CM5X0E general magnetic flux vector control inverter user manual

CONTENTS

PREFACE ................................................................................................................................................................ 3
CHAPTER1 SAFE AND NOTICE ...................................................................................................................... 5

1.1 SECURITY MATTERS .................................................................... 5


1.2 NOTICE ............................................................................ 6
CHAPTER2 PRODUCT INFORMATION ........................................................................................................ 8

2.1 NAMING RULES ....................................................................... 8


2.2 NAMEPLATES ......................................................................... 8
2.3 CM5X0 SERIES INVERTER (X REPRESENTS 3 OR 8) ............................................ 9
2.4 SPECIFICATION ...................................................................... 10
2.5 PRODUCTS SHAPE, SIZE AND MOUNTING HOLES .............................................. 13
2.6 OPTIONAL ACCESSORIES ............................................................... 20
2.7 THE DAILY MAINTENANCE AND MAINTENANCE OF THE CONVERTER ............................... 20
2.8 THE INVERTER'S WARRANTY: ............................................................ 21
2.9 SELECTION GUIDE ................................................................... 21
2.10 BRAKE COMPONENT SELECTION GUIDE ................................................... 22
CHAPTER3 INSTALLATION OF MECHANICS AND ELECTRONICS .................................................... 26

3.1 MECHANICS INSTALLATION ............................................................. 26


3.2 INSTALLATION OF ELECTRONICS ......................................................... 30
CHAPTER4 OPERATION AND DISPLAY ........................................................................................................ 44

4.1 PERATION AND DISPLAY INTERFACE INTRODUCTION ........................................... 44


4.2FUNCTION CODE VIEW, MODIFY METHOD ................................................... 46
4.3THE CHECK METHOD OF PARAMETERS’ MONITORING .......................................... 46
4.4PASSWORD .......................................................................... 46
4.5 MOTOR PARAMETER AUTOMATIC TUNING STEPS .............................................. 49
CHAPTER 5 PARAMETER DESCRIPTION ................................................................................................. 50

5.1 F0 THE BASIC FUNCTIONAL GROUP ....................................................... 50


5.2 F1GROUP START-STOP CONTROL ......................................................... 56
5.3 V/F CONTROLS PARAMETER OF F2 GROUP .................................................. 60
5.4 F3 GROUP VECTOR CONTROL PARAMETERS ................................................. 63
5.5 F4 SET MOTOR PARAMETERS ............................................................ 66
5.6 F5 GROUP OF INPUT TERMINALS ......................................................... 67
5.7 INPUT TERMINAL OF F6 GROUP .......................................................... 75
5.8 F7 GROUP AUXILIARY FUNCTION AND USER-MACHINE INTERFACE FUNCTION ........................ 78
5.9 F8 GROUP COMMUNICATION FUNCTION .................................................... 84
5.10 F9 GROUP FAULT AND PROTECTION ...................................................... 86
5.11 FA GROUP PROCESS CONTROLLING PID FUNCTION ........................................... 88
5.12 FB GROUP PENDULUM FREQUENCY FUNCTION .............................................. 93
5.13 FC GROUP MULTISTAGE SPEED FUNCTION AND SIMPLE PLC FUNCTION ........................... 94
5.14 FD GROUP TORQUE CONTROLLING PARAMETERS ............................................ 98
5.15 FE GROUP FUNCTION ENHANCEMENT ................................................... 100
CHAPTER 6 ELECTROMAGNETIC COMPATIBILITY ............................................................................. 102

1
CM5X0E general magnetic flux vector control inverter user manual

6.1 DEFINITION ........................................................................ 102


6.2 EMC STANDARD INTRODUCTION ....................................................... 102
6.3 EMC GUIDANCE .................................................................... 102
CHAPTER7 TROUBLESHOOTING AND COUNTERMEASURES ......................................................... 104

