Você está na página 1de 20

Greenhouse Environment Control System

Considerations

1
Forward:

Greenhouse Environment Control Considerations provides an introduction to the many options


available in greenhouse controls. This document was prepared by NGMA members to familiarize you
with the control technology available from our members, and assist in understanding the value of
environment controls in your greenhouse operation. This document will help in the development of
action plans and setting of priorities for the selection and purchase of controls for new greenhouse
construction, and the retrofitting and expansion of existing greenhouses.

The NGMA does not intend to recommend or endorse any particular type of control system, brand,
or manufacturer. This document does not replace or supercede any electrical or building codes, or
set standards of compliance among manufacturers.

2
CONTENTS
Basics of Control
- History

The Value of Good Control

General Considerations
- Not an Office Computer
- Greenhouse vs. Building Controls
- Control Voltages
- Impact of Greenhouse Design
- Other Applications
- Climate Control Zones
- Common/Global Systems
- Plan Ahead
- Look at the Whole Picture
- What to Control
- Cost Comparison

Levels of Control
- Equipment Level
- Function Level
- System Level

Types of Control Equipment


- Thermostats and Timers
- Step Controls
- Computer Zone Controls
- Integrated Computer Controls

Technical Considerations
- Control Signals
- Sensors

Irrigation Control
- General
- Irrigation Decision Making

Power Management
- Load Shedding
- Peak Shaving
- Phase Shutdown
- Staged Power Up

Installation Considerations
- Contactors & Relays
- Motor Controls
- Wiring
- Conduit
- Panel Locations

Training and Support

Control Concepts and Terminology

Getting Started Guide

3
The Basics of Control
A greenhouse environment is an incredibly complex and dynamic environment. The pressures of
labor availability and costs, energy costs, and market demands increasingly make efficiency and
automation key components for success and profitability. Environment control technology affects all
of these critical areas, and many others, so understanding controls and implementing their use is
more important than ever. Precise control of the greenhouse environment is critical in achieving the
best and most efficient growing environment and efficiency.

The controls companies represented in the NGMA have developed a wide array of standard controls
designed specifically for greenhouse control requirements and applications.

This document provides a general overview of:


1. The value of good environment control
2. Functions of environment control systems
3. Types of controls available
4. Considerations for selecting appropriate controls

History:
Early greenhouse control was as simple as pulling a chain to open or close a vent, turning a valve to
control heat or irrigation, or throwing a switch to activate a pump or fan. Over the years this evolved
as greenhouse systems themselves became more complex and more reliable. Early automated
control consisted of independent thermostats, humidistats, and timers. Even these simple devices
allowed major advances in efficiency and product quality and made grower’s lives simpler.
However, many of these control devices and methods cannot deliver the level of automation and
efficiency needed in today’s dynamic, competitive environment.

The common problems experienced with using several independent thermostats and timers to
control a greenhouse led to the development of early electronic analogue controls, also known as
“step” controls. These devices made a major contribution to improving the growing environment and
increasing efficiency by combining the functions of several thermostats into a single unit with a single
temperature sensor.

As operating costs increased, and greenhouse systems became increasingly complex, the demand
grew for increased control capability. The computer revolution of the late 70s/early 80s created the
opportunity to meet the needs for improved control. Consequently there have been dramatic
improvements in control technology. Today, computerized control systems are the standard for
modern greenhouses, with continued improvements as the technology advances.

4
The Value of Good Control timely. Growers report reduced overall water
use and runoff of as much as 70% with the
most effective irrigation controls.
A Dynamic Environment:
Greenhouse environments present unique Reduced Fertilizer Use: Constant monitoring
challenges to good control. Temperature and control provides higher accuracy that,
changes occur rapidly and vary widely when combined with efficient water use, can
depending on solar radiation levels, outside substantially reduce fertilizer application and
temperatures and humidity levels, wind speed improve its effectiveness.
and direction, the amount of plant material in
the greenhouse, watering routines, etc. Reduced Chemical Use: More precise
Proper control of this dynamic environment is control of temperatures and more effective
indeed challenging, but the benefits of good use of DIF and other growth regulating
control far exceed the costs. temperature regimens reduce the need for
growth regulators. Better management of
Ultimately, the objective of any greenhouse humidity, irrigation, and temperature also
system is to reduce the input cost per unit of helps reduce plant stress and diseases and,
production and maintain or increase the consequently, the need for fungicides and
quality of production. While some other chemicals.
investments effect the input cost and/or
quality of one or two specific tasks (i.e. Reduced Pesticide Use: Greenhouses with
transplanters, soil handling equipment, etc.), a better climate control and precise irrigation
well-integrated environment system will have produce healthier plants. Healthier plants are
a positive effect on virtually every function in a less susceptible to disease and insect
facility. Even a small percentage of infestation. Growers report noticeable
improvement in several areas will yield reductions in insect populations and pesticide
substantial improvements overall. Growers use in well-controlled environments.
that own Integrated Control Systems report
experiencing many real benefits resulting from Improved Plant Quality & Uniformity: Less
improved control. disease, more effective irrigation and
fertilization, improved grower information and
Higher Energy Efficiency: Better equipment management all combine to increase the
coordination and more accurate control can health and uniformity of plants. Uniform crops
reduce heating fuel and electrical costs. are easier to handle and market.
Savings vary depending on how well you
already manage your environment and the Reduced Equipment Wear & Tear: Poor
controls you purchase. control over-taxes equipment by over-cycling
and increasing operation hours. Good control
Better Labor Efficiency: Automated controls allows more precise management of the
increase the productivity of workers by equipment. Continuous monitoring and
enabling them to attend to more valuable alarms alert growers to pending breakdowns
tasks. Increased output reduces the pressure and other problems earlier, before more
for more labor. serious consequences occur.

Improved Management Effectiveness: Less Plant Loss from Failures: Good data
Perhaps the most important function of good logging and graphing of greenhouse
control systems is the additional information conditions and sophisticated early warning
available to managers and growers, enabling alarm systems help reduce losses from
them to make better management decisions catastrophic failures.
and spend more time managing the process
instead of being or doing the process.

