Você está na página 1de 12

MAKING MODERN LIVING POSSIBLE

Eliminator Liquid line filter driers,


type DCL and DML

Flare connection

Solder connection (copper)

REFRIGERATION &
AIR CONDITIONING DIVISION Technical leaflet
Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Contents Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Technical data and capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Selection example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Design and function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Dimensions and weights - Flare connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Dimensions and weights - Solder connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Conversions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Introduction

TE2

Eliminator  liquid line filter driers protect Eliminator  type DML, with a solid core
refrigeration and air-conditioning systems from of 100% Molecular Sieve, is optimized for use
moisture, acids, and solid particles. With these with HFC refrigerants and polyolester (POE)
contaminants eliminated, systems are safer from or polyalkyl glycol (PAG) oils. Type DML driers
harmful chemical reactions and from abrasive are designed for applications requiring high
impurities. water adsorption, and can be used with any
manufacturer’s compressor. Because type DML
There are two types of Eliminator  cores. driers contain no activated alumina, oil additives
Type DML driers have a core composition of will not be depleted.
100% Molecular Sieve, while type DCL contain
80% Molecular Sieve with 20% activated alumina. Eliminator  type DCL, with a solid core of
80% Molecular Sieve and 20% activated alumina,
All Eliminator  driers have a solid core with is the drier of choice for systems with HCFC and
binding material held to an absolute minimum. CFC refrigerants and mineral or alkyl benzene
Core selection is primarily based on the oils. Type DCL driers are particularly suited
refrigerant oil used in the system. for systems that operate at high condensing
temperatures and require high drying capacity.

Features The Core The Shell


Type DML UL approved for MWP up to 42 bar (610 psig).
100% 3Å Molecular Sieve core. Available with solder (copper) and flare
High drying capacity minimizing the risk of connections.
acid formation (hydrolysis). Compact 3 cubic inches drier ideal for
Optimized for HFC refrigerants (R134a, R404A, refrigeration and air conditioning units.
R410A, etc.) with POE or PAG oils. Corrosion resistant powder-painted finish.
Compatible with R22. Can be used in all environments including
Will not deplete oil additives. marine applications.
Allows installation with any orientation
Type DCL provided the arrow is in the flow direction.
80% 3Å Molecular Sieve with 20% activated Available in sizes from 3 to 75 cubic inches.
alumina.
Perfect core blend for systems that operate at The Filter
high condensing temperatures and require 25 µm (0.001 in.) filter provides high retention
high drying capacity. with minimal pressure drop.
Optimized for CFC and HCFC refrigerants (R22, Thermally stable up to 120°C (250°F).
R502, etc.) with mineral or alkyl benzene oils.
Compatible with HFC’s and refrigerant blends.

Approvals UL file no. SA 6398


PED 97/23/EC - a3p3

 Danfoss A/S (AC-DSL / SKT), 09 - 2006 DKRCC.PD.E00.B3.02 / 520H1643 


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Technical data Solid core Solid core Filter drier volume Filter drier volume
Filter surface volume (shell volume) (net volume)
Surface and volume [cm2] [cm3] [l] [l]
DML/DCL 03 82 41 0.08 0.038
DML/DCL 05 95 67 0.12 0.051
DML/DCL 08 131 104 0.17 0.065
DML/DCL 16 220 234 0.36 0.122
DML/DCL 30 378 494 0.72 0.224
DML/DCL 41 510 681 0.97 0.286
DML/DCL 60 756 988 1.34 0.352
DML/DCL 75 1019 1363 1.81 0.450

Acid capacity Acid


Filter capacity
[g]
DCL 03 0.58
DCL 05 0.87
DCL 08 1.36
DCL 16 3.12
DCL 30 6.40
DCL 41 8.90
DCL 60 12.80
DCL 75 17.80

Temperature range – 40 to 70°C (–40 to 160°F)

