Você está na página 1de 15

BS6O89: 1981

UDC 624[.0123/.4] .046:69132:620.17

Guide to

Assessment of concrete strength


in existing structures

Guide pour I'Cvaluation de la resistance du beton dans les constructions existantes

Leitfaden fur die Beurteilung der Betonfestigkeit in vorhandenen Bauwerken

British Standards Institution


Contents
Page
Foreword Inside front cover Tables
Cooperating organizations Back cover 1. Guide t o teas for assessing aspects
of conaete strength
Guide 2. Relative merits and limitations of
1. Scope various tests
2. References
3. Definitions Figures
4. Planning an investigation 1. Illustration of approximate relationship
5. Test methods of compressive strengths
: 6. Conducting an investigation 2. Comparisons between design strength
and estimated in-situ cube strength
Appendix
A. Bibliography

Foreword
The need to assess the strength of the concrete in an selection of the method and testing programme most
existing structure can arise from a variety of reasons, appropriate to the circumstances that prevail.
such as doubts following noncompliance of standard The interpretation of the test results and the factors that
cube strength results or possible deteriorationdue to influence the relationshipbetween the standard cube
aggressive environments or a wish to check that the strength and the strength of the conaete in the structure
strength is acceptable for a particular loading system, are also discussed. . .
especially when additional loading is being considered. The recommendations in this standard are intended to
The drilling and testing of cores has been common provide guidance only; they are not intended to supplant
practice for many years and several nondestructive engineering judgement or to inhibit the development and
tests have been available, well established test methods use of other test methods.
being described in BS 1881 and BS 4408. Numbers in parentheses in the text of the standard refer
This guide presents information on the standard method to the numbered references given in appendix A.
and on certain other methods that will assist in the
I ___ - - -. . . - -.- . - ____-- ' I

British Standard Guide to

Assessment of concrete strength in existing structures

1. Scope 3.6 characteristic cube strength. The value of the standard


This British Standard gives information on tests that are cube strength (which in CP 110 i s measured a t 28 days)
available to determine strength of concrete in a structure. below which 5 % of the population of all possible strength
Relative merits of these tests are indicated and methods measurements are expected to fall.
of carrying out such tests are given. 3.7 design strength. The strength of concrete as used in
This standard also contains guidelines to assist the engineer calculations so that the allowable stress as defined by the
in interpreting results of tests, and outlines possible ways relevant code of practice or other design basis employed
is not exceeded under the loading conditions appropriate
of comparing test results with the required strength for
to that code or other design basis.
design purposes.
3.8 design load capability of a structural member. A level
The information given in this standard amplifies sections
of loading that a structural member i s designed to sustain
of CP 110 : Part 1 : 1972 concerned with tests to measure
with the appropriate partial safety factors against collapse,
and assess the strength of concrete in structures, including:
deflection or local damage.
6.8.2.3 Action to be taken in the event of NOTE. Direct measurement of capacity of a member to withstand
noncompliance with the testing plan. such a load will not destroy the member under test unless this is
9.2 Check tests on structural concrete. inadequate for its envisaged purpose. (See 9.6 of CP 110 : Part 1 :
1972 for details of test loads and assessment of results.)