Reduced Water Use: With the modern


irrigation control capabilities in many systems
water application is more precise, and more

5
General Considerations transparent materials, they gain and loose
heat at many times the rate of even the most
poorly insulated or sealed conventional
Not an Office Computer buildings. To compensate for the dynamic
The most qualified person to evaluate energy fluxes within these structures,
greenhouse control systems is probably the extremely responsive heating and cooling
head maintenance person or grower, not the equipment is required, as well as
office computer expert. Do not use office sophisticated anticipative control systems that
computer standards to evaluate and select can maintain setpoints within the narrow
environment controls. Megabytes, Megahertz, tolerances required for modern horticultural
Gigabytes, and other standards of measure production.
for personal and office computers do not have
the same relevance in evaluating greenhouse Several attempts have been made to utilize
control systems. Greenhouse control is real- “off-the-shelf” industrial programmable logic
time process control and the software and controllers (PLCs) sold by major electrical
hardware requirements, costs, applications, manufacturers. However, while horticulture-
and support requirements, have little in specific control systems have advanced in
common with office computers. The important both sophistication and ease of use, PLC
factors in evaluating greenhouse controls are systems have proven to be comparatively
reliability, precision, and control functionality. much more expensive and difficult to use,
Speed, disk storage capacity, memory and while delivering much less capability than
software friendliness are all secondary integrated systems developed specifically for
considerations and, in some cases, may not horticulture and for use by non-programmer
be relevant at all. end users (farmers).

Greenhouse vs. Building Control Control Voltages


Conventional insulated buildings intended for Controllers use low voltage (24 volt), line
human occupancy and materials storage are voltage (115 volt), or a combination of both
very different in nature and function from signals, to activate equipment.
buildings intended for horticultural production.
Consequently, the types of control systems The controller itself must
that have evolved for each type of application
are very different. If you are retrofitting a facility with existing
high voltage controls it will be necessary to
The most important distinction between address the interface between low voltage
building controls and greenhouse control and line voltage.
systems is that building controls are primarily
designed to manage air temperature and For further information on electrical interfaces,
ventilation rates for human comfort, while see the Installation Considerations section
integrated greenhouse controls are designed toward the end of this document.
as production tools for facilitating horticultural
growth processes. Therefore, the capabilities
Impact of Greenhouse Design
of a greenhouse control system usually
extend far beyond air temperature Even the very best control system can’t make
management and ventilation, to the direct your greenhouse perform beyond the
process control of biological growth limitations of the equipment in the
parameters. Greenhouse control systems are greenhouse. A poorly engineered climate
developed with unique programs for operating zone will yield poor results or at best will be
specialized greenhouse equipment such as difficult to control. If you are building a new
fog systems, CO2 enrichment, shading and facility, be sure to involve the control
blackout curtains, roof vents, irrigation and manufacturer in the process of designing the
nutrient control. heating, cooling, and irrigation systems to
assure proper integration with the control
Since greenhouses are constructed of system.
essentially non-insulating transparent or semi-

6
Other Control Applications at various locations within the same
Systems sophisticated enough to control a enclosure, these zones may “fight” against
greenhouse environment can certainly control each other. This may result in one area doing
the environment in other areas that may be all of the heating, while the other area may
less dynamic but equally important. Heating, end up doing all the venting. The result will
air-conditioning/cooling, lights, fogging, and be very poor control and wasted energy.
more can often be controlled in areas such as
this: While it is very difficult to maintain multiple
cooling and humidity settings with a single
Head Houses & production buildings climate zone, it is often possible and desirable
Coolers and freezers to maintain individual heating sub-zones
Offices within a climate zone. For example individual
Growth Chambers bench heating zones for propagation and
germination areas are commonly used, and,
While most of these area can be easily of course, individual irrigation, misting, and
controlled by simple thermostats or other lighting zones within a single climate zone are
building controls, some, such as growth common.
chambers and seed coolers will benefit from
the precision provided by the greenhouse Common/Global Systems
control system. Additionally, the alarm and Boiler systems, main water supply systems,
data recording functions included in many and fog systems, are nearly always shared
control systems can be used to monitor these across several zones. Each of these systems
environments and protect their contents. can be quite complex, requiring specific
control management capabilities for optimum
Climate Control Zones performance and safety. It is important that
Control systems are configured and priced the control system be able to manage these
based on the zones and equipment controlled, individual systems while also coordinating
not per control unit or by greenhouse square them with the demands of the various zones.
footage, so understanding the definition of a For example: A boiler system may require
climate zone is important. A brief definition of certain supply and return temperatures,
a climate zone is: staging requirements, and other operational
minimums regardless of the heat demands of
“A specific enclosed area with common the zones it serves. Make sure the control
temperature and humidity requirements system can manage the boiler system
served by common heating and cooling independent of the zone pumps and valves to
systems.” optimize both.

However, in practice it is often more Plan Ahead


complicated than that. The easiest climate When considering controls it is very important
zone to understand is a freestanding to look ahead several years to take into
greenhouse. It is separated from other areas consideration both your present requirements
by walls, has common heating and cooling and probable or possible future needs. Make
systems and the same temperature and sure the system you select is capable of
humidity set-points. In a gutter connected expanding and changing with the needs of
range a single zone may include several your entire operation. Even if you don’t have
houses or bays with common heating and or forsee an immediate requirement for
cooling equipment and temperature and functions such automated irrigation, lighting,
humidity set-points. or boiler control, include these in your
considerations. Many growers start out by
Ideally the houses in one zone should be controlling only the basic heating and cooling
separated from other zones with a wall or functions, but quickly see the benefits of
barrier to prevent cross control problems. If controlling other equipment systems. Most
zones are not separated it will effect the computerized control systems can be
accuracy of control and may create difficulties expanded through the purchase and
in maintaining precise settings. For example, installation of additional components. Make
if you try to maintain different air temperatures sure you understand the expansion