Technical data
and capacities
DML R134a, R507, R404A,
Drying and liquid capacity - Type DML R22, R407C, R410A
Drying capacity [kg refrigerant] 1) Liquid capacity [kW] 2) Max
R404A R22, R407C Working
Type R134a R22 Pressure
R507 R410A R404A
R134a R407C PS
R507
24°C 52°C 24°C 52°C 24°C 52°C R410A [bar]
DML 032/032s 5.5 5 7.5 4.5 4.5 4 7 5 7 42
DML 032.5s 5.5 5 7.5 4.5 4.5 4 9 7 10 42
DML 033/033s 5.5 5 7.5 4.5 4.5 4 17 13 19 42
DML 034s 5.5 5 7.5 4.5 4.5 4 24 17 26 42
DML 052/052s 8.5 8 13 7.5 8 7 7 5 8 42
DML 052.5s 8.5 8 13 7.5 8 7 9 7 10 42
DML 053/053s 8.5 8 13 7.5 8 7 18 14 19 42
1
) Drying capacity is based on DML 054s 8.5 8 13 7.5 8 7 25 18 27 42
following moisture content test DML 055s 8.5 8 13 7.5 8 7 34 25 38 42
standards before and after drying: DML 082/082s 12.5 12 20 11.5 12.5 11 7 5 8 42
R134a: DML 082.5s 12.5 12 20 11.5 12.5 11 10 8 11 42
DML 083/083s 12.5 12 20 11.5 12.5 11 19 14 21 42
From 1050 ppm W to 75 ppm W. DML 084/084s 12.5 12 20 11.5 12.5 11 26 20 29 42
If drying to 50 ppm W is required, DML 085/085s 12.5 12 20 11.5 12.5 11 42 31 46 42
reduce stated capacities by 15%.
DML 162/162s 27 25.5 43.5 24 27 23 7 5 8 42
R404A, R507: DML 162.5s 27 25.5 43.5 24 27 23 10 8 11 42
From 1020 ppm W to 30 ppm W. DML 163/163s 27 25.5 43.5 24 27 23 22 16 24 42
R407C: DML 164/164s 27 25.5 43.5 24 27 23 30 22 33 42
From 1020 ppm W to 30 ppm W. DML 165/165s 27 25.5 43.5 24 27 23 43 30 47 42
R410A: DML 166/166s 27 25.5 43.5 24 27 23 44 31 48 35
From 1050 ppm W to 60 ppm W. DML 167s 27 25.5 43.5 24 27 23 44 31 48 35
R22: DML 303/303s 57 54 92.5 51 57 48.5 21 15 23 42
From 1050 ppm W to 60 ppm W in DML 304/304s 57 54 92.5 51 57 48.5 31 22 34 42
accordance with ARI 710-86. DML 305/305s 57 54 92.5 51 57 48.5 45 33 49 42
DML 306/306s 57 54 92.5 51 57 48.5 62 45 68 35
R12: DML 307s 57 54 92.5 51 57 48.5 62 45 68 35
From 565 ppm W to 15 ppm W in DML 309s 57 54 92.5 51 57 48.5 62 45 68 30
accordance with ARI 710-86.
DML 413 80 75 130 70 80 74 25 18 27 42
R502: DML 414/414s 80 75 130 70 80 74 32 23 35 42
From 1020 ppm W to 30 ppm W in DML 415/415s 80 75 130 70 80 74 53 37 58 42
accordance with ARI 710-86. DML 417s 80 75 130 70 80 74 91 65 100 35
DML 419s 80 75 130 70 80 74 91 65 100 30
2
) Given in accordance with DML 604s 113 107 185 101 114 97 27 20 31 42
ARI 710-86 for DML 607s 113 107 185 101 114 97 75 54 82 35
te = –15°C (5°F), DML 609s 113 107 185 101 114 97 87 64 95 30
tc = 30°C (85°F) and DML 757s 160 150 260 140 160 148 82 60 90 35
∆p = 0.07 bar (1 psig). DML 759s 160 150 260 140 160 148 94 68 102 30

 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Technical data
and capacities
DCL R134a, R507, R404A,
Drying and liquid capacity - Type DCL R407C, R410A
Drying capacity [kg refrigerant] 1) Liquid capacity [kW] 2) Max
Working
R404A R407C
Type R134a R404A R407C Pressure
R507 R410A R134a R507 R410A PS
24°C 52°C 24°C 52°C 24°C 52°C [bar]

