Você está na página 1de 216

Book 2

Volume 1

Generator
Protection
2005 Protection Seminar

Contents

• Generator Basics
• Generator Protection Upgrade Tutorial
• Implementing Power Plant Control Logic
Scheme Logic

6190-118th Avenue North – Largo, Florida 33773


www.beckwithelectric.com
Generator
Protection
Generator Basics

2005 Protection Seminar

6190-118th Avenue North – Largo, Florida 33773


www.beckwithelectric.com
GENERATOR
BASICS
Chuck Mozina
Consultant
Beckwith Electric

January 17, 2005


Generator Basics

Generator Basics

ƒ Basic Synchronous Generators

ƒ Connections to the system

ƒ Short Circuits

ƒ Device Numbers
Generator Basics

Basic Synchronous Generator


Generator Basics

Generator Excitation & AVR Control

Generator Step-up
Transformer
Generator
Field CT VT
Gen.

Excitation
AVR
Transformer
Static
Exciter
Generator Basics

Synchronous Generator Types


Generator Basics
Generator Basics
Generator Basics
Generator Basics

Direct Connected Generator to Power System


Generator Basics

Unit Connected Generator


Unit Connected Generator toto Power
Power SystemSystem
Generator Basics

Symmetrical Trace of a Generator Short-


Circuit Current
Generator Basics

Symmetrical Trace of a Generator Short-


Circuit Current
Generator Basics

Generator Short-Circuit Currents Phase B


Generator Basics

Generator Terminal Fault Current


Generator Basics

Multi-Phase Generator Fault Oscillograph

Fault Inception
High Side of
Generator
Breaker
Currents

High Side Breaker Opens

Generator
Neutral
Terminal
Currents
Generator Basics

Accumulation of damage over time:


8000

watt seconds
6000
Watt-seconds

Total
4000
Generator

2000

System

0
0.01 0.1 1 10
time, sec

Most of the damage occurs in the period after


the generator breaker opens
Generator Basics

Discussed in
Device Function Tutorial
Section
21 Distance Relay. Backup for system 11
and generator zone phase faults.
24 Volts/Hz protection for generator 6
overexcitation.
32 Reverse power relay. Anti-motoring 14
protection.
40 Loss-of-field protection. 8
46 Negative sequence unbalance 10
current protection for the generator.
Generator Basics

Discussed in
Device Function Tutorial
Section
49 Stator Thermal Protection. 14
51GN Time overcurrent ground relay. 4 & 11
51TN Backup for ground faults. 4 & 11
51V Voltage-controlled or voltage- 11
restrained time overcurrent relay.
Backup for system and generator
phase faults.
59 Overvoltage protection. 6

59GN Overvoltage relay. Stator ground 4


fault protection for a generator.
Generator Basics

Discussed in
Device Function Tutorial
Section
78 Loss-of-synchronism protection. 9
81 Frequency relay. Both 5
underfrequency protection.
86 Hand-reset lockout auxiliary relay. 14
87G Differential relay. Primary phase-fault 2
protection for the generator.
87N Stator ground fault differential . 4
87T Differential relay. Primary protection 2
for the transformer.
87U Differential relay for overall generator 2
and transformer protection.
Generator Basics

Typical Unit Generator –


Transformer Configuration
Generator Basics

Typical Combine Cycle Plant


UTILITY TRANSMISSION SYSTEM

GSU GSU #1 GSU #2

G ST GT-1 G GT-2 G

AUX. TRANS. #1 AUX. TRANS. #2


ST = STEAM TURBINE
GT = GAS TURBINE
GSU = GEN. STEP-UP UNIT
V1 V2
TRANSFORMER A C
N.0. = NORMALLY OPEN
Aux. Bus #1 Aux. Bus #2
B
N.O.

M M M M M
Generator Basics

GENERATOR
BASICS
QUESTIONS ?
Generator
Protection
Generator Protection Upgrade Tutorial

2005 Protection Seminar

6190-118th Avenue North – Largo, Florida 33773


www.beckwithelectric.com
Generator Protection

Upgrade Tutorial
Generator Protection Upgrade

Discussion Objectives
ƒ Why upgrade generator protection?

ƒ Explore the M-3425A Generator Protective Relay

- Advanced attributes for security, reliability and


maintenance use

ƒ Demonstrate Commissioning/Event Investigation


Tools and New Osillograph Viewing Program
(IPSPlot)

ƒ Q&A
Generator Protection Upgrade

IEEE PSRC Survey


ƒ Conducted in early ’90s, showed many areas of
protection lacking

ƒ Reluctance to upgrade includes:


- Lack of expertise

ƒ To recognize deficiency
ƒ To perform the work

- “Generators don’t fail”

- Operating procedures will save the day

PSRC = Power System Relay Committee


Generator Protection Upgrade

Protection Upgrade Opportunities


ƒ Improved sensitivity
- Negative sequence
- 100% stator ground fault
- Field ground fault
- Loss of Field
ƒ Voltage supervision for fast trip release
- Overexcitation
- Reverse power

ƒ Improved Security
- Distance Element Enhancements
ƒ Load encroachment blinding
ƒ Power swing blocking (for stable swings)
Generator Protection Upgrade

Protection Upgrade Opportunities


ƒ New protections
- Inadvertent energizing
- VT fuse loss (integrated)

ƒ Special applications unique to generators


- Generator breaker failure
ƒ Pole flashover (prior to syncing)
Generator Protection Upgrade

ANSI/IEEE Standards
ƒ Latest developments reflected in:

- Std. 242: Buff Book

- C37.102: IEEE Guide for Generator Protection

- C37.101: IEEE Guide for AC Generator Ground


Protection

- C37.106: IEEE Guide for Abnormal Frequency


Protection for Power Generating Plants

These are created/maintained by the IEEE PSRC & IAS


They are updated every 5 years
Generator Protection Upgrade

Small Machine Protection IEEE “Buff Book”

Small – up to 1 MW to 600V, 500 kVA if >600V


Generator Protection Upgrade

Small Machine Protection IEEE “Buff Book”

Medium – up to 12.5 MW
Generator Protection Upgrade

Small Machine Protection IEEE “Buff Book”

Large – up to 50 MW
Generator Protection Upgrade

Large Machine
Protection
IEEE C37.102

Unit Connected,
High Z Grounded
Generator Protection Upgrade

Generator Protection
ƒ Internal Fault ƒ Abnormal Operating
- Stator Phase Conditions
- Stator and Field - Over/under voltage
Ground - Overexcitation
ƒ System Back Up for - Load Unbalance
Faults - Loss of Field
- Phase and Ground - Loss of Synchronism
- Frequency
ƒ Sequential Shutdown - Loss of prime mover
- Power sensitivity
- Inadvertent Energizing
ƒ Sync Security - Compromised potential
- Sync Check source (blown fuse)
- Open trip circuit
Generator Protection Upgrade

Generator Protection: Faults

System
Field Ground Ground

Stator
Ground
Exciter

G System

Stator
Phase

System
Phase
Generator Protection Upgrade

Generator Protection: Abnormal Operating


Conditions
Overexcitation
Over Open
Power Loss of Field Loss of Field
Circuits
Overexcitation Overexcitation
Brush LIft Off
Open
Exciter
Trip Circuits

G System
Abnormal
Inadvertent Frequency
Energizing,
Abnormal Pole Flashover
Frequency Loss of
Reverse Breaker Synchronism
Power Failure
Generator Protection Upgrade

Review of Grounding Techniques


ƒ Why Ground?