7
capabilities of any control system you are costs of a system by the number of zones
considering. Growers that are initially unsure controlled to make the most accurate cost
of the value of a greenhouse control system comparison.
often end up finding more uses for them than
they imagined and quickly look to expand their
use.
Levels of Control
Look at the Whole Picture: There are three levels of control requirements
When reviewing your control needs, it is and equipment that need to be addressed in
important to consider all functions of every zone.
environment management in your facility, not
just heating and cooling. Consider everything, Equipment Level:
including systems like irrigation, that you may Control of individual equipment: This refers to
not see a need to control at present. The devices that control or interface with a single
following are many of the functions that may type of equipment. Examples include motor
be involved. All of these systems are controllers to control vent operation,
independent. They may effect or be affected contactors and motor starters for pumps, fans,
by other functions, so controlling them in an etc. Any control system must be able to
integrated mater is important. manage the equipment based on its specific
and unique operational requirements.
What to Control
ƒ Temperature Control (heating & cooling) Function Level:
ƒ Boiler System Management This refers to control of all equipment for a
ƒ Air Circulation & Air Exchange (HAF, Jet particular function, such as temperature
Fans, Louvers & Vents) management, irrigation, fertilization, etc.
ƒ Humidity Management (fog, mist, Individual controllers may be electronic
dehumidification vents & heat) (analog step controllers) or microprocessor
ƒ Shade Curtain systems based controls. For example, temperature
ƒ Lighting Control (artificial lighting and controllers generally provide 5-12 control
blackout) outputs, depending on manufacturer and
ƒ CO2 Management (monitoring and model, that allow for 2 or 3 stages of heating,
injection) and 3-5 stages of cooling. Some models will
ƒ Heat storage control cooling vents and heat mixing valves.
ƒ Irrigation (pumping, capacity, valves)
ƒ Chemical Treatment System Level:
ƒ Nutrient Management (fertilization Control of all equipment, functions, and
injection/mixing) systems: The operation of each piece of
ƒ Water Supply and Storage Systems equipment in the greenhouse is effected by
ƒ Heat Storage Systems the operation of other equipment and changes
ƒ Co-Generation Systems in climate conditions. A single piece of
equipment or system often performs more
than one task (i.e. heaters both heat and
Cost Comparison: dehumidify) and these requirements can
A full appreciation of the total capabilities of a occur simultaneously, or overlap due to time
particular control system is important. lags between an equipment operation and its
Accurate cost comparisons are best made by ultimate effect. Fully integrated, system level
examining the nominal cost per climate zone, control, is designed to bring all of the systems
rather than cost per square foot or cost per in the greenhouse facility together into a
control unit. Cost per square foot varies single well-orchestrated and coordinated
significantly depending on the size of the system. These integrated systems can only
operation and of each zone. Cost per control be effectively managed by computers which
unit is similarly misleading, as it does not can monitor and control every aspect of the
account for the capability of the system, climate simultaneously.
complexity of each zone, or the number of
zones. To compare costs, divide the overall

8
Types of Control Equipment Step controllers bring two benefits to basic
temperature control: automatic sequence of
The following is a brief review of the types of operation, and remote sensing. Consequently,
control units and systems available, and how a single step controller takes the place of
to analyze the costs of controls. several thermostats. Step controls use a
single sensor element to control both heating
There are essentially 4 types of controls and cooling functions in a greenhouse zone.
available. That sensor can be located among the plants
1. Thermostats and timers while the controller can be located more
2. Analogue “step” Controllers conveniently and safely outside the plant
3. Computer Zone Controllers environment. These controllers divide the
4. Integrated Computer Controls actions of the greenhouse heating and cooling
equipment into steps, or stages, called a
sequence of operation. While multiple
thermostats with different settings can
Thermostats and Timers: accomplish the same effect, it is difficult to
These simple devices are low cost and keep their temperature readings
provide limited control. A typical greenhouse synchronized. As a result, heating and
zone may require 3 or more individual cooling equipment can be on simultaneously
thermostats to control heating and cooling (and expensively!).
functions, plus timers for irrigation and lighting
control. Additional relays are often necessary A single step can include one or more heat
to interconnect fans and louvers and other sources or one or more cooling sources. For
devices that must work together. example, in a zone with three exhaust fans,
two unit heaters, three motorized shutters,
A simple zone will generally require 2 or 3 and an evaporative cooling pad; the
thermostats (1 for heat and 1 or 2 for cooling equipment might be divided into steps as
stages). More complex zones may require 5 follows:
or 6 thermostats, including multiple stage Heating Step 1 First unit heater ON
thermostats for some devices such as vents, Heating Step 2 Second heater ON
plus individual controls or timers for irrigation (first heater still ON)
and lighting. Cooling Step 1 1 exhaust fan ON
3 shutters OPEN
Beyond the low initial cost there is little if any Cooling Step 2: 2 exhaust fans ON.
benefit. They provide very limited control, no Cooling Step 3 3 exhaust fans ON.
coordination between equipment and Cooling pad pump
functions, poor accuracy, and poor energy ON.
efficiency. The initial low price is deceiving.
The increased energy consumption and the As the measured temperature falls below the
effects of lost production due to poor control desired temperature, controller activates Heat
devices far exceeds savings from their lower Step 1. If the temperature continues to fall, it
initial cost. turns on Heat Step 2. As the zone returns to
the desired temperature, the controller first
turns off Heat Step 2, then Heat Step 1.
Step Controls
The primary benefit of these devices is their As long as the greenhouse remains near the
low initial cost, better equipment coordination desired temperature, the controller leaves all
and greater accuracy than either single or the equipment off. When the measured
multiple stage thermostats. These units are temperature rises above the desired
not expandable and serve only one zone. temperature, the controller turns on Cooling
They are generally most appropriate for Step 1, and if the temperature continues to
simple greenhouse zones limited to 6-8 total rise, it activates Cooling Step 2, then Step 3.
stages of heating and cooling, and in smaller As zone temperature drops, the controller
operations not anticipating expansion. turns off each cooling step in last-on, first-off
order.

