Electrical network protection

Sepam Series 80
Configuration

Sepam label: ........................................................................... Feeder +L01


Application type: .................................................................... M81
Configuration file: .................................................................. +L01
Date of last modification: ...................................................... 29-Oct-2018
Date printed: ........................................................................... 29-Oct-2018

Customer: ...............................................................................
Project: ....................................................................................
Switchboard: ...........................................................................
Cubicle: ...................................................................................
Contents

1. GENERAL SETTINGS .......................................................................................................................................... 4


1.1. Hardware setup ....................................................................................................................................... 4
1.2. General characteristics ............................................................................................................................ 4
1.3. CT-VT sensors ........................................................................................................................................ 5
1.4. CT/VT circuit supervision ......................................................................................................................... 6
1.5. Particular characteristics .......................................................................................................................... 7
1.6. Predefined control logic ........................................................................................................................... 7
1.7. Logic input/output assignment ................................................................................................................. 8
2. SET PROTECTIONS ............................................................................................................................................ 9
2.1. Motor M81 .............................................................................................................................................. 9
2.2. Protection units on ................................................................................................................................... 9
2.3. Customized tripping curve ....................................................................................................................... 10
2.4. 50/51: Phase overcurrent ........................................................................................................................ 10
2.5. 50N/51N: Ground fault ............................................................................................................................. 11
2.6. 50BF: Breaker failure ............................................................................................................................... 11
2.7. 46: Negative sequence current / unbalance ............................................................................................. 11
2.8. 49RMS: Thermal overload ....................................................................................................................... 12
2.9. 67N: Directional ground fault ................................................................................................................... 12
2.10. 32P: Active overpower ........................................................................................................................... 12
2.11. 32Q: Reactive overpower ...................................................................................................................... 13
2.12. 37: Phase undercurrent ......................................................................................................................... 13
2.13. 48/51LR: Excessive starting time and locked rotor ................................................................................ 13
2.14. 66: Starts per hour ................................................................................................................................. 13
2.15. 40: Field loss ......................................................................................................................................... 13
2.16. 78PS: Pole slip ...................................................................................................................................... 13
2.17. 12: Overspeed ....................................................................................................................................... 14
2.18. 14: Underspeed ..................................................................................................................................... 14
2.19. 27D: Positive sequence undervoltage .................................................................................................... 14
2.20. 27R: Remanent undervoltage ................................................................................................................ 14
2.21. 27: Undervoltage ................................................................................................................................... 15
2.22. 59: Overvoltage ..................................................................................................................................... 15
2.23. 59N: Neutral voltage displacement ........................................................................................................ 15
2.24. 47: Negative sequence overvoltage ....................................................................................................... 15
2.25. 81H: Overfrequency ............................................................................................................................... 16
2.26. 81L: Underfrequency ............................................................................................................................. 16
2.27. 38/49T: Temperature monitoring ............................................................................................................ 16
3. LOGIPAM SETTINGS ........................................................................................................................................... 17
3.1. Logipam ................................................................................................................................................... 17
4. DEFINITION OF EQUATIONS .............................................................................................................................. 18
4.1. Logic equations ....................................................................................................................................... 18
5. SET CONTROL MATRIX ...................................................................................................................................... 19
5.1. Protection matrix ...................................................................................................................................... 19
5.2. Control logic output matrix ....................................................................................................................... 24
5.3. Logic input matrix .................................................................................................................................... 25
5.4. Logic equation output variable matrix ...................................................................................................... 25
5.5. GOOSE input matrix ................................................................................................................................ 27
6. SET FUNCTIONS ................................................................................................................................................. 28
6.1. Fault recording ......................................................................................................................................... 28
6.2. Edit singleline diagram ............................................................................................................................. 28
6.3. Motor start report (MSR) .......................................................................................................................... 29
6.4. DLG ......................................................................................................................................................... 30
1. GENERAL SETTINGS

