Proposed Project Page:

Address of Project Project No.: 15-0001


Architect Designed: b
Column C08
TIMBER COLUMN V5.02 Demo User

Column: (Column C08) 2 / 90mm x 45mm MGP10 (Laminated)


Comp: Nc(dl)* = 4.05kN < øNc(dl) = 19.01kN, Nc* = 6.60kN < øNc = 31.35kN OK (0.21,0.21)
Ncw* = 3.60kN < øNcw = 33.35kN OK (0.11)
Tension: Nt(dl)* = 0.00kN < øNt(dl) = 24.89kN, Nt* = 0.00kN < øNt = 41.04kN

Combined: Refer table below OK (0.41)

Geometry (For a primary building member)

Category = 2 (1) House, (2) Primary building elements, (3) Important


House = Y (Y)es,(N)o
Length (L) = 2700 mm
Strong axis eff. length (Lax) = 2700 mm Edge restrained = C (T)ension, (C)omp.
Weak axis eff. length (Lay) = 1200 mm, (C)ontinuous Bending (Layb) = 1200 mm
Effective length factor (g13) = 0.90 Studs in framing=0.9, Restrained both ends in pos.=1.0, Other cases - Table 3.2
Loadings
Compression Tension
Dead load (Ndl) = 3.00 kN Dead load (Ndl) = kN
Live load (Nll) = 2.00 kN Live load (Nll) = kN
Wind load (Nwl*) = kN (Comp.) Wind load (Nwl*) = kN (Tension)
Bending Mx* My*
Live Load Duration = Roof M(dl)* = 0.18 kNm
Duration (k1) = 0.94 Table 2.3 M* = 0.30 kNm
Long term LL factor (Ψl) = 0.00 Table 4.1, AS1170.0 Mw* = 0.16 kNm
Combination factor (Ψc) = 0.00 Table 4.1, AS1170.0

Nc(dl)* = 1.35*(Ndl+Ψl*Nll) = 4.05 kN Nt(dl)* = 1.35*(Ndl+Ψl*Nll) = 0.00 kN


Nc* = 1.2*Ndl+1.5*Nll = 6.60 kN Nt* = 1.2*Ndl+1.5*Nll = 0.00 kN
Ncw* = 1.2*Ndl + Nwl* + 1.5*Ψc*Nll = 3.60 kN Ntw* = 1.2*Ndl + Nwl + 1.5*Ψc*Nll = 0.00 kN

Axial capacity - Cl 3.3 & Cl 3.4

Member = 2 / 90mm x 45mm MGP10 Area (A) = 8100 mm²


Description = MGP10 seasoned softwood Section modulus (Zx) = 122 x10³ mm³
Design depth (dD) = 90 mm Section modulus (Zy) = 61 x10³ mm³
Design width (dW) = 90 mm Stiffness (Ix) = 5.5 x10⁶ mm⁴
Modulus of elasticity (E) = 10000 MPa - Table H3.1
Strength reduction factor (ø) = 0.7 Table 2.1
S3x =min(g13*L/dD & Lax/dD) = 27.00 k12cx = 0.327 for ρc*S3x ≥ 20 - Cl 3.3.3
S4y = min(g13*L/dW & Lay/dW) = 13.33 k12cy = 0.889 for 10 < ρc*S4y ≤ 20 - Cl 3.3.3
Critical S = 27.00 k12 = 0.327 for ρc*S ≥ 20 - Cl 3.3.3
f'c = 18.0 MPa
øNc(dl) = ø*0.57*k4*k6*k12*f'c*A = 19.0 kN f't = 7.7 MPa
øNc = ø*k1*k4*k6*k12*f'c*A = 31.4 kN Material constant (ρc) = 0.92 (rc=0.45)
øNcw = ø*(k1=1)*k4*k6*k12*f'c*A = 33.4 kN Moisture factor (k4) = 1.00
øNt(dl) = ø*0.57*k4*k6*f't*A = 24.9 kN Temp. factor (k6) = 1.00
øNt = ø*k1*k4*k6*f't*A = 41.0 kN Size modifer (mod.c) = 1.00
øNtw = ø*(k1=1)*k4*k6*f't*A = 43.7 kN Size modifer (mod.t) = 1.00
Bending capacity - Cl 3.2

S1=1.25*dD/dW*(Lay/dD)⁰·⁵ = 4.56 For comp. edge restrained - Cl 3.2.3.2


k12 = 1.000 for ρb*S < 10 - Cl 3.2.4

øM(dl) = ø*(k1=0.57)*k4*k6*k9*k12*f'b*Zx = 0.94 kNm f'b = 17.0 MPa


øM = ø*k1*k4*k6*k9*k12*f'b*Zx = 1.55 kNm Material constant (ρb) = 0.72 (rb=0.45)
øMw = ø*(k1=1)*k4*k6*k9*k12*f'b*Zx = 1.65 kNm Duration factor (k1) = 0.94
øMy(dl) = ø*(k1=0.57)*k4*k6*k9*(k12=1)*f'b*Zy = 0.47 kNm Moisture factor (k4) = 1.00
øMy = ø*k1*k4*k6*k9*(k12=1)*f'b*Zy = 0.77 kNm Sharing factor (k9) = 1.14
øMwy = ø*(k1=1)*k4*k6*k9*(k12=1)*f'b*Zy = 0.82 kNm Size modifer (mod.b) = 1.00
Combined - Cl 3.5.1, Cl 3.5.2 & E5

Comp/Bend Nc(dl)* Nc* Nc(dl+wl)* Tension/Bend Nt(dl)* Nt* Nt(dl+wl)*


Out-of-plane 0.12 0.11 0.05 Out-of-plane 0.19 0.19 0.10
In-plane 0.41 0.40 0.21 In-plane 0.19 0.19 0.10

Deflection limits

Service class = N (1),(2),(3),(S)evere/Adverse,(N)ot applicable


Notes:
Double members:
Double members are considered laminated.
Refer to AS1684.2 Cl 2.3 for requirements of
vertical lamination.
Laminated = Y (Y)es,(N)o

Importance:
Category 1 House failure affecting < 25m², secondary building element
Category 2 Building, house failure affecting > 25m²
Category 3 Important

AS1684.1 - Design Criteria:


Table 3.2.5 states studs supporting concentrated
load has a moment of M = 0kNm.
For studs subject to lateral wind, design as a mullion.

Duration:
Storage and passage durations used
are based on intermediate durations from Table 2.3
and used with engineering judgement.

k4 factor:
Partial seasoning factor
Refer Cl 2.4.2.2 & 2.4.2.3 for more information.

k6 factor:
Refer Cl 2.4.3 if designing structures near coastal
regions of Queensland north of 25°S and all other
regions north of 16°S

Material constant:
Refer to Appendix E2
Bending ratio = 0.45
Compression ratio = 0.45

X-Axis Y-Axis
kN kN
øNc(dl) = 19.0 51.7
øNc = 31.4 85.3
øNcw = 33.4 90.7

Compression/Bending:
Refer 3.5(1) & 3.5(2)

Tension/Bending:
Refer 3.5(3) & 3.5(4)

Service class:
Service class defined in AS/NZS 1328.1 1998 Glued Laminated Structural Timber
1 - Domestic houses, Commerical Offices
2 - Open sheds, exposed beams under soffits, porches, laundries
3 - Marine structures, Bridges
S - Severe/Adverse requires specialist advice