9
Greenhouse step controllers incorporate The cost per zone for ICC systems is
greenhouse-specific features such as dependent on the number of zones controlled
separate day and night temperature settings, and the total equipment to be controlled. The
gradual equipment startup after power initial acquisition cost is higher than for the
failures, outdoor temperature influence, initial purchase of a single step or computer
provision for humidity control, partial or zone controller for a single zone. However,
complete lockout of cooling functions at night, when compared over the cost of controlling 3
adjustable time delay between steps, and or 4 greenhouse zones, and more, the cost of
display of the temperature at the remote ICC systems compares quite favorably. As
sensing point. ICC systems are expanded to control more
zones and more equipment and functions, the
average cost per zone and per output tends to
Computer Zone Controllers decrease.
These devices bring the benefits of
computerization to the step controller concept, Since ICC systems provide substantially more
providing greater control flexibility and capability than most individual zone control
programmability, and the ability to provide units, comparing costs can be difficult. It is
improved accuracy and better equipment important to consider all equipment and
coordination. They are generally designed to functions that may require control and future
provide control and coordination of expansion plans in order to derive a fair
temperature and humidity in a single zone, comparison. Although generally favored for
although some companies offer units that are operations with 3 or more zones, ICC systems
expandable to 2 or 3 zones. The number of can be cost effective for operations with as
outputs per zone controller is typically 10-15 little as 1 or 2 zones, if the zones are complex
outputs each and some units can be and control requirements are demanding.
expanded to up to 24 outputs per zone,
perhaps more. Irrigation, lighting, and/or CO2 There are two types of Integrated Computer
control is available on some control units. Control systems:
1. Single processor control units
The cost per zone generally starts slightly 2. Multiple processor distributed controls
higher than for step controllers, depending on
the capabilities offered in the controller and Single Processor Centralized Control:
the amount of equipment needing to be These systems have a single computer
controlled in each zone. Many computer zone processor that controls all zones from a single
controllers also offer the optional capability to unit. Sensors and outputs can be wired back
connect to an office PC for storing and to the central unit or connected to local
viewing data and graphs and for changing stations that then communicate with the
settings from a single PC location. central processor unit. A dedicated terminal
or PC generally accesses these units. This
architecture was common in early systems
Integrated Computer Controls and is still used in some systems, particularly
These systems combine the capability of European systems. Installation of this type of
several Step or Computer Zone Controllers, system generally requires more wiring and
plus irrigation and lighting controls, and can be more complex. If the single control
various other individual control devices such unit fails, the entire facility is without
as timers, into a single, integrated computer automated control until it can be repaired.
system. Integrated Computer Controls (ICC) The overall capability of these systems is
can provide coordinated control of virtually all comparable to Multiple processor controls.
greenhouse environment functions, including
heating, cooling, irrigation, fertilization, boiler Multiple Processor Distributed Control:
control, lighting, CO2 management, alarms, These systems are comprised of multiple
and much more. Usually the need for any control units, each with its own processor,
additional individual control units can be connected together to share information and
eliminated. integrate the control of common or global
systems such as water mains and boilers.

10
Each distributed control unit is typically Technical Considerations
capable of handling from 1 to 4 zones,
depending on manufacturer and model. The
control units are located in or near the zones Control Signals
or groups of zones to be controlled throughout Digital and Analog are the two types of control
a facility. Sensors and control outputs are signals most commonly used in greenhouse
wired locally to the control units at or close to control systems:
each zone rather than running back to a
central unit. The individual control units in the Digital Control: Digital control is simple
system are usually accessed through one or on/off switch control and is used to control
more computer terminals, which are usually a on/off devices such as motors, louvers,
standard PC. In some systems the access is solenoids, etc.
available through a screen and keypad
mounted on the individual control panels, Direct Digital Control (DDC): Proportional
although most companies offer a central PC devices such as vents, motorized valves,
interface as an option or standard to provide curtains, and other open/close devices can
centralized full-featured operator access. are also be controlled with a digital signal.
Direct Digital Control is achieved by activating
Integrated Control Systems provide more than an open or close relay for a period of time to
control. They also deliver substantial move the device to the desired position.
management information to managers and Proportional devices can then be controlled
growers. Data Recording programs capture based on movement time. For example: if a
sensor readings and trends, and record the vent takes 200 seconds to open, the controller
computer’s functions, automatically saving activates the open relay for 200 seconds to
this data for analysis. Growers can identify open it 100%, or 100 seconds to open it 50%.
unacceptable environment trends in the
greenhouse, such as insufficient temperatures Analogue Control: Analogue signals such as
or excessive humidity, or equipment 4-20 ma or 0-10 VDC are often used to
malfunctions, before the plants are negatively control proportioning devices and variable
effected. Previous successes can be more speed motors. While DDC is generally
easily repeated by capturing and duplicating simpler and less expensive method of control,
conditions that worked well. Light levels and there are special applications where analog
quality, soil moisture levels, CO2 levels, water control provides additional flexibility and may
application rates and quantities, nutrient and be desirable. Analog is the standard method
pH levels, and a host of other factors and of control for some equipment and for certain
conditions can be monitored and archived. equipment manufacturers. Analog control is
preferred where a faster equipment response
Maintenance staff can track equipment is needed. Some manufacturers make
operation times and cycles in some systems, equipment actuators available with either a
allowing them to set alarms for run-time DDC or analog interface.
and/or cycle related preventative maintenance
functions, or to trouble shoot equipment Overrides
problems. When combined with climate data, It is preferable to have manual override
a detailed story can be pieced together to switches, also known as hand/off/auto, on
identify problems in the greenhouse. most control outputs. This enables any output
Managers can analyze greenhouse to be controlled by hand, or switched to
performance data to make wiser decisions automatic control by the computer. Overrides
about future greenhouse equipment are necessary for emergency (i.e. computer
purchases, or even plant variety selections failure) and maintenance of equipment.
and nutrient requirements. However, they are not to be used for normal
control operation. Analog outputs should also
be equipped with on/off switches and a
potentiometer to manually select motor speed
or the opening percentage of analog
actuators.