DCL 032/032s 4.5 4 7 3.5 4 3.5 7 5 7 42


DCL 032.5s 4.5 4 7 3.5 4 3.5 9 7 10 42
DCL 033/033s 4.5 4 7 3.5 4 3.5 17 13 19 42
1
) Drying capacity is based on DCL 052/052s 6.5 6 10 5.5 6 5.5 7 5 8 42
following moisture content test DCL 052.5s 6.5 6 10 5.5 6 5.5 9 7 10 42
standards before and after drying: DCL 053/053s 6.5 6 10 5.5 6 5.5 18 14 19 42
R134a: DCL 082/082s 10 9 16 8 9.5 9 7 5 8 42
From 1050 ppm W to 75 ppm W. DCL 082.5s 10 9 16 8 9.5 9 10 8 11 42
If drying to 50 ppm W is required, DCL 083/083s 10 9 16 8 9.5 9 19 14 21 42
reduce stated capacities by 15%. DCL 084/084s 10 9 16 8 9.5 9 26 20 29 42
R404A, R507: DCL 162/162s 24 22 37 20 22 20 7 5 8 42
From 1020 ppm W to 30 ppm W. DCL 162.5s 24 22 37 20 22 20 10 8 11 42
R407C: DCL 163/163s 24 22 37 20 22 20 22 16 24 42
From 1020 ppm W to 30 ppm W. DCL 164/164s 24 22 37 20 22 20 30 22 33 42
DCL 165/165s 24 22 37 20 22 20 43 30 47 42
R410A: DCL 166/166s 24 22 37 20 22 20 43 30 47 35
From 1050 ppm W to 60 ppm W. DCL 167s 24 22 37 20 22 20 43 30 47 35
R22:
DCL 303/303s 47 44 77 41 44 41 21 15 23 42
From 1050 ppm W to 60 ppm W in DCL 304/304s 47 44 77 41 44 41 31 22 34 42
accordance with ARI 710-86. DCL 305/305s 47 44 77 41 44 41 45 33 49 42
R12: DCL 306/306s 47 44 77 41 44 41 62 45 68 35
From 565 ppm W to 15 ppm W in DCL 307s 47 44 77 41 44 41 62 45 68 35
accordance with ARI 710-86. DCL 309s 47 44 77 41 44 41 62 45 68 30
R502: DCL 413 65 61 106 56 61 56 25 18 27 42
From 1020 ppm W to 30 ppm W in DCL 414/414s 65 61 106 56 61 56 32 23 35 42
accordance with ARI 710-86. DCL 415/415s 65 61 106 56 61 56 53 37 58 42
DCL 417s 65 61 106 56 61 56 91 65 100 35
DCL 419s 65 61 106 56 61 56 91 65 100 30
2
) Given in accordance with
ARI 710-86 for DCL 604s 94 76 150 82 89 82 27 20 31 42
te = –15°C (5°F), DCL 607s 94 76 150 82 89 82 75 54 82 35
DCL 609s 94 76 150 82 89 82 87 64 92 30
tc = 30°C (85°F) and
∆p = 0.07 bar (1 psig). DCL 757s 130 128 212 114 121 112 82 60 90 35
DCL 759s 130 128 212 114 121 112 94 68 102 30

