TH-404
TH-404, 0808
Sid 1
pH-Transmitter
TH-404
Mjk Automation AB
Box 105
661 23 SÄFFLE
Tel. 0533-177 50
Fax 0533-138 11
E-post kontoret@mjk.se
www.mjk.se
TH-404, 0808
Sid 2
TH-404, 0808
Sid 3
Innehåll
1. Allmänt ........................................................................................................................... 5
2. Mått ................................................................................................................................. 6
3. Montage alternativ .......................................................................................................... 7
4. Elektrisk inkoppling ........................................................................................................ 8
5. Inställning ....................................................................................................................... 9
Meny ............................................................................................................................... 9
Inställningar pH-mätning .............................................................................................. 10
Kontroll pH–mätning .................................................................................................... 18
Kalibrering pH-mätning ................................................................................................ 20
Drift pH–mätning .......................................................................................................... 22
6. Modbus kommunikationsprotokoll ............................................................................... 23
TH-404, 0808
Sid 4
1. Allmänt
1 Frontpanel i ABS
2 Alfanumerisk display, 2 rader med 16 tecken
3 3 tryckknappar för inställningar:
<ESCAPE> = Backa ett steg i menyn för varje tryck. Håll intryckt cirka 5 sekunder
för att lämna mätläget.
<SELECT> = Val av det alternativ som blinkar.
<ENTER> = Bekräfta det som valts.
4 Kabelgenomföringar 4 × 3/8"
5 Aluminium hus
6 Monteringsbeslag för vägg, montage på 2" rör eller panelmontage.
TH-404, 0808
Sid 5
2. Mått
TH-404, 0808
Sid 6
3. Montage alternativ
TH-404, 0808
Sid 7
4. Elektrisk inkoppling
TH-404, 0808
Sid 8
5. Inställning
OBS!: Varje gång som symbolerna ”<” och ”>” syns i displayen så innebär detta att aktuellt
värde kan ändras, uppåt eller neråt.
För att öka värdet tryck <SELECT> till dess att ”>” blinkar, sedan trycks <ENTER> och där
efter kan värdet ökas genom att trycka <SELECT> varje tryck ökar värdet med en enhet. När
önskat värde är uppnått sparas detta genom att trycka <ENTER>.
Inställningen kan avbrytas genom att trycka på <ESCAPE> innan värdet sparas.
För att minska värdet tryck <SELECT> till dess att ”<” blinkar, sedan <ENTER> och värdet
kommer att minskas genom tryck på <SELECT>.
Meny
För att komma in i huvudmenyn tryck <ESCAPE> och håll intryckt tills att displayen visar:
men det går lika bra att fortsätta från detta läge, om inte funktionssättet skall ändras mellan
pH och mV.
Välj funktion med <SELECT>, funktionen som blinkar väljs sedan genom att trycka
<ENTER>.
<Set Up> kräver lösenord och detta är som standard att <SELECT>, <ENTER>, <ESCAPE>
trycks i den ordningen.
1. Status indikering
2. Uppmätt värde (pH eller mV)
3. Referens temperatur som är vald
4. Uppmätt temperatur om temperaturgivare finns ansluten (visas ej om bargarf är valt)
5. Status för kontakter eller bargraf
TH-404, 0808
Sid 9
Inställningar pH-mätning
Texter markerade med fetstil i följande displaybilder symboliserar att denna text blinkar i
instrumentets display. För att ändra tryck <SELECT> och genomför val genom att trycka
<ENTER>.
TH-404, 0808
Sid 10
pH-mätaren kan återställas till
ursprungskalibreringen. Välj Ja och bekräfta
så kommer mätaren att återgå till
fabriksinställningarna. Detta kan vara
användbart om det inte finns någon annan
möjlighet att kalibrera.
Elektrod typ
Glas Antimon
Se
Sid 12
TH-404, 0808
Sid 11
Välj referenstemperatur genom att trycka
<SELECT> till dess att önskad temperatur
(20 eller 25°C) blinkar. Bekräfta valet med
<ENTER>.
Kalibreringspunkt för Antimon elektrod.
