Você está na página 1de 3

Project: Est. de Op. Conc. C1 e Hidro.

ETAP Page: 1
16.0.0C
Location: Arequipa - Perú Date: 17-05-2018
Contract: SN: 4359168
Engineer: CELICON INGENIEROS SAC Revision: Base
Study Case: A_NORMA ANSI
Filename: C1 Config.: C1-SC-001

Summary - Arc Flash Hazard Calculations

Faulted Bus Fault Current Trip Device


Arc Flash Incident Working
Equipment Bolted Fault (kA) Trip Open FCT Boundary Energy Distance Energy
Gap PD Arc
ID Nom. kV Type (mm) Bus PD Fault (kA) Source Trip Device ID (cycle) (cycle) (cycle) (m) (cal/cm²) (cm) Level

C-3110-MC-051 4.160 MCC 102 7.660 6.524 6.361 C-3110-CB-051 12.00 5.00 17.00 2.4 5.9 46 Level 2

C-3110-MC-052 0.480 MCC 25 27.225 19.240 10.903 C-3110-CB-052 6.00 0.00 6.00 1.1 5.3 46 Level 2

C-3120-MC-061 4.160 MCC 102 9.238 9.157 8.900 C-3120-CB-061 7.20 5.00 12.20 2.1 5.2 46 Level 2

C-3120-MC-062 0.480 MCC 25 9.648 8.888 5.859 C-3120-CB-062 12.00 0.00 12.00 1.0 4.1 46 Level 2

C-3200-MC-041 4.160 MCC 102 22.733 17.836 17.071 C-3200-CB-041 2.00 5.00 7.00 3.1 7.8 46 Level 2

C-3200-MC-042 4.160 MCC 102 23.249 17.586 16.825 C-3200-CB-042 2.00 5.00 7.00 3.2 8.0 46 Level 2

C-3200-MC-043 0.480 MCC 25 29.417 26.856 15.048 C-3200-CB-043 3.94 0.00 3.94 0.9 3.7 46 Level 1

C-3200-MC-044 0.480 MCC 25 32.436 26.947 14.885 C-3200-CB-044 3.95 0.00 3.95 1.0 4.1 46 Level 2

C-3200-MC-045 0.480 MCC 25 32.004 27.575 15.262 C-3200-CB-045 3.93 0.00 3.93 1.0 4.0 46 Level 2

C-3200-MC-046 0.480 MCC 25 32.627 28.038 15.475 C-3200-CB-046 3.92 0.00 3.92 1.0 4.1 46 Level 2

C-3200-MC-047 0.480 MCC 25 22.977 17.090 9.927 C-3200-CB-047 8.10 0.00 8.10 1.2 6.1 46 Level 2

C-3210-MC-071 4.160 MCC 102 19.846 16.808 16.124 C-3210-CB-071 3.00 5.00 8.00 3.1 7.7 46 Level 2

C-3210-MC-072 0.480 MCC 25 40.304 31.779 17.007 C-3210-CB-072 3.90 0.00 3.90 1.1 5.0 46 Level 2

C-3210-MC-073 0.480 MCC 25 40.304 40.020 21.418 C-3210-CB-073 0.35 0.00 0.35 0.2 0.4 46 Level 1

C-3230-MC-010 0.460 Other 13 1.291 1.291 0.958 C-3230-CBTR010 111.32 0.00 111.32 1.0 5.3 46 Level 2

C-3300-MC-081 4.160 MCC 102 21.945 18.562 17.776 C-3300-CB-081 2.00 5.00 7.00 3.0 7.5 46 Level 2

C-3300-MC-082 4.160 MCC 102 21.549 18.199 17.434 C-3300-CB-082 2.00 5.00 7.00 2.9 7.4 46 Level 2

C-3300-MC-083 0.480 MCC 25 37.739 31.328 16.927 C-3300-CB-083 4.02 0.00 4.02 1.1 4.8 46 Level 2

C-3300-MC-084 0.480 MCC 25 38.091 32.824 17.712 C-3300-CB-084 3.96 0.00 3.96 1.1 4.8 46 Level 2

C-3300-MC-087 0.480 MCC 25 30.817 26.391 14.687 C-3300-CB-087 4.20 0.00 4.20 1.0 4.2 46 Level 2