7.1 FAULT ALARM AND COUNTERMEASURES .................................................. 104


7.2 THE COMMON FAULTS AND PROCESSING METHODS .......................................... 106
CHAPTER8 CM5X0E SERIES INVERTER SERIAL COMMUNICATION PROTOCOL ......................... 108

8.1 THE CONTENTS OF THE AGREEMENT ..................................................... 108


8.2 APPLICATION MODE .................................................................. 108
8.3 BUS STRUCTURE .................................................................... 108
8.4 PROTOCOL SPECIFICATION ............................................................. 108
8.5 COMMUNICATION FRAME STRUCTURE .................................................... 108
8.6 PARITY (CRC CHECK WAY) ............................................................ 112
8.7 COMMANDS AND STATUS .............................................................. 113
APPENDIX A:FUNCTION PARAMETER TABLE ......................................................................................... 115

APPENDIX B:CARD SPECIFICATION ....................................................................................................... 143

2
CM5X0E general magnetic flux vector control inverter user manual preface

Preface

First of all thank you for purchasing our company’s completely independent development products of CM series
magnetic flux vector control frequency converter.
In CM series inverter adopts modular design to satisfy customers under the premise of general requirements, by
extending the design flexibility to meet the individual needs of customers, industry demands, represents the
application of frequency converter in the future industry trends.Built-in universal extension interface and powerful
speed control and torque control, the process of practical simple closed loop control, PLC, flexible input/output
terminals, pulse frequency, power and stop given the parameter selection, the frequency of a given storage channels
and run the command bound, advocate complementary given control, frequency control, the speed tracking,
encoder break line monitoring, fault self-recovery, built-in brake unit, 28 kinds of fault monitoring, as many as 16
segment multistage speed control, parameter copy, etc.Meeting the requirements of all kinds of complex high
precision transmission, and at the same time it has great value for equipment manufacturing industry customers
with high integration integration solutions to reducethe system cost, to improve the system reliability.
We provide two seed modules for users to choose, namely CM530E function module and CM580E function
modules, modular design, on behalf of the inverter development direction in the future.The difference between
them are shown in table 1:
TABLE1 THE DIFFERENCE BETWEEN THE function MODULES OF CM530E AND CM580E

CM580E:high-performance modular
CM530E:general magnetic flux vector
magnetic flux vector control frequency
control frequency converter
converter
one of the seven DI input for high-speed pulse input
2、double-road AI input, current voltage is optional
INPUT/OUTPUT 3、double-road relay output
TERMINALS 4、simple-road open collector output
5、simple-road high speed pulse output
6、double-road AO output
The open-loop flux vector 1
The open-loop flux vector 2 The open-loop flux vector 1
V/F The open-loop flux vector 2
CONTROLING mode The closed-loop flux vector (additional V/F
purchase of PG card) Open loop torque The closed-loop flux vector (additional
The closed loop torque (additional purchase of PG card)
purchase of PG card)
Control motor Ac asynchronous motor Ac asynchronous motor

Industry-specific
Y Y
module extensions
The I/O expansion
Y Y
card
PG Card Y Y

Fixed-length control Y Y

Modbus communication (485 standard)


Communication
Profibus DP (extension) by extending the Modbus communication (485 standard)
function
card
Two sets of motor
parameter switch Y N
function

3
CM5X0E general magnetic flux vector control inverter user manual preface

Magnetic flux vector control is the traditional voltage vector control,and the advantage of the current vector
control mainly embodies the following aspects:
1, large start torque: 0.5 Hz, 180% rated torque (open-loop flux vector control);
2, excellent weak magnetic control algorithm, the realization of high performance high speed control;
3, the precise speed control precision: open-loop flux vector control: plus or minus 0.5% or less (rated synchronous
speed)
The closed-loop flux vector control plus or minus 0.2% or less (rated synchronous speed);
4, more stable speed control stability: open-loop flux vector control: plus or minus 0.3% or less (rated synchronous
speed)
The closed-loop flux vector control plus or minus 0.1% or less (rated synchronous speed);
The torque response of 5, faster performance: 40 ms or less (open-loop flux vector control)
20 ms or less (closed-loop flux vector control).
This manual for CM530, CM530E, CM580 and CM580E inverter operation instruction manual, which USES
CM530E standard is introduced.
This manual provides the user selection, installation, parameter setting, the scene debugging, fault diagnosis and
daily maintenance and the maintenance of the relevant matters needing attention and the instruction.For proper use
of this series of frequency converter, please read this manual carefully in advance, and please keep for later
use.Equipment supporting the customer to send this manual with the equipment to the end user, please.

