Although separate busbar sections emergency conditions
principles as described under a) above, so
exist, the switchgear classification will remain
• Flexibility during inspection and the cost of this design can be quite high;
a single busbar arrangement, as each
maintenance procedures without load
circuit (incoming or feeder) is connected to however, the cost of duplicating common
interruption
the busbar section where it is placed in the equipment such as circuit breakers can be
• Extension without switchgear shutdown.
switchgear arrangement. omitted. This system can provide on-load
Which double busbar system? transfer between busbars if a spare circuit
Fig. 2 shows two incoming circuits with
breaker is available. However, if no spare
cable voltage transformers, two feeder Double busbar systems are based on various
circuits, and a bus section with voltage / transfer circuit breaker is available this
different schemes. Below are some examples
transformers on each bus section. Each system may not provide the option of on-
of double busbar arrangements with a short
circuit contains its required circuit breaker, load transfer.
description of the arrangements and the
instrument transformers (CTs and VTs), earth
basic features of these systems: Systems connected to two separate circuit
switch and relay / control equipment. This type
breaker compartments, using either a single
of arrangement can be easily understood by Systems connected to two separate circuit
or two circuit breakers, in a double-tier
operators, with little or no reference to any breaker compartments, each fitted with a
arrangement.
additional documentation. If for any reason circuit breaker.
a cable or cubicle in any busbar section is This arrangement has the same functionality
damaged, the cable can be isolated from This system is achieved using single busbar
as described above, and is generally more
the busbar, or the busbar section can be switchgear connected in a back-to-back /
cost-effective than separate single busbar
isolated for repairs if required. front-to-front arrangement, with a common
switchgear connected back to back.

Systems connected to a common circuit


Advantages Disadvantages
breaker compartment, via disconnecting
switches.
Cost of equipment is less Flexibility of operations is reduced
Ease of use Load shedding is more complex This system is achieved using disconnecting
Requires less space Extension of the switchgear without de-energising is switches to connect the different busbars
not possible to a common circuit breaker. The cost
Cost of installation is less Non-synchronised systems may present a problem of this system is less prohibitive than that
Cost of maintenance and spares holding is less above, while providing the same level
of redundancy for the busbars and the
Table 1: Advantages and disadvantages of double busbar switchgear.
opportunity to switch between busbars
without load interruption.
Advantages Disadvantages
Systems, connected to a common circuit
Flexibility of operations is increased Cost of equipment is more
breaker compartment, by changing the
Load shedding is easier to achieve Operation is more complex
position of the circuit breaker or the circuit
Extension of the switchgear without de-energising Requires more space
breaker connections to connect to the
is possible
different busbars.
Non-synchronised systems can be used, to supply Cost of installation is more
outgoing circuits
This may be the most cost effective solution;
On load transfer is possible with certain double Cost of maintenance and spares holding is more
however, for this system, it is not possible to
busbar designs, such as the ABB UniGear ZS1 range
transfer the load between busbars without
Table 2: Advantages and disadvantages of double busbar switchgear. interrupting the supply

energize - July 2008 - Page 32


DISTRIBUTION
solution is fault levels, load shedding and/
or connection of different systems, then it
would stand to reason that the need for
full redundancy is reduced and a simpler
and more cost-effective design can be
used. The design selected should then
give consideration to the type of switching
devices that can be used, the ease of
operation, safety, and any requirement to
do on-load transfer.

The insert below shows a typical


arrangement available for the ABB UniGear
ZS1 double busbar switchgear, described
under d) above. With this design, the circuit
breaker can be connected to any busbar,
and load can be transferred (provided
from the same source) by first closing
the disconnector to the busbar to be
connected (both disconnectors closed)
and then opening the disconnector from
the busbar to be disconnected.

In the double busbar, this feature is built into


the disconnecting switch that transfers the
load between the busbars. This eliminates
the need for a bus-coupler switch, or load
transfer switch that couples both busbars
Fig. 1: Typical single busbar cubicles available. together when doing on-load changeover.
However, as a principle, users may not
want to use disconnecting switches alone,
All busbar systems described above provide also lost. Users should therefore consider and include a bus-coupler to connect
for full busbar redundancy, i.e. physical the level of redundancy required, with the the busbars together before attempting
isolation between source busbar systems operating procedures, when deciding which on load transfer. The switchgear, using
a), b), c), and d) have a distinct advantage solution is most appropriate. disconnecting switch principles, provides
over system e) in that the incoming or feeder a wide range of switching arrangements,
Considerations at a cost-effective price, whilst not
cubicles can be transferred between busbars
without load interruption. Fig. 3 shows the The main consideration is the level of compromising on useful features such as
relationship between cost, redundancy and redundancy required, followed by the on load transfer.
functionality. It can be seen that the higher operating philosophy. For full redundancy, In many instances, single busbar switchgear
the cost of the switchgear, the higher the with on-load transfer, a back-to-back solution can provide a suitable solution, a high
redundancy. It can also be seen that below with all the equipment duplicated would level of security of supply, and a practical
a certain cost the option of load transfer is suffice. If the reason for a double busbar solution. Users in process industries and
utilities such as power generation, where
security of supply is most important, opt in
many instances for single busbar designs. It
is generally realised by users that, although
double busbar switchgear provides for
busbar redundancy, achieving full busbar
redundancy in a confined environment is
not always practical. For example, if one
busbar on a double busbar system were to
fail, the system could be easily changed
over to a reserve or stand-by busbar but
the switchgear, in all likelihood, would have
to be completely de-energised in order to
carry out repairs safely.

To provide for full redundancy, and


Fig. 2: Typical single busbar switchgear. safer conditions for maintenance and

energize - July 2008 - Page 34


Fig. 3: Relationship between cost, redundancy and load transfer options.

repairs, users opt for separate switchboards, A final word: users should take note of the
connected together with bus sections, or need to ensure that any switchgear meets Fig. 4: Typical arrangement for
back-to-back solutions. In instances where the requirements of the latest revision of the double busbar switchgear.

synchronised systems and double busbar applicable standards. Most manufacturers


systems are needed, preference is normally will test and provide proof of testing to these
given to switchgear in which load transfer standards. The standard that should be
standard and related type test certification
is possible. Only in rare circumstances, in considered, over and above the normal
may be out of date.
which load transfer is not required, do users specifications concerning switchgear, is the
opt for double busbar systems where on- IEC62271-200; any other standard quoted Manufacturers should be able to provide
load transfer is not possible. should be treated with caution as the test certification for the full fault level of the
switchboard, up to 1000 ms, classification
AFLR to the IEC62271-200 specification.
In short, this means the switchgear can
withstand the forces created during an
internal arc, at full fault level, for up to 1000
ms, and be accessible to operators from the
front, lateral and rear of the switchgear. Users
who do not specifically call for certification
to the latest IEC 62271-200 specification
may find themselves being presented with
switchgear that does comply with these
requirements, and thereby open themselves
up to litigation claims.

Switchgear is a sizeable investment, so the


choice of switchgear at the design stage is
critical to ensure the investment is well made,
will safely meet with the life expectancy of
the installation to the latest standards
applicable at the time of purchase, and
will provide the most appropriate flexibility
of operation.

Acknowledgement: This article was originally


published in ABB Technology Solutions
4/2007 and is republished with permission.

Contact Bryan Johnson,


ABB South Africa, Tel 011 878-8146,
Fig. 5: Example of disconnector switch in UniGear Z21 double busbar switchgear. bryan.johnson@za.abb.com v

energize - July 2008 - Page 36