Basic Objects
Reference Manual

800xA – AC800M Connect - Minerals Library

Version 5.1/4a

Based on Project Minerals Library, CoE Cement and Minerals


Prep. ATBPA / P.Topfmeyer 10.07.2009
Appr. ATBPA / M.Knabenhans 30.04.2010
Doc. kind Reference Manual Doc. Item

Title Basic Objects des. des.

800xA Minerals Library version 5.1/4a Resp. dept. CHIND / ATBPA


Document identity Lang. Rev. ind. Sheet 1
3BHS 161556 en R
ABB Switzerland Ltd No. of sh. 113
Template: Design Description_1,1_A4h_en_standard.dot; Filename: 02 Minerals Library Basic Objects 5p1s4a.docx; Print: 9/15/2013 10:02:00 PM; Save: 9/14/2013 4:34:00 PM; CHIND No. 3BHS102547 ZAB E01 Rev A. -; I-Q
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

CONTENT
1 SUMMARY ................................................................................................................ 5
2 COMMON DATA ....................................................................................................... 5
2.1 BASIC DESCRIPTION ..................................................................................... 5
2.2 CONTROL ....................................................................................................... 6
2.2.1 Library location .................................................................................... 6
2.2.2 Control modes ..................................................................................... 6
2.2.3 PCC, Interlock Bus (Process Control Connection) ............................... 6
2.2.3.1 PCC Bus concept ................................................................ 6
2.2.3.2 Basic Functions of PCC ....................................................... 6
2.2.3.3 PCC Interlock Parameter Description .................................. 7
2.2.4 Simulation Mode ............................................................................... 11
2.3 OPERATION.................................................................................................. 11
2.3.1 Properties.......................................................................................... 11
2.3.1.1 IndicationType ................................................................... 11
2.3.1.2 EnableLimitLabel ............................................................... 13
2.3.1.3 NumberOfDigits ................................................................. 13
2.3.1.4 EnableUnit ......................................................................... 13
2.3.1.5 TextIndAbnormalPos / TextIndNormalPos ......................... 13
2.3.1.6 Orientation ......................................................................... 14
2.3.1.7 SymbolSize ........................................................................ 14
2.3.1.8 EnableFitToBestSize ......................................................... 14
2.3.1.9 EnableLogicalColor ............................................................ 14
2.3.1.10 ValueColor ......................................................................... 14
3 AI Analogue Input .................................................................................................. 16
3.1 BASIC DESCRIPTION ................................................................................... 16
3.2 CONTROL ..................................................................................................... 17
3.2.1 Diagram Graphical Representation AIS ............................................. 17
3.2.2 Diagram Graphical Representation AIC............................................. 17
3.2.3 Parameter description ....................................................................... 17
3.2.3.1 Parameter AIS ................................................................... 17
3.2.3.2 Parameter AIC ................................................................... 19
3.2.4 Data Type description ....................................................................... 22
3.2.5 Project Constants .............................................................................. 24
3.2.6 PCC Interlock Limitations for AIS and AIC......................................... 24
3.3 OPERATION.................................................................................................. 25
3.3.1 Graphic elements .............................................................................. 25
3.3.1.1 AISandUnit or AICandUnit ................................................. 26
3.3.1.2 AISTxt or AICTxt ................................................................ 28
3.3.1.3 AISBar or AICBar............................................................... 30
3.3.2 Faceplate .......................................................................................... 33
3.3.2.1 Aspect Link Buttons ........................................................... 33
3.3.2.2 Default View ...................................................................... 33
3.3.2.3 Extended View ................................................................... 34
3.3.2.4 Faceplate Control Permission ............................................ 41
3.3.3 Alarm & Event List ............................................................................. 42
3.3.3.1 Object Status and Modes................................................... 42
3.3.3.2 Alarm Messages ................................................................ 42
4 AO Analogue Output.............................................................................................. 44
4.1 BASIC DESCRIPTION ................................................................................... 44
4.2 CONTROL ..................................................................................................... 44
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 2
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.2.1 Diagram Graphical Representation AOS ........................................... 44


4.2.2 Diagram Graphical Representation AOC ........................................... 44
4.2.3 Parameter description ....................................................................... 45
4.2.3.1 Parameter AOS ................................................................. 45
4.2.3.2 Parameter AOC ................................................................. 45
4.2.4 Data Type description ....................................................................... 46
4.3 OPERATION.................................................................................................. 48
4.3.1 Graphic elements .............................................................................. 48
4.3.1.1 AOSandUnit or AOCandUnit .............................................. 49
4.3.1.2 AOCBar or AOSBar ........................................................... 51
4.3.1.3 AOCIncDecButton or AOSIncDecButton............................ 53
4.3.2 Faceplate .......................................................................................... 54
4.3.2.1 Aspect Link and Command Buttons ................................... 54
4.3.2.2 Default View ...................................................................... 54
4.3.2.3 Extended View ................................................................... 55
4.3.2.4 Faceplate Control Permission ............................................ 58
4.3.3 Alarm & Event List ............................................................................. 59
4.3.3.1 Object Status and Modes................................................... 59
4.3.3.2 Alarm Messages ................................................................ 59
5 DI Digital Input ....................................................................................................... 60
5.1 BASIC DESCRIPTION ................................................................................... 60
5.2 CONTROL ..................................................................................................... 61
5.2.1 Diagram Graphical Representation DIS............................................. 61
5.2.2 Diagram Graphical Representation DIC ............................................ 61
5.2.3 Parameter description ....................................................................... 61
5.2.3.1 Parameter DIS ................................................................... 61
5.2.3.2 Parameter DIC ................................................................... 62
5.2.4 Data Type description ....................................................................... 63
5.2.5 Project Constants .............................................................................. 64
5.2.6 PCC Interlock Limitations .................................................................. 64
5.3 OPERATION.................................................................................................. 65
5.3.1 Time Diagram.................................................................................... 65
5.3.2 Graphic elements .............................................................................. 65
5.3.2.1 DIS or DIC ......................................................................... 66
5.3.2.2 DISTxt or DICTxt ............................................................... 68
5.3.3 Faceplate .......................................................................................... 70
5.3.3.1 Aspect Link and Command Buttons ................................... 70
5.3.3.2 Default View ...................................................................... 70
5.3.3.3 Extended View ................................................................... 71
5.3.3.4 Faceplate Control Permission ............................................ 74
5.3.4 Alarm & Event List ............................................................................. 75
5.3.4.1 Object Status and Modes................................................... 75
5.3.4.2 Alarm Messages ................................................................ 75
6 DO Digital Output ................................................................................................... 76
6.1 BASIC DESCRIPTION ................................................................................... 76
6.2 CONTROL ..................................................................................................... 76
6.2.1 Diagram Graphical Representation DOS ........................................... 76
6.2.2 Diagram Graphical Representation DOC........................................... 76
6.2.3 Parameter description ....................................................................... 77
6.2.3.1 Parameter DOS ................................................................. 77
6.2.3.2 Parameter DOC ................................................................. 77
6.2.4 Data Type description ....................................................................... 78
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 3
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3 OPERATION.................................................................................................. 79
6.3.1 Graphic elements .............................................................................. 79
6.3.1.1 DOS or DOC...................................................................... 80
6.3.1.2 DOSTxt or DOCTxt ............................................................ 82
6.3.1.3 DOSButton or DOCButton ................................................. 84
6.3.2 Faceplate .......................................................................................... 86
6.3.2.1 Aspect Link and Command Buttons ................................... 86
6.3.2.2 Default View ...................................................................... 86
6.3.2.3 Extended View ................................................................... 87
6.3.3 Faceplate Control Permission ........................................................... 89
6.3.4 Alarm & Event List ............................................................................. 90
6.3.4.1 Object Status and Modes................................................... 90
6.3.4.2 Alarm Messages ................................................................ 90
7 PCC_Connect_2 ..................................................................................................... 91
7.1 BASIC DESCRIPTION ................................................................................... 91
7.2 CONTROL ..................................................................................................... 91
7.2.1 Parameter description ....................................................................... 91
7.3 OPERATION.................................................................................................. 92
7.3.1 PCC Parent Link ............................................................................... 92
8 PCC_Connect ......................................................................................................... 93
8.1 BASIC DESCRIPTION ................................................................................... 93
8.2 CONTROL ..................................................................................................... 93
8.2.1 Diagram Graphical Representation ................................................... 93
8.2.2 Parameter description ....................................................................... 93
8.2.3 Interlock Masks ................................................................................. 95
8.2.4 Application Example .......................................................................... 96
8.3 OPERATION.................................................................................................. 98
8.3.1 PCC Parent Link ............................................................................... 98
9 PCC_Threshold_AND3 .......................................................................................... 99
9.1 Basic Description ........................................................................................... 99
9.2 CONTROL ................................................................................................... 100
9.2.1 Diagram Graphical Representation ................................................. 100
9.2.2 Parameter description ..................................................................... 100
9.2.3 Application Example ........................................................................ 102
9.2.4 PCC Viewer Presentation ................................................................ 103
9.3 OPERATION................................................................................................ 104
9.3.1 Faceplate ........................................................................................ 104
9.3.1.1 Aspect Link Buttons ......................................................... 104
9.3.1.2 Default View .................................................................... 104
9.3.1.3 Application Example ........................................................ 108
10 PCC_Intlk .............................................................................................................. 109
10.1 BASIC DESCRIPTION ................................................................................. 109
10.2 CONTROL ................................................................................................... 109
10.2.1 CDE Graphical Representation ....................................................... 109
10.2.2 Parameter description ..................................................................... 109
10.2.3 Data Type Definition ........................................................................ 110
10.2.3.1 OPERATION ................................................................... 111
10.2.3.2 Extended View ................................................................. 112
11 DOCUMENT REVISION HISTORY........................................................................ 113

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 4
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

1 SUMMARY
This document contains a detailed description of the following Basic Objects:
·AI (Analog Input)
·AO (Analog Output)
·DI (Digital Input)
·DO (Digital Output)

Additionally, four PCC specific Function Blocks and Control Modules are described
·PCC_Connect_2
·PCC_Connect
·PCC_Threshold_AND3
·PCC_Intlk

2 COMMON DATA

2.1 BASIC DESCRIPTION


Basic Objects provide access and control for process IO-signals and calculated IO-signals
from the ABB System 800xA operator workplace.
All basic objects have the following common basic functions:
· Tracking of control mode and status changes on the Operator station
· Operator Station Interface (graphic element and faceplate) including detailed alarm
and interlock indications.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 5
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.2 CONTROL

2.2.1 Library location


The Control Module Types for basic objects and its corresponding Structured Data Types
are located in the library BMIStandard for Control Builder M Professional.

2.2.2 Control modes


The basic objects AO and DO have 2 different control modes Man and Auto. All modes
are selectable from the operator station or the superior application.
Man:
Object is controlled via On/Off commands for DO’s and Set Value commands for AO’s.
These commands are issued from the faceplate.
Auto:
Object is controlled by On/Off commands for DO’s and Set Value commands for AO’s.
These commands are issued from the superior application.

2.2.3 PCC, Interlock Bus (Process Control Connection)

2.2.3.1 PCC Bus concept


Using the unique PCC (Process Control Connection) concept input signal objects
(AIS/AIC and DIS/DIC) can propagate their state to the consumer object. Depending on
the configuration, signals may send interlock actions to the connected consumer without
using binary interlock code. In addition it is possible to link between faceplates of signals
and consumers as soon a PCC is available.

2.2.3.2 Basic Functions of PCC


· Interlock configuration for connected consumers thru parameters on AIS/AIC and
DIS/DIC.
· Connection of unlimited number of AIS and DIS to a Consumer Object or Group
· Local Start override and Start Inhibit
· Automatic first fault detection of signal causing an interlock. First fault is presented on
the Consumer Object and Group faceplates including a link button to the source signal
· Link between AIS, AIC / DIS, DIC faceplates and to the consumer / group faceplate
· Two direction Alarm Acknowledgement between AIS/DIS and Consumer / Group.
Typical use is the auto alarm-acknowledge while a Consumer Object is controlled in
Local.
· Function Block PCC_Connect allows connecting two or more consumers or groups to
one AIS / DIS. In addition, this Function Block allows overwriting of the PCC
Alarm/Event enabling from the consumer for the connected AIS / DIS. For each
connected consumer an individual Interlock forwarding mask defines which interlocks
are blocked on a per limit basis if they are not desired.
· Function Block PCC_ThresholdAND3 to handle complex interlocks. It allows defining
multiple custom conditions to be used as interlocks on the PCC bus.
· PCC Status viewer for consumer and group objects
· Automatic disabling of AIS / DIS alarming with the following option:

cBMI.Std_Type: 0
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 6
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Motor is not running, NC Valve is closed, NO Valve is Open, for PCC connected to
Group: if Group is not started

cBMI.Std_Type: 1
Same as Std_Type 0 but always alarm on all Objects if Group is started and
Consumer preselected. In case object is standby preselected alarm priority is
automatically reduced from Failure to Warning.

PCCAEListFrcEn = true
Automatic alarm disabling switched off. This option shall be used in cases a signal
has to alarm independent from the status of its parent.

2.2.3.3 PCC Interlock Parameter Description


The following configuration options are applicable for AIC, AIS, DIC, DIS, PIDCtrl,
PCC_Intlk and PCC_Threshold_AND3.
IntlkType and IntlkDir are limit based configurations where as IntlkStartInhibit and
IntlkLocStartOverride are valid for all limits of the object.