2. References 3.9 ultimate strength of a structural member. A measure


The titles of the standards publications referred to in this of the maximum load that a member i s capable of
sustaining, the loading pattern being that applied in service.
standard are listed on the inside back cover.
NOTE. Direct measurement of the ultimate strength of a member
A bibliography of some appropriate references is given results in destruction of that member, but in some cases it may be
in appendix A. necessary to undertake such a test to assess the loadbearing
capacity of similar members. ( A suitable test method applicable
3. Definitions to individual precast units is described in 9.53 of
CP 110 : Part 1 : 1972.)
For the purposes of this British Standard the following
definitions apply. 4. Planning an investigation
3.1 standard cube strength. The measured compressive 4.1 Information required from tests. A knowledge of
strength of a cube made, cured and tested in accordance in-situ strength of concrete in a structural member may
with BS 1881 : Parts 1,3 and 4. be required for one or more of the following reasons.
3.2 cylinder strength. The compressive strength of a (a) Doubt concerning the strength of concrete in the
cylinder with,a lengthldiameter ratio (A) of 2 made and structure as a result of noncompliance of standard
cured in accordance with clause 5,of BS 1881 :Part 3 : cube test results carried out in accordance with a
1970, and tested in accordance with 3.2 of specified compliance plan.
BS 1881 : Part 4 : 1970.
(b) Doubt concerning workmanship involved in
3.3 core strength. The compressive strength of a core, batching, mixing, placing, compacting or curing
cut, prepared and tested in accordance with the of concrete.
requirements of BS 1881 : Part 4, for a stated length1
(c) Deterioration of concrete due to:
diameter ratio.
over loading;
3.4 estimated in-situ cube strength. The strength of
fatigue;
wncrete at a location in a structural member estimated
chemical action;
from indirect means and expressed in terms of specimens
fire;
of cubic shape.
explosion;
NOTE. A direct measure of the in4tu cube strength cannot be
obtained because it is not possible to produce a cast cubic weathering.
specimen from that location. However, it is possible to obtain (d) To ascertain whether the in-situ strength of
an estimated in-ritu cube strength by using one w more of the concrete is acceptable for:
methods described in clause 5.
the designed loading system;
3.5 location. A region of wncrete that, for practical
the actual loading system;
purposes, is assumed to be of uniform quality.
a projected loading system for a new use.
Any structural investigation should be carefully planned precision may not be necessary. The level of accuracy
' and executed if the engineer is to obtain information that can be achieved will depend upon:
which can be used to provide a reliable assessment of (1) test method;
concrete strength in a structure. The detailed test
(2) number of measurements;
programme will depend upon the reason for the
investigation and whether: (3) accuracy and reliability of available correlations
(e.g. between pulse velocity and strength).
[k (1) an estimate of the in-situ strength of concrete in
a structural member i s required; 4.4.3 Accuracy of estimates of in-situ strength. Confidence
P with which it is possible to assess insitu strength of
(2) a comparison of the suspect concrete with
concrete will increase with the number of assessments
satisfactory concrete in other parts of the structure
made. In the case of some tests (e.g. ultrasonic pulse
is adequate;
velocity, surface hardness) little extra cost is incurred by
(3) the investigation is required on the immediate obtaining a large number of test results. In other cases
surface, near to the surface, or in greater depth; (e.g. core and gamma-ray testing) the cost of each test is
(4) additional information is required, e.g. uniformity appreciable. The decision on the number and type of tests
i and density of concrete and quality of materials used. to be made will, therefore, be based upon an assessment
4.2 Acceptance of test data. Before any programme i s of the cost of obtaining a result of adequate reliability.
+ commenced, it is desirable that there i s complete agree- Benefit may be obtained by combining different testing
ment between the interested parties on the validity of techniques, e.g. combining pulse velocity measurements
the proposed testing procedure, the criteria for acceptance with core tests. Pulse velocity measurements on cores
and the appointment of a person and/or laboratory to prior to crushing can increase the accuracy of strength
take responsibility for the testing. estimates from pulse velocity measurements. The ease of
4.3 Aspects of concrete strength. Table 1 provides a broad taking a large number of pulse velocity measurements on
' guide to various test methods to assess different aspects structural components can provide a more comprehensive
of the strength of concrete in the structure, or of a evaluation of the strength of a structure.
1 structural member. However. the most direct method of assessing in-situ
/ 4.4 Selecting a test programme strength of concrete in a structural element is by
core tests.
4.4.1 General. The test programme will be determined
by the objectives of the investigation, the site conditions Accuracy of estimates of insitu strength, obtained from
and economic factors, as outlined in 4.4.2 to 4.4.5. indirect nondestructive tests, will depend upon reliability
of correlation between test method and core strengths.
4.4.2 Choice of test methods. The relative merits and
A combination of different test methods may be chosen
limitations of tests for various depths from the surface
for the following reasons:
are summarized in table 2. The symbol **** indicates that
the test compares well with other methods. The symbol (a) use of one method as a preliminary to another
indicates that the test has disadvantages compared (e.g. use of ultrasonic methods to select areas from
with others. which to drill cores);
The particular t e s t method used will depend upon the (b) use of a limited core investigationtogether with
following. ultrasonic pulse velocity in order to establish a more
accurate correlation for the particular site and permit
(a) Test location (see also 3.5). Factors to be
a wider use of non-destructive methods;
considered include:
(c) resalts from two or more different nondestructive
(1) position of suspect concrete in the member;
methods can be used together to provide a more