When unpacking, please confirm carefully:


1, whether the machine types and frequency converter of the nameplate rating in accordance with your orders.You
order machine, product certification, in the user manual and warranty.
2, the product in the process of transportation is to see if there is any breakage phenomenon;If it has some kind of
missing or damaged, please contact with the company or your supplier.
For the first time use:
For first-time users of this product, you should read this manual first.If the functions and performance are of some
doubts, please consult our technical support staff, in order to obtain help, which is good for the correct use of this
product.
Due to the continuous improvement of frequency converter,if the information
provided by the company has any change, it has been without prior notice.

CM series inverter is in accordance with the following international standards, and some products have passed CE
certification;
IEC/EN61800-5-1:2003 adjustable speed electric drive system safety requirements;
IEC/EN61800-3 2004 adjustable speed electric drive system, the third part: the electromagnetic compatibility
product standard and its specific test method.

4
CM5X0E general magnetic flux vector control inverter user manual safe and notice

Chapter1 SAFE AND NOTICE

Security definition:
In this manual, safety precautions in the following two categories:
! Danger
Because there is a risk of violation operation caused by breaking the rules, it may result in serious injury
and even death
! Caution
Because there is a risk of violation operation caused by breaking the rules,it can lead to moderate
damage or injuries, and the situation of the equipment damage

1.1 security matters

1.1.1 before installation:


! Danger
1.If there has damage of the inverter and the lack of a frequency converter, please do not use, there is a risk of
injury.
2. Please use the above class B insulation of the motor, or get an electric shock risk.
! Danger
1.1.2 when installation:

1. Please install on the metal objects such as flame retardant, away from combustible material.Otherwise may
cause a fire!
! Caution
2.When two or more frequency converter on the same case, please pay attention to the installation location (see
chapter 3 mechanical and electrical installation), and ensure that the cooling effect.
3. You Can't let the wire head or screw off into the converter.Otherwise may cause damage of frequency
converter.

1.1.3 when wiring:


! Danger
1.It Should be by professional electrical engineering construction, or get an electric shock risk!
2.It Must have a circuit breaker separated inverter and power supply, otherwise may fire!
3. Please confirm the power before wiring in the off state, otherwise there is risk of electric shock!
4.grounding terminals must be reliable grounding, or get an electric shock risk.
! Caution
5.Inputing the power cord can not be connected to the output U, V, W, or cause the inverter damaged!
6.Ensure that matchs line meet EMC requirements and safety standards of the region, the wire line diameter
advice, please refer to the manual or accident may occur!
7.Braking resistance cannot directly connect to dc bus (+), (-) terminal, otherwise may cause a fire!

1.1.4 before power on:


! Danger
1. Please confirm whether the power supply voltage level and frequency converter rated voltage is consistent,
the connection position of input, output, whether it is right, and pay attention to check whether there is a short
circuit in the peripheral circuit, the line is fastening, otherwise may cause damage of frequency converter.
2.The inverter must be on the cover plate to electricity, or may cause electric shock!

5
CM5X0E general magnetic flux vector control inverter user manual safe and notice

! Danger
3. The frequency converter don't have to withstand voltage test,because this factory product has done testing,
otherwise may cause accident!
4. If all peripheral accessories according to the manual provided by the circuit wiring correctly, otherwise may
cause accident!