Parameter Name Description


IntlkType - assigns the interlock to one of the interlock categories
- ready for start (RFS) configuration option to keep consumer ready
for group start even when interlock is present
- can be configured to start consumer in auto mode
IntlkDir - direction of interlock for two direction consumers
- Option to act only as start interlock
IntlkStartInhibit the interlocks are bypassed for the set time after the start of the
PCC parent (MOTx, VLVx)
Application example: bypass of rush in for motor current
IntlkLocStartOverride Bypass interlocks in Local mode if LCBStart is continuously
pushed. All PCC parents need to be in LOC.
Application example: temporary bypass of drift switches for a belt
conveyor in local mode to align the belt

The possible configuration settings for Interlock Type are:


IntrlkType Description
Configuration Option
PCC_Disabled No alarm or interlock forwarding on PCC bus
No_Interlock No interlock forwarding, only alarm forwarding
PD_PrevDrive Previous drive interlock, group remains ready for start
IA_Process Process interlock
If the consumer is in Auto mode the IA interlock is not reset again
on the ok condition. It is only reset by an Auto_Start command from
another PCC limit or signal.
IA_Process_RFS Process interlock, group remains ready for start
Same functionality in Auto as described above.
IB_Equipment Equipment interlock
IB_Equipment_RFS Equipment interlock, group remains ready for start
IC_Safety Safety interlock
IC_Safety_RFS Safety interlock, group remains ready for start
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 7
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Auto_Start Only used if consumer is in Auto mode: removes retained IA


interlock if it is not active anymore and thus the drive will start
(IO.In.IA also needs to be ok)

The possible configuration settings for Interlock Direction are:


IntlkDir Description
Configuration Option
DirX Configured interlock is only valid for direction X
DirXStart Same as DirX, but once the consumer is running in direction X (or
has reached end position X) the interlock is disregarded.
DirY Configured interlock is only valid for direction Y
DirYStart Same as DirY, but once the consumer is running in direction Y (or
has reached end position Y) the interlock is disregarded.
DirXY Configured interlock is valid for direction X and Y
DirXYStart Same as DirXY, but once the consumer is running in direction X/Y
(or has reached end position X/Y) the interlock is disregarded.
DirFBX Configured interlock is dynamic feedback (like FB1 in MOT1) for
direction X.
IO.Out.RunX or PosX will only become active if condition is fulfilled.
It can be used for additional limit switches [MOTP], speed-,
pressure, flow-switch with advantage of prewarning, alarm and
ready delay.
DirFBY Configured interlock to handle as dynamic feedback (like FB1 in
MOT2) for direction Y.
IO.Out.RunY or PosY will only become active if condition is fulfilled.
It can be used for additional limit switches [MOTP], speed-,
pressure, flow-switch with advantage of prewarning, alarm and
ready delay.
DirFBXY Configured interlock to handle as dynamic feedback for direction
X/Y.
IO.Out.RunX/Y or PosX/Y will only become active if condition is
fulfilled.
It can be used for additional limit switches [MOTP], speed-,
pressure, flow-switch with advantage of prewarning, alarm and
ready delay.
DirXFast Configured interlock to execute action in fast task for direction X.
Applicable for stop at position for MOT2, middle position stop for
MOTP and the other application where fast stop is required.
DirYFast Configured interlock to execute action in fast task for direction Y.
Applicable for stop at position for MOT2, middle position stop for
MOTP and the other application where fast stop is required.
DirXYFast Configured interlock to execute action in fast task for direction X/Y.
Applicable for stop at position for MOT2, middle position stop for
MOTP and the other application where fast stop is required.
DirFBXFast Combination of FB and Fast for Direction X
DirFBYFast Combination of FB and Fast for Direction Y
DirFBXYFast Combination of FB and Fast for Direction X/Y
DirXnoAck Configured interlock to use "Value" instead of "Normal". Useful for
cases where operation will be possible even if the alarm was not
acknowledged but the value returned to Normal Position.
DirYnoAck Configured interlock to use "Value" instead of "Normal". Useful for
cases where operation will be possible even if the alarm was not

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 8
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

IntlkDir Description
Configuration Option
acknowledged but the value returned to Normal Position.
DirXYnoAck Configured interlock to use "Value" instead of "Normal". Useful for
cases where operation will be possible even if the alarm was not
acknowledged but the value returned to Normal Position.
DirXStartnoAck Same as DirXnoAck, but once the parent is running in direction X
(or has reached end position X) the interlock is disabled.
DirYStartnoAck Same as DirYnoAck, but once the parent is running in direction Y
(or has reached end position Y) the interlock is disabled.
DirXYStartnoAck Same as DirXYnoAck, but once the parent is running in direction
X/Y (or has reached end position X/Y) the interlock is disabled.
DirFBXnoAck Combination of FB and noAck for Direction X.
DirFBYnoAck Combination of FB and noAck for Direction Y.
DirFBXYnoAck Combination of FB and noAck for Direction X/Y.
DirXFastnoAck Combination of Fast and noAck for Direction X.
DirYFastnoAck Combination of Fast and noAck for Direction Y.
DirXYFastnoAck Combination of Fast and noAck for Direction X/Y.
DirFBXFastnoAck Combination of FB and Fast and noAck for Direction X.
DirFBYFastnoAck Combination of FB and Fast and noAck for Direction Y.
DirFBXYFastnoAck Combination of FB and Fast and noAck for Direction X/Y.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 9
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

The possible assignment for different control modules are:


IntlkDir PCC_Com_ PCC_Thresh
Configuration AIS AIC DIS DIC Drive old_AND_3 PID
Option (ComError) & PCC_Intlk
DirX Yes Yes Yes Yes Yes Yes Yes
DirXStart Yes Yes Yes Yes Yes Yes Yes
DirY Yes Yes Yes Yes Yes Yes Yes
DirYStart Yes Yes Yes Yes Yes Yes Yes
DirXY Yes Yes Yes Yes Yes Yes Yes
DirXYStart Yes Yes Yes Yes Yes Yes Yes
DirFBX Yes Yes Yes Yes - Yes Yes
DirFBY Yes Yes Yes Yes - Yes Yes
DirFBXY Yes Yes Yes Yes - Yes Yes
DirXFast - - Yes - - - -
DirYFast - - Yes - - - -
DirXYFast - - Yes - - - -
DirFBXFast - - Yes - - - -
DirFBYFast - - Yes - - - -
DirFBXYFast - - Yes - - - -
DirXnoAck Yes Yes Yes Yes - - Yes
DirYnoAck Yes Yes Yes Yes - - Yes
DirXYnoAck Yes Yes Yes Yes - - Yes
DirXStartnoAck Yes Yes Yes Yes - - Yes
DirYStartnoAck Yes Yes Yes Yes - - Yes
DirXYStartnoAck Yes Yes Yes Yes - - Yes
DirFBXnoAck Yes Yes Yes Yes - - Yes
DirFBYnoAck Yes Yes Yes Yes - - Yes
DirFBXYnoAck Yes Yes Yes Yes - - Yes
DirXFastnoAck - - Yes - - - -
DirYFastnoAck - - Yes - - - -
DirXYFastnoAck - - Yes - - - -
DirFBXFastnoAck - - Yes - - - -
DirFBYFastnoAck - - Yes - - - -
DirFBXYFastnoAck - - Yes - - - -

For more details about PID refer to the Loop Object Reference manual document ID:3BHS
161562.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 10
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.2.4 Simulation Mode


It is possible to simulate DIS, AIS, DOS and AOS objects. Under simulation mode the
hardware error connection is not considered.
When set the simulation mode, the following is set as initial behaviour after a warm start.
Notice that it is the initial condition which can be changed afterwards.
§ AIS hardware connection (error condition) is not considered and the value
is set to 50% of the total range. Input is blocked. Notice that the input will
be blocked and the value will be set to 50% only in case of warm start.
§ DIS hardware connection is not considered and the value is set to the
normal position. Input is blocked. Notice that the value is simulated only in
case of warm start.
§ DOS and AOS hardware connections are not considered.

In case any of output objects (DOS and AOS) are connected to the
hardware all the changes to them will be written to the hardware.
For safety reason we advise to disconnect the Profibus, modulebus or any
other hardware interface.

2.3 OPERATION
Details on all available graphic elements for the basic objects are available in the
operation chapter of the individual object type e.g. Analog Input.

2.3.1 Properties
Below is an overview of the properties that are applicable for the graphic elements that
represent basic objects.

2.3.1.1 IndicationType
Name DataType Default Value Description
IndicationType IndicationTypeEnum A03_MotorM Symbol type selection

Name Values
IndicationTypeEnum A00_Rectangle.
A01_Motor.
A03_MotorM.
A04_Pump.
A05_Fan.
A06_RotaryFeeder.
E77_BeltCleaner.
A02_Valve.
B11_Damper.
B14_LouvreDamper.
B16_PropRoller.
B15_AirslideDiverter.
B12_Shut.
B13_Diverter.
E21_GearwheelPump.
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 11
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

C31_Valve3way.
C32_ValveMan.
C33_ValveAuto.
E41_Generator.
E42_Switch.
E07_Triangle.
E08_Lollipop.
E09_Diamond.
E99_TagName.
F00_None.

With this property the type of graphic symbol that shall represent a DI or DO object can
be selected.
Not applicable for AI / AO objects.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 12
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3.1.2 EnableLimitLabel
Name DataType Default Value Description
EnableLimitLabel Boolean True Show limit labels
When set to “True”, the alarm limits are visible next to the graphic element.
Only applicable for AI objects.

2.3.1.3 NumberOfDigits
Aspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit
Name DataType Default Value Description
NumberOfDigits Integer 4 Number of presented digits
Used for setting how many digits need to be shown.
This is only applicable for AI / AO objects.
Not applicable for the bar graph.

2.3.1.4 EnableUnit
Aspect: AISandUnit, AICandUnit, AOSandUnit, AOCandUnit, PIDCtrl
Name DataType Default Value Description
EnableUnit Boolean True Show units
When set to “true”, the engineering units are visible next to the graphic element.
This is only applicable for AI / AO / PID objects.

2.3.1.5 TextIndAbnormalPos / TextIndNormalPos


Aspect: DISTxt, DICTxt, DOSTxt, DOCTxt
Name DataType Default Value Description
TextIndAbnormalPos String "On" Text for abnormal position
TextIndNormalPos String "Off" Text for normal position
With these properties a text can be added for abnormal position and normal position.
This text will be represented on the graphic symbol for DI / DO objects.

Aspect: AISTxt, AICTxt


Name DataType Default Value Description
TextIndTrH1AbnormalPos String "H1" TextIndTrH1AbnormalPos
TextIndTrH1NormalPos String "Off" TextIndTrH1NormalPos
With these properties a text can be added for abnormal position and normal position.
This text will be represented on the graphic symbol for AI.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 13
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

2.3.1.6 Orientation
Name DataType Default Value Description
Orientation Integer 0 Obsolete property used for migration
only, Orientation in degrees, clockwise.
Obsolete property used for migration only, Orientation in degrees, clockwise.
Orientation is still used (to rotate the symbol indication) in the following Generic
Elements core:
· DigitalCmdButtonCore
· DigitalCore
· DriveCmdButtonCore
· DriveCore
· SymbolCore

2.3.1.7 SymbolSize
Name DataType Default Value Description
SymbolSize Integer 12 Defined the square size in case of
IndicationType = 10
Size of the symbol in the graphic display.
E.g. Symbol size in pixel: 8 = Little
12 = Small
16 = Standard
20 = Large
24 = XXL

2.3.1.8 EnableFitToBestSize
Name DataType Default Value Description
EnableFitToBestSize Boolean True Set best unit size
When set to “True”, the unit size is calculated to best size according to the string.
Not applicable for the bar graph.

2.3.1.9 EnableLogicalColor
Name DataType Default Value Description
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
set it to false.
When set to “True”, the colors are based on logical colors.
Not applicable for the PID object.

2.3.1.10 ValueColor
Name DataType Default Value Description
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 14
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

ValueColor Color BMIvalueMV Value color. Only applied if


(AI) EnableLogicalColor is set to false.

BMIvalueOUT
(AO)
When EnableLogicalColor set to “False”, the ValueColor is used to show the value color or
Bar color with the defined ValueColor.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 15
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3 AI Analogue Input

3.1 BASIC DESCRIPTION


The Control Module Types AIS and AIC are used to access and control an analog input.
· AIS module is used to read one analog input signal, coming from the process
· AIC module is used to write a calculated signal from the application, that is to be
indicated on the operator station and that will have alarm limit control.

The analog input module provides the following features:


· Blocking and forcing of input value
· Threshold detection and alarming on 4 alarm limit levels (L2,L1,H1,H2)
· Threshold detection and eventing on 2 Process Limit levels (PLo, PHi)
· Adjustable Low Pass Filter to create the FilteredSignal output.
· FilteredSignal Rate of change calculation and alarm. The ROC is presented in % of
Total Range per second.
· All Substatus for DP, PA and FF Field Devices will generate error control when quality
is Bad or Uncertain for AIS Control Module.
· Common or Individual alarm delay for all 6 limits.
· Alarm blocking (from faceplate). All alarm limit levels will be blocked.
· Alarm disabling/enabling of each alarm limit individually (from application program /
Faceplate); generating events when blocked.
· Single and Triple trend and automatic log configuration for:
· FilteredSignal
· IOSignal
· RateofChange
· Minerals Library Process Control Connection (PCC)
· Parameterized interlocks towards parent objects
· Advanced alarm disabling from parent objects
· Interface to Process Panel

Additionally, the AIS Control Module has the following feature:


· Signal Error pre-warning with adjustable alarm delay.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 16
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.2 CONTROL

3.2.1 Diagram Graphical Representation AIS


The default view is shown, it’s possible to modify the visible ports in CBM.

3.2.2 Diagram Graphical Representation AIC


The default view is shown, it’s possible to modify the visible ports in CBM.

3.2.3 Parameter description

3.2.3.1 Parameter AIS


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AIS (allowed deliminators
are "_" or "." or "-", no blanks,":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AIS
3 IO AISData 1 in_out IN/OUT: Connection to AISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus, Priority
a Command/Interlock to motors, valves or groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
7 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
8 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
9 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
10 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =
Event

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 17
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


11 StatusTr bool true 0 in IN: True enables events on Forced value
changes
12 LogTr bool true 0 in INIT: Limit change treatment: true = Event on
limit value change, false = Events on limit value
change are disabled.
13 ErrCtrl bool true 0 in IN: Action in case of Signal Error: false = no
action; true = IO.Signal.Value is forced to Err_Val
14 ErrVal real 99999 0 in IN: Error Value used in case of Err_Ctrl = true
15 ErrTr dint cBMI.AE.Sig 0 in IN: Severity for the Signal Error AlarmCond
Err_Sev
16 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
17 HiLim2 real 100 0 in COLD INIT: Initial limit for High2 alarm.
18 BlkHiLim2 bool false 0 in COLD INIT: Initial value for blocking of the limit
high 2 handling
19 IntlkTypeHiLim dint No_Interlock 1 in INIT:
2 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
20 IntlkDirHiLim2 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
21 HiLim1 real 100 0 in COLD INIT: Initial limit for High1 alarm.
22 BlkHiLim1 bool false 0 in COLD INIT: Initial value for blocking of the limit
high 1 handling
23 IntlkTypeHiLim dint No_Interlock 1 in INIT:
1 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
24 IntlkDirHiLim1 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
25 PHiLim real 90 0 in COLD INIT: Initial limit for Process High alarm.
26 BlkPHiLim bool true 0 in COLD INIT: Initial value for blocking of the limit
Process High handling
27 IntlkTypePHiLi dint No_Interlock 0 in INIT:
m PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
28 IntlkDirPHiLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;
DirYStart; DirXY; DirFBXY; DirXYStart;
29 PLoLim real 10 0 in COLD INIT: Initial limit for Process Low alarm.
30 BlkPLoLim bool true 0 in COLD INIT: Initial value for blocking of the limit
Process Low handling
31 IntlkTypePLoLi dint No_Interlock 0 in INIT:
m PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
32 IntlkDirPLoLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;
DirYStart; DirXY; DirFBXY; DirXYStart;
33 LoLim1 real 0 0 in COLD INIT: Initial limit for Low1 alarm.
34 BlkLoLim1 bool false 0 in COLD INIT: Initial value for blocking of the limit
low 1 handling
35 IntlkTypeLoLim dint No_Interlock 0 in INIT:
1 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
36 IntlkDirLoLim1 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
37 LoLim2 real 0 0 in COLD INIT: Initial limit for Low2 alarm.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 18
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


38 BlkLoLim2 bool false 0 in COLD INIT: Initial value for blocking of the limit
low 2 handling
39 IntlkTypeLoLim dint No_Interlock 0 in INIT:
2 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
40 IntlkDirLoLim2 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
41 IntlkTypeROC dint No_Interlock 0 in INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
42 IntlkDirROC dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;
DirXYStart
43 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after
start of PCC parent (MOTx, VLVx), Time will start
with Ord# instead of Run# where the IntlkD
44 IntlkLocStartO bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStart
verride is continuously pushed. All PCC parents need to
be in LOC.
45 Hyst real 1.0 0 in COLD INIT: Initial Hysteresis in %
46 AlarmDelay time 0s 0 in COLD INIT: Initial time delay for the limit level
supervision
47 EnIndividualAl bool cBMI.AIS.En 0 in IN: Enables the individual alarm delay setting for
armDelays IndividualAla all the 6 limits in the faceplate. If True,
rmDelays AlarmDelay has only effect for upgrade.
48 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms
49 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only
For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.