C-3300-MC-088 0.480 MCC 25 31.058 25.939 14.420 C-3300-CB-088 3.99 0.00 3.99 0.9 4.0 46 Level 1

C-3320-MC-101 0.480 MCC 25 35.325 31.638 17.260 C-3320-CB-101 3.60 0.00 3.60 1.0 4.0 46 Level 2

C-3320-MC-201 0.480 MCC 25 31.785 28.097 15.567 C-3320-CB-201 3.60 0.00 3.60 0.9 3.7 46 Level 1

C-3320-MC-301 0.480 MCC 25 29.304 25.620 14.363 C-3320-CB-301 3.60 0.00 3.60 0.9 3.4 46 Level 1

C-3320-MC-401 0.480 MCC 25 32.412 28.750 15.883 C-3320-CB-401 3.60 0.00 3.60 0.9 3.7 46 Level 1

C-3320-SG-085 0.480 MCC 25 40.625 3.859 1.754 3300-C-085 84.61 7.80 92.41 6.7 99.2 46 >Max.

C-3320-SG-086 0.480 MCC 25 39.758 3.769 1.718 3300-C-086 96.39 7.80 104.19 7.2 109.6 46 >Max.

C-3340-MC-089 0.480 MCC 25 19.159 18.102 10.797 C-3340-CB-089 10.20 0.00 10.20 1.3 6.5 46 Level 2

C-3400-MC-113 0.480 MCC 25 28.382 21.866 12.316 C-3400-CB-113 6.00 0.00 6.00 1.2 5.5 46 Level 2

C-3400-MC-1114 0.480 MCC 25 35.163 31.076 16.965 C-3400-CB-114 4.02 0.00 4.02 1.0 4.5 46 Level 2

C-3400-SG-1114 0.480 MCC 32 36.881 32.821 16.619 C-3400-SG1-MDS632 8.10 0.00 8.10 1.6 5.6 61 Level 2

C-3410-MC-091A 0.480 MCC 25 49.576 41.175 18.174 C-3410-CB-091A 3.06 0.00 3.06 0.9 3.9 46 Level 1

C-3410-MC-091B 0.480 MCC 25 49.576 41.175 18.174 C-3410-CB-091B 3.06 0.00 3.06 0.9 3.9 46 Level 1

C-3410-MC-092A 0.480 MCC 25 47.649 39.250 17.424 C-3410-CB-092A 3.06 0.00 3.06 0.9 3.8 46 Level 1
Project: Est. de Op. Conc. C1 e Hidro.
ETAP Page: 2
16.0.0C
Location: Arequipa - Perú Date: 17-05-2018
Contract: SN: 4359168
Engineer: CELICON INGENIEROS SAC Revision: Base
Study Case: A_NORMA ANSI
Filename: C1 Config.: C1-SC-001

Summary - Arc Flash Hazard Calculations

Faulted Bus Fault Current Trip Device


Arc Flash Incident Working
Equipment Bolted Fault (kA) Trip Open FCT Boundary Energy Distance Energy
Gap PD Arc
ID Nom. kV Type (mm) Bus PD Fault (kA) Source Trip Device ID (cycle) (cycle) (cycle) (m) (cal/cm²) (cm) Level

C-3410-MC-092B 0.480 MCC 25 46.184 37.786 19.825 C-3410-CB-092B 3.06 0.00 3.06 1.0 4.4 46 Level 2

C-3410-MC-093A 0.480 MCC 25 48.652 40.260 17.819 C-3410-CB-093A 3.06 0.00 3.06 0.9 3.9 46 Level 1

C-3410-MC-093B 0.480 MCC 25 50.246 41.852 18.436 C-3410-CB-093B 3.06 0.00 3.06 1.0 4.0 46 Level 1

C-3410-MC-094A 0.480 MCC 25 50.252 41.857 18.438 C-3410-CB-094A 3.06 0.00 3.06 1.0 4.0 46 Level 1

C-3410-MC-094B 0.480 MCC 25 48.903 40.510 17.916 C-3410-CB-094B 3.06 0.00 3.06 0.9 3.9 46 Level 1

C-3410-MC-096 0.480 MCC 25 14.426 13.869 8.622 C-3410-CB-096 3.06 0.00 3.06 0.5 1.5 46 Level 1