R22, R12, R502


Drying capacity [kg refrigerant] 1) Liquid capacity [kW] 2) Max
Working
Type R22 R12 R502 Pressure
R22 R12 R502 PS
24°C 52°C 24°C 52°C 24°C 52°C [bar]
DCL 032/032s 4 3.5 15 15 7 3.5 7 6 5 42
DCL 032.5s 4 3.5 15 15 7 3.5 10 8 7 42
DCL 033/033s 4 3.5 15 15 7 3.5 19 14 13 42
DCL 052/052s 5.5 5 20 20 10 5 8 6 5 42
DCL 052.5s 5.5 5 20 20 10 5 10 8 8 42
DCL 053/053s 5.5 5 20 20 10 5 19 15 14 42
DCL 082/082s 9 8 30 30 15 8 8 6 5 42
DCL 082.5s 9 8 30 30 15 8 10 8 8 42
DCL 083/083s 9 8 30 30 15 8 21 15 14 42
DCL 084/084s 9 8 30 30 15 8 29 22 20 42
DCL 162/162s 20 19 70 70 35 18 8 6 5 42
DCL 162.5s 20 19 70 70 35 18 13 10 9 42
DCL 163/163s 20 19 70 70 35 18 24 18 16 42
DCL 164/164s 20 19 70 70 35 18 33 24 22 42
DCL 165/165s 20 19 70 70 35 18 47 35 30 42
DCL 166/166s 20 19 70 70 35 18 47 35 30 35
DCL 167s 20 19 70 70 35 18 47 35 30 35
DCL 303/303s 42 41 140 140 75 37.5 23 17 15 42
DCL 304/304s 42 41 140 140 75 37.5 34 25 22 42
DCL 305/305s 42 41 140 140 75 37.5 49 37 33 42
DCL 306/306s 42 41 140 140 75 37.5 68 51 45 35
DCL 307s 42 41 140 140 75 37.5 68 51 45 35
DCL 309s 42 41 140 140 75 37.5 68 51 45 30
DCL 413 59 56 200 200 100 50 26 20 18 42
DCL 414/414s 59 56 200 200 100 50 35 26 23 42
DCL 415/415s 59 56 200 200 100 50 58 43 37 42
DCL 417s 59 56 200 200 100 50 100 74 65 35
DCL 419s 59 56 200 200 100 50 100 74 65 30
DCL 604s 84 80 250 250 150 75 29 22 19 42
DCL 607s 84 80 250 250 150 75 83 63 54 35
DCL 609s 84 80 250 250 150 75 97 73 63 30
DCL 757s 120 110 300 300 200 100 91 69 59 35
DCL 759s 120 110 300 300 200 100 104 79 68 30

 Danfoss A/S (AC-DSL / SKT), 09 - 2006 DKRCC.PD.E00.B3.02 / 520H1643 


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Ordering
Flare DCL
Type Conn. Multipack Industrialpack
in. mm Code no. Code no. Qty.
DCL 032 1
/4 6 023Z5000*
DCL 032 1
/4 6 023Z5075 023Z8075
28
DCL 033 3
/8 10 023Z5001*
DCL 033 3
/8 10 023Z5089 023Z8089
DCL 052 1
/4 6 023Z5002 023Z8002
16
DCL 053 3
/8 10 023Z5003 023Z8003
DCL 082 1
/4 6 023Z5004 023Z8004
DCL 083 3
/8 10 023Z5005 023Z8005 16
DCL 084 1
/2 12 023Z5006 023Z8006
DCL 162 1
/4 6 023Z5007 023Z8007
DCL 163 3
/8 10 023Z5008 023Z8008
DCL 164 1
/2 12 023Z5009 023Z8009 12
DCL 165 5
/8 16 023Z5010 023Z8010
DCL 166 3
/4 19 023Z5011
DCL 303 3
/8 10 023Z0012
DCL 304 1
/2 12 023Z0013 023Z3013
8
DCL 305 5
/8 16 023Z0014 023Z3014
DCL 306 3
/4 19 023Z0156 023Z3156
DCL 413 3
/8 10 023Z0101
DCL 414 1
/2 12 023Z0102
DCL 415 5
/8 16 023Z0103
* Wire mesh in filter drier outlet