3.2.3.2 Parameter AIC


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AIC (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AIC
3 IO AISData Default 1 in_out IN/OUT: Connection to AISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Min real 0 1 in INIT: Scaling Parameter Range.
7 Max real 100 1 in INIT: Scaling Parameter Range Max.
8 Unit string '%' 1 in INIT: Scaling Parameter Unit.
9 Fraction dint 1 1 in INIT: Fraction (Number of Decimals).
10 SignalError bool false 1 in IN false: Input for calculated signal error
indication
11 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
12 Lim2Tr dint 3 0 in INIT: Alarm L2/H2 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
13 Lim1Tr dint 2 0 in INIT: Alarm L1/H1 limit treatment: -1 no AE; 0 =
Event ; 1,2,3 = ALPrio# (1=lowest)
14 ROCLimTr dint -1 0 in INIT: ROC limit treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
15 PLimTr dint 0 0 in INIT: Process limit treatment: -1 no AE; 0 =
Event
16 LogTr bool true 0 in INIT: Limit change treatment: true = Event on
limit value change, false = Events on limit value
change are disabled.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 19
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


17 ErrCtrl bool true 0 in IN: Action in case of Signal Error: false = no
action; true = IO.Signal.Value is forced to Err_Val
18 ErrVal real 0.0 0 in IN: Error Value used in case of Err_Ctrl = true
19 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
20 EnExtAlarm dint in no cBMI.AIC. IN: Limit checks are external and Events are
EnExtAlar generated by writing to IO.H1.Value etc. for H2/1,
m.None PLo/Hi and L1/2. AlarmDelays are disabled.
21 HiLim2 real 100 0 in COLD INIT: Initial limit for High2 alarm.
22 BlkHiLim2 bool false 0 in COLD INIT: Initial value for blocking of the limit
high 2 handling
23 IntlkTypeHiLim dint No_Interlock 1 in INIT:
2 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
24 IntlkDirHiLim2 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
25 HiLim1 real 100 0 in COLD INIT: Initial limit for High1 alarm.
26 BlkHiLim1 bool false 0 in COLD INIT: Initial value for blocking of the limit
high 1 handling
27 IntlkTypeHiLim dint No_Interlock 1 in INIT:
1 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
28 IntlkDirHiLim1 dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
29 PHiLim real 90 0 in COLD INIT: Initial limit for Process High alarm.
30 BlkPHiLim bool true 0 in COLD INIT: Initial value for blocking of the limit
Process High handling
31 IntlkTypePHiLi dint No_Interlock 0 in INIT:
m PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
32 IntlkDirPHiLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;
DirYStart; DirXY; DirFBXY; DirXYStart;
33 PLoLim real 10 0 in COLD INIT: Initial limit for Process Low alarm.
34 BlkPLoLim bool true 0 in COLD INIT: Initial value for blocking of the limit
Process Low handling
35 IntlkTypePLoLi dint No_Interlock 0 in INIT:
m PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
36 IntlkDirPLoLim dint DirXY 0 in INIT: DirX; DirFBX; DirXStart; DirY; DirFBY;
DirYStart; DirXY; DirFBXY; DirXYStart;
37 LoLim1 real 0 0 in COLD INIT: Initial limit for Low1 alarm.
38 BlkLoLim1 bool false 0 in COLD INIT: Initial value for blocking of the limit
low 1 handling
39 IntlkTypeLoLim dint No_Interlock 0 in INIT:
1 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
40 IntlkDirLoLim1 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
41 LoLim2 real 0 0 in COLD INIT: Initial limit for Low2 alarm.
42 BlkLoLim2 bool false 0 in COLD INIT: Initial value for blocking of the limit
low 2 handling

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 20
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


43 IntlkTypeLoLim dint No_Interlock 0 in INIT:
2 PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
44 IntlkDirLoLim2 dint DirXY 0 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
45 IntlkTypeROC dint No_Interlock 0 in INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
46 IntlkDirROC dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;
DirXYStart
47 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after
start of PCC parent (MOTx, VLVx), Start by Ord
instead of Run where the IntlkDir is DirFB
48 IntlkLocStartO bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStart
verride is continuously pushed. All PCC parents need to
be in LOC.
49 Hyst real 1.0 0 in COLD INIT: Initial Hysteresis in %
50 AlarmDelay time 0s 0 in COLD INIT: Initial time delay for the limit level
supervision
51 EnIndividualAl bool cBMI.AIS.En 0 in IN: Enables the individual alarm delay setting for
armDelays IndividualAla all the 6 limits in the faceplate. If True,
rmDelays AlarmDelay has only effect for upgrade.
52 ExtendedInfo dint in no 0 IN: Extended Info on Faceplace - setting only
useful if Faceplate is including the Extended Info
53 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms

For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 21
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.2.4 Data Type description


Together with the AIS and AIC Control Module Type a Structured Data Type AISData is
available. This makes it possible to create one Global Variable in the application for each
AI instance.
AISData; components
Name Data Type Attributes Initial Description
Value
1 LimEn bool retain true IN true: External Enabling of AIS Limit
nosort Supervision, used to temporary block the
alarming
2 EnHiLim2 bool retain true IN true: Enables High Limit 2
nosort
3 EnHiLim1 bool retain true IN true: Enables High Limit 1
nosort
4 EnPHiLim bool retain true IN true: Enables Process High Limit
nosort
5 EnPLoLim bool retain true IN true: Enables Process Low Limit
nosort
6 EnLoLim1 bool retain true IN true: Enables Low Limit 1
nosort
7 EnLoLim2 bool retain true IN true: Enables Low Limit 2
nosort
8 AEListEn bool retain true IN true: External Alarm List Enabling of AIS,
nosort temporary disabling of unack alarming and
entries in alarmlist, NOTE: Overwritten by
PCC
9 H2 BoolAL retain OUT: Alarm Status of limit H2. Use the
.Normal value for interlocking
10 H1 BoolAL retain OUT: Alarm Status of limit H1. Use the
.Normal value for interlocking
11 PHi bool retain OUT: Indication of limit Process Limit High
12 PLo bool retain OUT: Indication of limit Process Limit Low
13 L1 BoolAL retain OUT: Alarm Status of limit L1. Use the
.Normal value for interlocking
14 L2 BoolAL retain OUT: Alarm Status of limit L2. Use the
.Normal value for interlocking
15 SigErr BoolAL retain OUT: Alarm Status of Signal Error (e.g.
electrical signal less than 4 mA)
16 SigErrWarn bool retain OUT: Signal Error Warning Normal
17 ROCLim BoolAL retain OUT: Alarm Status of Rate of Change limit.
Use the .Normal value for interlocking
18 Signal RealIO retain IN/OUT: Signal to be connected to the S800
displayvalu HW I/O
e
19 FilteredSignal RealIO retain IN/OUT: Filter to Signal.Value
20 RateofChange RealIO retain IN/OUT: Signal rate of change
21 FieldDeviceStat dword retain cBMI.AI IN: 2nd DWORD for Field Device Status
us nosort S.FDStat Supervision e.g. Profibus PA Devices etc. If
usNC value equals 16#80C0 the faceplate
indication is hidden
22 FieldDeviceStat dint retain cBMI.AI IN: 2nd DINT for Field Device Status
usDINT nosort S.FDStat Supervision e.g. Profibus PA Devices etc. If
usNCDI value equals 16#80C0 FieldDeviceStatus
NT dword is used inste
23 ProcessPanel PanelLink retain Interface from / to ProcessPanel
AIS
24 Name string[24] retain Name of AIS/AIC

For AIS, use the Data type structure as follows:


Write: no supported (directly connected to IO Channel)
Read: IO.<TagName>. FilteredSignal.Value
Interlock: IO.<TagName>.<Limit>.Normal

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 22
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

For AIC, use the Data type structure:


Write: IO.<TagName>.Signal.IOValue
Read: IO.<TagName>. FilteredSignal.Value
Interlock: IO.<TagName>.<Limit>.Normal

FilteredSignal is related to the Signal as follows:


1
y k = xk a + y k -1 (1 - a );a =
FilterTime × 0.87
+1
DT
FilterTime
Which is equivalent to a 1st order low pass with t =
1.15

Note that the IO.FilteredSignal.Parameter Values are copied from the


IO.Signal.Parameter on Application Start only. In case of changes in the
Hardware Structure for the Channel where IO.Signal is connected, the
Parameter Value can be different between these two Variables after the
download to the Controller.

PanelLinkAIS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (Ready, H,HH,Phi,Plo etc.)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 SignalValue real Retain Signal Value to Process Panel
nosort
hidden
4 Blink bool Retain Enabling of Basic Object Blinking
nosort
hidden

Cmd; Bits

Name Bit
Position
1 AlarmAck 0

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 23
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.2.5 Project Constants


Name Data Type Default Value
1 cBMI.AIS.DisabledIntMaxIndTr dint (dint): 13
2 cBMI.AIS.EnIndividualAlarmDelays bool (bool): false
3 cBMI.AIS.FDStatusNC dword (dword): 16#80c0
4 cBMI.AIS.FDStatusNCDINT dint (dint): 16#80c0
5 cBMI.AIS.H1_txt string (string): 'H1'
6 cBMI.AIS.H2_txt string (string): 'H2'
7 cBMI.AIS.L1_txt string (string): 'L1'
8 cBMI.AIS.L2_txt string (string): 'L2'
9 cBMI.AIS.PHi_txt string (string): 'PHi'
10 cBMI.AIS.PLo_txt string (string): 'PLo'
11 cBMI.AIS.PropagateSigErrToPCC bool (bool): true
12 cBMI.AIS.ROC_Txt string (string): 'ROC'
13 cBMI.AIS.SigErr_txt string (string): 'SigError'
14 cBMI.AIS.SigErrDelay time (time): 0s
15 cBMI.AIS.SigErrWarn_txt string (string): 'SigError'
16 cBMI.AIS.UncertainAsGood bool (bool): false

FDStatusNC defines the Value that is used to detect that no Status is connected to the
Module. Note that this Value should be “impossible” to be sent at any time by a Field
Device.

3.2.6 PCC Interlock Limitations for AIS and AIC


The “Fast” interlock direction (e.g. DirXFast, DirFBXFast) is not supported for AIS and
AIC.
shown in FPL as
Param Error

With Fast

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 24
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3 OPERATION

3.3.1 Graphic elements


Graphic Element Description Example

AISandUnit or AICandUnit Value indication and unit.

AISBar or AICBar Bar graph indication

AISTxt or AICTxt Limit status text indication

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 25
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.1 AISandUnit or AICandUnit


The value and unit presents the measured value, alarm limits and status information.

3.3.1.1.1 Presentation
Indication Type Description Example

Value and Unit Value and unit indication

3.3.1.1.2 Status
Object status Symbol color

Value in normal range Value green

H2 Limit and signal blocked Red thick frame / Value green

Signal Quality Bad Yellow background color

3.3.1.1.3 Labels
Description Indication

Signal blocked

Limit High 2

Limit High 1

Limit Process High 1

Limit Process Low 1

Limit Low 1

Limit Low 2

Rate of Change

Example:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 26
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.1.4 Properties
Name DataType Default Value Description
EnableDisplayBackgroundColor Boolean False Show display background color as
symbol background
EnableFitToBestSize Boolean True Set best unit size
EnableLimitLabel Boolean True Show limit labels
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
set it to false.
EnableUnit Boolean True Show units
NumberOfDigits Integer 4 Number of presented digits
UnitSize Integer 8 Unit size in pixel: 7 = Small, 8 =
Standard, 10 = Large, 12= XXL
ValueColor Color BMIvalueMV Value color. Only applied if
EnableLogicalColor is set to false.
ValueSize Integer 12 Value size in pixel: 8 = Small, 10
Medium, 12 = Standard, 14 = Large,
16 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 27
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.2 AISTxt or AICTxt


AIS and AIC text can be used to show alarm limits of analogue inputs as labels. The label
text can be customized. The text appearance can be configured to show the text only on
alarm, depending on the value, always but with different colours depending on value or
alarm condition.

3.3.1.2.1 Presentation
Indication Type Description Example

Text with background color Text with background color

Square in front of text Square in front of text

Text colored Text colored

3.3.1.2.2 Status
Object status Symbol color
Normal Position for
Appearance Types, 0 = Alarm, 2 Gray dimmed (semitransparent)
= value
Normal Position for
Appearance Types, 10 = Alarm, Green
12 = Value interlock
Normal Position for
Appearance Types, 0 = Alarm, 2 Red
= value

3.3.1.2.3 Labels
Description Indication

Status blocked

Example:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 28
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.2.4 Properties
Name DataType Default Value Description
AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value custom
color, 10 = Alarm interlock, 12 Value
interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value
custom color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value
custom color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableNormalPos Boolean True Hide symbol in normal position
Font Font Font( "Arial" ,10 Text font wehn EnableFont is true
,Regular, Bold)
IndicationType Integer 0 0 = Text with background color, 10 =
Square in front of text, 20 = Text colored
IndicationValue Integer 1 0 = All, 1 = H2, 2 = H1, 3 = PH2, 4 = PH1,
5 = PL1, 6 = PL2, 7 = L1, 8 = PL2
NormalPos Boolean False Used for AppearanceType 2 = Value, 3 =
Value custom color
SymbolSize Integer 12 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
TextBold Boolean True Text style is bold
TextColor Color BMIstaticTextOff Text color
TextIndTrH1AbnormalPos String "H1" TextIndTrH1AbnormalPos
TextIndTrH1NormalPos String "H1" TextIndTrH1NormalPos
TextIndTrH2AbnormalPos String "H2" TextIndTrH2AbnormalPos
TextIndTrH2NormalPos String "H2" TextIndTrH2NormalPos
TextIndTrL1AbnormalPos String "L1" TextIndTrL1AbnormalPos
TextIndTrL1NormalPos String "L1" TextIndTrL1NormalPos
TextIndTrL2AbnormalPos String "L2" TextIndTrL2AbnormalPos
TextIndTrL2NormalPos String "L2" TextIndTrL2NormalPos
TextIndTrPH1AbnormalPos String "PH1" TextIndTrPH1AbnormalPos
TextIndTrPH1NormalPos String "PH1" TextIndTrPH1NormalPos
TextIndTrPH2AbnormalPos String "PH2" TextIndTrPH2AbnormalPos
TextIndTrPH2NormalPos String "PH2" TextIndTrPH2NormalPos
TextIndTrPL1AbnormalPos String "PL1" TextIndTrPL1AbnormalPos
TextIndTrPL1NormalPos String "PL1" TextIndTrPL1NormalPos
TextIndTrPL2AbnormalPos String "PL2" TextIndTrPL2AbnormalPos
TextIndTrPL2NormalPos String "PL2" TextIndTrPL2NormalPos
TextSize Integer 10 Text size in pixel: 8 = Small, 10 =
Standard, 12 = Large, 16 = XXL
TextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos, 2 = OPC Text, 3 =
NLS Text
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 29
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.3 AISBar or AICBar


AIS and AIC bar presents the analogue value as bar. Alarm or process limits are graphical
shown and different bar graph appearances are possible.