C-3440-MC-095A 0.480 MCC 25 47.563 39.172 17.394 C-3410-CB-095A 3.06 0.00 3.06 0.9 3.8 46 Level 1

C-3440-MC-095B 0.480 MCC 25 48.674 40.281 17.827 C-3410-CB-095B 3.06 0.00 3.06 0.9 3.9 46 Level 1

C-3440-MC-1097 0.480 MCC 25 38.565 33.114 17.836 C-3440-CB-1097 3.95 0.00 3.95 1.1 4.8 46 Level 2

C-3500-MC-011 0.480 MCC 25 29.662 24.589 13.761 C-3500-CB-011 6.00 0.00 6.00 1.2 5.7 46 Level 2

C-3500-MC-012 0.480 MCC 25 28.497 24.459 13.768 C-3500-CB-012 6.00 0.00 6.00 1.2 5.5 46 Level 2

C-3500-MC-015E 0.480 MCC 25 12.814 12.519 7.918 C-3500-CB-015E 0.90 0.00 0.90 0.2 0.4 46 Level 1

C-3600-MC-013 0.480 MCC 25 40.447 30.576 16.355 C-3600-CB-013 3.90 0.00 3.90 1.1 5.0 46 Level 2

C-3600-MC-013A 0.480 MCC 25 41.788 41.740 18.888 C-3500-CB-013A 2.75 0.00 2.75 0.8 3.0 46 Level 1

C-3600-MC-111 4.160 MCC 102 22.018 17.568 16.823 C-3600-CB-111 2.00 5.00 7.00 3.0 7.5 46 Level 2

C-3600-MC-112 4.160 MCC 102 21.097 17.262 16.542 C-3600-CB-112 2.00 5.00 7.00 2.9 7.2 46 Level 2

C-3600-MC-1013B 0.480 MCC 25 37.390 34.444 18.636 C-3600-CB-MC1013B 3.90 0.00 3.90 1.0 4.6 46 Level 2

C-3600-MC-1113A 0.480 MCC 25 24.902 23.731 13.624 C-3600-CB-113A 0.55 0.00 0.55 0.2 0.4 46 Level 1

C-3700-MC-121 4.160 MCC 102 18.218 13.884 13.338 C-3700-CB-121 3.00 5.00 8.00 2.8 7.0 46 Level 2

C-3700-MC-122 0.480 MCC 25 18.522 16.418 9.841 C-3700-CB-122 6.00 0.00 6.00 0.9 3.7 46 Level 1

C-3700-MC-122A 0.480 MCC 25 15.796 15.435 9.469 C-3700-CB-MC122A. 0.73 0.00 0.73 0.2 0.4 46 Level 1

C-3700-MC-123E 0.480 MCC 25 6.624 5.595 3.896 C-3700-CB-123E 1.27 0.00 1.27 0.2 0.3 46 Level 1

C-3700-MC-1122B 0.480 MCC 25 16.080 15.330 9.380 C-3700-CB-1122B 3.06 0.00 3.06 0.6 1.7 46 Level 1

C-3810-MC-321 4.160 MCC 102 11.106 10.659 10.327 C-3810-CB-321 3.00 5.00 8.00 1.6 4.2 46 Level 2

C-3810-MC-322 0.480 MCC 25 21.612 16.846 9.873 C-3810-CB-322 8.10 0.00 8.10 1.2 5.8 46 Level 2

C-3810-MC-331 4.160 MCC 102 10.820 10.727 10.397 C-3810-CB-331 6.00 5.00 11.00 2.2 5.6 46 Level 2

C-3810-MC-332 0.480 MCC 25 10.743 9.848 6.391 C-3810-CB-332 8.10 0.00 8.10 0.9 3.9 46 Level 1

C-3820-MC-31A1 0.480 MCC 25 10.958 9.252 5.088 C-3820-CB-31A1 8.10 0.00 8.10 0.9 3.4 46 Level 1

C-3820-MC-311 4.160 MCC 102 11.257 11.091 10.743 C-3820-CB-031 3.00 5.00 8.00 1.7 4.2 46 Level 2

C-3840-DP-141 0.380 Panelboard 25 1.788 1.732 1.175 C-3840-CB-141DP 1.67 0.00 1.67 0.1 0.1 46 Level 1