Om glaselektrod är valt
alternativ blinkar och bekräfta med
<ENTER>.
TH-404, 0808
Sid 12
Inställning av min och max-värden för
bargrafens visningsområde.
Se sid 15
Endast tillämplig om speciell
självrengörande elektrod används. Skall
normalt vara NEJ.
TH-404, 0808
Sid 13
Inställning av signalens beteende när
pH-mätaren sätts i stand-by läge. Möjliga
val är På, Av eller HOLD.
Se sid 15
Funktion hos kontakt S2 kan väljas som
larmkontakt, regulator eller rengörning.
TH-404, 0808
Sid 14
Val om mA-signalen skall konfigureras.
Se sid 16
mA-utgången kan stängas av helt om den
inte skall användas.
TH-404, 0808
Sid 15
Val om utgående mA-signal skall
kalibreras.
Val av paritet.
TH-404, 0808
Sid 16
Möjlighet att ställa instrumentets id-
nummer i nätverket, maximalt 256
instrument.
TH-404, 0808
Sid 17
Kontroll pH–mätning
Med denna funktion kan elektrodens kondition kontrolleras
Texter markerade med fetstil i följande displaybilder symboliserar att denna text blinkar i
instrumentets display. För att ändra tryck <SELECT> och genomför val genom att trycka
<ENTER>.
TH-404, 0808
Sid 18
TH-404, 0808
Sid 19
Kalibrering pH-mätning
Texter markerade med fetstil i följande displaybilder symboliserar att denna text blinkar i
instrumentets display. För att ändra tryck <SELECT> och genomför val genom att trycka
<ENTER>.
Tryck <ENTER>
TH-404, 0808
Sid 20
pH mätare kalibrerar nu mot pH 7 och
strecken i displayens övre rad fylls på under
tiden
Kalibreringen klar
Skölj elektroden.
När elektroden är sköljd tryck <ENTER>
TH-404, 0808
Sid 21
Drift pH–mätning
Texter markerade med fetstil i följande displaybilder symboliserar att denna text blinkar i
instrumentets display. För att ändra tryck <SELECT> och genomför val genom att trycka
<ENTER>.
Håll <ESCAPE> intryckt ca 5 sekunder till dess att
displayen ser ut som det visas till höger.
Tryck <ENTER>
Tryck <SELECT> till dess att Matning blinkar.
Välj genom att trycka <ENTER>.
OK Elektrodproblem Temp.-givarproblem
TH-404, 0808
Sid 22
6. Modbus kommunikationsprotokoll
Address Variable Type Funct. Description Configuration Unit R/W
0x0100 Condition Byte pH Set-Point 1 On = 0x00 Off = 0x01 -- R/W
0x0101 Condition Byte pH Set-Point 2 On = 0x00 Off = 0x01 -- R/W
0x0102 Condition Byte pH Set-Point 3 On = 0x00 Off = 0x01 -- R/W
0x0103 Condition Byte mV Set-Point 1 On = 0x00 Off = 0x01 -- R/W
0x0104 Condition Byte mV Set-Point 2 On = 0x00 Off = 0x01 -- R/W
0x0105 Condition Byte mV Set-Point 3 On = 0x00 Off = 0x01 -- R/W
0x0106 Condition Byte Sb(pH) Set-Point 1 On = 0x00 Off = 0x01 -- R/W
0x0107 Condition Byte Sb(pH) Set-Point 2 On = 0x00 Off = 0x01 -- R/W
0x0108 Condition Byte Sb(pH) Set-Point 3 On = 0x00 Off = 0x01 -- R/W
0x0109 Configuration Byte pH Set-Point 1 Alarm = 0x00 PWM = 0x01 -- R/W
0x010A Configuration Byte pH Set-Point 2 Alarm = 0x00 PWM = 0x01 Cleaning = 0x02 p/TH404 -- R/W
0x010B Configuration Byte pH Set-Point 3 --- --- Cleaning = 0x02 p/TH401 -- R/W