3.3.1.3.1 Presentation
Appearance Description Example

Standard
This is the standard appearance of the bar graph. The value will
0 be indicated in relation to the maximum and minimum range. The
green bar will always start from the minimum range.

Start from Pivot


1 Use this appearance to start the bar graph from another value
than the minimum range. The related property is “Pivot”.

Inverse
2 The bar will be inverse to the standard appearance.

Line
3 The value will be indicated as a small line instead of a bar.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 30
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.3.2 Status
Example Object status Symbol color

Limit Alarm or process limit Colored Alarm band on one side.


exceeded.

Alarm Blocked Yellow thin frame

3.3.1.3.3 Labels
Description Indication

Signal blocked

Signal Quality Bad

Limit High 2

Limit High 1

Limit Process High 1

Limit Process Low 1

Limit Low 1

Limit Low 2

Example:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 31
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.1.3.4 Properties
Name DataType Default Value Description
Appearance Integer 0 0 = Standard, 1 = Start from Pivot, 2 = Inverse,
3 = Line
BarColorCustom Color BMIbarMV Bar color. Only applied if EnableLogicalColor is
set to false.
EnableLimitLabel Boolean True Show limit labels
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all used
colors are logical colors. The logical color
reference is equal to the default logical color
used in the color properties. To use an
individual color set it to false.
EnableManualRange Boolean False If set to true, the bar's range can be set
manually
Pivot Real 0. Used together with Appearance = 1 (Start from
Pivot). The bar will start from the value set as
Pivot.
RangeMax Real 100. Maximum range if EnableManualRange is true
RangeMin Real 0. Minimum range if EnableManualRange is true
SubscriptionRate Integer 0 The update rate for all aspect object properties
subscribed for
SymbolSize Integer 14 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
VerticalBar Boolean True VerticalBar: True = vertical appearance, false =
horizontal appearance.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 32
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2 Faceplate

3.3.2.1 Aspect Link Buttons


The following aspect view buttons are available on AIS and AIC Faceplates
Icon Aspect View
Alarm List

Event List

Single Trend (Filtered Value)

Multi Trend (Filtered Value / IO Value / Rate of Change)

Operators Note

Faceplate Documentation, reference to this document

3.3.2.2 Default View

Tagname
&
Description

Measured Value
&
alarm indication
Mini Trend
Measure Value

Graphical Bar
Measured Value
&
alarm limits

Apply Button

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 33
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.3 Extended View


The faceplate extended view gives more detailed information about the Analogue Input.

Tabbed Browse forward /


information backwards to show hidden
tabs

Reduced View
default

Additional information for the AIS is structured in tabs. The available tabs and a short
description of the contained information are shown below.
Tab Description
Trend Mini trend of filtered measured value, IO value and rate of change
Limit Limits and alarm delay settings for the measured value
ROC Rate of change settings
Block - Input Blocking
- Alarm Blocking
MVStatus Sub status for DP, PA and FF Field Devices
PCC - PCC interlock configuration summery
- Link to connected consumer or consumer overview list

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 34
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.3.1 Trend
On-Line single Triple trend and log Configuration aspect with the actual values: Signal,
FilterdSignal and RateofChange.
Move over the trend area a curser will appear, showing enabled traces’ value and record
time.

Show / Hide Grid

Show / Hide Traces


Record Time MV: Filtered Signal
IO: Signal
3.3.2.3.2 Limit ROC: Rate of Change

Limit settings for measured value are done here.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 35
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Reference Table
Description
B Indication that the corresponding alarm limit has been blocked. Yellow
means that the alarm limit is blocked (disabled)
nd
H2 2 High limit (H2) - Failure
st
H1 1 High limit (H1) - Warning
PHigh Process High Limit
PLow Process Low Limit
st
L1 1 Low limit (L1) - Warning
nd
L2 2 Low limit (L2) - Failure
Alarm Delay Time delay before alarm message will be send to the operator station.
Check below the special mode for 6 alarm limits.
Hysteresis Alarm Hysteresis in %

F When limits are changed from the faceplate, you must take into consideration that
these values will be overwritten again with the initial values when a cold restart /
reset is performed and the coldretain files are not available for the corresponding
controller.
To avoid this, you need to update the initial values for the corresponding AIS/AIC
control module instance with Control Builder, after changing the Values from the
Faceplate.

3.3.2.3.2.1 Six limits alarm delay – special mode


There is a possibility to enable individual alarm delays for each AIS/AIC element. The
way to do that is setting EnIndividualAlarmDelays parameter to true in each AIS/AIC
element.
After a download, you will be able to notice the following appearance of the AIS
faceplate

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 36
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.3.3 ROC

Description
ROC High Limit Rate Of Change in % of Total Range per seconds High Limit
ROC Hysteresis ROC Alarm Hysteresis in %
Filter Time Filter time to be applied to the IO.<AISTag>.FilteredValue

F When limits are changed from the faceplate, you must take into consideration that
these values will be overwritten again with the initial values when a cold restart /
reset is performed and the coldretain files are not available for the corresponding
controller.
To avoid this, you need to update the initial values for the corresponding AIS/AIC
control module instance with Control Builder, after changing the Values from the
Faceplate.

3.3.2.3.4 Block / Override


Block / Force Input

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 37
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Block Alarm

Reference Table, Block


Description
Block Input The analog input will be “forced” on controller hardware input level.
The IO Value shows the actual value in the process. Alarm limits remain
active.
Block Alarm All 4 alarm limits will be blocked as well as Signal Error and ROC Alarms.
They are not taken into account anymore.

3.3.2.3.5 MVStatus

Substatus for Foundation Fieldbus and S800 Field Devices

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 38
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

All Substatus for DP, PA and FF Field Devices will generate error control when quality is
Bad or Uncertain for AIS Control Module.
An Aspect Link giving access to the “Device Management” Object can be configured via
the “BMI DTM Link” General Properties Aspect.

General Properties Property Description


Aspect
BMI DTM Link FPLAspectLink.DTM.ObjectName Name of the DTM Object
BMI DTM Link FPLAspectLink.DTM.AspectName Name of the DTM Aspect
BMI Overlap Link FPLAspectLink.DTM.DefaultAspectName Default Name of the DTM
Aspect
The “Device Management” Button will be shown only if the Properties are not empty
Strings.

Description
Signal Error Time between the Signal Error occurs until the Value is forced to
Delay ErrValue. Only available for AIS Module.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 39
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.3.6 PCC
PCC interlock configuration

The PCC interlock configuration tab shows the actual configuration and a link to the
parent object.

If the configuration via control module parameters “IntlkType” and “IntlkDir” is wrong, the
error message “PCC Intlk Param Error” will be displayed in the Faceplate.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 40
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.2.4 Faceplate Control Permission


By the Property Attribute Override Aspect, the faceplate Write permissions (IntPar) can be
configured according the plants access and permission concept. This can be done in the
Control Structure or in the Object Type Structure.

F Note that forcing to a Value in the Faceplate does require Write permission for
IO.Signal.Value and IO.Signal.Forced, these are not set on IntPar Variables.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 41
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

3.3.3 Alarm & Event List

3.3.3.1 Object Status and Modes


Object status and modes are presented on the event list. When ever the object changes
its status or mode the complete information of the object at the time of the change is
logged in the event list.
The AIS and AIC object event message has a dynamic structure, this means that it can
change depending on the case you have.
The first case for eventing is when some limit value is changed for some limits from the
faceplate. In this case the structure for the event message is the following:
[LIMIT SHORT NAME] + Value: + [OLD VALUE] -> [NEW VALUE]
[LIMIT SHORT NAME] Description
L1 Low limit 1
L2 Low limit 2
H1 High limit 1
H2 High limit 2
PHi Process limit high
PLo Process limit low
The OLD VALUE and NEW VALUE correspond exactly to the old and new value of the
limit.
The next case is when some limit is blocked from the faceplate. In this case the structure
for the event message is the following.
Limit Blk: + [LIMIT NAME]
[LIMIT NAME] Description
L1 Low limit 1 is blocked
L2 Low limit 2 is blocked
H1 High limit 1 is blocked
H2 High limit 2 is blocked
PHi Process limit high is blocked
PLo Process limit low is blocked
The 3rd and last case of event messages in AIS and AIC is when we have a forced
condition for the MV value. In this case three types of messages are possible:
§ When the Forced flag is selected the message is:
FRC Value: [VALUE]
Where value is the actual value set for the MV value:
§ When the Forced selection is undone the message is:
FRC Deselected
§ Or when MV value is changed under forced condition, the message is:
FRC Value: [OLD VALUE] -> [NEW VALUE]

3.3.3.2 Alarm Messages


For the AIS and AIC we have basically 3 main conditions for the alarm messages
§ Limit H2 or L2
§ Limit H1 or L1
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 42
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

§ ROC (Rate of change)


§ Signal Error

F Notice that Process Limit (PLo/PHi) does not create any alarm. The maximum
indication treatment for the Process Limit is 0 (event) as described in the parameter
description.

For the alarm limits (Limits H2, L2, H1 and L1) the message will always be:
[LIMIT TYPE]: [LIMIT VALUE]
[LIMIT TYPE] Description
L1 Low limit 1 is reached
L2 Low limit 2 is reached
H1 High limit 1 is reached
H2 High limit 2 is reached
PHi Process limit high is reached
PLo Process limit low is reached
Limit Value is the number defined over the Lim1 and Lim2 Tab for each Limit Type.
ROC is the rate of change for the MV values in a normal scale (0-100% of the total range).
It will create an alarm after the rate of change in seconds for the MV value is higher then
the one defined in the faceplate over the Lim2 tab.
When a ROC appears, the following message is shown in the alarm list:
ROC [ROC HIGH LIMIT]
Where the ROC HIGH LIMIT is the value set over Lim2 faceplate tab.
The signal error alarm is created every time a hardware failure which that analog input is
connected is encountered. If the configured Signal Error Delay Time is bigger than 0
seconds, a warning alarm will be sent immediately. The message for both, the warning
and the alarm, is defined as:
SigErr

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 43
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4 AO Analogue Output

4.1 BASIC DESCRIPTION


The Control Module Types AOS and AOC are used to access and control an analogue
output.
· AOS module is used to control (write) one analogue output process signal
· AOC module is used to control (write) one analogue output calculated signal, that is
to be indicated on the operator station and that will have no alarm limit control.

The analog output module provides the following features:


· Automatic control from a superior application
· Manual control from the Operator Station (via the faceplate)
· Tracking of mode and output changes
· Output limitation high/low
· On-Line trend with actual output value shown in the faceplate.
· All Substatus for IO and FF Filed Device will generate error control when quality is
Bad or Uncertain for AOS Control Module
· Process Panel Interface

4.2 CONTROL

4.2.1 Diagram Graphical Representation AOS


The default view is shown, it’s possible to modify the visible ports in CBM.

4.2.2 Diagram Graphical Representation AOC


The default view is shown, it’s possible to modify the visible ports in CBM.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 44
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.2.3 Parameter description

4.2.3.1 Parameter AOS


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AOS (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AOS
3 IO AOSData 1 in_out IN/OUT: Connection to AOSData variable (do not
connect to PID or VVVF !)
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on output value changes
in Manual Mode
7 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
8 OutpH real 100 0 in COLD INIT: External and initial high limit for
output limitation
9 OutpL real 0 0 in COLD INIT: External and initial low limit for
output limitation
10 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only

4.2.3.2 Parameter AOC


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the AOC (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the AOC
3 IO AOSData default 1 in_out IN/OUT: Connection to AOSData variable
4 Min real 0 1 in INIT: Scaling Parameter Range.
5 Max real 100 1 in INIT: Scaling Parameter Range Max.
6 Unit string '%' 1 in INIT: Scaling Parameter Unit.
7 Fraction dint 1 1 in INIT: Fraction (Number of Decimals).
8 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
9 ModeTr bool true 0 in IN: True enables events on mode change
10 StatusTr bool true 0 in IN: True enables events on output value changes
in Manual Mode
11 EnExtLimits bool false 0 in IN: false = limit settings from Operate IT, true =
COLD INIT can be used as external limits
12 OutpH real 100 0 in COLD INIT: External and initial high limit for
output limitation
13 OutpL real 0 0 in COLD INIT: External and initial low limit for
output limitation

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 45
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.2.4 Data Type description


Together with the AOS and AOC Control Module Type a Structured Data Type AOSData
is available.
AOSData; components
Name Data Type Attributes Initial Description
Value
SetMan bool retain false IN: Set operation mode to Man. If
permanentaly set to true, selection of
1 Auto is not possible from FCP
SetAuto bool retain false IN: Set operation mode to Auto. If
permanentaly set to true, selection of
2 Manual is not possible from FCP
H bool retain false OUT: High limit output
3 nosort
L bool retain false OUT: Low limit output
4 nosort
5 AutoValue real retain 0.0 IN: Value reference in Auto Mode.
Man bool coldretain false OUT: Indication of Operation mode Man
6 nosort
SigErr bool retain false OUT: Indication of Signal Error
7 nosort
Signal RealIO retain IN/OUT: Signal to be connected to the
nosort S800 HW I/O
displayval
8 ue
ProcessPa PanelLinkAOS retain Interface from / to ProcessPanel
9 nel
For AOS, use the Data type structure:
Write: IO.<TagName>.AutoValue
Together with IO.<TagName>.SetAuto
Read: IO.<TagName>.Signal.Value

For AOC, use the Data type structure:


Write: IO.<TagName>. AutoValue
Together with IO.<TagName>.SetAuto
Read: IO.<TagName>.Signal.Value

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 46
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

PanelLinkAOS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (NoError, SignalErr)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 ManOut real Coldretain Manual Output Signal from Process Panel to
nosort Basic Object
hidden
4 EnManOutFld bool Retain Enabling of Input Field (Manual Output)
nosort
hidden

Status; Bits

Name Bit
Position
1 NoError 0
2 SignalErr 1

Cmd; Bits

Name Bit
Position
1 Auto 0
2 Man 1

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 47
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3 OPERATION

4.3.1 Graphic elements


Graphic Element Description Example
AOSandUnit or
Value and unit indication
AOCandUnit

AOSBar or AOCBar Bar indication

AOSIncDec or Command button to increase /


AOCIncDec decrease the value.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 48
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.1.1 AOSandUnit or AOCandUnit


The value and unit presents the output value, it allows direct entry of the value.

