Distribution
GM6
MV Gas Insulated Switchgear
up to 36 kV
GM6 General presentation
Protection and control
of electrical networks
For over 30 years, Schneider has been providing Medium Voltage electrical
network protection, monitoring and control solutions in the public distribution,
industry and building sectors.
GM6 is a range of medium voltage equipment included in an offer that covers all
the functions required for network operation.
Main functions:
t supervisory control and data acquisition,
t network restoration,
t wallboard replacement,
t geographic and schematic views,
t switching schedules,
t safety, checks and documentation,
t outage statistics,
t management of maintenance operations,
t management of construction programs.
Main functions:
t remote control,
t HV and MV protection integration,
t data and alarm logging,
t centralized local control.
Main functions:
t installation display,
t real time access to protection and control units,
t alarm management,
t data analysis,
t electricity consumption management,
t power availability and quality,
t protection functions,
t web technology.
2 Schneider Electric
GM6
GM6 offer
Three levels of components are available to protect, monitor and control the
medium voltage switchboard:
t A control and monitoring system interfaceable with a higher level system.
t Sepam: protection and control unit for each switchgear unit (or cubicle).
Services
t Equipment design, installation and maintenance.
t Personnel training.
t Electrical network availability studies.
t 5-year extended warranty.
Schneider Electric 3
GM6 General presentation
Main characteristics
of MV equipment
Service continuity
Service continuity is achieved by means of GM6, which is a highly reliable
equipment offering with all the required functions to provide users with maximum
energy availability and quality.
With GM6, the user benefits from:
t adoption of long proven technical solution; for instance, aluminium castings for
the gas-filled compartment enclosures have been used for many years in MAGRINI
GALILEO gas-insulated high voltage equipment,
t quality organization in accordance with the ISO 9001 (EN29001) issued from
CSQ, the official certification body in the electric field in Italy,
t fully factory-tested equipment with type test reports (required by IEC standards
and ENEL specifications) available for each performance and type of cubicle,
t negligible maintenance requirements, confined to simple periodical checks and
possible monitoring of all electrical data affecting the working condition of
equipment,
t equipment that cannot be affected by humid, dusty, corrosive or polluted
operating environments since all live parts are contained in SF6 filled and sealed
enclosures,
t a supervision offer open to all specifications regarding substation management
and enabling users to control and follow up their energy supply.
Safety
Maximum safety is achieved through GM6 design and functions.
With GM6, the user benefits from:
t a very comprehensive set of mechanical and electrical interlocks preventing
operator errors and compliant with the user’s security protocol,
t internal arc withstand of all the functional units, validated in accordance
with IEC 60298, appendix AA, criteria 1 to 6, class A accessibility,
t operations with reliable and clear signalling devices and direct visibility of the
disconnecting contacts,
t high ratio between maximum withstand pressure for the gas-filled compartments
and normal filling pressure,
t pressure relief devices for exausting accidental excess internal pressure in order
to safeguard the operator,
t earthing switch on the cable side provided with making capacity,
t cable plug-in terminations housed in earthed metal shields, connectors to DIN
47637 standards,
t a temperature compensated pressure gauge (with alarm and signal contacts)
complete with a dial which is adjusted according to the elevation above sea level,
t voltage indicating devices located close to operating shaft of the earthing switch
on the cable side.
4 Schneider Electric
GM6
General characteristics
The values below are given for normal operating conditions as defined
in IEC 60298 and 60694.
Normal operating conditions, according to IEC 60694 for indoor switchgear (4)
t Ambient air temperature:
y less than or equal to 40 °C,
y less than or equal to 35 °C on average over a 24-hour period,
y greater than or equal to -5 °C.
(1)
two units in parallel, please consult us.
(2)
the short-circuit making current is equal to 2.5 times the short time current.
(3)
standard degree of protection, for other values, please consult us.
(4)
for different conditions, please consult us.
(5)
31.5kA x 0.5 sec.
(6)
for 40,5 kV rated voltage, please consult us.
(7)
please, consult us.
Standards
GM6 units comply with the following standards:
t IEC 298-694
t ENEL (Italian National Eletricity Board) DY 0072
t Italian Work Safety Regulations
t U.K. Electrical Association approvat.