(2) position of highly stressed sections; accurate assessment of strength;
t
(3) variation of strength through depth of lift; (dl order of accuracy of different correlations between
(4) position of reinforcement identified by the use nondestructive tests and strength varies at different
of drawings or cover meter; strength levels.
(5) need to avoid detrimental effect on 4.4.4 Site conditions The site conditions that should be
reinforcement; considered include:
(6) presence of local defects that may influence (a) general site location, and ease of transport of test
t e s t results. equipment;
(b) Effect of damage. The choice between destructive (b) accessibility to suspect region on site;
and nondestructive methods be influenced by the (c) safety of personnel on site and general public,
effect of: e.g. when gamma rays are used.
(1) testing on the surface appearance of member; 4.4.5 Economics. The test programme will be influenced
(2) drilling of holes (e.g. in small columns or by economic factors such as the value of the work and
retaining walls); costs arising from:
(3) cutting of reinforcement. (a) delays in construction whilst testing is conducted
and decisions are made;
(c) Testing accuracy required. This will depend upon the
nature of the investigation and, often, upon the (b) delays in completion and hand-over;
magnitude of the measured strength; if the measured (c) removal of defective concrete or strengthening
i strength is considerably higher than that required, of structure;
(dl different test methods; If circumstances dictate, a core may have a length of less
(el selection of an adequate number of tests for than its diameter. Again,,the result may be treated in a
assessment. similar manner to results of tests on longer cores but
the results may be less reliable; l i t t l e reliance can be
placed on results obtained on cores having a length/
5. Test methods diameter ratio of less than 0.5.
5.1 Core test
5.1.5 Core drilling, Cores should be drilled by a skilled
5.1.1 General. The most direct method of obtaining a operator using well-maintained equipment complying
value of the estimated cube strength is generally to drill with dimensional requirements of BS 4019 :Part 2.
cylindrical cores and test these in compression.
While drilling work proceeds, a simple record of any
Whenever possible, the cores should be drilled, prepared
observations likely to have a bearing on the validity in
and tested in accordance with section 3 of
interpretation of core test results should be prepared.
BS 1881 : Part 4 : 1970, although this standard recom-
mends alternative methods of treating the results. 5.1.6 Treatment of cores prior to testing. The laboratory
Detailed advice for core testing procedure is given in should trim (see 3.1.5 of BS 1881 : Part 4 : 1970),
Technical Report No. 11 published by the Concrete examine and photograph each test core in accordance
Society (5). with instructions given by the engineer.
5.1.2 Selection of drillingpoints. Each drilling point The ends of cores should preferably be ground to
should be selected so that the core contains no steel tolerances applicable to capped ends as given in
parallel to its length and as little as possible perpendicular BS 1881 : Part 3 or they may be capped with high-alumina
to i t s axis. cement mortar or a sulphur compound in accordance
with 5.5.2 of the same British Standard.
5.1.3 Accuracy of test and number of cores. The number
of cores will depend upon the amount of information 5.1.7 Core tesring. Each core should be measured in
required, the required accuracy of strength estimates and accordance with 3.1.4 of BS 1881 : Part 4 : 1970 to the
the cost of drilling, preparing and testing the cores, nearest millimetre; i t s average cross-sectionalarea and i t s
length/diameter ratio, A, when prepared for test should
The accuracy of strength estimates depends upon the
be calculated.
reproducibility of the test method and the number of
cores tested. The strength estimated from a single core The core should be tested in compression in accordance
can be considered to lie (with 95 % confidence) within with 3.2 of BS 1881 : Part 4 : 1970, the mode of failure
f 12 % of the strength of the concrete a t that location. being noted and a sketch diagram made, if unusual.
The accuracy of the estimate is increased i f more cores The maximum load sustained by the core should then
are taken at the same location. For n cores, the mean be divided by i t s cross-sectional area to establish the
core strength can be considered to be accurate within core strength for the particular lengthldiameter ratio.
f 1 2 V n % of the strength a t that location. 5.1 -8 Estimated in-situ cube strength
The degree of uncertainty that can be tolerated in the (a) Cores without steel. The estimated cube strength
estimated in-situ strength will often depend upon the can be obtained from the measured core strength by
measured value of the in-situ strength when compared using the following equation (5):
with the value that may be considered acceptable. D
Ifin-situ strength, based on the mean core strength, Estimated cube strength = -
1.5 + 1 h
x core strength
is found to be near the limit of acceptance, it may be
t- necessary to drill further cores. where
5.1.4 Size of cores. Before capping, a core should have D = 2.5 for cores drilled horizontally (for precast
a length a t least 95 % of i t s diameter. When prepared units perpendicular to height when cast), or
for test, it should preferably have a length at least equal D = 2.3 for cores drilled vertically (for precast
to its diameter and not exceeding 1.2 times its diameter. units parallel to height when cast), and
Cores of both 100 mm and 150 mm nominal diameter
A is the length/diameter ratio
may be tested provided the nominal maximum aggregate
size does not exceed 20 mm and 40 mm respectively. (b) Cores with steel. If in spite of efforts to obtain cores
Whenever possible, however, 150 mm diameter cores free of steel, they contain bars perpendicular to their
should be drilled as less variability due to drilling and axes, it becomes necessary to allow for the resulting
more reliable results are obtained, with the following reductions in core strength.
exceptions: A convenient correction for the presence of a single
(a) when reinforcement is congested, 100 mm diameter bar can be made by multiplying the strength from
cores are less likely to contain pieces of steel; the above formula by a factor of
(b) when it is necessary to restrict sampling to within 1.o + 1.5 r#Jrd/r#Jcl
a length of less than 150 mm. to give the estimated cubic strength