4.3.1.1.1 Presentation
Indication Type Description Example
Value indication.
Value and Unit Used in Graphic Displays.

4.3.1.1.2 Status
Object status Symbol color

Value in normal range Value pink

4.3.1.1.3 Labels
Description Indication
Mode auto No indication of the default mode

Mode manual

Output Signal is Blocked /


Forced

Examples:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 49
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.1.1.4 Properties
Name DataType Default Value Description
EnableBackAppearance Boolean False Switch on the value and unit back
appearance
EnableFitToBestSize Boolean True Set best unit size
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all
used colors are logical colors. The
logical color reference is equal to the
default logical color used in the color
properties. To use an individual color
set it to false.
EnableModeManualLabel Boolean True Show mode manual label
EnableUnit Boolean True Show units
NumberOfDigits Integer 4 Number of presented digits
UnitSize Integer 8 Unit size in pixel: 7 = Small, 8 =
Standard, 10 = Large, 12= XXL
ValueColor Color BMIvalueOUT Value color. Only applied if
EnableLogicalColor is set to false.
ValueSize Integer 12 Value size in pixel: 8 = Small, 10
Medium, 12 = Standard, 14 = Large,
16 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 50
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.1.2 AOCBar or AOSBar


AOS and AOC bar presents the analogue value as bar. Alarm or process limits are
graphical shown and different bar graph appearances are possible.

4.3.1.2.1 Presentation
Appearance Description Example

Standard
This is the standard appearance of the bar graph. The value will
0 be indicated in relation to the maximum and minimum range. The
green bar will always start from the minimum range.

Start from Pivot


1 Use this appearance to start the bar graph from another value
than the minimum range. The related property is “Pivot”.

Inverse
2 The bar will be inverse to the standard appearance.

Line
3 The value will be indicated as a small line instead of a bar.

4.3.1.2.2 Status
Example Object status Symbol color

Output Range Yellow cross pattern

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 51
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.1.2.3 Labels
Description Indication
Output Signal is Blocked /
Forced

Signal Quality Bad

Mode manual

Example:

4.3.1.2.4 Properties
Name DataType Default Value Description
Appearance Integer 0 0 = Standard, 1 = Start from Pivot, 2 =
Inverse, 3 = Line
BarColorCustom Color BMIbarOUT Bar color. Only applied if
EnableLogicalColor is set to false.
EnableLogicalColor Boolean True If EnableLogicalColor is true, then all used
colors are logical colors. The logical color
reference is equal to the default logical
color used in the color properties. To use
an individual color set it to false.
EnableManualRange Boolean False If set to true, the bar's range can be set
manually
EnableModeManualLabel Boolean True Show mode manual label
Pivot Real 0. Used together with Appearance = 1 (Start
from Pivot). The bar will start from the
value set as pivot.
RangeMax Real 100. Maximum range if EnableManualRange is
true
RangeMin Real 0. Minimum range if EnableManualRange is
true
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 14 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
VerticalBar Boolean True VerticalBar: True = vertical appearance,
false = horizontal appearance
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 52
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.1.3 AOCIncDecButton or AOSIncDecButton


Command button to increase or decrease the object value.

4.3.1.3.1 Presentation
IndicationType Example
1

4.3.1.3.2 Status
Status Example
Ready

Disabled

Status Quality Bad

Action in Progress
(Feedback active)

4.3.1.3.3 Properties
Name DataType Default Value Description
Action Action Direct Controls the action type, i.e. whether the button
has direct or applied (two step oparation) action.
ButtonType Integer 0 0 = Increase, 1 = Decrease
IndicationType Integer 1 1 = Arrow, 2 = OpenArrow, 3 = StealthArrow, 4 =
Diamond, 5 = Rectangle, 6 = Oval, 7 = Line, 8 =
Triangle
SubscriptionRate Integer 0 The update rate for all aspect object properties
subscribed for
SymbolOrientation Real 0. Orientation in degree, clockwise
SymbolSize Integer 12 Symbol size in pixel: Little = 8, Small = 12,
Standard = 14, Large = 18, XXL = 22
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 53
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.2 Faceplate

4.3.2.1 Aspect Link and Command Buttons


The following aspect view buttons are available on AOS and AOC Faceplates
Icon Aspect View
Alarm List

Event List

Single Trend

Operators Note

Faceplate Documentation, reference to this document


The following command buttons are available on AOS and AOC Faceplates
Icon Operation Mode
Manual: Output value is defined in faceplate

Auto: Value is written from application

4.3.2.2 Default View

Tagname
&
Description

Operation Mode
indication

Output Value
indication Mini Trend
Output Value

Graphical Bar
Output value and
limits

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 54
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.2.3 Extended View

Auto Mode

F Operation Mode Auto: output value (OUT) written from the application. The value of
the AOS/AOC actually corresponds to the output value.

Manual Mode

F Operation Mode Man: output value (OUT) entered from the faceplate. The value of the
AOS/AOC corresponds to the output value. The Auto value indicates the actual value
coming from the application.
The last entered value in Man mode will be preserved during a cold restart.

Furthermore, the faceplate extended view gives more detailed information about the
Analog Output, such as:
Tab Description
Trend Mini trend of output value, IO value and auto value
Limit Limits for output value
Block - Output Blocking
- Alarm Blocking
IOStatus Sub status for IO and FF Field Devices

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 55
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.2.3.1 Trend
On-Line trend with actual output value and auto value.
Move over the trend area a curser will appear, showing enabled traces’ value and record
time.

Show / Hide Grid

Record Time Show / Hide Traces


Out: Output Signal
IO: Signal
Auto: Auto Signal
4.3.2.3.2 Limits

Reference Table, Limits


Description
High Limit Output High limitation
Low Limit Output Low limitation
Speed Rate of change Limitation for the Output value
Enable Auto Auto Calculation sets the Stepsize to a multiple of 10 times 1 or 5
Calc for Inc/Dec dependent on the Range of the Setpoint
Step
Inc/Dec Step If “Enable Auto Calc for Inc/Dec Step” is not set, the Stepsize used for the
Inc/Dec Buttons and the Direct Entry Window can be set manually
Enable relative If set, the Max Increase / Decrease Values are enforced
Limits for Entry
Window

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 56
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Description
Max Increase The Direct Entry Window’s high limit is set to the current Value plus the
Value given here
Max Decrease The Direct Entry Window’s low limit is set to the current Value minus the
Value given here

4.3.2.3.3 Override

F The IO value (process output value) indicates the “frozen” output value before forcing.
The Auto value indicates the actual value coming from the application.

Reference Table, Block


Description
Block Output Block an output value. Value going to the process (IO value) is frozen and can
be forced later on, by changing the IO value.

4.3.2.3.4 IOStatus

All Sub-statuses for IO Devices in Quality Bad or Uncertain will be indicated as Signal
Error in the Faceplate.
An Aspect Link giving access to the “Device Management” Object can be configured via
the “BMI DTM Link” General Properties Aspect. See AIS MVStatus for details.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 57
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.2.4 Faceplate Control Permission


By the Property Attribute Override Aspect, the faceplate Write permissions (IntPar) can be
configured according the plants access and permission concept. This can be done in the
Control Structure or in the Object Type Structure.

F Note that forcing to a Value in the Faceplate does require Write permission for
IO.Signal.IOValue and IO.Signal.Forced, these are not set on IntPar Variables.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 58
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

4.3.3 Alarm & Event List

4.3.3.1 Object Status and Modes


The following conditions creates a event message for AOS and AOC.
· Mode changes from Auto to Manual and vice versa.
· When OUT value is changed (only in manual mode).

Then, the structure of the message will always be:


[MODE] + Value: + [Value]
Or
[MODE] + Value: + [Old Value] + -> + [New Value]

Where mode can be:


[MODE] Description
Aut Auto Mode
Man Manual Mode
In the second case, will just appear when Out value is different from the old value when
changing the modes or in manual mode, where all changes are tracked.

4.3.3.2 Alarm Messages


For the AOS and AOC object there is not generation of alarms.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 59
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5 DI Digital Input

5.1 BASIC DESCRIPTION


The Control Module Type DIS and DIC are used to access and control a digital input.
· DIS module is used to read one digital input signal, coming from the process
· DIC module is used to write a calculated signal from the application, that is to be
indicated on the operator station and that will have alarm indication.
The digital input module provides the following features:
· Blocking and forcing of input value
· Alarming if input value differs from pre-defined (healthy; normal position) state
· Warning delay time to generate a pre warning alarm or event before the main alarm
(failure) occurs.
· Ready Delay time to hold the alarm position in order to prevent noisy signals to clear
and re-activate the alarm very often.
· Alarm delay
· Alarm blocking (from faceplate). All alarms and warnings will be blocked.
· Alarm disabling/enabling (from application program)
· On-Line trend with actual input value
· Minerals Library Process Control Connection (PCC)
· Parameterized interlocks towards parent objects
· Advanced alarm disabling from parent objects
· Process Panel Interface

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 60
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.2 CONTROL

5.2.1 Diagram Graphical Representation DIS


The default view is shown, it’s possible to modify the visible ports in CBM.

5.2.2 Diagram Graphical Representation DIC


The default view is shown, it’s possible to modify the visible ports in CBM.

5.2.3 Parameter description

5.2.3.1 Parameter DIS


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DIS (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DIS
3 IO DISData 1 in_out IN/OUT: Connection to DISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 ExtTimeStamp bool false 0 in INIT: False = Signal is monitored; True =
SignalID is monitored with external time stamp
7 SignalID string '' 0 in INIT: Identifier of the signal with external time
stamp. Valid when ExtTimeStamp = True
8 UseSigToInit bool false 0 in INIT: True = Use Signal to get an init value. Valid
when ExtTimeStamp = True
9 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
10 AETxt string cBMI.Empty 1 in INIT: Alarm Message description (e.g. Pull Rope
_str Switch, Level High) for NLS support use
||AE_NLS_ preffix and no space in the text
11 ValTr dint 3 0 in INIT: Alarm Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
12 WarnValTr dint 2 0 in INIT: Warning Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 61
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


13 NormPos bool true 1 in IN: Normal position of the DI signal. Alarm is
activated when signal is not in this position.
14 IntlkTypeAlarm dint No_Interlock 1 in INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
15 IntlkDirAlarm dint DirXY 1 in INIT: 1:DirX/Y/XY+Fast+noAck;
2:DirX/Y/XYFB+Fast+noAck;
3:DirX/Y/XYStart+noAck; Ex. DirX,
DirXFastnoAck, noAck=Acknowledge not need
16 IntlkTypeWarni dint No_Interlock 0 in INIT:
ng PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
17 IntlkDirWarnin dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;
g DirXYStart
18 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after
start of PCC parent (MOTx, VLVx), Start by Ord
instead of Run where the IntlkDir is DirFB#
19 IntlkLocStartO bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStart
verride is continuously pushed. All PCC parents need to
be in LOC.
20 ErrCtrl bool true 0 in IN: Action in case of Signal Error: false = no
action; true = IO.SigHW.Value forced to NOT
Norm_Pos
21 AlarmDelay time 0s 0 in COLD INIT: Initial time delay before the Alarm is
activated after the signal has left the Normal
Position
22 WarnDelay time 0s 0 in COLD INIT: Initial time delay before the Warning
is activated after the signal has left the Normal
Position
23 ReadyDelay time 0s 0 in COLD INIT: Initial time delay before the Warning
or Alarm is reset after the signal is returned to
the Normal Position
24 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms.
25 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only

For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.

5.2.3.2 Parameter DIC


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DIC (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DIC
3 IO DISData 1 in_out IN/OUT: Connection to DISData variable
4 PCC PCCComDat Default 1 out IN/OUT: Interlock Bus,
a PriorityCommand/Interlock to motors, valves or
groups
5 PCCAEListFrc bool false 0 in IN: PCC AE List handling forced to be always on
En and not controlled by PCC parent
6 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
7 AETxt string cBMI.Empty 1 in INIT: Alarm Message description (e.g. Pull Rope
_str Switch, Level High) for NLS support use
||AE_NLS_ preffix and no space in the text
8 ValTr dint 3 0 in INIT: Alarm Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
9 WarnValTr dint 2 0 in INIT: Warning Treatment: -1 no AE; 0 = Event ;
1,2,3 = ALPrio# (1=lowest)
10 NormPos bool true 1 in IN: Normal position of the DI signal. Alarm is
activated when signal is not in this position.
11 IntlkTypeAlarm dint No_Interlock 1 in INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 62
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Initial Value Port Direction Description


12 IntlkDirAlarm dint DirXY 1 in INIT: 1:DirX/Y/XY+noAck;
2:DirFBX/Y/XY+noAck;
3:DirX/Y/XYStart+noAck;Ex.DirFBX,DirXnoAck,n
oAck=Acknowledge not need if value back to
NormPos
13 IntlkTypeWarni dint No_Interlock 0 in INIT:
ng PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Pr
ocess;IA_Process_RFS;IB_Equipment;IB_Equip
ment_RFS;IC_Safety;IC_Safety_RFS;Auto_Start
14 IntlkDirWarnin dint DirXY 0 in INIT: DirX; DirXStart; DirY; DirYStart; DirXY;
g DirXYStart
15 IntlkStartInhibit time 0s 0 in INIT: Bypass Interlock for a certain time after
start of PCC parent (MOTx, VLVx), Start by Ord
instead of Run where the IntlkDir is DirFB#
16 IntlkLocStartO bool false 0 in INIT: Bypass Interlock in LOC mode if LCBStart
verride is continuously pushed. All PCC parents need to
be in LOC.
17 AlarmDelay time 0s 0 in COLD INIT: Initial time delay for the Norm_Pos
handling
18 WarnDelay time 0s 0 in COLD INIT: Initial time delay before the Warning
is activated after the signal has left the Normal
Position
19 ReadyDelay time 0s 0 in COLD INIT: Initial time delay before the Warning
or Alarm is reset after the signal is returned to
the Normal Position
20 AlarmAck bool false 0 in IN pulse: Acknowledge the alarms.

For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.

5.2.4 Data Type description


Together with the DIS and DIC Control Module Type a Structured Data Type DISData is
available.
DISData; components
Name Data Attributes Initial Description
Type Value
retain IN true: External Alarm Enabling of DIS, temporary
1 AlarmEn bool nosort TRUE blocking of alarming and interlocking
IN true: External Alarm List Enabling of DIS,
retain temporary disabling of unack alarming and entries
2 AEListEn bool nosort TRUE in alarmlist
OUT: Indication of Signal Error (e.g. S800
3 SigErr bool retain FALSE Hardware Error)
retain OUT: Treated Signal to be used for process
4 Signal BoolAL nosort interlocks in glue logic
OUT: Pre Warning Signal can be used for process
retain control in glue logic, true if object is in prewarning
5 PreWarning bool nosort state
retain IN/OUT: Signal to be connected to the S800 HW
6 SigHW BoolIO nosort I/O
Process PanelLin
7 Panel kDIS retain Interface from / to Process Panel
8 Name string[24] retain Name of DIS/DIC

For DIS, use the Data type structure:


Write: not available, use DIC control module if the signal
shall be written from Glue Logic
Read: IO.<TagName>.Signal.Value
Interlock: IO.<TagName>.Signal.Normal
For DIC, use the Data type structure:
Write: IO.<TagName>. SigHW.IOValue
Read: IO.<TagName>.Signal.Value
Interlock: IO.<TagName>.Signal.Normal
Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 63
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

PanelLinkDIS; components
Name Data Attributes Initial Description
Type Value
1 Status dint Retain Object Status (Ready,Event, Warning etc.)
nosort
hidden
2 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
3 SignalValue bool Retain Signal Value to Process Panel
nosort
hidden
4 Blink bool Retain Enabling of Basic Object Blinking
nosort
hidden

Cmd; Bits

Name Bit
Position
1 AlarmAck 0

5.2.5 Project Constants


Name Data Type Default Value
1 cBMI.DIS.DisabledIntMaxIndTr dint (dint): 13

5.2.6 PCC Interlock Limitations


The “Fast” Interlock configuration Option is not supported by the DIC CM. If IntlkDir is
configured as Fast (e.g. DirXFast, DirXYFastnoAck) the Interlock will still be executed as
but without the “Fast” option, and the FPL will indicate PCC Param Error.
For explanation of the different configuration options see chapter PCC Interlock Parameter
Description.