All switches, devices and components included in the switchgear conform to the
relevant IEC Standards.
Schneider Electric 5
GM6 Functional units
Description
Power connections are made between functional units by a busbar set located
inside a SF6 compartment. Steady electrical continuity of all metal frames is
ensured by connection of each functional unit’s earthing busbar to the switchgear’s
main earthing circuit.
Low voltage compartments, for protection relay (front) and auxiliary
relay-terminal board (rear) are provided.
Cubicle
The cubicle is an earthed, metallic enclosure, gas insulated switchgear that
complies with the requirements of the IEC 60298 standard.
The busbar compartment is separate and independent from the circuit breaker
compartment, so that the circuit breaker can be replaced if necessary while
the busbars are energized. An inspection window enables a visual check of the
position of the busbar disconnector blades. The compartment using SF6 as
isolating medium, is situated in the top of the unit and it contains:
t the main busbars,
t the three-pole, two way busbar disconnector.
The Low Voltage compartments are separated from the Medium Voltage section;
the first is located in the top of the unit and it contains protection and control
system, while the other are located on the back and contains the low voltage
auxiliaries. Three basic cubicle lay-out are offered:
t incoming or outgoing feeder AD1/AD2,
t bus section CL1/CL2 and double busbar system,
t the busbar metering TT1.
6 Schneider Electric
GM6
8
1
1 SF6 busbar compartment
2 12 2 busbar disconnector
3 SF6 circuit breaker
3 7 compartment
I
O
4 cable compartment
13
5 current transformer
3
4
5
6
5
6
3
44
I
O
8 10
6 voltage transformer
11 7 SF6 circuit breaker
9 8 LV cubicles
4 9 MV plug-in connectors
10 line disconnector
5
6
11 earthing switch
12 inspection window
13 sliding contacts
8
1
11
2 1 SF6 busbar compartment
2 busbar disconnector
3 7 3 SF6 circuit breaker
compartment
O
12
4 cable compartment
8
3 5 5 3
O
3 5 5 3
I
4 6 6 44
10 5 current transformer
6 voltage transformer
9 7 SF6 circuit breaker
O
4
I
8 LV cubicles
9 MV plug-in connectors
5
6 10 earthing switch
11 inspection window
12 sliding contacts
Schneider Electric 7
GM6 Functional units
Choice Single Busbar System
The GM6 range is composed of 7 functional units. The chart below may be used
to link up needs and functional units, and it gives information on the general
composition of each unit.
How to select: if the user wishes to supply power to a transformer, the solution
is a Transformer Feeder.
The matching functional unit is therefore a TF, comprising an AD1 cubicle
equipped with a disconnector switch, circuit breaker and a type T Sepam.
8 Schneider Electric
GM6 Functional units
Choice Double Busbar System
The GM6 range is composed of 8 functional units. The chart below may be used
to link up needs and functional units, and it gives information on the general
composition of each unit.
How to select: if the user wishes to supply power to a transformer, the solution
is a Transformer Feeder.
The matching functional unit is therefore a TF, comprising an AD1 cubicle
equipped with a disconnector switch, circuit breaker and a type T Sepam.
(1)
use one unit for each busbar
Schneider Electric 9
GM6 Functional units
Description
function 24 kV 36 kV
line incomer LI kA kA
transformer incomer TI 31,5 31,5
switchboard coupler SS 25 25
AD2
AD1 AD2
line feeder LF kA kA
transformer feeder TF 31,5 31,5
capacitor feeder CF 25 25
AD2
AD1 AD2
* busbar current
** only for double busbar system
10 Schneider Electric
GM6
TT1 TT1
Dimensions (mm) and approximate weights (kg)
by type of cubicle
AD1 AD2 CL1 CL2 TT1
width (mm) 500 700 1075 1475 500
height (mm) 2560
depth (mm) 1800-2200* 1800
(*) without-with VTs weight (kg) 720-840* 1080-1260*
1700 1900-2000*** 700
(**) without CTs- min weight with 1 CT set- max weight with 720-770-820** 1080-1130-1310**
2 CTs sets
(***) without-with CTs.