- Safety
- Ability to detect less harmful (hopefully)
phase-to-ground fault before phase-to-phase
fault occurs
- Limit damage from ground faults
- Stop transient overvoltages
- Provide ground source for other system
protection (other zones)
Generator Protection Upgrade

Types of Generator Grounds


ƒ Low Impedance

- Can get expensive as resistor size increases

- Usually a good ground source

- Generator still likely to be damaged on internal


ground fault

ƒ Ground fault current typically 200-400 A

G System
Generator Protection Upgrade

Types of Generator Grounds


ƒ High Impedance

- Moderately expensive
- Used when generators are unit connected
- System ground source obtained from unit xfmr
- Generator damage minimized or mitigated from
ground fault
- Ground fault current typically <=10A

G System
Generator Protection Upgrade

Types of Generator Grounds


ƒ Compensated (special type of High Z)

- Most expensive (tuned reactor, plus unit xfmr and


grounding xfmr)
- System ground source obtained from unit xfmr
- Generator damage mitigated from ground fault
- Reactor tuned against generator capacitance to
ground to limit ground fault current to very low
value (can be less than 1A)

G System
Generator Protection Upgrade

Types of Generator Grounds


ƒ Hybrid Impedance

- Combines advantages of Low Z and High Z ground


- Low Z ground provides ground source for normal
conditions
ƒ 51N acts as back up protection for uncleared
system faults
ƒ 51N is too slow to protect generator for internal
fault
- If an internal ground fault (in the generator) is
detected by the 87GD element, the Low Z ground
path is opened, leaving only the High Z ground
path
ƒ The High Z ground path limits fault current to
approximately 10A (saves generator!)
Generator Protection Upgrade
51
51
N

52
F3
Hybrid Ground
51
51
N
Converts from low to
52
F2
high if internal
52
generator fault is
B
51
51
N detected
52
F1

52
G 87
GD

G
51
G Trip
Excitation,
Prime Mover

VS

59
N
Generator Protection Upgrade

Stator Iron Burning


ƒ Pictures of stator damage after an internal ground
fault

ƒ This generator was high impedance grounded, with


the fault current less than 10A

ƒ Some iron burning occurs, but the damage is


repairable (vs. low impedance grounded machines
where the damage is typically severe)
Generator Protection Upgrade
Generator Protection Upgrade
Generator Protection Upgrade
Generator Protection Upgrade
Generator Protection Upgrade

Types of Generator Connections


ƒ Bus (No/Low Z)

- Directly connected to bus


- Likely in industrial, commercial, and isolated
systems
- Simple, inexpensive
BUS

G
Generator Protection Upgrade

Types of Generator Connections


ƒ Multiple Bus BUS
(No/Low Z/High Z)
- Directly connected to bus
- Likely in industrial, commercial,
and isolated systems
- Simple G G G
- May have problems with Same type of grounding used on 1 or mutiple generators
circulating 3rd harmonic
ƒ Use of single grounded
machine can help
- Adds complexity to
discriminate ground fault
source
Generator Protection Upgrade

Types of Generator Connections


ƒ High Impedance

- Generator has dedicated unit xfmr

- Generator has dedicated ground xfmr

- Likely in large industrial and utility systems

- 100% stator ground fault protection available

BUS

G
Generator Protection Upgrade

Types of Generator Connections


ƒ Multiple Bus (High Z), 1 or Multiple Generators
- Connected through one unit xfmr
- Likely in large industrial and utility systems
- No 3rd circulating harmonic issue
- Adds complexity to discriminate ground fault source
ƒ Special CTs needed for sensitivity, and directional ground
overcurrent elements
BUS

G
Generator Protection Upgrade

Stator Ground Fault-High Z Grounded


Machines
ƒ 95% stator ground fault provided by 59N

ƒ Tuned to the fundamental frequency

ƒ Must work properly from 10 to 80 Hz to provide


protection during startup.

ƒ Additional coverage near neutral (last 5%) provided


by:
- 27TN: 3rd harmonic undervoltage
- 59D: Ratio of 3rd harmonic at terminal and neutral
ends of winding

ƒ Full 100% stator coverage by 64S


- Use of sub-harmonic injection
Generator Protection Upgrade

100% Stator Ground Fault (59N/27TN)


ƒ High impedance ground limits
ground fault current to about 10A

- Limits damage on internal ground


fault

ƒ Conventional neutral overvoltage


relay provides 90-95% stator
coverage

ƒ Last 5-10% near neutral not covered

ƒ Undetected grounds in this region


bypass grounding transformer,
solidly grounding the machine!
Generator Protection Upgrade

59N Element
1.0

Voltage at Neutral
pu

(60 Hz)
0.5
pu

0
0% 50% 100%
N Fault Position T

ƒ Grounding transformer ratio


selected that provides 120V
(1.0 pu) for ground fault at
machine terminals
Generator Protection Upgrade

100% Stator Ground Fault (59N/27TN)


ƒ 59N – Generator Neutral Overvoltage

- Provides three levels of setpoints


ƒ 1st level set sensitive to cover down to 5% of stator
- Delay to coordinate with close-in system ground
faults capacitively coupled across GSU

ƒ 2nd level set higher than the capacitively coupled voltage


so coordination from system ground faults is not
necessary
- Allows higher speed tripping
- Only need to coordinate with PT fuses

ƒ 3rd level may be set to initiate waveform capture


and not trip
Generator Protection Upgrade

27TN – 3rd Harmonic Neutral Undervoltage


ƒ Provides 0-15% stator winding coverage (typ.)
ƒ Tuned to 3rd harmonic frequency
ƒ Provides two levels of setpoints
ƒ Supervisions for increased security under various
loading conditions
- Any or All May be Applied Simultaneously
ƒ Positive Sequence Undervoltage Block
ƒ Underpower Block; Forward & Reverse
ƒ Under VAr Block; Lead & Lag
ƒ Power Factor Block; Lead & Lag
ƒ Definable Power Band Block
Generator Protection Upgrade

27TN Supervision
ƒ Phase voltage
- No phase voltage, cannot generate 3rd harmonic
voltage

ƒ Power
- 3rd harmonic typically increases as power output
increases

ƒ VAr, PF, I, Power Band


- Additional supervisions for cases where 3rd harmonic
levels vary with modes of operation (sync condenser,
pump storage, VAr sink)
Generator Protection Upgrade

27TN Supervision
Generator Protection Upgrade

100% Stator Ground Fault (59N/27TN)

Third-Harmonic Undervoltage Ground-Fault Protection Scheme


Generator Protection Upgrade

3rd Harmonic in Generators:


Typical 3rd Harmonic Values

ƒ 3rd harmonic values tend to increase with power and VAr loading
ƒ Fault near neutral causes 3rd harmonic voltage at neutral to go to zero volts
Generator Protection Upgrade

3rd Harmonic in Generators


ƒ 3rd harmonic present in
terminal and neutral ends

ƒ Can vary with loading

ƒ Useful for ground fault


detection near neutral

- If 3rd harmonic goes away,


conclude a ground fault near
neutral
Generator Protection Upgrade

100% Stator Ground Fault (59N/27TN)

Overlap of Third Harmonic (27TN) with 59N Relay


Generator Protection Upgrade

59D – 3rd Harmonic Ratio Voltage


ƒ Examines 3rd harmonic at line
and neutral ends of generator
ƒ Provides 0-15% stator winding
coverage and 85-100% (typ.)
ƒ Does not have a security issue
with loading, as can a 27TN
- May be less reliable than 27TN
(note enough difference to trip)

ƒ “Blind spot” at mid-winding


protected by 59N
ƒ Needs wye PTs; cannot use delta
PTs
Generator Protection Upgrade

59D – 3rd Harmonic Ratio Voltage


Generator Protection Upgrade

Stator Ground Faults: High Z Element Coverage

59N-1

59N-2
27TN 59D

0% 100%
Generator Protection Upgrade

64S – Subharmonic Injection


ƒ Injects subharmonic frequency

- Does not rely on third harmonic signature of


generator

ƒ Provides full coverage protection

ƒ Provides on and offline protection

ƒ Frequency independent
Generator Protection Upgrade

Natural Capacitance 64S

* V

Coupling Voltage M-3425A


Filter Injector Measurements
other ground voltage elements
Notes:
¾ Subharmonic injection typically at 15-20 Hz
¾ Coupling filter low pass or notch tuned for subharmonic frequency
¾ Measurement inputs tuned to respond to subharmonic frequency
Generator Protection Upgrade