0x010C Configuration Byte mV Set-Point 1 Alarm = 0x00 PWM = 0x01 -- R/W
0x010D Configuration Byte mV Set-Point 2 Alarm = 0x00 PWM = 0x01 Cleaning = 0x02 p/TH404 -- R/W
0x010E Configuration Byte mV Set-Point 3 --- --- Cleaning = 0x02 p/TH401 -- R/W
0x010F Configuration Byte Sb(pH) Set-Point 1 Alarm = 0x00 PWM = 0x01 -- R/W
0x0110 Configuration Byte Sb(pH) Set-Point 2 Alarm = 0x00 PWM = 0x01 Cleaning = 0x02 p/TH404 -- R/W
0x0111 Configuration Byte Sb(pH) Set-Point 3 --- --- Cleaning = 0x02 p/TH401 -- R/W
0x0112 Action Byte pH Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0113 Action Byte pH Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x0114 Action Byte mV Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0115 Action Byte mV Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x0116 Action Byte Sb(pH) Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0117 Action Byte Sb(pH) Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x0118 Burn-Out Byte pH Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
TH-404, 0808
Sid 23
Address Variable Type Funct. Description Configuration Unit R/W
0x0119 Burn-Out Byte pH Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x011A Burn-Out Byte mV Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x011B Burn-Out Byte mV Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x011C Burn-Out Byte Sb(pH) Set-Point 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x011D Burn-Out Byte Sb(pH) Set-Point 2 Direct = 0x00 Reverse = 0x01 -- R/W
0x011E Unit Byte pH Set-Point 1 pH = 0x00 -- R
0x011F Unit Byte pH Set-Point 2 pH = 0x00 -- R
0x0120 Unit Byte mV Set-Point 1 mV = 0x01 -- R
0x0121 Unit Byte mV Set-Point 2 mV = 0x01 -- R
0x0122 Unit Byte Sb(pH) Set-Point 1 pH = 0x00 -- R
0x0123 Unit Byte Sb(pH) Set-Point 2 pH = 0x00 -- R
0x0150 Proportional Band Word pH Set-Point 1 Min = 0 Max = 1000 % R/W
0x0152 Proportional Band Word pH Set-Point 2 Min = 0 Max = 1000 % R/W
0x0154 Proportional Band Word mV Set-Point 1 Min = 0 Max = 1000 % R/W
0x0156 Proportional Band Word mV Set-Point 2 Min = 0 Max = 1000 % R/W
0x0158 Proportional Band Word Sb(pH) Set-Point 1 Min = 0 Max = 1000 % R/W
0x015A Proportional Band Word Sb(pH) Set-Point 2 Min = 0 Max = 1000 % R/W
0x015C Períod Word pH Set-Point 1 Min = 1 Max = 1000 s R/W
0x015E Períod Word pH Set-Point 2 Min = 1 Max = 1000 s R/W
0x0160 Períod Word mV Set-Point 1 Min = 1 Max = 1000 s R/W
0x0162 Períod Word mV Set-Point 2 Min = 1 Max = 1000 s R/W
0x0164 Períod Word Sb(pH) Set-Point 1 Min = 1 Max = 1000 s R/W
0x0166 Períod Word Sb(pH) Set-Point 2 Min = 1 Max = 1000 s R/W
0x0168 Cleaning Interval Word -- Set-Point 2/3 Min = 0 Max = 120 SP2-TH404 SP3-TH401 h R/W
0x016A Cleaning Time Word -- Set-Point 2/3 Min = 5 Max = 1000 SP2-TH404 SP3-TH401 s R/W
0x0200 Value float pH Set-Point 1 Min = 2 Max = 20 pH R/W
0x0204 Value float pH Set-Point 2 Min = 2 Max = 20 pH R/W
TH-404, 0808
Sid 24
Address Variable Type Funct. Description Configuration Unit R/W