1.1.5 after power on:


! Danger
1.Don't open the cover after power on, otherwise there is risk of electric shock!
2.Do not use wet hand to touch inverter and peripheral circuit, or get an electric shock risk!
3.Don't touch the inverter terminals (including control terminal), or get an electric shock risk!
4.At the beginning of electricity, inverter automatic external high voltage test, safety loop at this point, please
don't touch the inverter terminals U, V, W or motor terminal blocks, or get an electric shock risk!
! Caution
5.If the parameter identification is required, please pay attention to the motor rotation in the risk of injury,
otherwise may cause accident!
6.Please do not arbitrarily change the inverter parameters, otherwise may cause equipment damage!

1.1.6 In the operation :


! Danger
1.If you choose to restart function, please do not close to the mechanical equipment, otherwise may cause
personal injury!
2. Do not touch the cooling fan and discharge resistance to test temperature, otherwise may cause burns!
3. Professional technology personnel do not signal detection in operation, otherwise may cause personal injury
or equipment damage.
! Caution
4.In the operation of the inverter, avoid something fall into the equipment, or equipment damage caused by!
5. Do not use contact on-off method to control frequency converter of rev. Stop, or cause equipment damage!

1.1.7 when maintenance:


1.Please do not charged to repair and maintenance of equipment, or there is a risk of contact!
2. Confirm on inverter frequency converter charge lights to maintenance and repair, or residual charge on the
capacitor harm the people!
3. No trained staff do not implement repair and maintenance for the inverter, or cause personal injury or
equipment damage.

1.2 NOTICE

1.2.1 motor insulation inspection


Motor in the first use, after a long period of time before use, and regular inspection, should make motor
insulation inspection, prevent damage to the frequency converter for motor winding insulation failure.Insulation
inspection must separate motor attachment from the frequency converter, the recommended 500 v voltage
megohmmeter, should guarantee the measured insulation resistance is not less than 5MΩ.

1.2.2 motor thermal protection


If choose the motor and inverter rated capacity does not match, especially when the rated power is greater than
the motor rated power, be sure to adjust the frequency converter motor protection within the relevant parameter
values or in front of the motor is equipped with thermal relay protection for the motor.

1.2.3 operation above power frequency


This converter can provide 0 ~ 400 hz output frequency.If the customer need to operate in more than 50 hz,
please consider the affordability of mechanical device.

1.2.4 The vibration of mechanical device


Some output frequency inverter in the place, may encounter the mechanical resonance point of load device, can
6
CM5X0E general magnetic flux vector control inverter user manual safe and notice

be set up by frequency converter in jumping frequency parameters to avoid.

1.2.5 about motor heat and noise


For the inverter output voltage is PWM waves, contain certain harmonic, therefore the rise of temperature of the
motor, noise and vibration compared to run the power frequency will increase slightly.

1.2.6 output side with pressure-sensitive devices or improve the condition of the power factor of the
capacitance
Inverter output PWM wave, the output side such as the installation have or to improve the power factor, such as
thunder with varistor easy cause instantaneous over-current and even damage the inverter frequency converter,
please do not use.

1.2.7 inverter input, output the contactor switch devices, etc


adding contact between power supply and frequency converter input is not allowed to use the start-stop
contactor to control frequency converter.Must need to use the contactor control frequency converter and
stopping time, interval of not less than an hour.Frequent charging and discharging is easy to reduce the service
life of the capacitor in the inverter.If output with contactor switch device, such as between motor and shall
ensure to the output of the inverter in the absence of on-off operation, otherwise easy to cause the inside of the
inverter modules.

1.2.8 The use of rated voltage values


Not suitable for outside the allowed working voltage range stipulated in the manual use CM series inverter, easy
to cause the inside of the frequency converter device.If you need, please use the corresponding device to step-up
or step-down transformer.

1.2.9 three-phase input into two phase


Do not change the CM series three-phase inverter to use two phase, otherwise will lead to failure or damage of
the inverter.

