GUIDE TO IP CODES
COMPANIES INVOLVED IN THE
PREPARATION OF THIS GUIDE
Elsteel UK Ltd
Off Davy Way Rappell Group Ltd
Llay Industrial Estate, Llay Moston Road
Wrexham Sandbach
LL12 0PG CW11 3HL
Tel: +44 (0) 1978 855909 Tel: +44 (0) 1270 761135
Fax: +44 (0) 1978 855824 Fax: +44 (0) 1270 762997
Email: sales@elsteel.co.uk Email: sales@rappell.co.uk
www.elsteel.co.uk www.rappell.co.uk
Siemens Ltd
Legrand Electric Ltd Sharston Road
Great King Street North Wythenshawe
Birmingham Manchester
B19 2LF M22 4RA
Tel: +44 (0) 370 608 9020 Tel: +44 (0) 161 945 3956
Fax: +44 (0) 345 600 6760 Fax: +44 (0) 8456 053114
Email: powersales.uk@legrand.co.uk www.siemens.co.uk
www.legrand.co.uk
ABOUT BEAMA
BEAMA is the long established and respected trade association for the
electrotechnical sector. The association has a strong track record in the
development and implementation of standards to promote safety and product
performance for the benefit of manufacturers and their customers.
This Guide provides guidance on the degree of protection provided by
enclosures (IP Code).
This Guide has been produced by BEAMA’s Installation Sector which comprises
of major UK manufacturing companies operating under the guidance and
authority of BEAMA, supported by specialist central services for guidance on
European Single Market, Quality Assurance, Legal and Health & Safety matters.
Details of other BEAMA Guides can be found on the BEAMA website
www.beama.org.uk
DISCLAIMER
This publication is subject to the copyright of BEAMA Ltd. While the information herein
has been compiled in good faith, no warranty is given or should be implied for its use
and BEAMA hereby disclaims any liability that may arise from its use to the fullest extent
permitted under applicable law.
Acknowledgements
BEAMA would like to thank IEC and BSI for allowing references to their standards;
Health and Safety Executive (HSE) for reference to their documents.
CONTENTS
1. INTRODUCTION 6
2. SCOPE 6
3. OVERVIEW 7
4. DESIGNATIONS 8
5. SELECTION 9
6. WEATHERPROOF APPLICATIONS 14
7. DRAINAGE HOLES 15
8. VENTILATED EQUIPMENT 16
9. EMPTY ENCLOSURES 16
The purpose of this guide is to provide Principally, these requirements are Additional information has been
an easily understood document, aiding detailed in BS EN 60529:1992+A2:2013 included having regard to the particular
understanding and application of the (IEC 60529:1989+A1:1999+A2:2013) considerations necessary for equipment
requirements for degrees of protection which defines the degrees of protection intended for exposure to weather and to
provided by enclosures. provided by enclosures classified under the requirement for natural ventilation,
the International Protection (IP) Code which exists with some products.
and the test conditions required to meet
these classifications. International
Protection (IP) is commonly referred to
in the UK as “Ingress Protection”. For
technical correctness this guide uses
the IEC Normative reference.
READERS SHOULD
NOTE THE REQUIREMENTS
IN THE STANDARD CALL
FOR COMPARATIVE TESTS
AND THESE BEAR NO
ACTUAL RELATIONSHIP
TO SPECIFIC WEATHER OR
CORROSIVE CONDITIONS.
BS EN 60529 describes a method for the enclosure, but specifying a higher The code letters IP of BS EN 60529
classifying degrees of protection degree of protection does not refer to International Protection as
provided by enclosures, principally for necessarily ensure it is the most suitable applicable to enclosures of electrical
electrical equipment. for a particular application. For instance, equipment with a rated voltage not
ventilation reduces the possibility of exceeding 72.5kV. It should be noted
Whilst this method is suitable for use
internal condensation (See sections 6, 7 that this standard is also applicable to
with most types of electrical equipment,
and 8). Within a sealed enclosure, it empty enclosures provided that the
it should not be assumed that all the
may also be necessary to use devices general test requirements are met and
listed degrees of protection are
with a higher free air rating and that the selected degree of protection
applicable to a particular type of
conductors with increased cross is suitable for the type of equipment to
equipment.
sectional area. be enclosed.