0x0208 Value float mV Set-Point 1 Min = -2000 Máx = 2000 mV R/W
0x020C Value float mV Set-Point 2 Min = -2000 Máx = 2000 mV R/W
0x0210 Value float Sb(pH) Set-Point 1 Min = 2 Max = 14 pH R/W
0x0214 Value float Sb(pH) Set-Point 2 Min = 2 Max = 14 pH R/W
0x0218 Hystereses float pH Set-Point 1 Min = -2 Max = 20 pH R/W
0x021C Hystereses float pH Set-Point 2 Min = -2 Max = 20 pH R/W
0x0220 Hystereses float mV Set-Point 1 Min = -2000 Max = 2000 mV R/W
0x0224 Hystereses float mV Set-Point 2 Min = -2000 Max = 2000 mV R/W
0x0228 Hystereses float Sb(pH) Set-Point 1 Min = 2 Max = 14 pH R/W
0x022C Hystereses float Sb(pH) Set-Point 2 Min = 2 Max = 14 pH R/W
0x0300 Condition Byte pH mA 1 On = 0x00 Off = 0x01 -- R/W
0x0301 Condition Byte pH mA 2 (TH401) On = 0x00 Off = 0x01 -- R/W
0x0302 Condition Byte mV mA 1 On = 0x00 Off = 0x01 -- R/W
0x0303 Condition Byte mV mA 2 (TH401) On = 0x00 Off = 0x01 -- R/W
0x0304 Condition Byte Sb(pH) mA 1 On = 0x00 Off = 0x01 -- R/W
0x0305 Condition Byte Sb(pH) mA 2 (TH401) On = 0x00 Off = 0x01 -- R/W
0x0306 Configuration Byte pH mA 1 Transmission = 0x00 Control = 0x01 -- R/W
0x0307 Configuration Byte pH mA 2 (TH401) Transmission = 0x00 Control = 0x01 -- R/W
0x0308 Configuration Byte mV mA 1 Transmission = 0x00 Control = 0x01 -- R/W
0x0309 Configuration Byte mV mA 2 (TH401) Transmission = 0x00 Control = 0x01 -- R/W
0x030A Configuration Byte Sb(pH) mA 1 Transmission = 0x00 Control = 0x01 -- R/W
0x030B Configuration Byte Sb(pH) mA 2 (TH401) Transmission = 0x00 Control = 0x01 -- R/W
0x030C Action Byte pH mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x030D Action Byte pH mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x030E Action Byte mV mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x030F Action Byte mV mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x0310 Action Byte Sb(pH) mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
TH-404, 0808
Sid 25
Address Variable Type Funct. Description Configuration Unit R/W
0x0311 Action Byte Sb(pH) mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x0312 Burn-Out Byte pH mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0313 Burn-Out Byte pH mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x0314 Burn-Out Byte mV mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0315 Burn-Out Byte mV mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x0316 Burn-Out Byte Sb(pH) mA 1 Direct = 0x00 Reverse = 0x01 -- R/W
0x0317 Burn-Out Byte Sb(pH) mA 2 (TH401) Direct = 0x00 Reverse = 0x01 -- R/W
0x0318 Unit Byte pH mA 1 pH = 0x00 -- R
0x0319 Unit Byte pH mA 2 (TH401) pH = 0x00 °C = 0x02 -- R
0x031A Unit Byte mV mA 1 mV = 0x01 -- R
0x031B Unit Byte mV mA 2 (TH401) mV = 0x01 °C = 0x02 -- R
0x031C Unit Byte Sb(pH) mA 1 pH = 0x00 -- R
0x031D Unit Byte Sb(pH) mA 2 (TH401) pH = 0x00 °C = 0x02 -- R
0x0350 Proportional Band Word pH mA 1 Min = 0 Max = 1000 % R/W
0x0352 Proportional Band Word pH mA 2 (TH401) Min = 0 Max = 1000 % R/W