1.2.10 lightning Impact protection


This series of frequency converter with a lightning over current protection device, the induction lightning has
certain ability of self-protection.For frequent lightning place customers should also be in inverter front add
protection.

1.2.11 altitude and derating use


More than 1000 meters in elevation areas, due to thin air heat dissipation effect of variation of frequency
converter, it is necessary to use derating.The situation, please consult my company technical.

1.2.12 some special usages


If the customers use this manual provided by outside wiring diagram of recommendations, such as common dc
bus, please consult our company.

1.2.13 Pay attention to when inverter is abandoned


Main circuit of the electrolytic capacitors and electrolytic capacitors on the PCB burnt may explode, plastic
burned, and will produce toxic gases, so treat them as industrial wastes, please.

1.2.14 about adaptation motor


1) standard adapter motor as quadrupole squirrel-cage asynchronous induction motor, if not please make
sure the motor by the motor rated current equipped with frequency converter.If need to drive permanent
magnet synchronous motor, please consult our company;
2) the frequency conversion motor cooling fan and the rotor shaft is coaxial connection, reduced speed when
the fan cooling effect is reduced, therefore, should be equipped with strong exhaust fan motor overheating
occasions or replacement for the frequency conversion motor;
3) inverter has built-in adaptation motor standard parameters, according to actual circumstances, there is a
need for motor parameter identification or modify the default to conform to the actual value as far as
possible, otherwise it will affect the running effect and protection performance;
4) converter due to cable or motor internal short circuit will call the police, even Fried machine, therefore,
please first to the initial installation of motor and cable insulation short circuit test, also need to often in daily
maintenance for this test.Note: to do the test times will inverter and the part under test all broken.

7
CM5X0E general magnetic flux vector control inverter user manual product information

Chapter2 product information

2.1 naming rules

CM5X0 A X 4T 4R0 G / 5R5 P B


变频器系列
Inverter Series
X代表3或8
Model
机型
Design edition A G:Gerneral Type
G:通用型
设计版本A
Design edition B P:Fan Pump Type
P:风机水泵型
设计版本B
Design edition C
设计版本C
…… Brake Unit
内置制动单元
款机箱
B:Including Brake Unit
B:内置制动单元
0: On behalf of 5300:代表530
chassis models
空:无 NULL:None
1: On behalf of 530E 款机箱
chassis models
1:代表530E

Voltage
电压等级Level
2S:Single Phase 110V
2S:单相110V
3S:Single Phase 220V
3S:单相220V 适配电机功率
Adaptable Motor Power
3T:Three Phase 220V
3T:三相220V 标识:
Mark: R75R75 1R51R5 …… 011 015
1.5 …… 11 15
4T:三相380V
4T:Three Phase 380V Motor PowerKW 0.75 1.5
7T:三相690V
电机功率(KW)0.75
7T:Three Phase 690V
……
Map2-1naming rules

2.2 nameplates

Barcode

Map2-2nameplates
Table above represents 530E 2.2KW universal converter ,4.0KW FRENIC-VP

8
CM5X0E general magnetic flux vector control inverter user manual product information

2.3 CM5X0 series inverter (X represents 3 or 8)

Table2-1 CM5X0E Inverter models and technical data

Fit electrical
Input current Output current
Inverter models Input Voltage machine
(A) (A)
(kW)

R4GB 5.4 2.3 0.4


CM5X0 R75GB Single 220V 8.2 4.0 0.75
- phase:
xx3S 1R5GB -15%~20% 14.0 7.0 1.5

2R2GB 23.0 9.6 2.2

R75GB 3.4 2.1 0.75


1R5GB/2R2P
5.0/5.8 3.8/5.1 1.5/2.2
B
2R2GB/4R0P
5.8/10.5 5.1/9.0 2.2/4.0
B
4R0GB/5R5P
10.5/14.6 9.0/13.0 4.0/5.5
B
5R5GB/7R5P
14.6/20.5 13.0/17.0 5.5/7.5
B
7R5GB/9R0P
20.5/22.0 17.0/20.0 7.5/9.0
B Triple 380V
9R0GB/011P Phase:
CM5X0 22.0/26.0 20.0/25.0 9.0/11.0
B -15%~20%
- 011GB/015P
xx4T 26.0/35.0 25.0/32.0 11.0/15.0
B
015GB/018P
35.0/38.5 32.0/37.0 15.0/18.5
B
018G/022P 38.5/46.5 37.0/45.0 18.5/22.0