Solder (copper) DCL


Type Conn. Multipack Industrialpack Conn. Multipack Industrialpack
in. Code no. Code no. Qty. mm Code no. Code no. Qty.
DCL 032s 1
/4 023Z5013* 023Z8013* 6 023Z5012* 023Z8012*
DCL 032.5s 5
/16 023Z5014 023Z8014* 28 8 023Z5014 023Z8014* 28
DCL 033s 3
/8 023Z5015 10 023Z5016
DCL 052s 1
/4 023Z5018 023Z8018 6 023Z5017 023Z8017
DCL 052.5s 5
/16 023Z5114 16 8 023Z5114 16
DCL 053s 3
/8 023Z5019 023Z8019 10 023Z5020 023Z8020
DCL 082s 1
/4 023Z5022 023Z8022 6 023Z5021
DCL 082.5s 5
/16 023Z5116 8 023Z5116
16 16
DCL 083s 3
/8 023Z5023 023Z8023 10 023Z5024
DCL 084s 1
/2 023Z5026 023Z8026 12 023Z5025 023Z8025
DCL 162s 1
/4 023Z5028 6 023Z5027
DCL 162.5s 5
/16 023Z5118 8 023Z5118
DCL 163s 3
/8 023Z5029 10 023Z5030 023Z8030
DCL 164s 1
/2 023Z5032 023Z8032 12 12 023Z5031 12
DCL 165s 5
/8 023Z5033 023Z8033 16 023Z5033 023Z8033
DCL 166s 3
/4 023Z5070 19 023Z5070
DCL 167s 7
/8 023Z5034 22 023Z5034
DCL 303s 3
/8 023Z0030 023Z3030 10 023Z0196
DCL 304s 1
/2 023Z0031 12 023Z0198 023Z3198
DCL 305s 5
/8 023Z0032 023Z3032 16 023Z0032 023Z3032
8 8
DCL 306s 3
/4 023Z0033 18 023Z0216
DCL 307s 7
/8 023Z0034 023Z3034 22 023Z0034 023Z3034
DCL 309s 11/8 023Z0035 28 023Z0200
DCL 414s 1
/2 023Z0104 12 023Z0227
DCL 415s 5
/8 023Z0105 16 023Z0105
DCL 417s 7
/8 023Z0106 22 023Z0106
DCL 419s 11/8 023Z0107 28 023Z0202
DCL 604s 1
/2 023Z0241 12 023Z0221
DCL 607s 7
/8 023Z0036 22 023Z0036
DCL 609s 11/8 023Z0037 28 023Z0204
DCL 757s 7
/8 023Z0115 22 023Z0115
DCL 759s 11/8 023Z0116 28 023Z0206
* Wire mesh in filter drier outlet

 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Ordering (cont.)
Flare DML
Type Conn. Multipack Industrialpack
in. mm Code no. Code no. Qty.
DML 032 1
/4 6 023Z5035* 023Z8035*
DML 033 3
/8 10 023Z5036* 023Z8036* 28
DML 033 3
/8 10 023Z5090 023Z8090
DML 052 1
/4 6 023Z5037 023Z8037
16
DML 053 3
/8 10 023Z5038 023Z8038
DML 082 1
/4 6 023Z5039 023Z8039
DML 083 3
/8 10 023Z5040 023Z8040
16
DML 084 1
/2 12 023Z5041 023Z8041
DML 085 5
/8 16 023Z5073 023Z8073
DML 162 1
/4 6 023Z5042 023Z8042
DML 163 3
/8 10 023Z5043 023Z8043
DML 164 1
/2 12 023Z5044 023Z8044 12
DML 165 5
/8 16 023Z5045 023Z8045
DML 166 3
/4 19 023Z5046 023Z8046
DML 303 3
/8 10 023Z0049 023Z3049
DML 304 1
/2 12 023Z0050 023Z3050
8
DML 305 5
/8 16 023Z0051 023Z3051
DML 306 3
/4 19 023Z0193 023Z3193
DML 413 3
/8 10 023Z0108 023Z3108
DML 414 1
/2 12 023Z0109 023Z3109 6
DML 415 5
/8 16 023Z0110 023Z3110
* Wire mesh in filter drier outlet