11
the pipe with a piece of insulation and a hose
Sensors clamp or tie wrap.

Sensor technology is an important Wet-well sensors are actually threaded into a


consideration for controls manufacturers. The hole (well) in the pipe and sense the actual
accuracy and responsiveness of the control stream of water. They provide the most
system is limited by the accuracy and accurate temperature reading, and the fastest
responsiveness of the sensors it uses. A response, although it is questionable if this
computer may be able to read a sensor many accuracy is necessary in most hot water
times per second and resolve the systems. Wet well sensors are more difficult
temperatures to within 1/1000th of a degree, to service since the pipe must usually be
but if, for example, the sensor takes 2 minutes drained or at least cooled and depressurized
to respond to a change, it is of little value to before they can be replaced.
the system. The reliability and accuracy of a
sensor, and its construction, are of particular Dry-well Sensors are the most expensive but
importance in the greenhouse environment, to provide the best combination of accuracy and
its ability to withstand the generally ease of service. A well is threaded into the
unfavorable conditions of the greenhouse pipe forming a permanent seal, and the
environment. sensor is placed in the well sometimes with
thermal grease and can be easily removed for
Temperature maintenance or replacement.
Air Temperature is best accomplished with an
aspirated housing to move the air sample Irrigation Water Temperature can be
across the sensor and protect it from direct monitored with a pipe temperature sensor, as
exposure to solar radiation. This ensures a above, or with a simple waterproof sensor
more accurate representation of the air in the dropped into the water.
general greenhouse environment as opposed
to a specific spot. Other Temperatures can be monitored for a
variety of purposes. For example, equipment
Soil temperature probes are typically used to operation can often be confirmed with a
control bottom heat systems. They are also simple appropriately placed temperature
used to monitor soil temperatures and the sensor to confirm things like unit heater
temperature within the microclimate of the operation, an overheated irrigation or heating
plant. This information can be valuable for pump, even fan operation or open vents.
determining how and why the plant is Alarms can then be set in the system to alert
responding and what measures the grower staff when problems occur.
may want to take to improve performance or
identify problems. Humidity
Controlling the humidity in the greenhouse
can yield powerful benefits in disease
Pipe Temperature sensors are used to reduction, improved water and nutrient
monitor the water temperature and pipe uptake, and improved growth. It is too often
surface temperature in hot water heating under utilized and not well understood.
systems to control mixing valves, minimum Humidity control is a standard function of
pipe temperatures for dehumidification, as nearly all control systems.
well as boiler output and/or transport system
temperatures. There are three methods of Humidity measurement is expressed as a
sensing: 1)surface mount temperature percentage of relative humidity. It is the
sensors, 2)wet well sensors, and 3) dry well amount of actual moisture in the air, relative to
sensors. the capacity of the air to hold it. Humidity
sensing is difficult even with the most
Strap-on surface sensors are inexpensive and expensive sensors, and these are typically not
effective since the pipe surface closely follows suitable or practical for the greenhouse
the water temperature within. Sensing can be industry.
as simple as clamping a small thermistor on

12
There are three common types of humidity horticulture production, other than detecting
sensors: capacitive, resistive, and wet/dry the difference between night and day.
bulb. Both capacitive and resistive solid state
sensors are fairly common in U.S. production CO2
because they offer reasonable accuracy and, Carbon Dioxide sensors are typically used in
in the humidity range typical of most controlled CO2 enrichment applications. The
horticulture applications, maintenance is most common types of sensors employ an
generally limited to cleaning once or twice per infrared sensing element. A separate sensor
year. However, solid state sensors are may be used in each zone, or to reduce costs,
susceptible to chemical contamination and a single sensor may be used to multiplex
high humidity conditions (i.e. over 90%), that samples from several zones. Control
may require more frequent recalibration or systems can initiate CO2 injection from boiler
replacement. stacks, CO2 burners, or liquid CO2 tanks
based on light and temperature conditions
Wet Bulb/Dry Bulb sensors offers the best and CO2 target levels.
accuracy if maintained properly, particularly in
environments with humidity levels consistently Wind Speed & Direction
over 90%, such as germination chambers and Mounted on the outdoor weather station, an
fog houses. These sensors do require anemometer measures wind speed and the
frequent maintenance that is easily performed vane measures approximate wind direction.
by the user. Water reservoirs must be refilled The controller uses this information to close or
and wicks trimmed and replaced regularly. limit the opening of vents, roofs, and side
The drier the climate, the more frequent the walls during high wind conditions, or winds
maintenance requirements. These sensors from a specific direction. This information can
are more common in Europe and Canada, also be used to optimize the operation and
due to a number of factors, including tradition, effectiveness of windward/leeward vent
more crops requiring closer humidity control, systems, and even to make or modify
and climates more appropriate for this type of irrigation decisions.
sensor.
Precipitation
Light These are sensors are mounted on outdoor
There are three basic measurements of light: weather stations to measure precipitation.
Global radiation, PAR, and photometric. Simple rain “grids” indicate either the
Global radiation is the most common light presence or absence of precipitation but not
measurement for greenhouse control because the volume. These simple sensors are
it measures the entire spectrum of energy commonly used to close or limit roof vents or
producing light. It is measured with a retractable roofs when it is raining. They are
Pyranometer, and is generally expressed in the most appropriate sensors for this purpose
units of Watts m2 . because they allow a fast response. Heated
rain grids enable snow sensing and
Photosynthetically Active Radiation (PAR) is differentiation between dew and rain.
another method of light measurement. It
measures the narrow band of light that is used Rain volume is normally measured using a
by plants in photosynthesis. This is tipping bucket rain gauge. This device
appropriate for use in research and for collects the water in a small cup or spoon that
monitoring PAR light at the plant level. PAR tips when it is full, triggering a small switch.
is of minimal value for environment control, The number of tips are counted to determine
other than lighting, as it does not accurately the amount and rate of rain fall, generally as
relate the total solar energy that affects accurately as 1/00th to 1/10th of an inch.
temperature or other aspects of plant These can also be used to measure
morphology. propagation misting, and irrigation application
and leachate rates. Measurements from
Photometric light meters measure luminosity, these should not be used for closing or
or the relative brightness of light to the human limiting vents and roofs due to their slow
eye. They are not particularly useful for response rate.