64S – Subharmonic Injection


Generator Protection Upgrade

Stator Ground Faults: High Z Element Coverage

59N-1

59N-2
27TH 59D

64S
0% 100%
Generator Protection Upgrade

Stator Ground Fault-Low Z Grounded Machines


ƒ 51N element typically applied

- Must be set to coordinate with system ground


fault protection for security and selectivity

- Results in long clearing time for internal ground


fault

- Selectivity issues with bused machines

Skip Low-Z Grounding


Generator Protection Upgrade

Stator Ground Fault-Low Z Grounded Machines


ƒ 67N element provides selectivity on multiple bused applications

ƒ 67N directionalized to trip for ground current toward a generator

ƒ 67N is set faster than 51N


- May be short definite time delay

- Ground current should not flow into a generator under normal


operating conditions

- May be applied on ungrounded machines for ground fault


protection

ƒ Ground current is from other generators/ or system


Generator Protection Upgrade

Stator Ground Fault-Low Z Grounded Machines


ƒ 87GD element provides selectivity on single and multiple
bused applications

ƒ 87GD uses differential quantity and directional comparison


of zero sequence current at terminals and ground current in
grounding path

ƒ 87GD is set faster than 51N


- May be very short definite time delay

- Difference in ground current in and out of machine should


never exist under normal operating conditions
Generator Protection Upgrade
Directional Neutral Overcurrent (67N)
Low Z Grounded Generator, Switched Ground

Directional Neutral Overcurrent (67N)


Low Z Grounded Generator, Switched Ground
BUS
ƒ Employed to
selectively find
3Y 3Y 3Y
machine ground
67
N
67
N
67
N fault in multiple
bus-connected
G G G arrangements
ƒ Use with 51N on
51
N
51
N
51
N grounded machine
for internal fault
and system back
up
R R R
ƒ 87GD could also be
applied instead of
67N
Generator Protection Upgrade

Directional Neutral Overcurrent (67N)


Low Z Grounded Generator, Switched Ground

ƒ Ground fault on
BUS system is detected
by grounded
generator’s 51N
67 67 67
element
N N N

ƒ Coordinated with
G G G system relays, they
should trip before
51N
51 51 51
N N N

ƒ 67N, wrong
direction, no trip
R R R
Generator Protection Upgrade

Directional Neutral Overcurrent (67N)


Low Z Grounded Generator, Switched Ground
BUS
ƒ Ground fault in grounded
machine is detected by 51N
ƒ 51N trips
67 67 67
N N N

ƒ 67N, does not see any zero


G G G sequence current since no
zero sequence source
51 51 51
N N N ƒ Ground another generator to
have ground source
ƒ Use 87GD on the grounded
R R R machine instead of 67N to
provide fast protection
Generator Protection Upgrade

Directional Neutral Overcurrent (67N)


Low Z Grounded Generator, Switched Ground
BUS
ƒ Fault in ungrounded
machine detected by 67N
ƒ 67N trips before 51N of
67 67 67
N N N
grounded machine
G G G ƒ Trip selectivity
maintained
51 51 51
N N N
ƒ 67N can also be applied
to High Z Grounded
machines if a toroidal
R R R
(doughnut) CT is
available on the line side
Generator Protection Upgrade

Use of 87GD and 67N for Trip Selectivity on


Multiple Bus-Connected Machines

67 87
N GD

G G
51
N

R
Generator Protection Upgrade

Adds Directional Neutral Overcurrent (67N)


Low Z Grounded Generator, Switched Ground

• Fault in
BUS ungrounded
machine detected
by 67N
• 67N trips before
G G
67 67
N N
51N of grounded
87
GD
87
GD
machine

51 51
• 87GD for fast
N N
tripping for fault on
grounded machine
• Trip selectivity
R R maintained
Generator Protection Upgrade

Hybrid Ground
Dynamic switching from low to high when internal
generator fault is detected

52
G

87
GD

G
51
G Trip
Excitation,
Prime Mover

VS

59
N
Generator Protection Upgrade

Stator Ground Faults: Low Z Element Coverage

51N

With single
generator 67N
With 2 or more
generators on 67N
bus
With single
generator 87GD
With 2 or more
generators on
bus
87GD
0% 100%
Generator Protection Upgrade

64F: Field/Rotor Ground Faults


Classic Conventional DC Systems

ƒ These DC systems do not measure impedance and report it


ƒ They may misoperate due to DC battery and field forcing transients
ƒ They alarm for a zero ohms short circuit
ƒ They cannot detect brush lift-off
Generator Protection Upgrade

64F: Field/Rotor Ground Faults


ƒ Measures impedance, and can alarm as impedance
starts going down
ƒ Use low frequency AC injection
ƒ Plan a shutdown to determine why impedance is
lowering, versus an eventual unplanned trip!
Generator Protection Upgrade

64B: Field/Ground Brush Lift Off


ƒ Conventional DC-type field ground protections do not
detect change in the field connection or rotor shaft
connection to ground as the field or grounding
brushes lift off.

ƒ By using low frequency AC injection, we can detect


the change in machine capacitance to ground due to
brush lift-off and alarm.

ƒ This is a great reliability-centered maintenance (RCM)


aid.
Generator Protection Upgrade
64B: Brush Lift Off

64B: Brush Lift Off


ƒ Commutation brush lift-off will lead to:
- Arcing
- Tripping on loss-of-field
ƒ Grounding brush lift-off can lead to:
- Stray currents that cause bearing pitting

Commutation
Brush

Grounding
Brush
Generator Protection Upgrade

64B: Brush Lift Off


ƒ As brushes lift-off, the sawtooth wave’s return
signal slope gets less rounded, which is detected
as a rise in voltage

Commutation
Brush

Grounding
Brush
Generator Protection Upgrade
64F: Field/Rotor Ground Faults
64B: Brush Lift Off
Generator Protection Upgrade

64B: Brush Lift Off


ƒ 64F/B using injection applicable on both brushed
and “brushless” machines

- Brushless machines typically employ a grounding


brush and pilot/pony brush (constant or
intermittent contact with rotor winding)

- Injection schemes examines normal capacitive


coupling between grounding and pilot/pony brush

- If pilot/pony brush is intermittent, use


control/status input to block element when brush
is not in contact with rotor winding
Generator Protection Upgrade

64F/B: “Brushless” Machines


Ground Fault
Detection Slip
Ground Fault Ring
Detection
Brush Rotor Winding

Rotor

Ground Fault
Detection
Slip Ring

Grounding
Brush

ƒ 64F/B application on “brushless” machine


Generator Protection Upgrade

Field/Rotor Ground Faults


ƒ 64F/B
Relay 1 Relay 2
(M-3425) (M-3425)
- It is possible to apply two
M-3425As and have
3 3
redundancy Switch
Field Assembly
System
Relay Panel
- The switch system is initiated 3

by manual means or by Exciter System


monitoring relay self Coupling M-3921
Unit
diagnostic contacts Rotor

Brush (Typ.)

+ R -

Exciter System
Generator Protection Upgrade

Field Ground Detection for Brushless


Machines without Pilot/Pony Brush
Generator Protection Upgrade

Split-Phase Differential (87SP)

Detect Turn-to-Turn
Faults with Individual
Definite Time Phase
Overcurrent Pickup
Adjustment
Generator Protection Upgrade

Stator Phase Faults


ƒ 87G – Phase Differential (primary)
- Must work properly from 10 Hz to 80Hz. Required to
operate correctly at off-nominal frequencies to provide
protection from internal faults during startup.
- Variable percentage slope
- Uses IRMS/IFUND to adaptively desensitize element when
challenged by large DC offset and harmonics for security
ƒ DC offset can occur from black starting and close-in
faults
ƒ 21 – Phase Distance (back up)
- Use Z1 with reach set 80% of impedance of GSU
- Provide high speed back up to 87G
Generator Protection Upgrade

Stator Phase Faults


ƒ 50/50N/51N – Phase and Ground Overcurrent (back
up)
- Designed to operate properly from 8 Hz to 80 Hz.
- Provides protection for generator from phase and
ground faults during startup and shutdown.
- Provides backup for 87 function and extends the
frequency range down to 8 Hz.