022G/030P 46.5/62.0 45.0/60.0 22.0/30.0

030G/037P 62.0/76.0 60.0/75.0 30.0/37.0

037G/045P 76.0/92.0 75.0/90.0 37.0/45.0

045G/055P 92.0/113.0 90.0/110.0 45.0/55.0

055G/075P 113.0/157.0 110.0/152.0 55.0/75.0

075G/093P 157.0/180.0 152.0/176.0 75.0/93.0

093G/110P 180.0/214.0 176.0/210.0 93.0/110.0


CM5X0
- 110G/132P 214.0/256.0 210.0/253.0 110.0/132.0
Triple 380V
xx4T
phase:
132G/160P -15%~20% 256.0/307.0 253.0/304.0 132.0/160.0

9
CM5X0E general magnetic flux vector control inverter user manual product information

Fit electrical
Input current Output current
Inverter models Input Voltage machine
(A) (A)
(kW)
160G/185P 307.0/345.0 304.0/340.0 160.0/185.0

185G/200P 345.0/385.0 340.0/380.0 185.0/200.0

200G/220P 385.0/430.0 380.0/426.0 200.0/220.0

220G/250P 430.0/468.0 426.0/465.0 220.0/250.0

250G/280P 468.0/525.0 465.0/520.0 250.0/280.0

280G/315P 525.0/590.0 520.0/585.0 280.0/315.0

315G/355P 590.0/665.0 585.0/650.0 315.0/355.0

355G/400P 665.0/785.0 650.0/725.0 355.0/400.0

400G/450P 785.0/883.0 725.0/820.0 400.0/450.0

450G/500P 883.0/920.0 820.0/900.0 450.0/500.0

500G/550P 920.0/1020.0 900.0/1000.0 500.0/550.0

550G/630P 1020.0/1120.0 1000.0/1100.0 550.0/630.0

630G 1120.0 1100.0 630.0

2.4 specification

Table 2-2 CM5X0 Inverter technology specification

Items Specification
The highest
400Hz
frequency
1K~15kHZ;According to the load characteristic, automatically adjust the
Carrier
frequency carrier frequency.
Major Input frequency resolution
Input frequency Digital setting:0.01Hz
resolution Simulation setting:The highest frequency×0.1%
Control
Open loop flux vector control 1, open loop flux vector control 2, V/F control,
The control
Closed-loop speed open-loop torque, the closed loop torque, the torque control
mode
CM580 and CM580E only
performance
G type machine: 0.5 Hz / 180% (open-loop flux vector control)
Starting torque P type machine: 0.5 Hz / 120% (open-loop flux vector control)
G type machine: 0 hz / 180% (closed-loop flux vector)

10
CM5X0E general magnetic flux vector control inverter user manual product information

Items Specification

Speed range 1:200(open-loop flux vector control)1:1000(closed-loop flux vector)

Steady speed
precision Open-loop flux vector control :≤±0.5%(rated synchronous speed )
(speed control Closed-loop flux vector control :≤±0.2%(rated synchronous speed )
precision)

Speed control Open-loop flux vector control:≤±0.3%(rated synchronous speed )


stability Closed-loop flux vector control:≤±0.1%(rated synchronous speed )

The torque ≤40ms (Open-loop flux vector control)


response ≤20ms (Closed-loop flux vector control)

G-machine:150% rated current up to 60 seconds;180% of the rated current


Overload for 5 seconds
capacity P-machine:120% rated current up to 60 seconds;150% of the rated current for
5 seconds