0x0354 Proportional Band Word mV mA 1 Min = 0 Max = 1000 % R/W
0x0356 Proportional Band Word mV mA 2 (TH401) Min = 0 Max = 1000 % R/W
0x0358 Proportional Band Word Sb(pH) mA 1 Min = 0 Max = 1000 % R/W
0x035A Proportional Band Word Sb(pH) mA 2 (TH401) Min = 0 Max = 1000 % R/W
0x035C Rate Word pH mA 1 Min = 0 Max = 1000 s R/W
0x035E Rate Word pH mA 2 (TH401) Min = 0 Max = 1000 s R/W
0x0360 Rate Word mV mA 1 Min = 0 Max = 1000 s R/W
0x0362 Rate Word mV mA 2 (TH401) Min = 0 Max = 1000 s R/W
0x0364 Rate Word Sb(pH) mA 1 Min = 0 Max = 1000 s R/W
0x0366 Rate Word Sb(pH) mA 2 (TH401) Min = 0 Max = 1000 s R/W
0x0368 Reset Word pH mA 1 Min = 0 Max = 1000 s R/W
0x036A Reset Word pH mA 2 (TH401) Min = 0 Max = 1000 s R/W
TH-404, 0808
Sid 26
Address Variable Type Funct. Description Configuration Unit R/W
0x036C Reset Word mV mA 1 Min = 0 Max = 1000 s R/W
0x036E Reset Word mV mA 2 (TH401) Min = 0 Max = 1000 s R/W
0x0370 Reset Word Sb(pH) mA 1 Min = 0 Max = 1000 s R/W
0x0372 Reset Word Sb(pH) mA 2 (TH401) Min = 0 Max = 1000 s R/W
0x0400 Value 4mA float pH mA 1 Min = 2 Max = 20 pH R/W
0x0404 Value 4mA float pH mA 2 (TH401) Min = 2 Max = 20 pH R/W
0x0408 Value 4mA float mV mA 1 Min = -2000 Max = 2000 mV R/W
0x040C Value 4mA float mV mA 2 (TH401) Min = -2000 Max = 2000 mV R/W
0x0410 Value 4mA float Sb(pH) mA 1 Min = 2 Max = 14 pH R/W
0x0414 Value 4mA float Sb(pH) mA 2 (TH401) Min = 2 Max = 14 pH R/W
0x0418 Value 20mA float pH mA 1 Mín = -2 Max = 20 pH R/W
0x041C Value 20mA float pH mA 2 (TH401) Mín = -2 Max = 20 pH R/W
0x0420 Value 20mA float mV mA 1 Min = -2000 Max = 2000 mV R/W
0x0424 Value 20mA float mV mA 2 (TH401) Min = -2000 Max = 2000 mV R/W
0x0428 Value 20mA float Sb(pH) mA 1 Min = 2 Max = 14 pH R/W
0x042C Value 20mA float Sb(pH) mA 2 (TH401) Min = 2 Max = 14 pH R/W
0x0430 Value SP float pH mA 1 Min = 2 Max = 20 pH R/W
0x0434 Value SP float pH mA 2 (TH401) Min = 2 Max = 20 pH R/W
0x0438 Value SP float mV mA 1 Min = -2000 Max = 2000 mV R/W
0x043C Value SP float mV mA 2 (TH401) Min = -2000 Max = 2000 mV R/W
0x0440 Value SP float Sb(pH) mA 1 Min = 2 Max = 14 pH R/W
0x0444 Value SP float Sb(pH) mA 2 (TH401) Min = 2 Max = 14 pH R/W
0x0448 Value I maintenance float pH mA 1 Min = -2 Max = 20 pH R/W
0x044C Value I maintenance float pH mA 2 (TH401) Min = -2 Max = 20 pH R/W
0x0450 Value I maintenance float mV mA 1 Min = -2000 Max = 2000 mV R/W
0x0454 Value I maintenance float mV mA 2 (TH401) Min = -2000 Max = 2000 mV R/W
0x0458 Value I maintenance float Sb(pH) mA 1 Min = 2 Max = 14 pH R/W
TH-404, 0808
Sid 27
Address Variable Type Funct. Description Configuration Unit R/W
0x045C Value I maintenance float Sb(pH) mA 2 (TH401) Min = 2 Max = 14 pH R/W
0x0500 Main Unit Byte -- Read pH = 0x00 mV = 0x01 pH = 0x00 -- R
0x0550 Principal float -- Read -- R
0x0554 Secondary float -- Read mV R
0x0558 Temperature float -- Read °C R
0x055C Current float -- Read - mA2 mA R
0x0560 Current float -- Read - mA2 Only for TH401 mA R
TH-404, 0808
Sid 28