1 MWp Solar Power Plant at ROMAINVILLE, MAHE, SEYCHELLES SLD OF PROJECT

103.6 KWp ROMAINVILLE,


To GRID MAHE, SEYCHELLES
Net Meter INVERTER
30 kW,Output Voltage=415 V
To Clients LT panel NET METER Tariff Meter
415Vac,625Amp,
3-Ph,4Pole
MCCB-O/C,E/F
200 Amp MCCB 415V,SPD-40KA
TYPE-I+II
CT-100 /5 AMP
CL-0.5, 10VA
0.5 Class CT (200/5)
CT with Solar Meter
1R*3.5C*120Sqmm
AL AR.XLPE LT CABLE INVERTER(50kW)
OUTPUT VOLTAGE=415V
TOTAL NUM OF STRINGS:-9 1 2 3 4 5 6 7 8 9 10
ACDB
A & B =100 Amps, 4 Pole
MCCB with O/C, E/F
415Vac +/-20%,
MODULE RATING:-320Wp 01
415V,
SPD-40KA
200A, 50HZ,TIN PLATED
with AC SPD Class-II TYPE-I+II
COPPER BUS BAR
1.Plant Capacity:-103.68KW
B A 2.Inverter Rating:-50KW (String)
3.Total No of Inverter :- 2 Nos
3.Module Rating:-320Wp
4.Total Number of Modules:- 324 nos
5.Module Per String :- 18 Modules
1R*3.5C*35SQMM 1R*3.5C*35SQMM 6.Module String per inverter :- 9 Nos
XLPE AR CU CABLE XLPE AR CU CABLE
1R*1C*16SQMM FOR PE 1R*1C*16SQMM FOR PE
INV. 1 INV. 2
INVERTER(50kW) INVERTER(50kW)
OUTPUT VOLTAGE=415V OUTPUT VOLTAGE=415V A - ISSUED FOR REVIEW
TOTAL NO. OF STRINGS=9 TOTAL NO. OF STRINGS=9 B - ISSUED FOR APPROVAL
TOTAL NO. OF 10 9 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10
TOTAL NO. OF C - ISSUED FOR CONSTRUCTION
MODULES=162(320Wp) MODULES=162(320Wp) D - AS BUILT
DC POWER INPUT-51.840KW DC POWER INPUT-51.840KW
01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01 01

1Cx4SQMM CU.

1Cx4SQMM CU.
02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 02 NATURE OF REVISION & DESCRIPTION DRAWN CHECKED REV. DATE
PROJECT TITLE :
103.68 KWp SOLAR POWER PROJECT AT
ROMAINVILLE, MAHE, SEYCHELLES

PV CABLE

PV CABLE
17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17 17
DWG. TITLE :
SINGLE LINE DIAGRAM
CLIENT : PUC PUBLIC UTILITIES CORPORATION
18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18 18
ELECTRICITY HOUSE
ROCHE CAIMAN, P. BOX NO. 174

STR-9

STR-8

STR-7

STR-6

STR-4

STR-2

STR-2

STR-4

STR-6

STR-7

STR-8

STR-9
STR-5

STR-3

STR-3

STR-5
STR-1

STR-1
MAHE, SEYCHELLES
EPC CONTRACTOR:
DRAWN BY : CHIRAG SCALE : NTS
REVIEWED BY : NARENDER DATE : 16/06/2018
APPROVED BY : ANUJ SHEET : 01 OF 01
PROJECT NO. DRAWING NO.
REV.
EPC-SIPL/PROJ/SEY/02 SEY-PV-ACSLD-A001 R00

Você também pode gostar