Any Interlock defined by IntlkTypeWarning / IntlkDirWarning is only active


before the Alarm, while IO.PreWarning is false and IO.Signal.Normal is still
true (see 5.3.1 for a diagram).
This means that the PCC Parameter for Alarm should always be set to an
Interlock with priority equal or higher than the Interlock defined for Warning.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 64
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3 OPERATION

5.3.1 Time Diagram


For the DIS and DIC, the following timing diagram shows the behaviour with Delays set:
AlarmDelay not NormPos
SigHW.Value WarnDelay ReadyDelay WarnDelay t<ReadyDelay ReadyDelay
NormPos
TRUE
Signal.Normal
FALSE
TRUE
IO.Prewarning
FALSE

The Alarm Condition is defined as SigHW.Value being different to NormPos. Warning


delay is the time between an Alarm Condition occurs until IO.Prewarning is set to true.
Alarm delay is the time between an Alarm Condition until the Alarm is generated and
Signal.Normal, used in the glue logic as Interlock to Consumers, becomes false.
Ready delay is the time to disable IO.Prewarning or set Signal.Normal to true after the
Alarm Condition has disappeared. Note that if the AlarmCondition comes back, the Ready
Delay Timer will be reset. In case this happens during Prewarning is set, the whole
AlarmDelay time will be needed to change Signal.Normal again.
Warning delay, alarm delay and ready delay can be set from the faceplate.
The NormPos is a parameter set thru Control Builder in order to define the normal position
for the signal, which means, the value of the signal that will not create any warning or
alarm.

5.3.2 Graphic elements


Graphic Element Description Example

DIS or DIC Signal status and alarm indication.

DISTxt or DICTxt Signal status or alarm text indication

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 65
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.2.1 DIS or DIC


This element presents the value and alarm of a digital input as symbol.

5.3.2.1.1 Presentation
Indication Type Example
A00_Rectangle

A01_Motor

A02_Valve

A03_MotorM

A04_Pump

A05_Fan

A06_RotaryFeeder

B11_Damper

B12_Shut

B13_Diverter

B14_LouvreDamper

B15_AirslideDiverter

B16_PropRoller

C31_Valve3way

C32_ValveMan

C33_ValveAuto

E07_Triangle

E08_Lollipop

E09_Diamond

E21_GearwheelPump

E41_Generator

E42_Switch

E77_BeltCleaner

E99_TagName

F00_None

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 66
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.2.1.2 Status
Object status Symbol color
OFF Grey

OFF / ALARM Grey / red thick frame

ON Green

ON / ALARM Green / red thick frame

5.3.2.1.3 Labels
Description Indication

Status blocked

Example:

5.3.2.1.4 Properties
Name DataType Default Value Description
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
Inverse Boolean False Inverse indication of on/ off status
MirrorPosition Boolean False Mirrors position left / right and open / close
indication
Orientation Integer 0 Rotate symbol clockwise 0 - 360 °
SensorText String "X" Sensor text if IndicationType = E08_Lollipop
SymbolSize Integer 16 8 = Litle, 12 = Small, 16 = Standard, 20 =
Large, 24 = XXL
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 67
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.2.2 DISTxt or DICTxt


Digital Input text can be used to create small error labels on process graphic displays, or
overlap displays with meaningful interlock texts. The text appearance can be configured to
show the text only on alarm, depending on the value, always but with different colours
depending on value or alarm condition.

5.3.2.2.1 Presentation
Indication Type Example

Text with background color

Square in front of text

Text colored

5.3.2.2.2 Status
Object status Symbol color
Normal Position for
Appearance Types, 0 = Alarm, 2 Gray dimmed (semitransparent)
= value
Normal Position for
Appearance Types, 10 = Alarm, Green
12 = Value interlock

Abnormal Position Red

5.3.2.2.3 Labels
Description Indication

Status blocked

Example:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 68
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.2.2.4 Properties
Name DataType Default Value Description
AppearanceType Integer 0 0 = Alarm, 2 = Value, 3 = Value custom color,
10 = Alarm interlock, 12 Value interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value custom
color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value custom
color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableNormalPos Boolean True If false, symbol and text are not visible in
NormalPos.
Font Font Font( "Arial" ,10 Text font when EnableFont is true
,Regular, Bold)
IndicationType Integer 0 0 = Text with background color, 10 = Square in
front of text, 20 = Text colored
NormalPos Boolean False Used for AppearanceType 2 = Value, 3 = Value
custom color, 12 = Value Interlock
SubscriptionRate Integer 0 The update rate for all aspect object properties
subscribed for
SymbolSize Integer 12 Defined the square size in case of
IndicationType = 10
TextBold Boolean True Text style is bold
TextIndAbnormalPos String "On" Text for abnormal position
TextIndNormalPos String "Off" Text for normal position
TextSize Integer 10 Text size in pixel: 8 = Small, 10 = Standard, 12
= Large, 16 = XXL
TextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos, 2 = OPC Text, 3 = NLS Text

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 69
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3 Faceplate

5.3.3.1 Aspect Link and Command Buttons


The following aspect view buttons are available on DIS and DIC Faceplates
Icon Aspect View
Alarm List

Event List

Operators Note

Faceplate Documentation, reference to this document

5.3.3.2 Default View

Tagname
&
Description

DIS: input signal


from the process
Time to Failure
(if Alarm Delay > DIC: calculated
Warning Delay) signal from the
application

Alarm or Event
Message Text

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 70
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3.3 Extended View

The faceplate extended view gives more detailed information about the Digital Input,
such as:
Tab Description
Trend Mini trend of output value and value from process (DIS) or application
(DIC)
Parameter Alarm, Warning and Ready Delay
Block - Input Blocking
- Alarm Blocking
PCC - PCC interlock configuration summery
- Link to connected consumer or consumer overview list

5.3.3.3.1 Trend
On-Line trend with actual input value.
Move over the trend area a curser will appear, showing enabled traces’ value and record
time.

Show / Hide Grid

Show / Hide Traces


Out: Output Signal
IO: input signal from
the process (DIS) or
calculated signal from the
Record Time application (DIC)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 71
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3.3.2 Parameters
Setting of Alarm, Warning and Ready Delay

Reference Table, Parameters


Description
Ready Delay Time delay before the Warning or Alarm is reset after the signal is
returned to the Normal Position.
Warning Delay Time delay between the signal leaving the normal position and pre-
warning. Incase Warning Delay = Alarm Delay no pre-warning will occur.
Alarm Delay Time delay between the signal leaving the normal position and alarm /
failure. Alarm Delay must be >= Warning Delay.

5.3.3.3.3 Block / Override


Block / Force Input

Block Alarm

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 72
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Reference Table, Block


Description
Block Input The digital input will be “forced” on controller hardware input level.
The IO Value shows the actual value in the process. Alarm handling remains
active.
Block Alarm The alarm treatment will be blocked. No alarm messages will be sent to the
operator station.

5.3.3.3.4 PCC
PCC interlock configuration:

The PCC interlock configuration tab shows the actual configuration and a link to the
parent object.

If the PCC interlock configuration via parameter “IntlkTypeAlarm”/“IntlkDirAlarm” resp.


“IntlkTypeWarn”/“IntlkDirWarn” is wrong, a yellow coloured error message “PCC Intlk
Param Error” will be displayed.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 73
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.3.4 Faceplate Control Permission


By the Property Attribute Override Aspect, the faceplate Write permissions (IntPar) can be
configured according the plants access and permission concept. This can be done in the
Control Structure or in the Object Type Structure.

F Note that forcing to a Value in the Faceplate does require Write permission for
IO.SigHW.Value and IO.SigHW.Forced, these are not set on IntPar Variables.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 74
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

5.3.4 Alarm & Event List

5.3.4.1 Object Status and Modes


For eventing in DIS and DIC we have the in forced condtion case, which can be:
§ When the Forced flag is selected the message is:
FRC Value: [VALUE]
Where value is the actual value is the IO.SigHw.Value
§ When the Forced selection is undone the message is:
FRC Deselected
§ Or when IO.SigHW.Value value is changed under forced condition, the message
is:
FRC Value: [OLD VALUE] -> [NEW VALUE]

5.3.4.2 Alarm Messages


For the DIS, an alarm message is generated when the Signal.Value is different of
NormPos parameter and the AlarmDelay time is elapsed. Then the message is the
following:
[AETxt] + [Severity]
Where AETxt is a parameter defined over DIS parameters in the Control Builder and for
severity the text can also be changed but then over BMIConstAndVar constants,
depending on the severity.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 75
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6 DO Digital Output

6.1 BASIC DESCRIPTION


The Control Module Types DOS and DOC are used to access and control a digital output.
· DOS module is used to control (write) one digital output process signal
· DOC module is used to control (write) one digital output calculated signal, that is to be
indicated on the operator station and that will have no alarm indication.

The digital output module provides the following features:


· Automatic control from a superior application
· Manual control from the Operator Station (via the faceplate)
· Tracking of mode and output changes
· On-Line trend with actual output value shown in the faceplate.
· Process Panel Interface

6.2 CONTROL

6.2.1 Diagram Graphical Representation DOS


The default view is shown, it’s possible to modify the visible ports in CBM.

6.2.2 Diagram Graphical Representation DOC


The default view is shown, it’s possible to modify the visible ports in CBM.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 76
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.2.3 Parameter description

6.2.3.1 Parameter DOS


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DOS (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string 'Description' 1 in IN: Description text of the DOS
3 IO DOSData 1 in_out IN/OUT: Connection to DOSData variable
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on status (on/off)
change
7 Simulation bool false 0 in IN: TRUE = override signal error indication in
Operate IT, used for simulations only

6.2.3.2 Parameter DOC


No Name Data Type Initial Value Port Direction Description
1 Name string 'Name' 1 in INIT: Tag name of the DOC (allowed
deliminators are "." and "-", no blanks ":" or ";"
allowed)
2 Description string 'Description' 1 in IN: Description text of the DOC
3 IO DOSData default 1 in_out IN/OUT: Connection to DOSData variable
4 Class dint 1 0 in INIT: AE Class 1 ... 9999 (Section)
5 ModeTr bool true 0 in IN: True enables events on mode change
6 StatusTr bool true 0 in IN: True enables events on status (on/off)
change

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 77
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.2.4 Data Type description


Together with the DOS and DOC Control Module Type a Structured Data Type DOSData
is available.
DOSData; components
Name Data Attributes Initial Description
Type Value
IN: Set operation mode to Man. If permanentaly set
1 SetMan bool retain to true, selection of Auto is not possible from FPL
IN: Set operation mode to Auto. If permanentaly set
2 SetAuto bool retain to true, selection of Manual is not possible from FPL
3 AutoValue bool retain FALSE IN: Value reference in Auto Mode.
coldretain
4 Man bool nosort FALSE OUT: Indication of Operation mode Man
retain
5 SigErr bool nosort FALSE OUT: Indication of Signal Error
retain
6 Signal BoolIO nosort IN/OUT: Signal to be connected to the S800 HW I/O
Process PanelLin
7 Panel kDOS retain Interface from / to Process Panel
For DOS, use the Data type structure:
Write: IO.<TagName>.AutoValue
Together with IO.<TagName>.SetAuto
Read: IO.<TagName>.Signal.Value
For DOC, use the Data type structure:
Write: IO.<TagName>. AutoValue
Together with IO.<TagName>.SetAuto
Read: IO.<TagName>.Signal.Value

PanelLinkDOS; components
Name Data Attributes Initial Description
Type Value
1 Cmd dint Retain Object Commands from Panel to Basic Object
nosort
hidden
2 SignalValue bool Retain Signal Value to Process Panel
nosort
hidden
3 ConEn bool Retain Enabling of Control
nosort
hidden

Cmd; Bits

Name Bit
Position
1 On 0
2 Off 1
3 Auto 2
4 Man 3
5 AlarmAck 4

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 78
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3 OPERATION

6.3.1 Graphic elements


Graphic Element Description Example
Signal status indication.
DOS or DOC Used in Graphic Displays.

DOSTxt or DOCTxt Signal status text indication

DOSButton or DOCButton Command button

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 79
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.1 DOS or DOC

6.3.1.1.1 Presentation
Indication Type Example
A00_Rectangle

A01_Motor

A02_Valve

A03_MotorM

A04_Pump

A05_Fan

A06_RotaryFeeder

B11_Damper

B12_Shut

B13_Diverter

B14_LouvreDamper

B15_AirslideDiverter

B16_PropRoller

C31_Valve3way

C32_ValveMan

C33_ValveAuto

E07_Triangle

E08_Lollipop

E09_Diamond

E21_GearwheelPump

E41_Generator

E42_Switch

E77_BeltCleaner

E99_TagName

F00_None

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 80
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.1.2 Status
Object status Symbol color
OFF Grey

ON Green

6.3.1.1.3 Labels
Description Indication

Status blocked

Mode auto
No indication of the default mode
Mode manual

Example:

6.3.1.1.4 Properties
Name DataType Default Value Description
EnableModeManualLabel Boolean True Show mode manual label
EnableObjectStatusColor Boolean False If set to false, the status color
depends on the indication type, else
the logical DO colors are used.
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
Inverse Boolean False Inverse indication of on/ off status
MirrorPosition Boolean False Mirrors position left / right and open /
close indication
Orientation Integer 0 Orientation
SymbolSize Integer 16 SymbolSize
For common settings and symbol logical colors please refer to [1] Minerals Library
Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 81
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.2 DOSTxt or DOCTxt

6.3.1.2.1 Presentation
Indication Type Example

Text with background color

Square in front of text

Text colored

6.3.1.2.2 Status
Object status Symbol color

Normal Position Gray dimmed (semitransparent)

Normal Position
(Appearance Type: Value Green
interlock)

Abnormal Position Red

6.3.1.2.3 Labels
Description Indication

Status blocked

Example:

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 82
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.2.4 Properties
Name DataType Default Value Description
AppearanceType Integer 0 2 = Value, 3 = Value custom color, 12
Value interlock
ColorAbnormalPos Color Lime Used for AppearanceType 3 = Value
custom color
ColorNormalPos Color RGB(159,159,159) Used for AppearanceType 3 = Value
custom color
EnableFont Boolean False Enable the Font property
EnableLogicalColor Boolean True To use an individual color set it to false
EnableModeManualLabel Boolean True Show mode manual label
EnableNormalPos Boolean True Hide symbol in normal position
Font Font Font( "Arial" ,10 Text font when EnableFont is true
,Regular, Bold)
IndicationType Integer 0 0 = Text with background color, 10 =
Square in front of text, 20 = Text colored
NormalPos Boolean False Used for AppearanceType 2 = Value, 3
= Value custom color
SubscriptionRate Integer 0 The update rate for all aspect object
properties subscribed for
SymbolSize Integer 12 Defined the square size in case of
IndicationType = 10
TextBold Boolean True Text style is bold
TextIndAbnormalPos String "On" Text for abnormal position
TextIndNormalPos String "Off" Text for normal position
TextSize Integer 10 Text size in pixel: 8 = Small, 10 =
Standard, 12 = Large, 16 = XXL
TextSource Integer 1 0 = None, 1 = TextIndAbnormalPos /
TextIndNormalPos, 2 = OPC Text, 3 =
NLS Text
For common settings please refer to [1] Minerals Library Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 83
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.3 DOSButton or DOCButton


Digital Output buttons allow sending of commands from the operator station. The type of
the command e.g. toggle, pulse, while down can be selected by properties. The button
can contain a symbol showing the feedback or text. The bar on top of the button can be
switched off.