ƒ 51V – Voltage Restrained/Controlled Overcurrent


(back up)
- Accommodate current decrement
- Provide back up to 87G
- May be applied in parallel with the 21 to initiate
waveform capture and not trip
Generator Protection Upgrade

Phase Distance (21)


ƒ Phase distance backup protection may be prone to tripping on
stable swings and load encroachment
- Employ three zones
ƒ Z1 can be set to reach 80% of impedance of GSU for 87G
back-up.
ƒ Z2 can be set to reach 120% of GSU for station bus backup,
or to overreach remote bus for system fault back up
protection. Load encroachment blinder provides security
against high loads with long reach settings.
ƒ Z3 may be used in conjunction with Z2 to form out-of-step
blocking logic for security on power swings or to overreach
remote bus for system fault back up protection. Load
encroachment blinder provides security against high loads
with long reach settings.
- Current threshold provides security against loss of
potential (machine off line)
Generator Protection Upgrade
3-Zone 21 Function with 3-Zone 21 Function
with OSB / Load Encroachment
OSB/Load Encroachment
Generator Protection Upgrade

21 – Distance Load
Fault (for Z1, Z2, Z3)
Element Impendance Blinder

+X
XL
Z3

XT Z2

Z1

-R +R

-X Power
PowerSwing
Swingoror
Z1, Z2 and Z3 used to trip Load
LoadEncroachment
Encraochment
Z1 set to 80% of GSU, Z2 set to 120% of GSU
Z3 set to overreach remote bus
Generator Protection Upgrade
21 – Distance
Element
21 – Distance Fault Load
Element Impendance Blinder
(for Z1 & Z2)

+X
XL
Z3

XT Z2

Z1

-R +R

-X Pow erSwing
Power Sw ing
or or
Z1 and Z2 used to trip LoadEncroachment
Load Encraochment
Z1 set to 80% of GSU, Z2 set to overreach remote bus
Z3 used for power swing blocking; Z3 blocks Z2
Generator Protection Upgrade

Generator Out-of-Step Protection (78)

ƒ Designed to cover the situation where electrical


center of power system disturbance passes
through the GSU or the generator itself.

ƒ Now is more common with modern EHV


systems where system impedance has
decreased compared to generator and GSU
impedance.
Generator Protection Upgrade
Generator Out-of-Step Protection (78)

Power Transfer

Pe = Pm
|Eg| |Es|
Pe = sin (Θg - Θs)
X

78 - Out-of-Step Protection Relay


Es - System Voltage
Eg - Generator Voltage
Θs - System Voltage Phase Angle
Θg - Generator Voltage Phase Angle
Pe - Electrical Power
Pm - Turbine (mech.) Power Pm
Generator Protection Upgrade
Generator Out-of-Step Protection (78)
Power Angle Analysis of Out-of-Step Conditions
Generator Protection Upgrade
Generator Out-of-Step Protection (78)

Power Transfer

Pe = Pm
|Eg| |Es|
Pe = sin (Θg - Θs)
X

78 - Out-of-Step Protection Relay


Es - System Voltage
Eg - Generator Voltage
Θs - System Voltage Phase Angle
Θg - Generator Voltage Phase Angle
Pe - Electrical Power
Pm - Turbine (mech.) Power Pm
Generator Protection Upgrade
Generator Out-of-Step Protection (78)
Power Angle Analysis of Out-of-Step Conditions

ƒ Reactance between generator and power system (X) is


increased beyond steady state power transfer
Generator Protection Upgrade

Generator Out-of-Step Protection (78)


ƒ When a generator goes out-of-step (synchronism)
with the power system, high levels of transient
shaft torque are developed.

ƒ If the slip frequency approaches natural shaft


frequency, torque produced can break the shaft.

ƒ High stator core end iron flux can overheat and


short the generator stator core.

ƒ GSU subjected to high transient currents and


mechanical stresses
Generator Protection Upgrade

Generator Out-of-Step Protection (78)


ƒ Positive sequence quantities used to maintain
security and accuracy over a wide frequency
range.

ƒ Must work properly from 50 to 70 Hz (60 Hz


systems).

ƒ Required to operate correctly (and not


misoperate) with wide frequency variations
possible during power swing conditions.
Generator Protection Upgrade
Abnormal Operating Conditions
ƒ 78 – Out of Step (Loss of Synchronism)
- Employs single blinder method
- Settable by study or graphical method

Unstable

Stable
Generator Protection Upgrade

Generator Out-of-Step Protection (78)


Generator Protection Upgrade

Loss of Field (40)


ƒ Generator effects
- Synchronous generator becomes induction
- Slip induced eddy currents heat rotor surface
- High reactive current drawn by generator
overloads stator
ƒ Power system effects
- Loss of reactive support
- Creates a reactive drain
- Can trigger system/area voltage collapse
ƒ May select from two methods
- Two Zone Offset Mho
ƒ GE method
- Impedance with Directional Unit
ƒ Westinghouse method
Generator Protection Upgrade

Loss of Field
GE and Westinghouse Methods

Two Zone Offset Mho Impedance w/Directional Unit


GE Westinghouse
CEH KLF
Generator Protection Upgrade

Multiple Loss-of-
Field Mho
Implementations
VAR to Better Fit
OUT
Normal Reactive
WATT
Capability
Curves
VAR Loss
IN of
Field

Generator capability curve viewed on the P-Q plane.


This info must be converted to the R-X plane.
Generator Protection Upgrade

Increased Power Out

P-Q Plane

Increased Power Out


Multiple Loss-of-Field
Mho Implementations
to Better Fit Reactive
Capability Curves
R-X Plane
Generator Protection Upgrade

Loss of Field (40)


ƒ Positive sequence quantities used to maintain security and
accuracy over a wide frequency range.
ƒ Must work properly from 50 to 70 Hz (60 Hz systems).
Required to operate correctly (and not misoperate) with wide
frequency variations possible during power swing
conditions.
ƒ May employ best of both methods to optimize coordination.
- Provide maximum coordination between machine limits,
limiters and protection
- Offset mho for Z1. Fast time for true Loss of Field event.
- Impedance with directional unit and slower time for Z2. Better
match of machine capability curve. Also able to ride through
stable swing.
- May employ voltage supervision for accelerated tripping of Z2
(slower zone) in cases of voltage collapse where machine is
part of the problem, importing VArs.
Generator Protection Upgrade
Multiple Loss-of-Field Mho Implementations
to Better Fit Reactive Capability Curves

Two Zone Offset Mho Impedance w/Directional Unit


Better ability to match capability curves after conversion from P-Q to R-X plane
Generator Protection Upgrade

Multiple Loss-of-Field Mho Implementations


to Better Fit Reactive Capability Curves

Two Zone Offset Mho Impedance w/Directional Unit


Better ability to match capability curves after conversion from P-Q to R-X plane
Generator Protection Upgrade

Negative Sequence (46)


ƒ Typically caused by open circuits in system

- Downed conductors
- Stuck poles switches and breakers

ƒ Unbalanced phase currents create negative


sequence current in generator stator

ƒ Negative sequence current interacts with


normal positive sequence current

- Induces a double frequency current, 120 Hz

ƒ Current (120 Hz) is induced into rotor causing


surface heating
Generator Protection Upgrade

Rotor End Winding Construction

Currents Flow in the Rotor Surface


Generator Protection Upgrade

Negative Sequence: Constant Withstand


ƒ Salient Pole
- With connected amortisseur 10%
- With non-connected amortisseur 5%
ƒ Cylindrical
- Indirectly 10%
- Directly cooled - to 960 MVA 8%
ƒ 961 to 1200 MVA 6%
ƒ 1200 to 1500 MVA 5%
Generator Protection Upgrade

Generator Ratings
ƒ Nameplate
- Constant Withstand
- “K” Factor
Generator Protection Upgrade

Generator
Ratings

Typical
K Values
Salient Pole
Generators
40
Synchronous
Generators
30
Generator Protection Upgrade

Negative Sequence (46)


Negative Sequence (46) Electromechanical Relays
Electromechanical Relays

ƒ Sensitivity restricted to about 60% I2 of generator


rating

ƒ Fault backup provided

ƒ Generally insensitive to load unbalances or open


conductors
Generator Protection Upgrade

Negative Sequence (46)


Negative Sequence (46) Digital Relay
Digital Relay

ƒ Protects generator down to its continuous I2


rating

ƒ Fault backup provided

ƒ Sensitive to load unbalances

ƒ Can detect open conductor conditions


Generator Protection Upgrade

Overexcitation (24)
Causes of V/HZ Problems
ƒ Generator voltage regulator problems
- Operating error during off-line manual regulator
operation
- Control failure
- VT fuse loss in voltage regulator (AVR) sensing
voltage
ƒ System problems
- Unit load rejection: full load, partial rejection
- Power system islanding during major disturbances
Generator Protection Upgrade