It may sometimes be necessary to drill cores with a where
smaller diameter than 100 mm, e.g. if the section is less $, is the diameter of the reinforcement;
than 100 mm thick. Results of tests on such cores may
a be treated in the same way as those obtain& on larger
cores but the results may be less reliable, pwticularlyit
4, is the diameter of core;
d is the distance of axis of bar from nearer end
size o t - m x c e e d s of core;
/ is the length of core
If the core contains two bars no further apart than the transducers are placed on adjacent faces of concrete
diameter of the larger bar, only the bar corresponding instead of the opposite faces used in the direct trans-
to the higher value of &d need be considered. If the mission measurement.
bars are further apart, their combined effect should be 5.2.3 Number of tests Ultrasonic test equipment permits
assessed by using the factor transit times to be measured with considerable
accuracy provided that the path length is not less than
150 mm and not so long that the transmitted pulse is
unduly attenuated. Accuracy of the calculated pulse
It should be noted that in-situ strengths estimated from
velocity also depends upon the accuracy with which the
the above formulae cannot be equated to standard path length can be measured. There i s little advantage
cube strengths. in taking more than one reading at any single location
5.2 Ultrasonic pulse velocity test (although this may usefully be checked) because accuracy
5.2.1 General. Ultrasonic pulse velocity (UPV) test of the pulse velocity will not be increased to any
equipment measures the transit time of a pulse vibration significant extent. The more effective procedure is to
through concrete. Provided the length of the pulse path measure velocities a t a number of locations over the
between transducers of the equipment is known, member or structure to facilitate plotting of 'velocity
the pulse velocity through the concrete can be established. contours'. The number of locations will depend upon the
detail required but it will usually be best to test at least
UPV tests do not provide a direct reading of concrete
40 locations on any one structural element, this being
strength. It has been established however that pulse
practicable because the test can be carried out rapidly
velocity bears a relationship to the quality of concrete.
and i s nondestructive.
This relationship will vary according to details of the
concrete mix, in particular the properties of aggregate. 5.2.4 Execution of tests. Positions chosen for test
locations should be marked out accurately on the surface
The main virtue of the test, therefore, is that it provides
of the concrete, which should be cleaned so as to be free
a method of determining the variation in quality of concrete
from grit and dust. Path lengths should be determined
in different locations in one element, or in a series of
to within an accuracy o f t 1 % and a suitable couplant
elements, where the same mix has been used throughout.
should be applied to each of the test points.
Where the strength of concrete has been determined by
Pulse transit times should be measured by a skilled
other means and pulse velocities in the same samples
operator using apparatus in accordance with
have been determined, a correlation curve can be
BS 4408 : Part 5, which requires an accuracy of measure-
established for that particular mix. In these circumstances
ment of not less than f 1 %. It is important that good
the ultrasonic pulse velocity test can be used to establish
acoustic coupling is established between transducers and
indirectly the strength of concrete, and particularly the
concrete surface for each test.
variation in strength, throughout the elements under test.
Test results should be examined and any unusual reading
For more detailed information see BS 4408 : Part 5.
should be repeated carefully to verify or amend the
5.2.2 Selection of test location. The direct transmission reading as necessary.
arrangement generally provides the most reliable measure- 5.2.5 Estimated in-situ cube strength. A reliable estimate
ment and should be used whenever possible. It is preferable of in-situ strength can only be obtained if correlation
to place transducers on smooth areas of the concrete between cube aushing strength and pulse velocity is
surface, a moulded surface being generally more known for the particular concrete mix used in the
satisfactory than a floated or trowelled one. condition in which it exists in the structure. The correlation 4
It is preferable to choose locations so that the length of can be obtained from tests on works cubes or from suitable
the pulse path is a t least 150 mm. Considerably longer beams made from the same concrete mix. It is advisable to
paths may be used but the longer the path the greater the carry out tests on a t least 30 cubes or beams over a wide
possibility that small regions of suspect concrete will range of strengths. A suitable range of strength may be
be undetected. obtained by varying the waterjcement ratio of the mix or
The presence of reinforcement can influence measurements the age of test. The correlation is influenced by moisture
since pulses travel faster through steel than through conditions of the concrete and, if this i s substantially
concrete. Measurements made on concrete containing steel different from that of the in-situ concrete, an appropriate
will indicate higher velocities than in plain concrete since allowance should be made.
the pulses will be travelling partly in steel and partly in Accuracy of values of estimated in-situ strength depends
concrete. When the pulse runs in the same direction as mainly upon the validity of an assumed correlation
the reinforcement, the pulse velocity is essentially that in between in-situ strength and pulse velocity rather than
the steel, which can be up to 50 % more than in concrete. the number of results. Accuracy of the estimated in-situ
BS 4408 : Part 5 shows how corrections can be made to cube strength of a concrete a t a single location can be of
allow for steel but these are approximate and the accuracy the order of -?r 20 % but only if a correlation curve is
of the estimated pulse velocity of the concrete i s reduced. available for that particular concrete.
The effect of steel on the measurement of the pulse If a correlation curve for the particular concrete is not
velocity is negligible if the pulse transmission is a t right available, a value of the estimated cube strength may be
angles to the direction of the steel. Locations where obtained by combining ultrasonic and core tests in order