If the degree of protection of the
Designation with a degree of protection The majority of BEAMA member
equipment or the enclosure is not
implies that the enclosure also complies products are within the scope of the
specified in the manufacturer’s
with all the lower degrees except for Low Voltage Directive. This guide is
literature, then the manufacturer should
IPX7, IPX8 and IPX9. therefore only intended to describe the
be consulted.
classifications for degrees of protection
For the most cost effective solution, the provided by enclosures of electrical
appropriate level of ingress protection equipment with a rated voltage not
that meets the need of the application exceeding 1000V ac and 1500V dc.
should be specified. In general, the
higher the IP code, the more expensive
• mechanical impact
• solar radiation
• corrosion
• icing
• corrosive solvents
• moisture (condensation)
• fungus
• explosive atmospheres
• vermin
• contact with moving parts
DESIGNATION external to the enclosure
WITH A DEGREE OF Where an enclosure needs to be
PROTECTION IMPLIES machined or adapted for the attachment
of cable glands, conduit or any other
THAT THE ENCLOSURE equipment, any instructions provided by
ALSO COMPLIES WITH the enclosure manufacturer should be
strictly observed to ensure the required
ALL THE LOWER DEGREES degree of protection is maintained.
EXCEPT FOR IPX7, IPX8 Although not a part of BS EN 60529,
AND IPX9. some general notes on weather
resistance, drainage holes and the need
for natural ventilation in certain products
are included in sections 6, 7 and 8 of
this guide.
2 Skilled Person (electrically): A person who possesses, as appropriate to the nature of the electrical work to be undertaken, adequate education, training and practical skills, and who is
able to perceive risks and avoid hazards which electricity may create. (BS 7671 refers).
3 Instructed Person (electrically): A person adequately advised or supervised by a skilled person to enable that person to perceive risks and to avoid hazards which electricity can
create. (BS 7671 refers).
Residential (households, Generally clean, dry and free from IP2XC for dry conditions
dwellings and similar)/ harmful deposits of dust, but some
Office/ School condensation may be present due to
atmospheric conditions
Control rooms / Generally dry and free from harmful IP2X where access is restricted to skilled or
Sub-Stations / deposits of dust, but some instructed persons
Switch-rooms condensation may be present due to
atmospheric conditions
Commercial / Light May not be clean, but normally dry a) IP2XC where condensation is not present
Industrial and free from harmful deposits of dust b) IP21C where condensation may be present
c) IP54 where fluids may be present e.g. lathes,
millers, etc
Heavy Industrial, May not be totally clean, with possible IP54 with special consideration given to
Chemical, Steel presence of corrosive elements and corrosion resistance of the enclosure
making, etc harmful deposits of dust
Food processing Will vary depending on the type of a) IP53 where fine powders are present
food being processed and the possible b) IP54 if the equipment is subject to splashing
requirements for washing down c) IP55 if the equipment is to be washed or
hosed down at low pressure
d) IP56 if the equipment is to be subject to
powerful water jets
e) IP59 if the equipment is subject to high
pressure and temperature water jets
Swimming pools / Will vary on depths and levels of a) IPX7 for equipment subject to temporary
Pumping stations submersion immersion
b) IPX8 for equipment permanently immersed
NOTE 1: Where hazardous live parts are covered with basic insulation (as defined in the appropriate product standard), which can only
be removed by destruction or by the use of a tool, the probe can touch the insulation.
FIGuRE 3B – IPXXC (SEE NOTE 1 BELOW) FIGuRE 3C – IPXXD (SEE NOTE 1 BELOW)
NOTE 1: Where hazardous live parts are covered with basic insulation (as defined in the appropriate product standard), which can only
be removed by destruction or by the use of a tool, the probe can touch the insulation.