Overexcitation (24)
Used to protect machine against excessive V/Hz
(overfluxing)
Legacy Protection
ƒ Typically “stair-step” two definite time setpoints
ƒ Two definite time elements

- One may be used to alarm

- One may be used for high set fast trip

ƒ Either overprotects or underprotects

ƒ Instantaneous Reset
Generator Protection Upgrade

Typical Relay Characteristics for


Dual-Level, Definite-Time V/Hz Protection

Relay A set at 118% volts/Hz with a 6-second time delay


Relay B set at 110% volts/Hz with a 60-second time delay
Generator Protection Upgrade

Overexcitation (24)
Modern Protection
ƒ Definite time elements

ƒ Inverse curves

- Select curve type for best coordination to


manufacturers recommendations

- Employ settable “integrating” reset

ƒ Provides “thermal memory” for repeat events


Generator Protection Upgrade

Optimal Protection and Operational Flexibility


Is Provided by using Both Inverse-Time and
Definite-Time Relays

Relay A is a definite-time relay, set at 123% Volts/Hz with a


2-second time delay
Relay B is an inverse-time relay
Generator Protection Upgrade

Overexcitation (24)

Typical plot
using definite
time and
inverse curve
Generator Protection Upgrade

Overexcitation (24)
Modern Protection
ƒ V/Hz measurement operational range: 2-80 Hz
- Necessary to avoid damage to steam turbine generators
during rotor pre-warming at startup
- Necessary to avoid damage to converter-start gas turbine
generators at startup
- In both instances, the generator frequency during startup and
shut down can be as low as 2 Hz
- NOTE: An Overvoltage (59) function, designed to work
properly up to 120 Hz, is important for Hydro Generators
where the generators can experience high speed (high
frequency) during full load rejection. Since the V/Hz during
this condition is low, the 24 function will not operate, and the
59 function will provide proper protection
from overvoltage.
Generator Protection Upgrade

Abnormal Operating Conditions


ƒ 81 – Four Step Frequency
- Any step may be applied over- or underfrequency
- High accuracy – 1/100th Hz (0.01 Hz)
- “Scheme 2” of C37.106 coordination with System Load
Shedding
ƒ 81R – Rate of Change of Frequency
- Allows tripping on rapid frequency swing
ƒ 81A – Underfrequency Accumulator
- Time Accumulation in Six Underfrequency Bands
- Limits Total Damage over Life of Machine
ƒ Typically used to Alarm
- “Scheme 1” of C37.106
Generator Protection Upgrade

Steam Turbine Off-Frequency Operating


Limitations
60 Continuous
Frequency (Hz)

59
Restricted
58

57
Prohibited

0.001 0.01 0.10 1.0 10.0 100.0


Time (Minutes)
“Scheme 1,” Typical, from C37.106
Generator Protection Upgrade
81A – Underfrequency Accumulator
Generator Protection Upgrade

Directional Power (32F/R)


ƒ Legacy power elements may lack sensitivity for
sequential tripping

- Digital elements sensitive to 0.002 pu

- May apply 32R or 32F depending on motoring


characteristic of machine (turbine control and
valving dependent)
Generator Protection Upgrade

Directional Power (32F/R)


Generator Protection Upgrade

Inadvertent Energizing

ƒ Operating errors
ƒ Breaker head flashover
ƒ Control circuit malfunctions
ƒ Combination of above
Generator Protection Upgrade

Generator Response & Damage from


Inadvertent Energizing

ƒ Generator behaves as an induction motor

ƒ Routing flux induced into the generator rotor

ƒ Resulting rotor current is forced into negative


sequence path in rotor body
Generator Protection Upgrade
Inadvertent Energizing Scheme

Inadvertent Energizing Scheme

ƒ Undervoltage (27) supervises low-set, instant


overcurrent (50)
ƒ Pick up timer makes sure generator is dead, and
rides through 3-phase external faults
ƒ Drop out timer assures that overcurrent element
gets a chance to trip if voltage stays up during IE
event (small machine)
Generator Protection Upgrade

Generator Breaker Failure


ƒ Generator trips may not always be from high current
events (faults)

ƒ Trips may not be from overcurrent events


- Overexcitation
- Overvoltage
- Sequential tripping

ƒ Need to examine auxiliary contact status in addition


to current detection
Generator Protection Upgrade

Typical Transmission Line Breaker Failure


Generator Protection Upgrade

Generator Breaker Failure


Generator Protection Upgrade

Breaker Pole Flashover & Stuck Pole


Generator Protection Upgrade

Modified Breaker Failure Logic for


Breaker Head Flashover
Note: Current Detector (CD) must be set below flashover current.
Generator Protection Upgrade

Generator Breaker Failure


Generator Protection Upgrade

Fuse Loss
ƒ Fuse loss (loss of voltage potential) can cause
voltage sensitive elements to misoperate

- 51V, 21, 78, 32, 67, 67N, 40

ƒ Typically performed using two sets of VTs and


a voltage balance relay

ƒ Some small hydro installations may only have


one set of VTs

ƒ Use Symmetrical Component and 3-Phase


Voltage/Current methods to provide fuse loss
detection on a single VT set
Generator Protection Upgrade

Fuse Loss

One VT

Two VTs
Generator Protection Upgrade

Fuse Loss (LOP) Detection:


Symmetrical Components & 3-Phase Voltage/Current Monitoring

ƒ Use to block voltage dependent elements from misoperating


and to alarm
- Stops nuisance tripping and attendant full load rejection on LOP
ƒ 1 and 2 phase LOP detection by symmetrical component
comparison
- Presence of Negative Sequence Voltage and Negative
Sequence Current indicates a Fault
- Presence of Negative Sequence Voltage and absence of
Negative Sequence Current indicates a Fuse Loss
ƒ 3 phase LOP detected by voltage and current monitoring
- Low 3-Phase Voltages and High 3-Phase Currents indicates a
Fault
- Low 3-Phase Voltages and Low 3-Phase Current indicates a
Fuse Loss
Generator Protection Upgrade

Trip Circuit Monitoring (74TC)


+

M-3425
1
52b Status Trip Circuit
Control/Status
Monitoring Monitoring Input
Input Input 2

Other Trip Devices


52/b

Output
Contact

52/a Typically at Breaker


if 52 TC
52TC
or
86

-
Generator Protection Upgrade

74TC – Trip Circuit Monitoring


- Uses breaker auxiliary switch status and voltage from trip
circuit to determine open in trip circuit
ƒ Burned trip coil, faulty auxiliary switch, break in wiring

0=CB Open (52b closed)


1=Failure 1=Failure
1=CB Closed (52b open)
0=OK 0=OK
CI-1 52b
1=Failure (contact closes)
0
0=OK (contact opened)
&
0
CO-1 Trip Coil Failure
0=Continuity (current) 0

1=No Continuity (no current) AND TDOE,


PS to 0
CI-2 TC Current

Notes:
A) TDOE = time delay on energizing, times from PS (preset) to zero. While timing, output = 0; when timed out (at 0),
output = 1
B) TDOE default at 20 cycles, range 0-120 cycles (or more)
C) Time delay is employed to account for indeterminate breaker position as "a" and "b" contacts change state. It prevents
nuisance alarms during the transition state.
D) The control/status input used in the DC circuit accepts an external DC voltage source (versus being self-wetted).
Generator Protection Upgrade

I/O
ƒ Standard and Expanded I/O
- Standard I/O (horizontal and vertical mount)
ƒ 6 Control/Status Inputs
ƒ Breaker Trip Coil Input
ƒ 8 Control Outputs (Trip Rated)
ƒ Self diagnostic contact
ƒ Optional sync input and field ground inputs
- Expanded I/O (horizontal mount)
ƒ 14 Control/Status Inputs
ƒ Breaker Trip Coil Input
ƒ 23 Control Outputs (Trip Rated)
ƒ Self diagnostic contact
ƒ Optional sync input and field ground inputs
ƒ Ability to have many discrete outputs for alarming,
annunciating and trip voting schemes
ƒ More inputs to track plant status for event logging and
oscillography
Generator Protection Upgrade

