SIEMENS incl. SSP for STARTER

General conditions and function limitations, notes for configuration and operation

These notes take precedence over statements contained in other documents.


Because these notes contain important information for the installation and use of the software, please read them carefully.

SINAMICS S110 V4.4 SP3 incl. SSP for STARTER


ARTSPlusRQ Brief description Description Possible work-around
SINAMICS_SW - CAN communication
AP00875674 If a CAN partial save (Store Com. If a CAN partial save (Store Com. or Store Appl. param) is triggered Execute a full data save p0977 "Save all
or Store Appl. param) is triggered without having previously performed a full save at least once, then the parameters" = 1.
without having previously corresponding ACX files (CCxxxxxx.ACX and CAxxxxxx.ACX) are
performed a full save at least available at /USER/SINAMICS/DATA/*, but are not read in at a restart
once, then the corresponding ACX and therefore have no effect. The files are also not saved to an
files (CCxxxxxx.ACX and inserted memory card.
CAxxxxxx.ACX) are available at
/USER/SINAMICS/DATA/*, but
are not read in at a restart and
therefore have no effect. The files
are also not saved to an inserted
memory card.
SINAMICS_SW - Safety Integrated
AP01095434 For SDI with setpoint input 0 and When the parameterized absolute current value in p9783 "SI motion Set parameter p9783 "SI motion
synchronous motor, safety fault synchronous motor current injection encoderless" is the same as the synchronous motor current injection
C01716/C30716 "SI motion: set minimum current in p9588 "SI motion actual value acquisition encoderless" to at least 1.2 times p9588
Tolerance for safe direction of encoderless minimum current" and the synchronous drive is in no-load "SI motion actual value acquisition
motion exceeded" or operation, then a faulty alarm of a safety monitoring function can encoderless minimum current".
C01711/C30711 (3) "SI motion: occur, such as C01716/C30716 "SI motion: Tolerance for safe
defect in a monitoring channel". direction of motion exceeded" or alarm C01711/C30711 "SI motion:
Defect in a monitoring channel".
AP01127246 Parameters p9554/p9354 "SI Parameters p9554/p9354 "SI motion transition time from STOP E to Reset p9554/p9354 to default value 100.
motion transition time from STOP SOS (SBH)" are erroneously displayed in the expert list for the
E to SOS (SBH)" are erroneously CU305. They have no function for the CU305 and must not be used. A
displayed in the expert list for the parameterization of p9554/p9354 results in the non-acknowledgeable
CU305. They have no function for fault C01711/C30711 "SI motion CU: Defect in a monitoring channel"
the CU305 and must not be used. with fault value 39 "Transition time from STOP E to SOS
A parameterization of (p9554/p9354)".
p9554/p9354 results in the non-
acknowledgeable fault
C01711/C30711 "SI motion CU:
Defect in a monitoring channel"
with fault value 39 "Transition time
from STOP E to SOS
(p9554/p9354)".
TFS77055 If p9500 "SI motion monitoring If p9500 "SI motion monitoring cycle clock" is not an integer multiple of Restore factory settings and recommission
cycle clock" is not an integer the current controller cycle clock p0115[0] "Sampling times for internal the drive object. Whereby, set p9500 "SI
multiple of the current controller control loops", the following faults can occur when powering up the motion monitoring cycle clock" as an
cycle clock p0115[0] "Sampling drive system; F01200 "CU: Time slice management internal software integer multiple of the current controller
times for internal control loops", error" with fault value 1009, F01000 "Internal software error" with fault cycle clock p0115[0] "Sampling times for
errors can occur when powering value hexadecimal 259_04DE, F30652 "SI MM: Illegal monitoring internal control loops". Note for the CU305,
up the drive system. cycle clock" with fault value 101. p0115[0] is permanently set to 250 us and
cannot be changed.
FH3 Funktionsh S110 - General
TFS36971 S110 Function Manual (FH3) S110 Function Manual (FH3) 06/2012 V4.4 SP1 Chapter 7.1.12 After the motor data identification, the
"Motor data identification" There is no note that after the motor data "Copy RAM to ROM" function must be
identification, function "Copy RAM to ROM" must be carried out to performed.
permanently save the data that have been determined.
TFS373719 S110 Function Manual (FH3) S110 Function Manual (FH3) 06/2012 V4.4 SP1 Chapter 3.5.2 The correct statement is that for a non-
"Commissioning with STARTER (example)" Table 3-5, 1st point It has configured drive, the "Automatic
been incorrectly described that the "Automatic configuration" must be configuration" is automatically performed.
manually initiated.
GS2 Getting Started S110 - General
TFS42205 S110 Getting Started (GS2) S110 Getting Started (GS2) 08/2008 V4.1 Fig. 2-1: The sequence The correct sequence is line reactor-line
when installing components – line filter-line reactor-Power Module – is filter-Power Module. See Catalog PM22 or
incorrect. S110 Device manual (GH8) 04/2015 V4.4
SP3.

Restrictions for SINAMICS S110 V4.4 SP3 incl. SSP for STARTER -1- 10.04.2015