13
Irrigation booms, curtain systems, retractable roofs,
Measuring the use of and/or presence of etc.
water for irrigation purposes can be
accomplished with a number of sensors
depending on the purpose, growing culture, Irrigation Control
and required accuracy. Soil tensiometers and
E.C. probes are used to indicate
approximately how much moisture is available As reported by growers, one of the most
in the media. Evaporation trays are used to significant benefits derived from automated
indicate the approximate evaporation rate of control is the management of daily irrigation
water in a particular environment. Water decisions. It is understandable that this is one
meters can measure the amount of water of the most difficult areas for growers to turn
being fed to the plants. Accumulation over to the control system.
gauges, such as a tipping bucket rain gauge,
can be used to measure how much water is Growers using automated irrigation control
leached out of the media and, consequently, report dramatically reduced water and
how much water the media absorbs. fertilizer use, better growth, less disease, less
chemical use, hardier plants, and less labor.
Nutrition
pH sensors are used to determine the amount Much of the apprehension about automated
of pH correcting concentrates required. E.C irrigation is based on the following
sensors are used to determine the level of conceptions:
salts in feeding solutions. Both types of
sensors are used for nutrient control and for 1. The grower is the only person that
monitoring and alarm information in an really knows when the plant
irrigation system. needs water.
2. You can’t grow without being in
Miscellaneous Sensors the greenhouse watering and
There are many sensors available to monitor checking things.
and record a wide variety of conditions. Many 3. Control systems are not
control systems can use these sensors to sophisticated enough to know
improve control, set alarm conditions, activate when to water.
equipment, or simply report occurrences.
Here are some typical sensors and uses. There are others but these represent the most
frequently heard comments. Here are some
Certain safety or alarm related sensors can be perspectives on these subjects that are based
incorporated into some computerized systems in modern control experience:
as well. An example may include flame
smoke or heat sensors to detect fire. In some 1. Only your grower knows for sure:
systems, particularly integrated computer Absolutely correct. Growers know best how
control systems, the system could be to determine when a plant needs water but
programmed to, for example, open/retract the humans are not the most reliable at making
shade or blackout curtain systems and close accurate measurements of when it actually
vents to minimize the spread of fire. needs to happen. Modern control systems
allow the grower to “teach” the computer just
Other sensors include: how they want those decisions to be made.
ƒ Flow switches to confirm proper pump The control system can then implement those
operation, detect clogged filters and line decision strategies much more reliably and
breaks, etc. with much greater accuracy than can any
ƒ Pressure transducers to monitor water human.
pressures, greenhouse pressures, fan
output, etc. 2. Gotta be there: Correct again. The
ƒ Potentiometers to monitor vent positions, grower does need to be in the greenhouse
mixing valve positions, etc. observing plants and managing people. That
ƒ Micro-Switches to monitor closure of does not necessitate holding the watering
vents and doors, the position of watering wand or turning the valves and switches.

14
Growers say they are actually better able to
manage the performance of the plants and ƒ Sensor feed back: Triggers irrigation
supervise staff when they are not preoccupied when certain environment conditions
with other labor functions. exist, such as low temperatures for frost
protection, or high temperatures for heat
3. Controls not smart enough: Not true stress. Also used for with paddle sensors
anymore. Irrigation control has come a long for mist control, or virtually any sensor
way in just the past few years and today’s feedback that a grower would use to
control systems provide sensor determine the need for irrigation or to stop
measurements and control methods that offer irrigation, for example, during rain periods
greater accuracy and timeliness particularly for outdoor crops. Other examples of
when managing large multi-zoned irrigation common sensors used:
systems. ƒ Soil tension: Measures the
relative level of moisture in the
Irrigation Decision Making: soil and triggers irrigation when
ƒ Manual: The grower makes the decision the soil dries to a certain level.
as to when to irrigate and uses the control ƒ Weight Scale: Triggers irrigation
system to implement that decision for when the weight of the pot
timing and sequencing valves and pumps. indicates a dry condition.
ƒ Evaporation Start Trays: Triggers
ƒ Time: This typical control type triggers irrigation when the moisture in a
irrigation cycles for preset times at a pre- tray is evaporated as measured
set time of day. Problem: Plants do not by weight or moisture level.
take up water based on the time on the ƒ Temperature: Triggers irrigation
clock. for freeze protection or to protect
from heat stress.
ƒ Accumulated Light: A computer light ƒ Electronic Rain Gauge: Limits
sensor (pyranometer) measures the total irrigation based on the amount of
energy input from the sun and triggers an rainfall received by outdoor crops.
irrigation cycle when a grower-set amount
of light has accumulated. An increasingly Capacity Management: Controls the cycling
popular method for determining when to of valves based on the water volume and/or
irrigate as it most closely measures the pressure available from the water source (well
primary factor that causes plants to pumps or city water). This allows the grower
require irrigation. This requires a to optimize irrigation for the plant while the
computer controller to implement. computer manages the timing of the valves
based on the available water capacity.
ƒ Evapo-transpiration Model: The computer Computers are able to manage on a second
measures the total energy input from light, by second or minute by minute basis enabling
humidity, and temperature conditions to a much closer management than is possible
model the rate of transpiration, need, and by a human. This may involve staging valves
uptake ability of the plant. This and pumps based on irrigation priority, pulsing
sophisticated method is probably the most irrigation cycles to serve several valves with a
accurate although complex way of given capacity while meeting the plants total
measuring the actual irrigation irrigation requirements.
requirements and also requires a
computer to implement.
Crop Modeling & Graphical
ƒ Vapor Pressure Deficit (VPD): This Tracking
method uses feed back from temperature
and humidity sensors to determine when Crop Modeling:
there is a vapor pressure deficit between This allows a control computer to use
the plant leaf and the surrounding air and research generated models of different
triggers watering based on the plants species and varieties of plants that predicts
ability to transpire. growth based on a history of environment