6.3.1.3.1 Presentation
Indication Type Description Example

Button Command Button.

6.3.1.3.2 Status
Object status Symbol color

Feedback signal Off Light gray steady

Feedback signal On Green steady

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 84
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.1.3.3 Properties
Name DataType Default Value Description
Action Action SystemDefault Controls the action type, i.e.
whether the button has direct or
applied (two step oparation)
action. Used only for ButtonType
= 0 (toggle) and ButtonType = 1
(single pulse)
ButtonType Integer 0 0 = toggle, 1 = single pulse, 2 =
while down: set signal, 3 = while
down: alternate, 4 = set signal, 5
= reset signal
EnableColorBar Boolean True If true the colored bar on top of
the button is presented.
EnableObjectStatusColor Boolean False If set to false, the status color
depends on the indication type,
else the logical DO colors are
used.
EnableStoreMode Boolean True After an action the original mode
will be restored
EnableSymbol Boolean True Show button with symbol
EnableWriteWhenAuto Boolean True If true, the button is enabled in
manual and auto mode
FeedBackSignal Boolean False If property FeedBackType = 1
then this property is used as the
feed back signal
FeedBackType Integer 0 0 = DO value, 1 = feedback
signal
IndicationType IndicationTypeEnum A00_Rectangle Symbol type selection
PulseTime Integer 1 Pulse time in seconds
SymbolPos Integer 5 1 = top left, 2 = top center, 3 =
top right, 4 = center left, 5 =
center center, 6 = center right, 7
= bottom left, 8 = bottom center,
9 = bottom right
SymbolSize Integer 10 8 = small, 10 = standard, 12 =
large, 14 = XXL
Text String "Text" Description text
TextAlign Integer 5 1 = top left, 2 = top center, 3 =
top right, 4 = center left, 5 =
center center, 6 = center right, 7
= bottom left, 8 = bottom center,
9 = bottom right
TextBold Boolean True Enable text style bold
TextSize Integer 10 8 = small, 10 = standard, 12 =
large, 14 = XXL
TextSource Integer 0 0 = None, 1 = Manual, 2 = OPC,
3 = NLS
For common settings and Symbol Logical colors please refer to [1] Minerals Library
Overview (3BHS 161555).

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 85
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2 Faceplate

6.3.2.1 Aspect Link and Command Buttons


The following aspect view buttons are available on AOS and AOC Faceplates
Icon Aspect View
Alarm List

Event List

Operators Note

Faceplate Documentation, reference to this document


The following command buttons are available on AOS and AOC Faceplates
Icon Command Buttons
Set Output Value, only enabled if operation mode is Manual.

Reset Output Value, only enabled if operation mode is Auto.

Operation Mode Manual: Output value is written from faceplate

Operation Mode Auto: Value is written from application

6.3.2.2 Default View

Tagname
&
Description

Operation Mode
indication

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 86
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.3 Extended View

AUTO Mode

F Operation Mode Auto: Output written from the application.

MAN Mode

F Operation Mode Man: Output controlled from the faceplate via the buttons ON and
OFF. The Auto value indicates the actual value coming from the application.
The last entered value in Man mode will be preserved during a cold restart.

Furthermore, the faceplate extended view gives more detailed information about the
Digital Output, such as:
Tab Description
Trend Mini trend of output value and value from process (DOS) or application
(DOC)
Block Output Blocking

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 87
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.2.3.1 Trend
On-Line trend with actual output value and IO value.
Move over the trend area a curser will appear, showing enabled traces’ value and record
time.

Show / Hide Grid

Show / Hide Traces


Record Time Out: Output Signal
IO: IO Signal
6.3.2.3.2 Override

F The IO value (process output value) indicates the “frozen” output value before forcing.
The Auto value indicates the actual value coming from the application.

Reference Table, Block


Description
Block Output Block an output value. Value going to the process (IO value) is frozen and can
be forced later on, to “1” or to “0”

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 88
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.3 Faceplate Control Permission


By the Property Attribute Override Aspect, the faceplate Write permissions (IntPar) can be
configured according the plants access and permission concept. This can be done in the
Control Structure or in the Object Type Structure.

F Note that forcing to a Value in the Faceplate does require Write permission for
IO.SigHW.IOValue and IO.SigHW.Forced, these are not set on IntPar Variables.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 89
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

6.3.4 Alarm & Event List

6.3.4.1 Object Status and Modes


For the DOS and DOC the only event created is when the mode is changed from manual
to auto and vice-versa. Then the following message can be seen:

[MODE] + [VALUE]
[MODE] Description
Aut Auto Mode
Man Manual Mode
And the value can be true or false depending on its status during the mode change

6.3.4.2 Alarm Messages


For the DOS and DOC object, no alarms are generated.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 90
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

7 PCC_Connect_2

7.1 BASIC DESCRIPTION


The Function Block Type PCC_Connect_2 is used to
· assign a Basic Object to 2 consumers / groups
· overwrite the Warning / Failure state to the Basic Object if needed

This Block is Obsolete and should not be used in new Projects.


PCC Interlocks are not forwarded to the consumers. For the full PCC functionality,
PCC_Connect should be used as a direct replacement for PCC_Connect_2.

7.2 CONTROL

7.2.1 Parameter description


No Name Data Type Attributes Direction Port Initial Value Description
1 Name string[20] retain in yes cbmi.Empty_ INIT: Tag name of PCC_Connect
nosort str Block (. : - ok, no blanks allowed!),
used to link from Signal to this Block,
needs to be unique
2 PCCIn1 PCCComD by_ref out yes IN/OUT: Connect to the first Consumer
ata
3 EnPCCIn1 bool retain in yes true IN true: enabling of PCC write from IO
Write nosort to device
4 PCCIn2 PCCComD by_ref out yes IN/OUT: Connect to the second
ata Consumer
5 EnPCCIn2 bool retain in yes true IN true: enabling of PCC write from IO
Write nosort to device
6 PCCOut_ bool retain in yes false IN false: enabling of override for PCC
Override nosort coming from PCCIn1 or 2
7 PCCOut_ bool retain in yes false IN false: overrides Warning X PCC
WarningX nosort coming from PCCIn1 or 2
En
8 PCCOut_F bool retain in yes false IN false: overrides Failure X PCC
ailureXEn nosort coming from PCCIn1 or 2
9 PCCOut_ bool retain in yes false IN false: overrides Warning Y PCC
WarningY nosort coming from PCCIn1 or 2
En
10 PCCOut_F bool retain in yes false IN false: overrides Failure Y PCC
ailureYEn nosort coming from PCCIn1 or 2
11 PCCOut PCCComD in_out yes IN/OUT: To be connected to the IO
ata through a new DataType

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 91
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

7.3 OPERATION

7.3.1 PCC Parent Link


The Function Block contains one Graphic Element that links to all connected PCC
Consumer / Group Objects. As this Element is linked from the signals connected to the
PCCOut Bus, it allows to trace all connections in case a signal is connected to more than
one parent.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 92
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

8 PCC_Connect

8.1 BASIC DESCRIPTION


The Function Block Type PCC_Connect has the same function as the PCC_Connect_2 Block,
but it allows connecting up to 32 Consumers.
Furthermore it supports the PCC Interlock concept:
1. Interlocks by default forwarded to all connected Consumers
2. Individual Interlock forwarding mask for each consumer:
· blocks interlocks if not desired for a specific consumer
· blocking is limit based (DIS: Alarm/Warning; AIS: H2, H1, PHi, PLo, L1, L2)
3. Indication of blocked signals on PCC Bus forwarded to the consumer.
Note that “Fast” interlock is not executed in Fast Task in case the signal is
connected via a PCC_Connect, but the Interlock is still forwarded thru PCC Bus.
Fast interlocking is only supported for a DIS connected directly to the parent in
the same diagram.

8.2 CONTROL

8.2.1 Diagram Graphical Representation


The default view is shown, it’s possible to change the visible ports in CBM.

8.2.2 Parameter description


No Name Data Type Attributes Direction Port Initial Value Description
1 Name string retain in 1 cBMI.Empty INIT: Tag name of PCC_Connect
nosort _str Block (. : - ok, no blanks allowed!),
used to link from Signal to this Block,
needs to be unique
2 SignalPCC bool retain in 0 false IN false: Enabling of override for PCC
_Override nosort coming from all PCCInX
3 SignalPCC bool retain in 0 false IN false: overrides Warning X PCC
_WarningX nosort coming from all PCCInX
En
4 SignalPCC bool retain in 0 false IN false: overrides Failure X PCC
_FailureXE nosort coming from all PCCInX
n
5 SignalPCC bool retain in 0 false IN false: overrides Warning Y PCC
_WarningY nosort coming from all PCCInX
En
6 SignalPCC bool retain in 0 false IN false: overrides Failure Y PCC
_FailureYE nosort coming from all PCCInX
n
7 SignalPCC PCCComD in_out 1 IN/OUT: To be connected to the IO
ata through a new DataType
5+ DrivePCC_ bool retain in 0 true IN true: enabling of PCC write from IO
3n EnWrite[1] nosort to consumer
6+ DrivePCC[ PCCComD by_ref out 1 IN/OUT: Connect to the first Consumer
3n 1] ata

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 93
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Attributes Direction Port Initial Value Description


7+ IntrlkMask[ dword nosort in 1 Transparent INIT:
3n 1] Transparent;NoInterlockForwarding;No
PCCForwarding;DI_Alarm;DI_Warning;
AI_PID_H2;AI_PID_H1;AI_PID_L1;AI_
PID_L2;AI_PID_H12;AI_PID_PHiLo

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 94
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

8.2.3 Interlock Masks


An interlock mask is composed of the following value definitions:
Mask Value Description
1 / 16#001 Interlock Action for H2 (AIS/PID) or Alarm (DIS) to be forwarded
2 / 16#002 Interlock Action for H1 (AIS/PID) or Warning (DIS) to be forwarded
4 / 16#004 Interlock Action for PHi (AIS/PID) to be forwarded
8 / 16#008 Interlock Action for PLo (AIS/PID) to be forwarded
16 / 16#010 Interlock Action for L1 (AIS/PID) to be forwarded
32 / 16#020 Interlock Action for L2 (AIS/PID) to be forwarded
64 / 16#040 Interlock Action for ROC (AIS) to be forwarded
128 / 16#080 Interlock Action for DEVH (PID) to be forwarded
256 / 16#100 Interlock Action for DEVL (PID) to be forwarded

Project Constants are used to ease the reading of the most common configurations
Constant Name Value Description
Transparent 1023 / 16#3FF All defined interlocks on the signal are
forwarded to the consumer
NoInterlockForwarding 0 / 16#0 Regardless of the configuration on the signal
no interlock is forwarded to the consumer
NoPCCForwarding 512 / 16#200 Alarm and interlock forwarding to the
consumer is disabled all together
DI_Alarm 1 / 16#001 Only interlock for DIS alarm is forwarded
DI_Warning 2 / 16#002 Only interlock for DIS warning is forwarded
AI_PID_H2 1 / 16#001 Only interlock for AIS/PID H2 limit is forwarded
AI_PID_H1 2 / 16#002 Only interlock for AIS/PID H1 limit is forwarded
AI_PID_L1 16 / 16#010 Only interlock for AIS/PID L1 limit is forwarded

AI_PID_L2 32 / 16#020 Only interlock for AIS/PID L2 limit is forwarded


AI_PID_H12 3 / 16#003 Interlock for AIS/PID H1 and H2 limit is
forwarded
AI_PID_L12 48 / 16#030 Interlock for AIS/PID L1 and L2 limit is
forwarded
AI_PID_All_H 7 / 16#007 Interlock for AIS/PID PHi, H1 and H2 limit is
forwarded
AI_PID_All_L 56 / 16#038 Interlock for AIS/PID PLo, L1 and L2 limit is
forwarded
AI_PID_PHiLo 12 / 16#00C Interlock for AIS/PID PHi and PLo limit is
forwarded
PID_DevHL 384 / 16#180 Interlock for PID DevH and DevL limit is
forwarded

Custom masks can be created in the project library if desired. The added up values of the
actions to be forwarded shall be defined as dword in hex format.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 95
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

8.2.4 Application Example


In the following example the oil pumps _561_LQ1_M1 and _561_LQ1_M2 or the oil heater
_561_LQ1_H1 should only be started if there is enough oil in the tank. The corresponding
level switch _561_LQ1_L1 is configured as an IB_Equipment interlock. Thru a
PCCComData variable the DIS is connected to the PCC_Connect. Because the interlock
should be defined for all 3 consumers, the IntrlkMask Transparent is used for all of them.

The same example made by CDE graphical representation.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 96
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

The same example as programmed in CBM Diagrams Editor

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 97
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

8.3 OPERATION

8.3.1 PCC Parent Link


The Function Block contains one Graphic Element that links to all connected PCC
Consumer / Group Objects. As this Element is linked from the signals connected to the
SignalPCC Bus, it allows to trace all connections in case a signal is connected to more
than one parent.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 98
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9 PCC_Threshold_AND3

9.1 Basic Description


The Function Block Type PCC_Threshold_AND3 allows handling of complex interlocks.
· Drive Condition (DriveCond) or main condition, which also acts as PCC interlock
according to the configuration, consists of up to 9 sub conditions. Each of these sub
conditions consists of 3 conditions itself.
· Level parameter defines how many of the sub conditions (SubCond) need to be
fulfilled for the DriveCond to be fulfilled.
· Equal defines if the fulfilled number must exactly match Level or if it can be equal and
also higher.
· Indication of blocked signals on PCC Bus forwarded to the consumer.