reinforcement lies directly along or close to the pulse to obtain a correlation between core strength and pulse
path should be avoided. To satisfy this, it may be velocity in the cores. This correlation is likely to be based
necessary to choose some of the pulse paths using the on only a few core test results with a limited strength
semidirect transmission measurement, where the range and accuracy of the estimated cube strength is
reduced accordingly.
5.3 Gamma ray test. The method of testing concrete by
means of gamma radiography (BS 4408 : Part 31 i s not any other discontinuity, or within 100 mm of another
considera suitable for strength assessment. This method testing point or within 25 mm of reinforcement unless
gives useful information on density variations and location the cover is more than 25 mm.
of reinforcement as well as the efficiency with which Correlation between the test result and the strength of
ducts are grouted. As this test is not recommendedfor concrete may be influenced by compressive strain on the
strength assessment, no further information is given in concrete and so it may be preferable to test concrete in
this standard. regions where compressive stresses are low. Selected test
5.4 Near-to-surface tests. In recent years, a number of tests locations should permit adequate access and space for
have been developed that provide a measure of the in-situ purposes of conducting the test.
strength of concrete near to the surface (4). The results 5.5.3 Number of tests. Six valid internal fracture tests
of such tests should be viewed with caution for larger are needed to obtain a mean value for one location.
elements, or in circumstances where the compaction of This mean value based upon six tests is likely to be
the original mix was such as to produce a hard 'skin' on accurate, with 95 % confidence, within 30 %.
the surface of the element under consideration.
5.5.4 Testing procedure. The method of test should be
The methods include those outlined in 5.4.1 to 5:4.3.
strictly in accordance with recommendations of the
5.4.1 Pull-out tests Building Research Establishment (l,2). Each test result
(a) Based on measurements of the force required to should be recorded as the maximum reading indicated
pull out special assemblies whose enlarged end has on a torque meter.
been cast into concrete. (See Malhotra and Carette'(81; 5.5.5 Estimated in-situ cube strength. Data available
Kierkagaard-Hansenand Bickley (91.1 suggests that the estimated cube strength, in N/mm2,
(b) Based on measurements of the force required to of concrete made with 20 mm maximum size gravel or
pull out bolts, fitted either with split-sleeveexpanding limestone aggregate and ordinary Portland cement may
assemblies or epoxy resin into holes drilled in hardened be estimated by applying the following formula to the
concrete. (See Chabowski and Bryden-Smith (1, 2); mean toque of six or more tests in one location:
Maillhot e t a l (lo).) Estimated cube strength = 3.74 T'.'' N/mm2
5.49 Break-off test. Based on direct measurements of the where T is the torque, in N m.
flexural strength of concrete in an annular moss section
For other types of concrete (and, preferably, for those
parallel to, and a t a definite distance from, the concrete
described above) it is recommended that, if possible,
surface. (See Johansen (1I).)
correlation between cube strength and torque should
5.43 Penetration test. Based on measurements of the be established by tests on samples of the concrete
resistance of concrete to penetration by a hardened alloy being examined.
probe fired into the surface.'
5.6 Surface hardness test
5.4.4 Use of tests. Experience with many of these methods
5.6.1 General. Surface hardness tests, which include
so far is limited. Some of the tests have to be pre-planned
rebound and indentation methods, provide only an
with assembJiesor disposable forms being placed in the
approximate indication of strength and are discussed in
formwork before casting. Others require more development
detail in BS 4408 : Part 4. Their application is generally
to reduce the within-test variation to acceptable limits.
limited to tests on concrete with ages between about
Whenever these or similar tests are used, it is recommended 3 days and 3 months. Concrete younger than 3 to 7 days
that the equipment, procedure and number of tests are may be damaged by what is essentially a nondestructive
fully described and the accuracy and reliability of the test while concrete older than 3 months is likely to
correlation between test measurement and i n 4 t u cube have suffered carbonation at the surface. This can increase
strength clearly defined. This is demonstrated in 5.5 for wrface hardness unduly and give rise to considerable
the internal fracture test developed by the Building errors in assessing the estimated cube strength.
Research Establishment (1, 2) to assist in the structural
5.6.2 Selection of test location. Smooth and dry surfaces
appraisal of high-alumina cement concrete structures.
should be selected as test locations. Wherever possible
5.5 Internalfracture test surfaces to be selected should have been formed by
56.1 General. This test was introduced in 1976 and thus shuttering. Free trowelled surfaces could however be used
experience to date is small. The test is sometimes called if necessary, although less reliance has to be placed on the
'pull-out' test but it is quite distinct from that described results unless surfaces are ground before testing.
in references (3).(8) and (9). Open-textured or honeycombed areas have to be avoided.
It should be emphasized that the internal fracture test The points chosen for tests should be at least 20 mm
provides information on the strength of concrete a t or away from an edge or sharp discontinuity and should be
near the surface of an element only. not less than 20 mm from each other.
5.5.2 Selection of test locations. The test involves drilling Presence of reinforcement does not normally influence
holes 6 mm in diameter and 30 mm to 35 mm deep, test results so that choice of test location should not be
in the surface of concrete. Conduct of the test may spall affected by the position of steel bars in concrete.
the concrete, leaving a shallow hole on the surface that Usual directions of test are either horizontal or vertically
can be some 50 mm across. Location of testing points down but any direction may be used provided this is
should, therefore, be planned with an appreciation that measured and taken into account in interpretingtest
the surface may be damaged. Holes should not be drilled results.