C-3840-DP-145 0.380 Panelboard 25 1.788 1.733 1.175 C-3840-CB-145DP 1.67 0.00 1.67 0.1 0.1 46 Level 1

C-3840-DP-211 0.220 Panelboard 25 4.531 4.435 2.473 C-3840-CB-211DP 1.13 0.00 1.13 0.1 0.1 46 Level 1

C-3840-DP-341 0.400 Panelboard 25 2.500 2.303 1.743 C-3840-CB-341DP 1.28 0.00 1.28 0.1 0.1 46 Level 1

C-3840-MC-141 4.160 Switchgear 102 12.231 8.760 8.473 C-3840-CB-141 9.00 5.00 14.00 3.2 4.1 91 Level 2
Project: Est. de Op. Conc. C1 e Hidro.
ETAP Page: 3
16.0.0C
Location: Arequipa - Perú Date: 17-05-2018
Contract: SN: 4359168
Engineer: CELICON INGENIEROS SAC Revision: Base
Study Case: A_NORMA ANSI
Filename: C1 Config.: C1-SC-001

Summary - Arc Flash Hazard Calculations

Faulted Bus Fault Current Trip Device


Arc Flash Incident Working
Equipment Bolted Fault (kA) Trip Open FCT Boundary Energy Distance Energy
Gap PD Arc
ID Nom. kV Type (mm) Bus PD Fault (kA) Source Trip Device ID (cycle) (cycle) (cycle) (m) (cal/cm²) (cm) Level

C-3840-MC-145 4.160 Switchgear 102 12.390 8.996 8.699 C-3840-CB-145 9.00 5.00 14.00 3.3 4.2 91 Level 2

C-3840-MC-211 4.160 Switchgear 102 9.318 6.697 6.508 C-3840-CB-211 12.00 5.00 17.00 2.9 3.7 91 Level 1

C-3840-MC-341 4.160 MCC 102 10.725 7.925 7.682 C-3840-CB-034 6.00 5.00 11.00 2.2 5.5 46 Level 2

C-3841-SB-001 0.400 Other 13 5.182 5.182 3.572 C-3841-CB-001 1.33 0.00 1.33 0.2 0.3 46 Level 1

C-3841-SB-002 0.480 Other 13 14.502 14.502 9.788 C-3841-CB-002 6.00 0.00 6.00 0.8 3.5 46 Level 1

C-3850-MC-200 4.160 MCC 102 8.512 6.422 6.250 C-3840-CB-200 12.00 5.00 17.00 2.7 6.7 46 Level 2

C-3900-MC-131 0.480 MCC 13 13.470 11.698 7.959 C-3900-CB-131 6.00 0.00 6.00 0.8 2.9 46 Level 1

C-5120-MC-171 0.480 MCC 25 23.811 18.736 10.827 C-5120-CB-171 6.00 0.00 6.00 1.0 4.7 46 Level 2

C-5130-MC-181 10.000 MCC 153 2.704 2.244 2.227 C-5120-FU-172 S 27.28 0.00 27.28 1.1 2.8 46 Level 1

C-5130-MC-182 0.480 MCC 13 24.880 23.404 14.891 C-5130-CB-182 6.00 0.00 6.00 1.1 5.3 46 Level 2

C-5130-MC-183 0.480 MCC 25 7.009 6.810 4.703 C-5130-CB-183 6.00 0.00 6.00 0.5 1.5 46 Level 1

C-5130-MC-184 0.480 MCC 13 18.354 17.839 11.734 C-5130-CB-184 0.58 0.00 0.58 0.2 0.4 46 Level 1

C-5140-MC-181 4.160 MCC 102 14.448 9.158 8.833 C-5140-CB-181 5.00 5.00 10.00 2.7 6.9 46 Level 2

C-5150-MC-191 4.160 MCC 102 17.568 12.103 11.635 C-5150-CB-191 3.00 5.00 8.00 2.7 6.8 46 Level 2

C-5700-DP-014 0.380 Panelboard 25 16.733 16.733 8.505 C-5700-CB-014DP 5.40 0.00 5.40 0.7 2.5 46 Level 1

C-5830-MC-131B 0.480 MCC 25 13.470 13.136 8.248 C-5830-CB-131B1 3.00 0.00 3.00 0.5 1.4 46 Level 1