Torque increase Automatic torque increase;Manual torque increase 0.1%~30.0%

V/F curve Three ways: linear model, multipoint, square type V/F curve

Deceleration A straight line or S curve deceleration mode, four kinds of deceleration time
curve Deceleration time range 0.0 s to 3000.0 s
Dc brake frequency: 0.0 Hz ~ maximum frequency
DC brake Braking time: 0.0 ~ 36.0 seconds, braking action current value: 0.0% ~
100.0%
Inching frequency range: 0.00 Hz ~ 50.00 Hz;Deceleration time at 0.0 s to
Inching control
3000.0 s
Simple PLC,
Through the built-in PLC or control terminal realizing at most 16 paraMap
multistage speed
speed operation
operation

Built-in PID Easy to realize process control closed loop control system

Automatic
When grid voltage change, can automatically maintain a constant output
voltage
voltage
regulation (AVR)
"Excavator" characteristics, the torque limit automatically during running,
Torque limit and
prevent frequent over-current trip;The torque control closed-loop vector
control
model is achieved

Peripheral
It can realize the electricity of peripheral equipment safety inspection such as
security
Personal grounding, short circuit, etc
self-check on
Common dc bus function
electricity

Common dc bus Can realize the function of the frequency converter common dc bus more

11
CM5X0E general magnetic flux vector control inverter user manual product information

Items Specification

function

JOG Key Programmable keys: positive &negative operation/inching operation function

Textile frequency
A variety of triangular wave frequency control function
control
function
Fast current Built-in current limiting algorithm quickly can reduce probability of
limiting function frequency converter to flow and enhance the anti-interference ability

Timing control Timing control function: set time range 0 h ~ 65535 h

Keyboard
extension cord Customers can use the standard Internet cable to extend the keyboard.
standardization

Run the
Three channels: the operation panel, control terminals given given, serial
command
communication is given.it can switch through a variety of ways
channel

A total of 10 kinds of frequency source: digital, analog voltage given,


Frequency source simulation given current is given, and a given pulse, given a serial port.Can
switch through a variety of ways
Auxiliary Ten kinds of auxiliary frequency source.Flexible realization of auxiliary
Operation frequency source frequency tuning and frequency synthesis
Five digital input terminals, compatible active PNP and NPN input mode
The input Two analog inputs, including AI1 can only be used as the input voltage, AI2
terminals can make input voltage or current.(such as extending the input, the output
terminal function, please choose CM580E series)

A digital output terminals (bipolar output)


Two relay output terminals
The output
An analog output terminals, respectively optional 0/4 ma ~ 20 ma or.two
terminals
survivors v ~ 10 v, which can realize a set frequency, output frequency, speed
and other physical quantities of output

LED Display Display parameters

Display LCD Dispaly Optional parts, Chinese/English instructions


and
keyboard Parameters
Using parameters copy special keyboard can achieve rapid replication
operation copy

Key lock and Implement part or all of the key lock, define the scope of some buttons, in
selection function order to prevent wrong operation
Electric motor on the short circuit test, input and output phase protection,
Protection
Protection over-current protection, overvoltage protection, under-voltage protection,
And
function overheating protection, overload protection, etc
Options
options

12
CM5X0E general magnetic flux vector control inverter user manual product information

Items Specification

options The LCD operation panel, brake components, etc

Indoor, is not subject to direct sunlight, no dust, corrosive gas, combustible


Using occasions
gas, oil mist, steam, water, or salt, etc

The altitude Below 1000 m

The environment - 10 ℃ ~ + 40 ℃ (in 40 ℃ to 50 ℃, environment temperature using the lower


temperature it)

Environment humidity Less than 95% RH, no water condense

vibration Less than 5.9 m/s 2 (0.6 g)