1.1. Hardware setup

Sepam label: .................................................................................................................................................................................. Feeder +L01 Application type: M81 Model: Mimic-based UMI
MES120 (14 input + 6 output module) n°1 .................................................................................................................................... Present
MES120 (14 input + 6 output module) n°2 .................................................................................................................................... Absent
MES120 (14 input + 6 output module) n°3 .................................................................................................................................... Absent
MSA141 (1 analog output module) ................................................................................................................................................ Absent
MET148 (8 temperature sensors module) n°1 .............................................................................................................................. Absent
MET148 (8 temperature sensors module) n°2 .............................................................................................................................. Absent
ACE 949/959/937 (communication network interface) n°1 .......................................................................................................... Present Communication protocol Modbus Sepam address 1
Speed 19200 Bauds Parity Even
Unsecured
COM2 module ................................................................................................................................................................................ Absent
ACE 850 (communication network interface) (Ethernet) ............................................................................................................. Absent
Memory Cartridge Type: ................................................................................................................................................................ MMS

1.2. General characteristics

Description Setting Description Setting


Network frequency 60 Hz Sepam working language UKEng-IEC
Main/feeder ANSI M/Fdr Time synchronization mode None
Phase rotation direction a_b_c Control voltage monitoring (Vaux) Off
Active setting group for all protection functions. Setting group A Rated Vaux 48 Vdc
Remote protection settings enabled No Low threshold alarm 80 % Vaux
Remote control with select before operate (SBO) No High threshold alarm 120 % Vaux
Demand Interval 5 min Cumulative breaking current alarm threshold 65535 (kA)²
Meter increment - Active energy 0.1 kWh
Meter increment - Reactive energy 0.1 kVARh
Temperatures C

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 4 / 30
1.3. CT-VT sensors

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 5 / 30
1.4. CT/VT circuit supervision

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 6 / 30
1.5. Particular characteristics

Motor speed
Rated speed (Rpm) 3000 rpm Zero speed threshold 5%
Pulses per rotation 1 Rated active Power 17.819 MW

Total inertia
Moment (J) 10000 kg.m2
Constant (H) 108.711 sec

Reactance
Synchronous reactance (Xd) 200 %
Synchronous reactance (Xq) 120 %
Transient react ance (X'd) 20 %

1.6. Predefined control logic

Description Setting
Switchgear control Circuit breaker
Zone selective interlocking No
Logic discrimination Acceleration No
Load shedding No
Time delay 0 ms
Restart No
Time delay 0 ms
Max. dip duration 300 s
Unlock logic discrimination time 200 ms

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 7 / 30
1.7. Logic input/output assignment

Used Charact. Pulse Used Charact. Pulse


O1 Yes NO O101 No
O2 Yes NC O102 No
O3 Yes NO O103 No
O4 No O104 No
O5 Yes NC O105 No
O106 No

Logic input Neg Latch


I101 Breaker closed
I102 Breaker open
I103 ------- (Not used) -----------
I104 ------- (Not used) -----------
I105 ------- (Not used) -----------
I106 ------- (Not used) -----------
I107 ------- (Not used) -----------
I108 ------- (Not used) -----------
I109 ------- (Not used) -----------
I110 ------- (Not used) -----------
I111 ------- (Not used) -----------
I112 ------- (Not used) -----------
I113 ------- (Not used) -----------
I114 ------- (Not used) -----------

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 8 / 30
2. SET PROTECTIONS

2.1. Motor M81

2.2. Protection units on

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 9 / 30
2.3. Customized tripping curve

1 2
I/Is 1.00 10.00
T(s) 1.00 1.00

2.4. 50/51: Phase overcurrent

Measurement Settings
Unit Activity Latching Trip C.B. Confirmation Group
origin Tripping curve Threshold Delay Icc min. H2 Timer hold curve Timer hold
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
1 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
2 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
3 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
4 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms

Restraint H2 threshold : 17

A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms


5 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
6 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
7 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
8 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms

Restraint H2 threshold : 17

Sepam label: Feeder +L01 29-Oct-2018


Application type: M81 10 / 30