I/O
Standard

Expanded
Generator Protection Upgrade

Interface and Analysis Software


ƒ Communications PC Software package for setpoint
interrogation / modification, metering, monitoring, and
downloading oscillographic records

ƒ Oscillographic Analysis Software package graphically


displays to facilitate analysis, and prints captured
waveforms

ƒ Both menu-driven, easy to use

ƒ Autodocumentation eliminates transcription errors


Generator Protection Upgrade

Relay Configuration
ƒ Delta-Y Transform to allow appropriate operation of
Distance (21) Elements

ƒ Any VT type, any grounding


- Open delta or 3Y
- Ground secondary on neutral or phase

ƒ Ability of the relay to derive L-L quantities from L-G


VT sources and use for voltage elements 21, 24, 27
and 59
- Prevents their operation from a VT secondary circuit
ground fault
Generator Protection Upgrade

Example:
Relay
Configuration
Generator Protection Upgrade

Example:
Element
Selection
Generator Protection Upgrade

Example:
Element
Setting
Generator Protection Upgrade
IPScom
Example:
I/O Assignment

Example:
I/O
Assignment
Generator Protection Upgrade

Example:
Settings
Summary
Generator Protection Upgrade

Programmable
Logic
Generator Protection Upgrade

Programmable
Logic
Generator Protection Upgrade

Graphic Metering and Monitoring


ƒ Metering of all measured inputs
- Measured and calculated quantities
ƒ Instrumentation grade

ƒ Commissioning and Analysis Tools


- Advanced metering
- Event logs
- Vector meters
- R-X Graphics
- Oscillograph recording
Generator Protection Upgrade
Advanced Metering
Advanced Metering
Generator Protection Upgrade
Event Log (512) Events
Generator Protection Upgrade
Pick up, drop out, trip Event Log (512 Events)
Event #, Date, Time Event Log (512) Events

Impedance,
Sync Info

Voltages

Currents

I/O Status
Generator Protection Upgrade

Event Log Trigger

Elements
trigger on
trip, drop out,
pick up

I/O triggers
on pick up,
drop out
Generator Protection Upgrade
Phasor Display (Vectors)

0.00 0.0

All Voltages and Currents Proper


Generator Protection Upgrade

Phasor Display (Vectors)

Phase A Current “Rolled”


Generator Protection Upgrade

R-X Graphics: Loss of Field (40)

Provides the ability to check settings and view testing


Generator Protection Upgrade

Oscillography
ƒ Determine if relay and circuit breaker operated
properly
- Identify relay, control or breaker problem
- Generators do experience faults / abnormal
conditions
ƒ In the machine or the system?
ƒ Speed generator’s return to service
- Identify type of testing needed
- Provide data to generator manufacturer
ƒ Gives plant engineer data to force unit off-line for
inspection
ƒ Uncovers unexpected problems
- Synchronizing, shutdown

Comtrade Format Oscillographs (*.cfg)


Record Length: 416 cycles, up to 16 records
Generator Protection Upgrade

Comtrade Format
Oscillographs
(*.cfg)
Generator Protection Upgrade

Waveform Capture (Legend)

B C D

A F

G H I K L M N
Generator Protection Upgrade

ƒ A) All analog traces. This view shows peak values. RMS values may also
be displayed
ƒ B) Controls for going to the beginning or end of a record, as well as
nudging forward or backward in time in a record
ƒ C) Zoom controls
ƒ D) Display controls for analog traces, RMS traces, fundamental waveform
display, frequency trace, power trace, power factor trace, phasor
diagram, impedance diagram and power diagram
ƒ E) Marker #1
ƒ F) Marker #2
ƒ G) Time at Marker #1
ƒ H) Time at Marker #2
ƒ I) Control status input and contact output traces (discrete I/O)
ƒ J) Scaling for each analog trace. This can be set automatically or manually
adjusted
ƒ K) Date and timestamp for record
ƒ L) Time of trip command
ƒ M) Time at Marker #1
ƒ N) Time at Marker #2
Generator Protection Upgrade

Waveform Capture (Legend)

P
Q
R
S
Generator Protection Upgrade

ƒ O) Drop down window for view selection, diagram selection


and zoom
ƒ P) Delta value between Marker #1 and Marker #2
ƒ Q) Value at Marker #1
ƒ R) Value at Marker #2
ƒ S) Scaling for each analog trace. This can be set
automatically or manually adjusted.
Generator Protection Upgrade

Waveform Capture (Phasor)

Phasor diagram with


values displayed

Phasor display shown at


at Marker #1 location

Area of current reversal


Generator Protection Upgrade

Waveform Capture (Phasor)

Phasor display shown at


at Marker #1 location

Phasor diagram with Area of current reversal


values display
Generator Protection Upgrade

Waveform Capture (Power and Impedance)

Impedance Trajectory
Over Record

Marker #1
Impedance Values
at Marker #1

Impedance Values
Marker #2 at Marker #2

Power Trajectory
Over Record

Power Value at Marker #1

Power Value at Marker #2


Generator Protection Upgrade

Waveform Capture (RMS and Power)

Marker #1

Marker #1

Power Value at Marker #1


RMS Display
Power Value at Marker #2

Power Trajectory Over Record


Power Diagram
Generator Protection Upgrade

Long Records Let You See the Issue – 416 cycles


Voltage collapse on Ph-Ph Fault

Ph-Gnd Fault

Ph-Ph Fault
3-Ph Fault

Gen feeding fault into low side of GSU, no low side breaker
Example of Ph-Gnd fault evolving into 3-Ph Fault
Insulation breakdown due to high voltage
21P backup element tripped
Generator Protection Upgrade

Communications
ƒ Communications PC Software package for setpoint
interrogation/modification, metering, monitoring, and
downloading oscillographic records

ƒ Modbus, Modbus/TCP Communications

- RS-232, RS-485, Ethernet

ƒ IRIG-B Time Synchronization


Generator Protection Upgrade

Communications
Telephony, PC at Plant, Integration
Generator Protection Upgrade

Communications
Generator Protection Upgrade
Utility System

52
Unit

87

Areas for
G
M-3425A Typical Connection Diagram VT *
50N

Targets

Upgrade
(Optional)
Integral HM I
(Optional) 25 52
VT Gen
Metering

W aveform Capture

81R 81A 81 59 27 24
IRIG-B

Front RS232
CT Areas for Upgrade
Communication
Rear Ethernet
Port (Optional) 3V o VT *
Rear RS-485
Communication
Multiple Setting M-3921
Groups +

Programmable I/O
-

Self Diagnostics 64F 64B


27

Dual Power Supply


(Optional)
CT
Breaker 78 60FL 51V 50/27 40 32 21 50 49 46
Monitoring
Trip Circuit
Monitoring

Alternate
Polarity
27 67N
TN

VT
To 87 CT
Termnal 50N 51N
27 GD
59D 59N R CTs
32
R

High-impedance Grounding with Third Low-impedance Grounding with Overcurrent


Harmonic 100% Ground Fault Protection Stator Ground Fault Protection
Generator Protection Upgrade

Summary
ƒ There are a number of serious protection
shortcomings on generators with relays older than
10 years (plants commissioned <1993)

ƒ This presentation attempted to bring those risks to


the attention of generator owners
- Utility

- IPP

- Industrial
Generator Protection Upgrade

Summary
ƒ Generator owners should address these risks
through comprehensive upgrade programs to protect
their generator investment