Solder (copper) DML


Type Conn. Multipack Industrialpack Conn. Multipack Industrialpack
in. Code no. Code no. Qty. mm Code no. Code no. Qty.
DML 032s 1
/4 023Z5048* 023Z8048* 6 023Z5047* 023Z8047*
DML 032.5s 5
/16 023Z5049 023Z8049 8 023Z5049 023Z8049
28 28
DML 033s 3
/8 023Z5050 023Z8050* 10 023Z5051 023Z8051*
DML 034s 1
/2 023Z5121 12 023Z5123
DML 052s 1
/4 023Z5053 6 023Z5052 023Z8052
DML 052.5s /16
5
023Z5115 8 023Z5115
DML 053s 3
/8 023Z5054 023Z8054 16 10 023Z5055 023Z8055 16
DML 054s 1
/2 023Z5101 12 023Z5099
DML 055s 5
/8 023Z5100 16 023Z5100
DML 082s 1
/4 023Z5057 6 023Z5056
DML 082.5s /16
5
023Z5117 8 023Z5117
DML 083s 3
/8 023Z5058 16 10 023Z5059
DML 084s 1
/2 023Z5061 023Z8061 12 023Z5060
DML 085s 5
/8 023Z5072 16 023Z5072
DML 162s 1
/4 023Z5063 023Z8133 6 023Z5062
DML 162.5s /16
5
023Z5119 8 023Z5119
DML 163s 3
/8 023Z5064 023Z8134 10 023Z5065
DML 164s 1
/2 023Z5067 023Z8067 12 12 023Z5066 12
DML 165s 5
/8 023Z5068 023Z8068 16 023Z5068 023Z8068
DML 166s 3
/4 023Z5071 023Z8071 19 023Z5071 023Z8071
DML 167s 7
/8 023Z5069 22 023Z5069
DML 303s 3
/8 023Z0067 10 023Z0197
DML 304s 1
/2 023Z0068 12 023Z0199
DML 305s 5
/8 023Z0069 023Z3069 16 023Z0069 023Z3069
8 8
DML 306s 3
/4 023Z0070 19 023Z0070
DML 307s 7
/8 023Z0071 023Z3071 22 023Z0071 023Z3071
DML 309s 11/8 023Z0072 28 023Z0201
DML 414s 1
/2 023Z0111 12 023Z0228
DML 415s 5
/8 023Z0112 16 023Z0112
6 6
DML 417s 7
/8 023Z0113 023Z3113 22 023Z0113 023Z3113
DML 419s 11/8 023Z0114 023Z3114 28 023Z0203
DML 604s 1
/2 023Z0224 12 023Z0229
DML 607s 7
/8 023Z0073 22 023Z0073
DML 609s 11/8 023Z0074 28 023Z0205
DML 757s 7
/8 023Z0117 023Z3117 22 023Z0117 023Z3117
4 4
DML 759s 11/8 023Z0118 023Z3118 28 023Z0207
* Wire mesh in filter drier outlet

 Danfoss A/S (AC-DSL / SKT), 09 - 2006 DKRCC.PD.E00.B3.02 / 520H1643 


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Identification Type codes


Filter drier D
Example for type codes
Solid core C 80 / 20% composite core
D C L 05 3 s M 100% Molecular Sieve core
Application L Liquid line
Size (volume) 03 3 in3
05 5 in3
08 8 in3
16 16 in3
30 30 in3
41 41 in3
60 60 in3
75 75 in3
Connection (filter connection 2 1
/4 in. / 6mm
in 1/8 of an inch increments) 2.5 5
/16 in. / 8 mm
3 3
/8 in. / 10 mm
4 1
/2 in. / 12 mm
5 5
/8 in. / 16 mm
6 3
/4 in. / 18 (19) mm
7 7
/8 in. / 22 mm
9 11/8 in. / 28 mm
Connection type (blank) Flare connection
s Solder connection

Selection Type selection is made considering the application


DCL DML
1
) For CFC systems, DCL filter
driers are recommended. HFC Can be used Recommended
In these systems, circumstances may Refrigerant HCFC Recommended Can be used
require the use of a filter drier with
acid adsorbing properties. CFC Recommended Not recommended 1)
2
) Use of filter driers containing Mineral or AB Recommended Can be used
activated alumina are not Oil POE or PAG, pure Can be used Recommended
recommended in systems with
oils containing additives. POE or PAG, with additives Not recommended 2) Recommended