'See ASTM C803-79 (12). The method is generally known as the Wincbor probe test.

K
i 5.6.3 Number of tests. Surface hardness tests are similar trated in the top 300 mm or 20 % of the depth,
: to pulse velocity tests in that they are essentially whichever a the less.
1
C

nondestructive (although the concrete surface is marked) (d) At 28 days after casting, columns can have a mean

iand accuracy of estimated in-situ cube strength depends


upon the validity of the assumed correlation between
in-situ strength and test results. Unlike the pulse velocity
in-situ strength of 65 % of the mean standard cube
strength, with strength in the individual columns
carrying from 50 % t o 80 % (7). The little evidence
! test, however, repeat tests within one location vary available for floor slabs suggests that mean in-situ

I significantly with random high and low results. Provided


a t least 10 readings are taken in any one location
(preferably an area not more than 300 mm square)
strength may only be 50 % of the mean standard
cube strength.
(el The gain in insitu strength from 28 days onwards
+
the mean reading is likely to be accurate within 151dn %
is not consistent. At 6 months, the increase in mean
with 95 % confidence, where n is the number of individual
strength can vary from 0 to 25 % and a t one year
from 0 to 35 %of the 28 day strength.
; 5.6.4 Execution of tests. Tests should be made with a Thus, the normal variation of an in-situ strength within
suitable device (rebound hammer or indentation device
and between structural members has to be borne in mind
of an appropriate size) and i t s correct functioning should
when evaluating insitu results. Examination of individual
be checked.
test results will identify whether variations between results
Tests should be made at each location in a systematic way are excessive. Further tests may be required to establish
by choosing points on the concrete surface a t intersections whether certain results are rogue values or not.
of a regular grid of lines 20 mm to 50 mm apart.
6.3 Eelationship between compressive strengths. Figure 1
The mean of all readings taken at each test location should illustrates numerical differences of the various strengths
be calculated using all readings (including abnormally high as defined. The strengths given are based on typical
and low values). situations, using average constants and rounding to the
,' 56.5 Estimated in-situ cube strend. A reliable estimate nearest N/mm2. The hatched areas show the surfaces
of in-situ strength can only be obtained if correlation through which the specimen is tested. A standard cube is
f
: between hardness reading and cube strength is known for tested on a surface obtained from a machined plate
the particular concrete mix used. A correlation may be whereas, inthe case of standard cylinders and cores,
obtained on cubes (preferably 150 mm size) of the the specimen is tested on a bedded or ground surface.
particular mix under test over a range of strengths. Details The strength of this single batch of concrete as measured
of the execution of correlation tests are given in by a standard cube strength is 30 ~/mrn'. If the strength
BS 4408 : Part 4. is measured on a cylindrical test specimen the most likely
By using a correlation curve obtained in this way, value of the cylinder strength is 24 ~/rnm'.
it is possible to estimate the strength of concrete near the If this single batch of concrete is now cast into a structural
surface to an accuracy of within + 20 % provided the member such as a column i t s strength will be less, owing
concrete i s not more than about 3 months old. to factors such as compaction and curing, and will vary
However, this degree of accuracy may be significantly depending on its position in the column (see 6.1).
reduced if the condition of in-situ concrete i s different For example. if cores were cut near the top and the base
from that of concrete used for the correlation tests, of the column, the core strength (A = 11 could be
since curing conditions and surface moisture conditions 20 N/mm2 and 23 N1mm2 respectively. The same values
can influence correlation considerably. of 20 NlmmZ and 23 N/mm2 would apply to the estimated
in-situ cube strengths. Ifthe lengthldiameter ratio differs
from 1, the formulae in 5.1.8 should be used.
: 6. Conducting an investigation 6.4 Location and number of test results
1 6.1 General. Having taken account of the various factors 6.4.1 Tests at a single location. The in-situ cube strength
outlined in clause 4 in the determination and execution of at a single location may be estimated by calculating the
a suitable test programme, the subsequent interpretation average of a number of individual test results. Any varia-
of test results and decisions regarding any future action
tion between individual results has tcrbe assumed to stem
will depend upon:
from testing errors rather than from variations in the
(a) the inherent variations in in-situ strength; quality of the concrete being tested. I f results do not
(b) the location and number of test results; support this assumption, the situation should be
reappraised and the results taken as coming from more
(c) interpretationof results;
than one location.
(d) potential courses of action;
6.4.2 Tests at a number of locations. The number of
f 6.2 @herentvariations in in-sit" strength. Tests on in-situ measurements should be sufficient to enable variations
i concrete (5.6.71 indicate the following. in the quality of the concrete to be identified and defined.
(a) ln-situ strength can vary within a structural member Once this has been done, it will often be necessary to
both randomly and, often, in an ordered fashion. conduct further tests on regions where the concrete
(b) The magnitude of variations of in-situ strength strength is relatively low, possibly using a different type
within structural members varies from one member of test. The results of such further tests should be treated
to another in a random fashion. as being from a single location.
(c) With height of a concrete lift, in-situ strength 6.4.3 Typical test programme. The object of most
investigationswill be to establish, for a particular
1
$
decreases towards the top of a lift, even for slabs, and
can be 25 % less a t the tor, thaninthe bod structural element, the in-situ strength at:
a x e . Concrete of lower strength is oe tf=/ (a) any critical design sections;
Ft:
(b) the region having the lowest in-situ strength; -to take measurements at these locations and, with appro-
(c) any other location of interest. priate correlation curves, obtain estimates of the
corresponding mean estimated in-situ cube strengths a t
These aims can be achieved by:
those locations. The accuracy of these estimates will
( I ) making a visual survey; depend upon the number of test measurements and the
(2) making a general scan of the structural element, reproducibility of the test method (see 5.12,5.2.2,
using a nondestructive technique such as ultrasonic 5.52 and 5.6.2).
pulse or surface hardness tests (or preferably both); 6.5.3 Comparisons between estimated in-situ cube
(3) making a more detailed local survey, both a t the strength and design strength. To ensure structural safety
aitical section and a t the location exhibiting the in accordance with design principles of section 2 of
weakest concrete; this should involve nondestructive CP 110 : Part 1 : 1972, it is recommended that a check
methods and in-situ strength tests such as cores, should be made to ensure that the estimated in-situ cube
internal fracture, pull-out or breakoff tests. strength, obtained from methods described in clause 5,
6.5 Interpretation of results is acceptable on the basis of comparisons with design
strength at:
6.5.1 General. Since there are many different reasons for
making an investigation into in-situ strength of concrete, (a) thg critical design sections;
it is possible to give only general guidance on interpretation (b) the locations identified with low strength concrete;
of estimates of the in-situ strength of concrete in a (c) any other location of interest.
structural element.
r 6.52 Relationship betwen standard cube strength,
design strength and estimated in-situ cube strength.
The level of in-situ cube strength that may be considered
acceptable in any particular case is a matter for engineering
judgement but should not normally be less than 1.2 times
Design of reinforced and prestressed concrete structures the design strength.
is based on the commonly accepted principle that concrete
The particular strength level selected should include an
can be considered as a randomly variable material, the test
allowance for possible future deterioration of the strength
results of which follow a normal distribution. Inevitable
of concrete that may result from chemical attack,
differences between in-situ strength of concrete and that of
weathering, vibration or some unforeseeable impact or
standard cubes mean that there will be different distribu-
other circumstances.
tions of results from large numbers of in-situ tests
compared with standard cube tests on the same concrete. Thus in cases where the design strength is based on
In design, these differences are taken into account by the , = 1.5, the following equation should assist in the use
7
introduction of the partial safety factor for strength .7, of the tables given in CP 110:
Figure 2 shows the relationships between standard cube Estimated in-situ cube strength
f, = 1.5
strength, design strength and estimated in-situ cube 1.2 (or other appropriate factor considered
strength. The standard cube strength is obtained from suitable in particular circumstances)
specimens compacted, cured and tested in a standard way
6.6 Courses of action. Action to be taken in respect of a
at one particular age.
structural member in which the in-situ wncrete is
An estimate of the characteristic strength f, can be considered to fall below the level required has to be
determined from the distribution of a large number of determined by the engineer. This may range from qualified
standard cube results using the expression acceptance in less severe cases to some form of remedial
F f,, = mean concrete cube strength - 1.64 x work, or to removal and replacement in the most severe
standard deviation cases. Alternatively, load tests may be carried out in
or assumed to be equal to, or greater than, the specified accordance with 9.6 of CP 110 : Part 1 : 1972.
strength grade, provided the test results comply with the In determining.theaction to be taken, the engineer should
appropriate compliance requirements as given in 6.8.2 have due regard to the technical and economic conse-
of CP 110 : Part 1 : 1972 or 16.2 of BS 5328 : 1976. quences of alternative remedial measures either to replace
the substandard concrete or to ensure the integrity of the
For the analysis of sections, the design strength is given
structural element from which it has been made. Other
by f,l'Y,, where, for CP llO,Y, = 1.5 for ultimate
factors that should be taken into account include:
strength.
(a) the actual load on the structural element in
For any particular element in a structure the design stress
comparison with the design strength and the
may differ from the des,gn strength depending on the
appropriate partial safety factor;
design philosophy adopted (see also 3.7).
(b) possible effects of any reduction in quality on the
The in-situ strength of concrete in a structural element
strength and durability of the particular structural
has to be found from the in-situtest programme.
element;
Owing to the limitations of in-situ testing, an accurate
estimate of the distribution of in-situ strengths is rarely (c) the influence of age on the strength of the in-situ
possible. However, by identifying the critical design section wncrete.
and/or the location of the weakest concrete. it is possible