The effects of continuous exposure Thus, both the material and the finish Consideration should also be given to
to weather and the environment are become important factors. the possible effects of condensation,
difficult to evaluate, and therefore which can be caused by occasional
Steel is often used but needs thorough
the choice of material for the temperature changes. This may be
pre-treatment in addition to an
enclosure is as important as the actual solved by ventilation, use of anti-
appropriate quality paint finish.
IP designation. BS EN 60529 does not condensation heaters, climate controls
include any guidance to the selection Stainless steel is relatively more or by ensuring any condensation
of enclosure materials. expensive at the outset, but generally created does not cause harm and may
gives a long maintenance free life in be allowed to drain away. Generally an
It should be noted that IP ratings are
most environments. air temperature inside the enclosure, of
for ingress only and that tests are
5 degrees above external ambient, will
comparative and are conducted with Aluminium is also often used for prevent condensation within the
fresh water. outdoor use, but its grade, location and enclosure.
finish needs careful consideration to
avoid corrosion. If the protective finish Drainage holes may be sufficient to
THEREFORE, THEY IN becomes damaged, it can quickly disperse the condensate, but these
NO WAY INDICATE THE corrode, however the oxides of apertures may reduce the IP rating.
aluminium themselves form a protective However, if correctly designed, drainage
ENCLOSURE’S ABILITY coating against corrosion in some holes can enhance the weatherproof
TO WITHSTAND THE atmospheres. capabilities of an enclosure. See
sections 7 & 10.
EFFECTS OF CORROSION Enclosures of moulded materials are
available for use in harsh environments Attention should also be paid to any
FROM SALT WATER, and generally provide good resistance gaskets used for the higher IP ratings
CHEMICALS, UV to corrosion and chemicals. However such that water cannot readily be drawn
to avoid deterioration, careful past the seal. This is most likely to occur
RADIATION, ACID RAIN consideration is required when choosing when a warm enclosure is suddenly
AND OTHER SPECIAL moulded enclosures as some materials cooled causing a pressure drop inside.
do not perform well with dilute acids or See section 7.
ENVIRONMENTS AS certain chemicals or when exposed to
The use of the supplementary letter ‘W’
WELL AS THE NORMAL ultra violet light (direct sun light). The
in the Code indicates that the unit is
vast range of moulding materials now
EXPECTED WEATHER available makes it essential for specifiers
suitable for use under specified weather
conditions and is provided with
CONDITIONS. to consult the manufacturer for
additional protective features as agreed
information on the ability of moulded
between the manufacturer and user.
materials to withstand hostile
environments. For additional guidance on
environmental testing, reference should
It should be noted that enclosures on
be made to IEC/BS EN 60068-1.
exposed outdoor sites might be subject
to dust, rain, hail, sleet and snow, all of
which can be windborne.
Ventilation can provide an important To minimise enclosure size and cost it is BS EN 60529 requires the final
contribution to the satisfactory common practice to employ natural manufacturer/installer of an assembly
operation of enclosed equipment. ventilation, using louvres, slots and/or to ensure that after any electrical
Where significant heat is generated in vents as required. Suitably located equipment has been installed within the
an enclosure, ventilation is generally louvres, slots and/or vents can provide enclosure, it still meets the required
employed to permit the equipment to protection against the ingress of heavy IP rating.
operate within its designed dust and occasional drips of condensate
performance characteristics. falling from above. Louvres, slots and It is particularly important where
vents can theoretically be of infinite enclosures need to be adapted or
length providing that the test criteria modified by the user for the attachment
is met. of other equipment or for installation
and cabling, that any instructions
Typically, applicable codes for totally dry
provided by the enclosure manufacturer
situations are IP2XC or IP3X. For
should be strictly observed, to ensure
installations where externally falling
the required degree of protection is
condensate is anticipated, IP21C or IP31
maintained.
would be appropriate.
The following are some typical examples chosen with BEAMA products in
mind. It is impossible to show every type of design and it is recognised that
other design variations are possible.