15
conditions and a predicted model of the plants if you know how to install a group of
response to those conditions. Although thermostats, you can install a computer
somewhat futuristic, models already exist for control system. It is not always necessary to
some plants, including certain vegetable and use the services of an electrician for
cut flower crops, as well as poinsettias and installation of the controls, although an
easter lillies. electrician is generally needed for installing
line voltage contactors and power
Graphical Tracking: transformers. Most control manufacturers
Computer control systems can provide can provide access to qualified installation
environmental data, such as temperatures contractors or company installers.
and light levels, to be used in graphical
tracking programs. These programs track the Contactors & Relays
height and other habits of a plant and allow All electronic controllers must interface tiny
the grower to adjust greenhouse conditions to electronic circuits with larger electrical loads.
produce the best plant to meet market Electromechanical relays or solid-state relays
requirements and timing. can handle this interface. Both use a small
electric signal from the controller to switch one
or more devices. Electromechanical relays
Power Management are most common, readily available and
Integrated Computer Control Systems can relatively inexpensive and allow switching of
also provide a level of power management. multiple devices with a single relay.
Be sure to identify which are important in your
operation. Most control systems provide a signal that is
able to directly control small loads and
Load Shedding: The ability to shut down contactors that will control heavier loads.
specific equipment during power outages or
brown-out to match the load capacity of the Most manufacturers will also provide the line
generator or reduced power supply. voltage interface/contactor panels that are
matched to their controls. These can also be
Peak Shaving: The ability to shut down built on site by your electrician or supplied by
specific equipment, usually sequentially, to other electrical component vendors. Be sure
stay within a specified power budget. This to investigate your options before deciding on
may be needed to achieve savings available the best method of supplying these relays and
with special power company plans, supply contactors. Discuss the matter with your
from co-generation plants, interruptible electrician/installer and controls vendor to
power/alternate power supply plans, or simply determine the most appropriate and cost
to optimize an insufficient power service. effective route.

Phase-Loss Shutdown: The ability to shut Motor Controls


down three phase motors and other sensitive Most motor controls can be provided in the
equipment in the event of loss of one of the contactor panels. Some devices, such as fog
power legs in a three phase power supply. systems, variable speed motors, or very large
motors often come already equipped with
Staged Power-up: When power returns after motor controllers or need special starters.
a power outage, this provides the ability to Motors for curtain systems, vent systems,
activate equipment gradually in stages to retracting roof systems, and retracting side
prevent stalling the generator or tripping the walls need special attention. These systems
overload protection of your power service. require reversing motor controllers that allow
the motor to turn in one direction to open and
in the reverse direction to close. This must be
accommodated in the motor controller by the
Installation Considerations manufacturer or in the contactor panel. It is
Installing a control system requires a working an often-overlooked item. All manufacturers
knowledge of your greenhouse electrical of these systems offer motor controllers as an
system and reasonable familiarity with option. Make sure these controllers are
standard control wiring. Generally speaking, accounted for in your design.

16
Open raceways, although a bit more
Wiring expensive than conduit, make installation
Most low voltage (24 volt) control wiring easier and future changes or additions easier
consists of 18-22 gauge wiring. The selection as well.
of the wiring should be based on
manufacturer recommendations or Do not run low voltage sensor and
specifications. Some sensors are calibrated communication wire in the same conduit as
to a specific wire size and length. The size of line voltage equipment wiring, or attached to
wire to connect control relays to the devices line voltage wires, as it may interfere with low
or contactors they control is based on the voltage signals, consequently yielding
amperage, voltage, and distance to run the incorrect sensor readings.
wire. 18 gauge is the most common and is
suitable for most connections but for longer Panel Locations
runs or larger loads you should consult a wire Where control panels are located is
sizing chart, electrician, or controls dependent on four factors
manufacturer. 1. Desired location for convenient
access to override switches
Conduit or Wire Tray 2. Location of electrical service and
Most control wiring need not be run in conduit. consequent desired location of
Many growers simply tie it to the outside of contactor panels
existing conduit, pipes or structure frames. 3. Type of control system
However, depending on local code, desired purchased and type and location
esthetics, overall quality of installation of interface (i.e. panel mounted
desired, it may be advisable to run wire in screen and keyboard or PC
conduit or wire raceways/trays. terminal)
4. Ease of wiring sensors and
contactors.

Training & Support


Regardless of the systems you consider and ultimately purchase, one of the most important aspects of any
system is the training and support available from the manufacturer. Make sure they can train your
operators and have technical support available when you need it. It is important that the people providing
your support be knowledgeable about greenhouse specific applications and have a good concept of how
greenhouses work. The horticulture industry is far flung geographically so it is impractical for
manufacturers to maintain support/technical staff in every geographical area. A few of the critical items:

¾ Are replacement components readily available overnight?


¾ Can the components be serviced or replaced by your own staff or is an on-site technician required
¾ Is hardware and software support available by telephone and modem or are on-site technicians
required?
¾ Does the manufacturer provide remote training by telephone and/or modem or is an on-site visits
required?
¾ Is there adequate system and program documentation provided in either written form or on-line so you
can help yourself with reasonably simple problems?
¾ Does the system provide standard programs to accommodate “typical” horticulture control routines and
equipment or does it require custom programming and equipment?
¾ Can the system be accessed remotely by the vendor and the user? Is there an additional cost for
remote access?

17
Other Considerations
¾ What is the software upgrade policy? How often is software upgraded? Are upgrades optional or
mandatory? What is the typical cost of a software version upgrade? When is the next upgrade
expected?
¾ What are the installation costs?
¾ What are ongoing maintenance and operation costs? Sensor replacements and recalibration, etc.
¾ What is the company reputation for after sales service and support?
¾ What levels of alarms and self-monitoring does the system offer?
¾ How fast are sensors refreshed and read by the system?
¾ Can the system be custom configured for special applications?
¾ What levels of lightning protection does the system provide? Are there additional costs to get this
level?