Selection example Select the appropriate type (DML or DCL) based drier, a 3/8 inch connection must be chosen.
SI-units on refrigerant and oil type. Then select the drier Larger connections can be chosen in
size based on the adsorption and liquid capacity accordance with the liquid line dimension.
required.
c. Result
a. Amount of charge: 25 kg R134a at tL = DML 163 or DML 163s can be used.
24°C To dry 25 kg R134a at 24°C from 1050
to 60 ppm moisture, a DML 16 is necessary. If the initial moisture content is very small or a
planned change of the filter drier is considered, a
b. Cooling capacity: Qe = 20 kW smaller filter drier size can be chosen.
To obtain a mass flow corresponding to
20 kW cooling capacity with a DML 16 filter
Drying capacity [kg refrigerant] 1) Liquid capacity [kW] 2) Max
R404A R22, R407C Working
Type R134a R22 Pressure
R507 R410A R404A
R134a R407C PS
R507
24°C 52°C 24°C 52°C 24°C 52°C R410A [bar]
DML 032/032s 5.5 5 7.5 4.5 4.5 4 7 5 7 42
DML 032.5s 5.5 5 7.5 4.5 4.5 4 9 7 10 42
DML 033/033s 5.5 5 7.5 4.5 4.5 4 17 13 19 42
DML 034s 5.5 5 7.5 4.5 4.5 4 24 17 26 42
DML 162/162s 27 25.5 43.5 24 27 23 7 5 8 42
DML 162.5s 27 25.5 43.5 24 27 23 10 8 11 42
DML 163/163s 27 25.5 43.5 24 27 23 22 16 24 42
DML 164/164s 27 25.5 43.5 24 27 23 30 22 33 42
DML 165/165s 27 25.5 43.5 24 27 23 43 30 47 42
DML 166/166s 27 25.5 43.5 24 27 23 44 31 48 35
DML 167s 27 25.5 43.5 24 27 23 44 31 48 35

 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Design and function

DML / DCL 03
DML / DCL 30, 41

DML / DCL 05 DML / DCL 60, 75

1. Inlet
2. Spring
3. Solid core
4. Polyester mat
5. Perforated plate
6. Seal cap, flare connection
7. Seal cap, solder connection
DML / DCL 08, 16

The relatively large diameter of the filter drier Powder formation is eliminated because the solid
means that the liquid flow velocity is suitably core grains are bonded and cannot move against
low and the pressure drop minimal. each other.

Dimensions and weights Flare connections

Type A A1 A2 L D1 D2 Weight
DCL/DML 032 mm 66 16 50 110 46 43 0.20 kg
DCL/DML 033 mm 66 16 50 123 46 43 0.23 kg

 Danfoss A/S (AC-DSL / SKT), 09 - 2006 DKRCC.PD.E00.B3.02 / 520H1643 


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Dimensions and weights Flare connections


(cont.)

Type A A1 A2 L D1 D2 Weight
DCL/DML 052 mm 75 24.5 50.5 119 58 54 0.39 kg
DCL/DML 053 mm 75 24.5 50.5 132 58 54 0.42 kg

Type A A1 A2 L D1 D2 Weight
DCL/DML 082 mm 101 50.5 50.5 145 58 54 0.40 kg
DCL/DML 083 mm 101 50.5 50.5 158 58 54 0.44 kg
DCL/DML 084 mm 101 50.5 50.5 166 58 54 0.48 kg
DML 085 mm 101 50.5 50.5 175 58 54 0.52 kg
DCL/DML 162 mm 110 55 55 154 80 76 0.79 kg
DCL/DML 163 mm 110 55 55 167 80 76 0.82 kg
DCL/DML 164 mm 110 55 55 175 80 76 0.87 kg
DCL/DML 165 mm 110 55 55 184 80 76 0.91 kg
DCL/DML 166 mm 110 55 55 182 80 76 0.99 kg

Type A A1 A2 L D1 D2 Weight
DCL/DML 303 mm 186 - - 243 80 76 1.33 kg
DCL/DML 304 mm 186 - - 251 80 76 1.38 kg
DCL/DML 305 mm 186 - - 260 80 76 1.42 kg
DCL/DML 306 mm 186 - - 258 80 76 1.49 kg
DCL/DML 413 mm 187 - - 244 93 89 1.86 kg
DCL/DML 414 mm 187 - - 252 93 89 1.91 kg
DCL/DML 415 mm 187 - - 261 93 89 1.95 kg

10 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Dimensions and weights Solder connections


(cont.)