ƒ An upgrade will offer other benefits in addition to the


protection – Insurance Company Requirements

ƒ Multifunction digital relays are an ideal, cost effective


way to implement such a program
Generator Protection Upgrade

Generator Protection
Beckwith Electric Is Generation Security

Upgrade Tutorial
Questions
Generator Protection Upgrade

The End
Generator
Protection
Implementing Power Plant Control Logic
Scheme Logic

2005 Protection Seminar

6190-118th Avenue North – Largo, Florida 33773


www.beckwithelectric.com
Scheme Logic

January 17, 2005


Scheme Logic
M-3425A Trip Matrix Logic
I/O Point Purpose
IN1 Gen CB Status IPSLogic Functions IPS LOGIC Input(s) TDDO
IN2 86U Status 5A Trip Sequence & Governor in manaul IPS#1 Out4/Out5/Out15/Out21+ IN4
IN3 Sync Condense Status 86G Trip Sequence Initiate IPS#2 IN11
IN4 Governor in Manual 86GH Trip Sequence Initiate IPS#3 IN12 SV13
IN5 Wicket Gate at SNL 86N Trip Sequence Initiate IPS#4 IN13
IN7 Exciter Low Level 86NH Trip Sequence Initiate IPS#5 IN14 SV14
IN8 Sync Condense Status Trip Gen CB + Wicket Gate IPS#6 OUT16 + IN5 OUT16 contact Seal-in time set at desire time delay
IN11 86G Trip Sequence Initiate
IN12 86GH Trip Sequence Initiate
IN13 86N Trip Sequence Initiate
IN14 86NH Trip Sequence Initiate

TRIP#1 /Arm Fire Prot. TRIP#2 / Arm Fire Prot. TRIP#3 SV13T SV14T
Supervised by 60FL 60FL 60FL+27 32+IN7 27+IN4 IN3 27+IN3
21 24-2 40-1&2 40-2 59-1 59-2 87-1/2 IPS#1 IPS#2 59N-1&2 27TN-1&2 81-1 IPS#4 32-1 78 46-2 81-2 25 IPS#3 IPS#5 IPS#6
Out1 Arm Fire Prot. X, X X, X X, X
Out2 Arm Fire Prot. X, X X, X X, X
Out3 Test point
Out4 PML Alarm X X X X
Out5 UCC PLC X X X X
Out6 BF Initiate X X X X X X X X X X X X X X
Out7 BF Initiate X
Out8 Trip Gen CB X
Out9 Trip Field CB X
Out10 Close PIV X
Out11 Trip 86U X X X X X X X X X X X X X X X
Out12 Trip Gen CB X X X X X X X X X X X X X X
Out14 Trip Field CB X X X X X X X X X
Out15 De Excite X X X X
Out16 IPSLogic#6 X X X X X
Out17
Out10 X
Out18
Out19
Out20 Block TIV X X
Out21 PAM PLC X X X X
Out22 Sync Check X

Seal-In Logic IPSLogic#1 IPSLogic#2


IN4 IN11 Output(s)
ARM Fire Protection Block TIV
Contacts Latch Out4 AND Output(s)
or use TDDO
Out5
Seal-in Seal-in Seal-in OR IPSLogic#4
1 - 8160 1 - 8160 1 - 8160 Out15
cycles cycles cycles
IN13 Output(s)
Out21

Out1 Out2 Out20

86U

IPSLogic#3 IPSLogic#6
IN12 TDDO Output(s) IN15
AND Output(s)
Seal-in Out16
BC Hydro application requires Seal-in of the ARM Fire Protection and Block TIV trip outputs.
Out1,Out2 and Out20 have output contact seal-in setting time of 1 - 8160 cycles. IPSLogic#5
IN14 TDDO Output(s)
Scheme Logic

Customer Scheme Inputs

Customer BECO
Input Input Description/Purpose
IN102 IN1 Gen CB Status
IN101 IN2 86U Status
IN103 IN3 Sync Condense Status
IN104 IN4 Governor in Manual
IN205 IN5 Wicket Gate at SNL
IN207 IN7 Exciter Low Level
IN8 Sync Condense Status
IN201 IN11 86G Trip Sequence Initiate
IN202 IN12 86GH Trip Sequence Initiate
IN203 IN13 86N Trip Sequence Initiate
IN204 IN14 86NH Trip Sequence Initiate
Scheme Logic

Customer Scheme Outputs

Customer BECO
Output Output Purpose
Out101 Out1 Arm Fire Prot.
Out102 Out2 Arm Fire Prot.
Out103 Out3 Test point
Out104 Out4 PML Alarm
Out105 Out5 UCC PLC
Out106 Out6 BF Initiate
Out201 Out11 Trip 86U
Out202 Out12 Trip Gen CB
Out204 Out14 Trip Field CB
Out205 Out15 De Excite
Out16 IPSLogic#6
Out207 Out17 Close PIV
Out210 Out20 Block TIV
Out211 Out21 PAM PLC
Out212 Out22 Sync Check
Scheme Logic

Customer Scheme Trip #3


TRIP#3
Supervised by IN3 27+IN8
32-1 78 46-2 81-2
Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
Out3 Test point
Out4 PML Alarm X X X X
Out5 UCC PLC X X X X
Out6 BF Initiate X X X X
Out11 Trip 86U
Out12 Trip Gen CB X X X X
Out14 Trip Field CB
Out15 De Excite X X X X
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC X X X X
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #3


TRIP#3
Customer Logic IN3 27+IN8
32PIT 32-1 78 46-2 81-2
AND
IN103

TRIP3
OOST OR
4602T

27B81P X X X X
AND
81D2T AND X X X X
X X X X
IN103

BECO Logic X X X X
32-1
AND
IN3
X X X X
78 OR TRIP3

46-2

27
AND
81-2 AND
X X X X
IN8
Scheme Logic

Customer Scheme Trip #3


TRIP#3
BECO Logic IN3 27+IN8
32-1 32-1 78 46-2 81-2
AND
IN3

78 OR TRIP3

46-2

27 X X X X
AND
81-2 AND X X X X
X X X X
IN8

Input Contact Activation State X X X X

IN11 IN3 IN8 X X X X


IN3 active IN8 active
contact closed contact open

Sync Condenser Status


X X X X
Scheme Logic

Customer Scheme Trip #3

BECO Input Contact Logic

IN3 active
when closed

IN8 active
when open
Scheme Logic

Customer Scheme Trip #3 (32-1)


Supervised by IN3
BECO Logic 32-1
32-1
TRIP3
Out1 Arm Fire Prot.
AND
IN3 OR
Out2 Arm Fire Prot.
Out3 Test point
Out4 PML Alarm X
IN3
Out5 UCC PLC X
Out6 BF Initiate X
Out11 Trip 86U
Out12 Trip Gen CB X
Out14 Trip Field CB
Out15 De Excite X
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC X
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #3 (81-2)


Supervised by 27+IN3
BECO Logic 81-2
27-1
AND
TRIP3 Out1 Arm Fire Prot.
AND OR
81-2
Out2 Arm Fire Prot.
IN8
Out3 Test point
Out4 PML Alarm X
Out5 UCC PLC X
Out6 BF Initiate X
Out11 Trip 86U
Out12 Trip Gen CB X
Out14 Trip Field CB
IN8 Out15 De Excite X
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC X

81 function internal cutoff voltage is 5-15V Out22 Sync Check


Scheme Logic

Customer Scheme Trip #3 (81-2)

81 Function Cutoff Voltage

20
Cutoff Voltage

15
10
5
0
0 10 20 30 40 50 60 70
Frequency

81 function internal cutoff voltage is 5-15V


Scheme Logic

Customer Scheme Trip #1

TRIP#1/Arm Fire Prot


Supervised by 60FL 60FL 60FL+27
21 24-2 40-1&2 40-2 59-1 59-2 87-1/2 IPS#1 IPS#2
Out1 Arm Fire Prot. X, X
Out2 Arm Fire Prot. X, X
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate X X X X X X X X X
Out11 Trip 86U X X X X X X X X X
Out12 Trip Gen CB X X X X X X X X X
Out14 Trip Field CB X X X X X X X X X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #1 (40-1)


Supervised by 60FL
60LOP
AND AND
TRIP1 40-1
40Z1T
Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
60FL 40-1
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate X
Out11 Trip 86U X
Out12 Trip Gen CB X
Out14 Trip Field CB X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #1 (40-2)


Supervised by 60FL+27
60LFL
AND T1 40-2
40-2 TRIP1
60LFL
OR Out1 Arm Fire Prot.
40-2 AND
T2 Out2 Arm Fire Prot.
27 Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate X
Out11 Trip 86U X
40-2
Out12 Trip Gen CB X
Out14 Trip Field CB X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Voltage
Control Out21 PAM PLC
Output Out22 Sync Check
Scheme Logic