Schneider Electric 11
GM6 Functional units
Description
12 Schneider Electric
GM6
If CTs are
required,
select CT2
with current
transformers.
Schneider Electric 13
GM6 Protection monitoring and control
Switchboard monitoring and control
Architecture
The user terminal consists of a compatible personal computer.
It is directly connected to the Sepam protection units via a standard communication
bus.
The control station can easily be connected to a higher level monitoring
and control system.
Basic functions
The main functions are:
t installation display by chained mimic diagrams
(animated single line diagram, device position, energized parts, current faults…),
t continuity of service by fast intervention provided by remote control of the GM6,
t understanding and analysis of events and loads.
14 Schneider Electric
GM6
Sepam advantages
Sepam, a digital multi-functional protection unit, provides you with the following
advantages:
t simple to use for better dayly efficiency: use-machine interface (UMI) which
is ergonomic and which provides comprehensive and clear information to operators
t simple to incorporate: flexibility and user friendliness of parameter setting
software, simplified tests
t money saving:
v integrating all functions required in one single, ready to use product
v upgradable solution, to spread the cost of investment over time
t centralized GM6 switchboard management:
v Sepam is easily integrated into all network control systems, due to its Modbus
communication interface
v all data required for installation monitoring and control are accessible through
the Modbus communication
t better network knowledge through the oscillo-disturbance recording function
and measurement of the imbalance ratio, motor operation parameters, etc.:
t improving continuity of service
v through effective preventive equipment maintenance using switchgear diagnosis
functions: time and number of operations, sum of breaking currents A2, etc.
v through clear and comprehensive information, both locally and remotely, reducing
the time needed to act in the event of a fault.
to remote
control centre
A V/Hz W/ϕ Wh clear alarm reset A V/Hz W/ϕ Wh clear alarm reset
A V/Hz W/ϕ Wh clear alarm reset A V/Hz W/ϕ Wh clear alarm reset A V/Hz W/ϕ Wh clear alarm reset A V/Hz W/ϕ Wh clear alarm reset
Schneider Electric 15
GM6 Protection monitoring and control
Functional unit protection
(1)
or any other combination of relays, automation devices, measurements and metering
apparatus.
16 Schneider Electric
Protection monitoring and control
Current and voltage transformers
In the protection system, the functional units are fitted with transformers designed
to supply the measurements and/or protection circuits:
t current transformers,
t voltage transformers,
The active parts are totally encapsulated in an integral epoxy resin molding
which serves a dual function:
t it ensures electrical insulation,
t it guarantees the assembly an excellent mechanical resistance.
Current transformers
AD1 and AD2 units
ARC, AOL, AOPC and ARL (see table on page 24) type toroidal-core current
transformers, located in the cable compartment. The toroidal core accommodates
the secondary windings, the cable is the primary winding.
The transformers have primary current values of 50A to 2500A and secondary
current 1A or 5A.
AOPC type
CL2 unit
ARO type toroidal-core current transformers, located in the bus-section unit.
The transformers have primary current values of 50A to 2500A and secondary
current 1A or 5A.
Schneider has a standardized list of CTs that are appropriate for use with digital
protections to simplify the determination of accuracy characteristics.
This list is available on request.
ARO type
Voltage transformer
TT1 unit
VRT type metal shielded voltage transformers, located in the cable compartment.
They have one insulated MV end with plug-in connector, for connection between
neutral and phase conductors in 3-phase systems.
The cores and windings are overcast in epoxy resin, providing electrical insulation.
The external surface is metal shielded.