Type A A1 A2 B L D1 D2 Weight
DCL/DML 032s mm 66 16 50 82 98 46 43 0.18 kg
DCL/DML 032.5s mm 66 16 50 84 102 46 43 0.19 kg
DCL/DML 033s mm 66 16 50 85 104 46 43 0.19 kg
DCL/DML 034s mm 66 16 50 87 108 46 43 0.20 kg

Type A A1 A2 B L D1 D2 Weight
DCL/DML 052s mm 75 24.5 50.5 91 107 58 54 0.37 kg
DCL/DML 052.5s mm 75 24.5 50.5 93 111 58 54 0.38 kg
DCL/DML 053s mm 75 24.5 50.5 94 113 58 54 0.38 kg
DML 054s mm 75 24.5 50.5 96 117 58 54 0.39 kg
DML 055s mm 75 24.5 50.5 99 123 58 54 0.40 kg

Type A A1 A2 B L D1 D2 Weight
DCL/DML 082s mm 101 50.5 50.5 117 133 58 54 0.38 kg
DCL/DML 082.5s mm 101 50.5 50.5 119 137 58 54 0.39 kg
DCL/DML 083s mm 101 50.5 50.5 120 139 58 54 0.39 kg
DCL/DML 084s mm 101 50.5 50.5 122 143 58 54 0.40 kg
DML 085s mm 101 50.5 50.5 125 149 58 54 0.41 kg
DCL/DML 162s mm 110 55 55 126 142 80 76 0.77 kg
DCL/DML 162.5s mm 110 55 55 128 146 80 76 0.78 kg
DCL/DML 163s mm 110 55 55 129 148 80 76 0.78 kg
DCL/DML 164s mm 110 55 55 131 152 80 76 0.79 kg
DCL/DML 165s mm 110 55 55 134 158 80 76 0.80 kg
DCL/DML 166s mm 110 55 55 140 170 80 76 0.82 kg
DCL/DML 167s mm 110 55 55 136 172 80 76 0.84 kg

 Danfoss A/S (AC-DSL / SKT), 09 - 2006 DKRCC.PD.E00.B3.02 / 520H1643 11


Technical leaflet Eliminator  Liquid line filter driers, type DCL and DML

Dimensions and weights Solder connections


(cont.)

Type A A1 A2 B L D1 D2 Weight
DCL/DML 303s mm 186 - - 205 224 80 76 1.29 kg
DCL/DML 304s mm 186 - - 207 228 80 76 1.30 kg
DCL/DML 305s mm 186 - - 210 234 80 76 1.31 kg
DCL/DML 306s mm 186 - - 216 246 80 76 1.33 kg
DCL/DML 307s mm 186 - - 212 248 80 76 1.35 kg
DCL/DML 309s mm 186 - - 207 249 80 76 1.36 kg
DCL/DML 414s mm 187 - - 208 229 93 89 2.03 kg
DCL/DML 415s mm 187 - - 211 235 93 89 2.04 kg
DCL/DML 417s mm 187 - - 213 249 93 89 2.08 kg
DCL/DML 419s mm 187 - - 208 250 93 89 2.09 kg
DCL/DML 604s mm 337 - - 358 379 80 76 2.34 kg
DCL/DML 607s mm 337 - - 363 399 80 76 2.39 kg
DCL/DML 609s mm 337 - - 358 400 80 76 2.40 kg
DCL/DML 757s mm 338 - - 364 400 93 89 3.38 kg
DCL/DML 759s mm 338 - - 359 401 93 89 3.39 kg

Conversions (kg of refrigerant × (Initial PPM of water - Final PPM of water))


Drops of water = 50
See ARI standard 710-86 for recommended initial
and final PPM values for different refrigerants.

12 DKRCC.PD.E00.B3.02 / 520H1643  Danfoss A/S (AC-DSL / SKT), 09 - 2006