Greenhouse Control Concepts and Terminology


This chart provides basic definitions and descriptions of terminologies often referenced relative to
environment controls. Understanding these terms will helps understand how different system provide
control of various functions.

Step control is used to Example: This method works quite well


Step Control apportion control Step 1: If the temperature rises for equipment such as fans or
responses in a number 2oF above the cooling setpoint, unit heaters that can be staged. It
of discreet steps. start the first exhaust fan. does not work as well for roof
Step 2: If the temperature rises vents and mixing valves that are
5oF above the setpoint start the capable of much finer full span
second exhaust fan. Etc. operation.

Integrated Control takes Example: The control system This method has advantages
Integrated into account the operates the roof vents and the over step control since a much
Control interdependent zone hot water mixing valve in an finer degree of control response
relationships and integrated manner to achieve is possible, and the
multiple effects of the both the temperature and interdependent effects of control
greenhouse equipment. humidity setpoints, as well as equipment are taken into
Control response can protect against wind gusts, snow account.
usually be proportioned loads, while correcting for wind
over the entire span direction, and outdoor conditions.
between full on and off.

18
The controller makes its Example: If the greenhouse This type of control must wait for a
Feed Back decisions based upon temperature has fallen below the deviation to occur before it responds.
differences between the heating setpoint, the controller Therefore, the actual response may be
actual measurements will start heating. somewhat sluggish, resulting in
and control setpoints. oscillations above and below the
Control reactions may setpoint. Useful in situations that do not
be modified by time of demand a high degree of precision.
day, and outdoor
weather conditions.
Proportional control is Example: the control system will Proportional response strategies are
Proportional used to deliver a control open a hot water mixing valve in very useful in greenhouse equipment
response in proportion proportion to how far away the control since they enable the use of an
to how far away from zone pipe temperature is from the appropriate response, somewhere
the setpoint the desired pipe temperature. If between full on and full off.
measured condition is. desired and actual temperatures
are close, the proportional
response will be small. If they are
far apart, the proportional
response will be greater.
Integral control is used Example: if a measured condition When used in conjunction with
Integral to deliver a control has deviated only slightly, but for proportional control, this type of
response in proportion some time, an integral strategy strategy provides a dual method for
to how long a measured will increase the rate of response returning a deviated condition to the
condition has deviated the longer that the deviation setpoint. The control system will
from its setpoint. occurs. respond to both the degree of deviation
and the amount of time that the
deviation has occurred.
Derivative varies the Example: Derivative control, Although useful for rapidly changing
Derivative degree of response with when used with proportional and conditions or processes derivative
the rate of change of integral calculations can shorten control is seldom required for
the measured condition. the time it takes to correct a greenhouse equipment due to other
control deviation. process lags.
Also referred to as Example: a nutrient injector may This type of control generally provides
Feed Forward anticipatory control. It be set to deliver a proportional greater precision than controls based
is used in systems that rate of fertilizer concentrate based solely on feedback, since the
employ Energy Balance upon measured water flows. appropriate response can be predicted
Equations and where ahead of any deviations. Where
the control response is feedback correction is used in
predictable for a given conjunction with feed forward control,
set of conditions. a high degree of precision can be
These systems calculate achieved.
the effect that current
conditions will have
upon the controlled
parameter, and activate
the equipment prior to a
deviation from the
setpoint.
The controller makes its Example: as outdoor light and Control systems using energy balance
Energy primary control temperature conditions change, an equations can produce a very smooth
Balance decisions by calculating ongoing energy balance is control response over a wide range of
the probable response calculated to determine how soon outdoor conditions.
of the environment and by how much the climate
based upon the current temperatures may be affected if
measured values of the the condition continues. The
inputs. Total heat gains system then initiates a control
are balanced with total action if required to pre-empt the
heat losses. anticipated changes.

19
Getting Started
The following process will help determine the controls needed and prepare to request proposals from
control system vendors:

A. Determine the total existing areas to be eventually controlled now and in the future

B. Determine the logical progression of purchase and installation phases and divide into three phases.
The first phase being the area(s) having highest priority, phase two the areas, next most important,
and phase three being all other areas, including probable future expansion areas.

C. Determine the number of individual, separate climate zones in each of the phases

D. Create or copy an existing plan view map of the entire facility including greenhouses, outdoor
production areas, offices, and utilities.
1. Label each individual greenhouse block the way you identify it (i.e. Zone 2, Ralph’s house,
Back house, etc)
2. Show dividing walls between climate zones
3. Label main power and water services
4. Identify boiler locations
5. Identify the growers office and management office

E. Survey the environment control equipment in each of the zones, in logical order following the
following categories, in the same order in each zone:
1. Heat Source (boilers, heat transport system, etc.

2. Heating
a. Number of heating zones
b. Type of heat in each zone (i.e. unit heaters, under bench hot water, etc.)
c. Heating control (stages of heating for unit heaters, mixing valves, pumps, zone valves, for
hot water and steam)

3. Air Circulation (HAF Fans, Jet Fans, etc.)

4. Energy Curtains

4. Cooling
a. Type of cooling (natural ventilation, fan and pad, etc.)
b. Cooling equipment (number and location of vents, fans, louvers, pads, etc.)
c. Cooling control (stages of fans, pad pumps, separate vent groups)

5. Irrigation
a. Number, type, and location of water sources
b. Location of fertilization stations (injector or tanks)
c. Number of irrigation main branches
d. Number of valves per branch

6. Other Equipment (CO2, etc.)


a. List for each zone
b. Describe type of equipment
c. Describe functions
d. Describe control requirements

F. Survey your maintenance staff and growers and ask them to identify their most important needs
and considerations in controls

G. Identify one or two qualified individuals that will be responsible for overseeing the purchase,
installation, and management of the system and appoint them to do the research and get proposals
from vendors/manufacturers.

20