VRT type
Schneider Electric 17
GM6 Apparatus
SF1-G circuit breaker up to 36 kV
fig. 3 fig. 4
18 Schneider Electric
GM6
1250 t t
2500 t t
4000 t* t*
O-0.3s-CO-3min-CO t t
Circuit breaker
The circuit breakers in the SF1-G range use SF6 for insulation and current
breaking. They are composed of three poles mounted on a base which supports
the operating mechanism. Acording to IEC 56 App. EE (1987), the circuit breaker
is defined as a sealed pressure system, that is an assembly for which no further
gas processing is required during its expected operating life.
t The fundamental feature of the circuit breaker- essential for the very concept
of a fully gas insulated switchgear- is its extremaly high dependability which means:
v high reliability
v long mechanical life: the circuit breakers are designed for 10000 mechanical
operation with no need to raplace parts with only ordinary maintenance of the
operating mechanism
v long electrical life: the capacity of breaking load and short circuit current is much
higher than it is normally required in 30years of operational life. by way of example,
the circuit breakers are guaranteed for the elctrical duration defined by Table IV
of the ENEL (Italian National Electricity Board) specification DY 1702.
v no need for any maintenance on the active parts
v manufactured under a fully quality assurance program.
standards
the indicated features are referred to the following standards and specifications:
IEC 56 and 694 International Standards
ENEL DY 1701-707 specifications
operating times
t opening time (interval of time between the instant of energizing the opening
release and the instant when the arcing contacts have separated in all poles):
40 to 60 ms
t break time (interval of time between the instant of energizing the opening release
and the instant when the arc extinguishes in all poles): 50 to 70 ms
t closing time (interval of time between energizing the closing circuit and the
instant when the contacts touch in all poles): 50 to 70 ms
operating sequence
Consult our technical department for other operating sequences.
Schneider Electric 19
GM6 Apparatus
GMh operating mechanism
* mitop: current-operated release used as an option with the Sepam 100 LA protection relay.
rated current 10 A
breaking AC 10 A with 220V
capacity (p.f. u 0.3)
DC 1.5 A with 110 or 220V
(L/R i 0.01 s)
and quantities or t1 t1 t1 t 1
or t1 t1 t1
or t1 t1 t1 t 1
or t1 t1 t 1
or t1 t1 t 1 t 1
or t1 t1 t 1 t 1
or t1 t1
** pick-up/hold consumption.
20 Schneider Electric
GM6 Apparatus
Auxiliary diagram
Auxiliary diagram
GMh circuit breaker operating mechanism
KN Anti-pumping relay.
M Spring charging motor.
M3 “Operating mechanism charged” indication. Sm1
Mitop “Mitop” operating release (current-operated).
Sm2
Q Circuit breaker.
QF Circuit breaker auxiliary contacts. Sm3
Sn
SE Latch check
SM Manual charging operation in progress.
M1-M2 End-of-charging contacts.
Sm1 Closing push button (outside).
Sm2 Opening push button for shunt trip release
SM
(outside).
Sm3 Opening push button for undervoltage release
QF
(outside).
Sn Closing disable contact (outside). SC
Q
SP1 Pressure-switch contact first level. SE KN
SP2 Pressure-switch contact second level.
YF Closing release. Y01 Y02 SP1
YM Undervoltage opening release. M1 M2 M3 Mitop
Y01-Y02 Shunt opening releases. YM SP2
SC Busbar to earth indication. M YF
Schneider Electric 21
GM6 Installation
Cable terminations
An addictional bushing to DIN 47637 can be provided on request for connecting a voltage
transformer per phase.
(1)
cable cross section
t for size 1 terminations: from 25 to 240 mm2
t for size 3 terminations: from 150 to 630 mm2
(2)
type ARC2 with only 1 cable per phase
(3)
type ARL4 with 3 cables per phase
AD2 AD2
AD2 AD1
22 Schneider Electric
GM6 Installation
Example of layout
Line-up switchgear
(two supply cubicles and one bus section 36 kV 2500 A)
800
1800
4200
50 50
500 700 700 700 500 1475 500 700 700 700
2 feeders incomer busbar bus section busbar incomer 2 feeders
1600
1250 A or 2500 A 1250A transformer 2500 A transformer 2500A 1250 A or 2500 A
with VT with VT
7675
1600(1)- 2000(2)
800(3)
280 800
1200 (4)
Schneider Electric 23
GM6 Environment
Preserving the environment
24 Schneider Electric
Schneider Electric S.p.A. Circonvallazione Est, 1 As standards, specifications and designs change from time to
24040 Stezzano (BG) time, please ask for confirmation of the information given in this
Tel. (035) 4151111 publication.