Customer Scheme Trip #1 (IPS#2)


Customer Logic TRIP1
IN11 OR
IPSLogic#2
IN11 Output(s)
Supervised by
IPSLogic#2 IPS#2
Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate X
Out11 Trip 86U X
Out12 Trip Gen CB X
Out14 Trip Field CB X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme SV13T (IPS#3)


Customer Logic
SV13T
IN12
TDDO
IPSLogic#3
86U
IN12 TDDO Output(s) SV13T
Supervised by
IPSLogic#3 IPS#3
Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
Out3 Test point
Out4 PML Alarm

Out5 UCC PLC


Out6 BF Initiate X
Out11 Trip 86U X
Out12 Trip Gen CB X
Out14 Trip Field CB X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV X
Out20 Block TIV X
Out21 PAM PLC
Dropout Time Delay Out22 Sync Check
Scheme Logic

Customer Scheme SV14T (IPS#5)


Customer Logic
SV14T
IN14
TDDO
IPSLogic#5
86U
IN14 TDDO Output(s)
SV14T
Supervised by
IPSLogic#5 IPS#5
Out1 Arm Fire Prot.
OR Out2 Arm Fire Prot.
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate
Out11 Trip 86U X
Out12 Trip Gen CB
Out14 Trip Field CB
Out15 De Excite
Out16 IPSLogic#6 X
Out17 Close PIV X
Out20 Block TIV X
Out21 PAM PLC
Dropout Time Delay Out22 Sync Check
Scheme Logic

Customer Scheme Trip #1 (IPS#1)


Customer Logic
IPSLogic#1 Trip#3
IN4 TRIP1
AND
Out4 AND Output(s)
IN4
Out5
OR
Out15
Out21 Supervised by

IPS#1
IPSLogic#1 Initiating Outputs Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
Initiating Inputs Out3 Test point
Out4 PML Alarm
AND
Out5 UCC PLC
Out6 BF Initiate X
Out11 Trip 86U X
Out12 Trip Gen CB X
Out14 Trip Field CB X
Out15 De Excite
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #2

TRIP#2 / Arm Fire Prot.


Supervised by 32+IN7 27+IN4
59N-1/2 27TN-1&2 81-1 IPS#4
Out1 Arm Fire Prot. X, X X, X
Out2 Arm Fire Prot. X, X X, X
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate
Out11 Trip 86U X X X X
Out12 Trip Gen CB
Out14 Trip Field CB
Out15 De Excite
Out16 IPSLogic#6 X X X X
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #2

Customer Logic TRIP#2 / Arm Fire Prot.


64G1T
32+IN7 27+IN4
64G2T
TRIP2 59N-1/2 27TN-1&2 81-1 IPS#4
32P2T AND OR
X, X X, X
IN207
X, X X, X
27B81P
AND
81D1T AND

IN104

IN203

X X X X
BECO Logic
59N1

27TN
TRIP2
32P2T AND OR

IN7 X X X X
27

81-1 AND

IN4

IN13 IPSlogic#4
Scheme Logic

Customer Scheme Trip #2 (27TN)


BECO Logic
27TN
32 Supervision TRIP2
32-2 AND OR

IN7

Supervised by 32+IN7
27TN-1&2
Out1 Arm Fire Prot. X
Out2 Arm Fire Prot. X
Out3 Test point
Out4 PML Alarm
Out5 UCC PLC
Out6 BF Initiate
Out11 Trip 86U X
Out12 Trip Gen CB
Out14 Trip Field CB
Out15 De Excite
X
Out16 IPSLogic#6
Out17 Close PIV
Out20 Block TIV
Out21 PAM PLC
Out22 Sync Check
Scheme Logic

Customer Scheme Trip #2 (Arm Fire)

Customer Logic
Seal-in Circuit
87U
Arm Fire Supervised by
87R Protection 32+IN7
OR
59N-1&2 27TN-1&2
64G1
Out1 Arm Fire Prot. X, X X, X
64G2 Out2 Arm Fire Prot. X, X X, X
AND
32P2T AND IN101 Out3 Test point
IN207 Out4 PML Alarm

Out5 UCC PLC


BECO Logic
Out6 BF Initiate
87U2
AND Out11 Trip 86U X X

IN2 Arm Fire Out12 Trip Gen CB


Protection Out14 Trip Field CB
AND OR Out15 De Excite
59N2
Out16 IPSLogic#6 X X
27TN2 Out17 Close PIV
Latching Outputs
32 Out20 Block TIV
AND or time delayed dropout
IN7 1 to 8160 cycles Out21 PAM PLC
Out22 Sync Check
IN2
Scheme Logic

Customer Scheme Block TIV

Customer Logic
Seal-in Circuit
SV13T SV14T
SV13T
Block TIV Supervised by
OR
SV14T IPS#3 IPS#5
Out1 Arm Fire Prot.
Out2 Arm Fire Prot.
AND
IN101
Out3 Test point
Out4 PML Alarm

Out5 UCC PLC


BECO Logic
Out6 BF Initiate X
Out11 Trip 86U X X
IPS#3 Block TIV Out12 Trip Gen CB X
OR Out14 Trip Field CB X
IPS#5
Out20 86U Out15 De Excite
Out16 IPSLogic#6 X
Out17 Close PIV X X
Out20 Block TIV X X
Latching Output
Out21 PAM PLC
or time delayed dropou
Out22 Sync Check
1 to 8160 cycles
Scheme Logic

Customer Scheme Trip 86U

Customer Logic Supervised by


Trip1

IN201 Out1 Arm Fire Prot.


Out2 Arm Fire Prot.
IN202 86U
OR Out3 Test point
Trip2
Out4 PML Alarm
IN203 Out5 UCC PLC
IN204 Out6 BF Initiate
Out11 Trip 86U
BECO Logic
Trip1 Out12 Trip Gen CB
IPS#1 Out14 Trip Field CB

IPS#2 Out15 De Excite


Out16 IPSLogic#6
IPS#3 86U
OR Out17 Close PIV
Trip2 Out20 Block TIV
IPS#4 Out21 PAM PLC

IPS#5 Out22 Sync Check


Scheme Logic

Customer Scheme Trip 86U

Customer Logic Supervised by


Trip1

IN201 Out1 Arm Fire Prot.


Out2 Arm Fire Prot.
IN202 86U
OR Out3 Test point
Trip2
Out4 PML Alarm
IN203 Out5 UCC PLC
IN204 Out6 BF Initiate
Out11 Trip 86U
BECO Logic
Trip1 Out12 Trip Gen CB
IPS#1 Out14 Trip Field CB

IPS#2 Out15 De Excite


Out16 IPSLogic#6
IPS#3 86U
OR Out17 Close PIV
Trip2 Out20 Block TIV
IPS#4 Out21 PAM PLC

IPS#5 Out22 Sync Check


Scheme Logic

Customer Scheme Trip Gen Breaker

Customer Logic Trip1

SV13T

Trip3
Trip2 Trip Gen
Breaker
SV14T OR SV7DO OR
AND
BFI
IN205
AND

Trip1
BECO Logic
SV13T

Trip3

OUT16 TDDO IPSLogic#6 Trip Gen


Trip2
1 - 8160 ~
Breaker
IPS#5 OR OR
AND
BFI
IN5
Scheme Logic

Customer Scheme IPSLogic #6


IPSLogic#6

OUT16 TDDO
1 - 8160 ~
Outputs Supervised by
AND
IPS#6
IN5
Arm Fire Prot.

Seal in time Arm Fire Prot.


Test point
PML Alarm
UCC PLC
BF Initiate X
Trip 86U
Trip Gen CB X
Trip Field CB
De Excite
IPSLogic#6
Close PIV
Block TIV
PAM PLC
Sync Check
Scheme Logic

THE END
000
2
1:
d
re
0
te
90

g is
Re
IS O

BECKWITH ELECTRIC CO., INC.


6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A.
Phone: (727) 544-2326 • Fax: (727) 546-0121
E-mail: marketing@beckwithelectric.com
Web Site: www.beckwithelectric.com

© 2005 Beckwith Electric Co.


Printed in U.S.A.

Você também pode gostar