***SAUDI ARAMCO PRODUCT SPECIFICATION*** NUMBER: A-120


ISSUE DATE: 03/10/98
REPLACE: 08/06/95
DRY GAS PAGE NO.: 1 of 2
_____________________________________________________________________________________________

TEST GUARANTEE METHOD

High Heating Value (HHV),


Min 930 (34.6) ASTM D-3588
BTU/SCF (MJ/CM)

Hydrogen Sulfide, grains/100 GAS CHROMATOGRAPH


Max 1 (35)
SCF (grains/100 CM) ASTM D-4084

Total Sulfur, grains/100 SCF ASTM D-2784 or ASTM D-


Max 20 (706)
(grains/100 CM) 4468

Moisture, lb/MMSCF
Max 7 (112) ASTM D-1142
(kg/MMCM)

USER TECHNICAL DATA

1. The Dry Gas Specification, A-120 will be the governing document at all times.

2. The attached table is only intended to give dry gas users expected values under variable
operational conditions and shall not be construed as SAUDI ARAMCO guarantees.
Upsets and other abnormal operations can cause the Dry Gas composition and sulfur
content to vary.
_____________________________________________________________________________________________

***SAUDI ARAMCO PRODUCT SPECIFICATION*** NUMBER: A-120


ISSUE DATE: 03/10/98
REPLACE: 08/06/95
DRY GAS PAGE NO.: 2 of 2
_____________________________________________________________________________________________

a. The normal composition of the Shedgum and Uthmaniyah dry gas supply will be between
the two compositions shown below. The composition varies with the level of Ethane
recovery at the gas plants and percentage of Khuff gas (high nitrogen) in the feed.

SHEDGUM AND UTHMANIYAH GAS PLANTS DRY GAS

Nitrogen 0.5 Mole % 12.0 Mole %


Methane 80.7 Mole % 82.7 Mole %
Ethane 16.0 Mole % 5.0 Mole %
Propane 2.8 Mole % 0.3 Mole %
Total > > > 100.0 Mole % 100.0 Mole %

Hydrogen Sulfide Less than 2 ppm Less than 2 ppm


Other Sulfur Compounds NIL NIL
HHV (at 14.696 psia) 1170 BTU/SCF (44 MkJ/CM) 930 BTU/SCF (35 MkJ/CM)

b. The normal range in composition of the Berri Gas Plant dry gas is expected to be as
stated below:

BERRI GAS PLANTS DRY GAS

Nitrogen/CO2 0.5 Mole % 2.9 Mole %


Methane 66.5 Mole % 79.2 Mole %
Ethane 30.0 Mole % 17.2 Mole %
Propane 3.0 Mole % 0.7 Mole %
Total > > > 100.0 Mole % 100.0 Mole %

Hydrogen Sulfide Less than 2 ppm


Other Sulfur Compounds Less than 5 ppm
HHV (at 14.696 psia) 1280 BTU/SCF (48 MkJ/CM) 1120 BTU/SCF (42 MkJ/CM)

c. The maximum temperature of dry gas is 150 deg. Fahrenheit (65 deg. Celcius)
d. The minimum pressure of Dry Gas is 300 psig (2070 kPa) for all Industries, except
SWCC-Khobar where the minimum pressure is 540 psig (3720 kPa).