DriveCond =
SubCond1 or
SubCond2 or
SubCond3
SubCond1 =
CondA1 and
CondB1 and
CondC1

CondA1

CondB1

CondC1

SubCond2 =
CondA2 and
CondB2 and
CondC2

CondA2

CondB2

CondC2

SubCond3 =
CondA3 and
CondB3 and
CondC3

CondA3

CondB3

CondC3

Example of PCC_Threshold_AND3 of the size 3

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 99
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.2 CONTROL

9.2.1 Diagram Graphical Representation


The default view is shown, it’s possible to modify visible ports in CBM.

9.2.2 Parameter description


No Name Data Type Attributes Direction Port Initial Value Description
1 Name string nosort in 1 INIT: Tag name of the PCC Threshold
Condition (allowed deliminators are "."
and "-", no blanks ":" or ";" allowed)
2 Description string nosort in 1 IN: Description text of the the PCC
Threshold Condition
3 Class dint nosort in 0 1 INIT: Alarm/Event class 1 ... 9999
(process section)
4 Level dint nosort in 1 9 IN: Number of conditions AND(3)
groups that should be true
5 Equal bool nosort in 1 true IN: If false DriveCond is ok when
number of true conditions >= Level. If
true DriveCond is ok when number of
true conditions = Level
6 DrivePCC PCCComD by_ref out 1 IN/OUT: Connect to the Consumer or
ata Group PCC Bus
7 DriveCond bool retain out 1 OUT: Threshold - AND(3) calculated
nosort drive condition
8 CondOnDe time coldretain in 0 0s IN: Time On Delay for DriveCond
lay nosort Output, can be set from FPL if not
connected
9 CondOffDe time coldretain in 0 0s IN: Time Off Delay for DriveCond
lay nosort Output, can be set from FPL if not
connected
10 IntlkTr dint nosort in 0 3 INIT: Interlock treatment: -1 AutoMode;
1,2,3 = ALPrio# (1=lowest)
11 IntlkType dint nosort in 1 No_Interlock INIT:
PCC_Disabled;No_Interlock;PD_Prev
Drive;IA_Process;IA_Process_RFS;IB
_Equipment;IB_Equipment_RFS;IC_S
afety;IC_Safety_RFS;Auto_Start
12 IntlkDir dint nosort in 1 DirXY INIT: 1:DirX/Y/XY; 2:DirFBX/Y/XY;
3:DirX/Y/XYStart; Ex. DirX,
DirFBY,DirXYStart
13 IntlkStartIn time nosort in 0 0s INIT: Bypass Interlock for a certain
hibit time after start of PCC parent (MOTx,
GROUP)

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 100
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Attributes Direction Port Initial Value Description


14 IntlkLocSta bool nosort in 0 false INIT: Bypass Interlock in LOC mode if
rtOverride LCBStart is continuously pushed
6+ CondA[1] bool retain in 1 true IN true: 1st Condition of the AND(3)
9n hidden
7+ NameCon string nosort in 1 cBMI.Empty IN/OUT: ConditionName / TagName
9n dA[1] hidden _str for the PCC Viewer
8+ SubTextCo string nosort in 1 cBMI.Empty IN/OUT: Condition Sub Text PCC
9n ndA[1] hidden _str Viewer (supports Control Builder NLS
A/E NLS Syntax)
9+ CondB[1] bool retain in 1 true IN true: 2nd Condition of the AND(3)
9n hidden
10+ NameCon string nosort in 1 cBMI.Empty IN/OUT: ConditionName / TagName
9n dB[1] hidden _str for the PCC Viewer
11+ SubTextCo string nosort in 1 cBMI.Empty IN/OUT: Condition Sub Text PCC
9n ndB[1] hidden _str Viewer (supports Control Builder NLS
A/E NLS Syntax)
12+ CondC[1] bool retain in 1 true IN true: 3rd Condition of the AND(3)
9n hidden
13+ NameCon string nosort in 1 cBMI.Empty IN/OUT: ConditionName / TagName
9n dC[1] hidden _str for the PCC Viewer
14+ SubTextCo string nosort in 1 cBMI.Empty IN/OUT: Condition Sub Text PCC
9n ndC[1] hidden _str Viewer (supports Control Builder NLS
A/E NLS Syntax)

For more information on how to use Interlock Parameters, see chapter PCC Interlock Parameter Description.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 101
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.2.3 Application Example


In the following example pump _561_LQ1_M1 or _561_LQ1_M2 must be running for the
ball mill _561_BM1_M1 to start/run. This precondition is a safety issue and therefore is
configured as Safety interlock (IC).
The run signals for both pumps are used, each as a sub condition. With Level = 1 the
interlock is ok as soon as 1 pump runs. Because Equal = false also a two pump running
situation is ok.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 102
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

The same example programmed in CBM Diagrams Editor:

9.2.4 PCC Viewer Presentation


Above example will present as below in the PCC Viewer.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 103
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.3 OPERATION

9.3.1 Faceplate

9.3.1.1 Aspect Link Buttons


The following aspect view buttons are available on PCC_Threshold_AND3 Faceplates
Icon Aspect View
Event List

Operators Note

Faceplate Documentation, reference to this document

9.3.1.2 Default View

Tagname & Description


of the main condition

AND
sub condition status

Tagname & Description B (Block)


of the sub conditions override condition

Threshold
main condition status

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 104
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

Additional information for the PCC_Treshold_AND3


is structured in tabs. The available tabs and a short description of the contained
information are shown below.
Tab Description
Status Status of sub and main conditions
Parameters On Delay / Off Delay time setting for interlock
PCC - PCC interlock configuration summery
- Link to connected consumer or consumer overview list

Reference Table, Block


Description
B (Block) Individual blocking of sub condition
The sub condition input will be “forced” on controller level.
The sub condition line shows the actual value of the condition.

Reference Table, PCC_Threshold


Equal or more then x
Condition color Main Condition color
out of Y

CondA1 not ok Gray


DriveCond not ok Gray
CondA2 not ok Gray

CondA1 ok Green DriveCond not ok until


Gray
CondA2 not ok Gray ON delay elapsed

CondA1 ok Green
DriveCond ok Green
CondA2 not ok Gray

CondA1 not ok Green DriveCond ok until


OFF delay elapsed Green
CondA2 not ok Gray

Ok
CondA1 not ok (B) Green
As long the condition Green
CondA2 not ok Gray
is blocked

Equal x out of y Condition color Main Condition color

CondA1 ok Green
DriveCond ok Green
CondB1 ok Green

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 105
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.3.1.2.1 Parameters
On/Off delay settings for the interlock output.

Reference Table
Description
On Delay Time On Delay for interlock output
Off Delay Time Off Delay for interlock output

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 106
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.3.1.2.2 PCC
PCC interlock configuration

The PCC interlock configuration tab shows the actual configuration and a link to the
parent object. For explanation of the different configuration options see chapter PCC
Interlock Parameter Description.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 107
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

9.3.1.3 Application Example


In the following example pump 561-LQ1.M1 or 561-LQ1.M2 must be running for the ball
mill 561_BM1_M1 to start/run.
In this example the interlock condition is ok.

In the following example air slide 591-AS2.M1 and distribution gate 591-DG1.M1 on
position to silo 1 or air slide 591-AS3.M1 and distribution gate 591-DG1.M1 on position to
silo 2 / 3 or air slide 591-AS2.M1 and air slide 591-AS3.M1 must be running for the air
slide 591-AS1.M1 to start/run.
In this example the interlock condition is not ok.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 108
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

10 PCC_Intlk

10.1 BASIC DESCRIPTION


PCC_Intlk is a simple State or Summary Block for the PCC Bus. It acts both as Child with
a single PCC Interlock to a Drive or Group connected to the PCC Output as well as a PCC
Parent to Signals connected to its IO Variable. It is also possible to use the Block to add a
single Interlock Signal to PCC via the ExtIntlk Boolean Input.
· Blocking of the Interlock
· Interlock Delay for an overall Delay on the Interlock
· Ready Delay Time

10.2 CONTROL

10.2.1 CDE Graphical Representation


This is a default view and only enabled ports shown in graphic. it’s possible to modify the
view via the Port visibility Dialog.

10.2.2 Parameter description


No Name Data Type Direction Port Initial Value Description
1 Name string[24] in yes 'Name' INIT: Tag name of the Interlock (allowed deliminators
are "." and "-", no blanks ":" or ";" allowed)
2 Description string[40] in yes 'Description' IN: Description text of the Interlock
3 IO PCC_IntlkD in_out yes default IN/OUT: PCC_Intlk Data Variable
ata
4 PCC PCCComDa out yes default IN/OUT: Interlock Bus, PriorityCommand/Interlock to
ta motors, valves or groups
5 ExtIntlk bool in yes true IN: Interlock (Trip) Signal from Glue Logic
6 StartedState bool in no true IN: Consumer Run/Started State, for Alarm Enable
and Start Inhibit Timer, Overridden by PCC
Connection
7 IntlkType dint in yes No_Interlock INIT:
PCC_Disabled;No_Interlock;PD_PrevDrive;IA_Proces
s;IA_Process_RFS;IB_Equipment;IB_Equipment_RFS
;IC_Safety;IC_Safety_RFS;Auto_Start
8 IntlkDir dint in yes DirXY INIT: 1:DirX/Y/XY; 2:DirFBX/Y/XY; 3:DirX/Y/XYStart;
Ex. DirX, DirFBY,DirXYStart
9 IntlkStartInhi time in no 0s INIT: Bypass Interlock for a certain time after start of
bit PCC parent (MOTx, VLVx), Start by Ord instead of
Run where the IntlkDir is DirFB#
10 IntlkLocStart bool in no false INIT: Bypass Interlock in LOC mode if LCBStart is
Override continuously pushed. All PCC parents need to be in
LOC.
11 IntlkDelay time in yes 0s COLD INIT: Delay Time for Interlock to get active, valid
for both ExtIntlk and any PCC Interlock

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 109
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

No Name Data Type Direction Port Initial Value Description


12 IntlkReadyD time in no 0s COLD INIT: Delay Time for Interlock to be released,
elay valid for both ExtIntlk and any PCC Interlock
13 Class dint in no 1 INIT: Alarm/Event class 1 ... 9999 (process section)
14 InterlockTr dint in no cBMI.AE.Interl INIT: Interlock Treatment; 1,2,3 = ALPrio# (1=lowest)
ockTr
15 StatusTr bool in no cBMI.MOT.Sta IN true: True enables events on status (on/off) change
tusTr

10.2.3 Data Type Definition


Together with the PCC_Intlk Control Module Type a structured Data Type PCC_IntlkData
is available.
PCC_ComData contains the two components Out, PCC
PCC_IntlkData; components
Name Data Type Attributes Initial ISP Description
Value Value
1 Out PCC_IntlkOutput retain Output variables from the block
2 PCC PCCComData retain IN Interlock Bus,
PriorityCommand/Interlock from
Input modules to Block

PCC_IntlkOutput; components
Name Data Type Attributes Initial ISP Value Description
Value
1 NoInt bool retain nosort true No INTerlock is active
2 Trip bool retain nosort false TRIPped Indication, an Interlock is active
and the AlarmDelay has passed
3 TimeToChange time retain Running Timer for change of Interlock
*State* e.g. until Trip will get the NoINT
state
4 FirstOrMaxAETag string[32] retain nosort '' Tag Name of the IO Device with the first
or highest Alarm or Event causing an
action on the Motor, Group or Valve
5 FirstOrMaxAEInd dint retain nosort 0 Indication treatment of the first or highest
Tr Alarm or Event causing an action
accroding to Minerals Library Alarm
Indication Standards
6 NoInt_IC bool retain nosort true No Interlock IC Safety is active
7 NoInt_IC_Start bool retain nosort true No Start Interlock IC Safety is active
8 NoInt_IB bool retain nosort true No Interlock IB Equipment is active
9 NoInt_IB_Start bool retain nosort true No Start Interlock IB Equipment is active
10 NoInt_IA bool retain nosort true No Interlock IA Process is active
11 NoInt_IA_Start bool retain nosort true No Start Interlock IA Process is active
12 NoInt_PD bool retain nosort true No Interlock PD PrevDrive is active
13 NoInt_PD_Start bool retain nosort true No Start Interlock PD PrevDrive is active

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 110
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

10.2.3.1 OPERATION

Tagname
PCC Viewer
&
Overview of all
Description
connected Signals

Actual State
indication Block Indication
Any Interlock
blocked

Extended View
for detailed
information and
settings

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 111
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

10.2.3.2 Extended View

The faceplate extended view gives more detailed information about the state of the
PCC_Intlk:
Tab Description
PCC Interlock State of the Interlocks connected via PCC to this PCC_Intlk
Parameters Interlock Blocking and Alarm Delay configuration
PCC Information about the configured Interlock Type and Link to the PCC
Parent

10.2.3.2.1 Parameters

Parameter Description
Ready Delay Delay until the PCC_Intlk is healthy again after all Interlock conditions
are ok and the Interlock is released
Alarm Delay Delay until the PCC_Intlk trips and the Interlock is activated
Block Input Block the PCC_Intlk trip, disables the Interlock

F Per Default, the Block Indication in the reduced Faceplate is visible both if the
PCC_Intlk itself or any Signal connected connected to PCC is blocked.

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 112
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2013 ABB. All rights reserved.

11 DOCUMENT REVISION HISTORY


Rev. Page (P) Description Date/Initials
ind. Chapt. (C)
A Initial Version 14.05.2003/PVG
B Update for Minerals Library Release 2.0/1 09.09.2003/GPC
C Update for Minerals Library Release 2.1/1 05.04.2004/GPC
D Further Update for Minerals Library Release 2.1/1 11.07.2004/GPC
E Update for Minerals Library Release 3.1/1 04.08.2004/GPC
F Update for Minerals Library Release 4.0/0 08.06.2005/HT
Data type for DIS/DIC added one variable
G Update for Minerals Library Release 5.0/0 16.01.2006/N.B
H Corrected description for AIS 09.01.2007/WV
I -Update all new faceplates and parameter tables for 5.0/1 19.06.2007/WV
-Added process panel function for 5.0/1 28.06.2007/MB
-Checked 04.07.2007/KN
K C 7,8 -Updated PCC Bus, added Hint for Write Perm to Blocked Value 02.12.2008/LK
Updated for 5.0/2 12.02.2009/LK
Added Project Constants and DTM Links 07.04.2009/LK
Short Description of DOSButton ButtonType choices 15.04.2009/LK
L Updated for 5.1/0 09.07.2009/TOP
M DO Button changes for Minerals Library Release 5.1/1 11.11.2009/MS
N Faceplate for PG2 30.03.2010/MS
Updated for 5.1/2 28.03.2010/CT
O Updated for 5.1/3 25.10.2010/CT
Updated for 5.1/3 29.10.2010/TOP
P Updated for 5.1/3a 17.02.2011/CT
9.3
23.03.2011/TOP
Q Updated for 5.1/4, Adding CDE graphical representation 14.01.2013/YM
Add PCC_Intlk 22.04.2013/LK
R Remove the “Cut Fast Interlock Dir” Sections 16.09.2013/LK

Doc. kind Reference Manual Project Minerals Library, CoE Cement and Minerals
Title Basic Objects
800xA Minerals Library version 5.1/4a
Document number Lang. Rev. ind. Pages 113
ABB Switzerland Ltd 3BHS 161556 en R No. of p. 113