I Reserve Collection
Appendix A

Bibliography 7. DAVIES, S.G. Further investigations into the strength


of concrete in structures. Cement and Concrete
ReferenceS
Association - 42.514, April 1976.
1. BUILDING RESEARCH STATION. Pull-out test for
References 8 to 10 that follow were papers presented a t
the assessment of the strength of HAC concrete.
Garston, November 1975, pp 2. Information sheet the American Concrete Institute Symposium on In-situ
Strength Evaluation of Concrete, Houston, Texas,
IS 28/75.
November 1978.
2. CHABOWSKI, A.J. and BRYDEN-SMITH, D. A simple
pull-out test to assess the in-situ strength of concrete. 8. MALHOTRA, V.M. and CARETTE, G. Comparison
Precast Concrete, May 1977, pp 243-246 and 258. of pullout strength of concrete with compressive
3. MALHOTRA, V.M. Testing hardened concrete; strength of cylinders and cores, pulse velocity and
nondestructivemethods, Chapter 4: Pull-out tests. rebound number.
Detroit, American Concrete Institute Monograph 9. KIERKAGAARD-HANSEN, P. and BICKLEY, JA.
No. 9,1976, pp 4351. ln-situ strength evaluation of concrete by the
4. MALHOTRA, V.M. Symposium review. ln-situ strength Lok-test system.
evaluation of concrete. Concrete International, 10. MAILLHOT, G., BISAILLON, A., MALHOTRA, V.M.
September 1979, pp 4042. and CARETTE, G. Investigations into the develop-
5. THE CONCRETE SOCIETY. Concrete core testing ment of new pullout techniques for in-situ strength
for strength. London, May 1976, pp 44. Technical determination of concrete. 4
Report No. 11. 11. JOHANSEN, R. ln-situ strength evaluation of concrete
6. CEB/CIB/FIB/RI LEM Report: Recommended - The 'brea kaff' method. Concrete International,
principles for the control of quality and the judgement September 1979, pp 4551.
of acceptability of concrete. Also published as 12. ASTM STANDARD C803-75. Penetration resistance
CEB Bulletin d'lnforrnation No. 110, May 1975. to hardened concrete.
Table 1. Guide to tests for assessing aspects of concrete strength

Structural rr#+

Concrete Standard Direct


cube strength

In-situ Indirect Indirect Fairly direct Indirect Indirect


strength
p~

Structural Design load Very indirect Very indirect Indirect Direct Direct
member capability

Ultimate Very indirect Very indirect Indirect lndirect Direct


strength

Table 2. Relative merits and limitations of various tests

A a u r ~ of
strength
estimate
y
I t It&
Speed of Ease of
It_
Economy of
I Lack of damage
to structure

In depth Core test BS 1881 :


Part 4

Ultrasonic BS 4408 :
pulse Part 5

Y ray BS 4408 : See 5 3


Part 3

Near to Internal lnsufficient experience available at present


surface fracture

Pullout lnsufficient UK experience available at present. Some pull-out tests


(e.g. reference (8) and (9)) generally not applicable unless bolt cast
Breakoff in a t time of construction.

Penetration
resistance

Immediate Surface BS 4408 :


surface hardness Part 4

I Reserve Co'ilection I
One batch Standard specimens

Standard cube Cylinder


strength strength

Cores from structure


t
Structure

I
1I Core strength $<:-* ,
Estimated in-situ
I
cube streriijfli-

Variations in compaction curing, position, age, eR.


-
$ Figure 1. Illustration of approximate relationship of compressive strenws
Standards publications referred to
BS 1881 Methods of testing concrete
Part 1 Methods of samplim fresh concrete
Part 3 Methods of rrmkin~ and curing test rpecimem
Part 4 Methods of testing concrete for strength
Part 5 Methods of testing hardened concrete for other than strength
BS 4019 Specifition for core drilling equipment
Part 2 Concrete drilling equipment
BS 4408 Recommendetiom for nondestructive methods of test for concrete
Part 3 Gamma rediogrsphy of concrete
Part 4 Surfaca hardness methods
Part 5 Measurement of the wlodty of ultrasonic pulses in concrete
CP 110 The muaural use of concrete
Part 1 Design, materials and workmamhip
This British Standard, having been prepared under the direction of the standard, of necessary details such as symbols and size, type or
the Civil Engineering and Building Structures Standards Committee. grade designations. Enquiries should be addressed t o the
was published und& the authority of the Executive Board and Publications Manager, 101 Pentonville Road. London N1 9ND
mmes int6 effect on 30 November 1981. (Telephone 01-837 8801;Telex 23218).
@ British Standards Institution, 1981 Contract requirements
ISBN 0 580 12441 X Anention is drawn to the fact that this British Standard does not
purport to include all the necessary provisions of a contract.
British Standards Institution Revision of British Standards
Incorporated by Royal Charter, BSI is the independent national British Standards are revised, when necessary, by the issue either
body for the preparation of British Standards. It is the UK member of amendment slips or of revised editions. It is important that
of the International Organization for Standardization and UK users of British Standards should ascertain that thoy are i n
sponsor of the British National Committee of the International possesion of the latest amendments or editions. Information
Electrotechnical Commission. on all BSI publications is in the BS Yearbook, supplemented
each month by BSI News which is available t o subscribing
Copyright
Usen of British Standards are reminded that copyright subsists in memben of the Institution and gives details of new publications,
revisions, amendments and withdrawn standards.
all BSI publications. No part of this publication may be reproduced
in any form without the prior permission in writing of BSI. The following BSI references relate t o the work on this standard:
This does not preclude the free use, in the course of implementing Committee reference CSB139 Draft for comment 77113782 DC

Cooperating organizations
The Civil Engineering and Building Structures Standards Committee, 'Institution of Structural Engineen
under whose direction this British Standard was prepared, consists lnstitution of Water Engineers and Scientists
of representatives from the following: London Transport Executive
Aluminium Federation Ministry of Agriculture, Fisheries and Food
'Association of Consulting Engineers 'National Federation of Building Trades Employers
Brick Development Association National Water Council
'British Precast Conaete Federation Ltd *Royal Institute of British Architects
British Steel Corporation Scottish Development Department
'British Steel Industry Timber Research and Development Association
*Cement and Concrete Association Trades Union Congress
'Concrete Society Limited
Consumer Standards Advisory Committee of BSI The organizations marked with an asterisk i n the above list,
Convention of Sconish Local Authorities together with the following, were directly represented on the
County Surveyors' Society Technical Committee entrusted with the preparation o f this
'Department of the Envitonment (PSA) British Standard:
'Department of the Environment (Building Research Establishment British Railways Board
'Department of the Environment (Housing and Construction) British Ready Mixed Conaete Association
'Department of the Environment (Transport and Road Research British Reinforcement Manufacturen'Awciation
Laboratory) Cement Admixtures Association
Department of the Environment (Water Engineering Division Cement Makers' Federation
including Water Data Unit) District Surveyon Association
Department of Transport Federation of Concrete Specialists
'Federation of Civil Engineering Contractors Greater London Council
Health and Safety Executive Incorporated Association of Architects and Surveyors
'Institution o f Civil Engineers National Building Agency
'Institution of Municipal Engineers Sand and Gravel Association Limited
lnstitution of Public Health Engineen

IPOLYTECB3li: LIBRARY

Amendments issued since publication

Amd. No. Date of issue Text affected

British Standards Institution . 2 Park Street London W1A 2BS Telephone 01-629 9000 Telex 266933

Você também pode gostar