Storage
-20℃~+60℃
temperature

Pollution levels 2

The product
Product IEC61800-5-1:2007
safety standards

Standards The product


IEC61800-3:2005
EMC standards

2.5 products shape, size and mounting holes

2.5.1 the shape of products:

Map 2-3 Inverter appearance and parts

13
CM5X0E general magnetic flux vector control inverter user manual product information

2.5.2 The dimensions and mounting holes:

Map 2-4 7.5KW and lower

Map 2-4 9.0Kw-93.0Kw

14
CM5X0E general magnetic flux vector control inverter user manual product information

Map 2-6 110-400KW

Map2-7 450-630KW

15
CM5X0E general magnetic flux vector control inverter user manual product information

Table2-3 Installation hole location and dimension Table(X represents Table 3or8)

Shape And Size Installation Holes


Aperture
The Inverter Types W D
H (mm) A (mm) B (mm) (mm)
(mm) (mm)

R4GB

R75GB
CM5X0-A3S
1R5GB

2R2GB
223 148 166 135 207 φ5.4
R75GB

1R5GB/2R2PB

2R2GB/4R0PB

4R0GB/5R5PB

5R5GB/7R5PB
238 162 171 150 226 φ5.4
7R5GB/9R0PB

9R0GB/011PB

011GB/015PB 340 222 194 160 326 φ7

CM5X0-xx4T 015GB/018PB

018G/022P

022G/030P 485 260 230 200 460 φ10

030G/037P

037G/045P
565 330 252 220 545 φ10
045G/055P

055G/075P 588 380 266 300 563 φ12

075G/093P
660 460 290 320 635 φ12
093G/110P

16
CM5X0E general magnetic flux vector control inverter user manual product information

Shape And Size Installation Holes


Aperture
The Inverter Types
W (mm)
H (mm) D (mm) A(mm) B (mm)
(mm)

110G/132P
875 475 305 340 845 φ12
132G/160P

160G/185P
1100 520 355 380 1066 φ12
185G/200P

200G/220P

5 220G/250P
3 1360 700 380 250 1320 φ14
250G/280P
0
CM5X0-
280G/315P
xx4T

315G/355P

355G/400P 1350 900 455 250 1300 φ16

400G/450P

450G/500P

500G/550P
1800 1060 500 - - -
550G/630P

630G

State:530 type 160G-400G for hanging and site dual-use chassis, top down out connection mode.

17
CM5X0E general magnetic flux vector control inverter user manual product information

Shape And Size Installation Holes


Aperture
The Inverter Types
W (mm)
H (mm) D (mm) A (mm) B (mm)
(mm)

110G/132P
850 475 325 180 820 φ12
132G/160P

160G/185P
1000 520 373 210 960 φ12
185G/200P

200G/220P
5 1180 580 400 225 1140 φ14
220G/250P
3
0 250G/280P
E 1300 650 423 250 1260 φ14
CM5X0-
280G/315P
xx4T

315G/355P

355G/400P 1420 720 430 270 1380 φ16

400G/450P

450G/500P

500G/550P
1800 1000 600 - - -
550G/630P

630G

State:530E type 110G-400G for hanging and site dual-use chassis, outlet and inlet line of the bottom.

18
CM5X0E general magnetic flux vector control inverter user manual product information

2.5.3 The way for leading out the Keyboard and the size of hole on iron plate

Map 2-8 Tray installation

Map 2-9 Direct fixation

19
CM5X0E general magnetic flux vector control inverter user manual product information

2.6 optional accessories

Table 2-4 CM5X0 the inverter chooses accessories Table(X represents Table 3or8)
A full explanation of the function and use options, see the relevant options.
If you need more options, please state when ordering.

Names Types functions Notes


The product Built-in brake units for
Built-in braking unit model with Braking energy use the standard
"B" configuration

The external LED CM530-LED LED display and keyboard The CM series general
operation panel operation RJ45 interface

Introduction of liquid crystal


The external LED
CM530-LCD display and keyboard carry a copy RJ45 interface
operation panel
operation
The external LED LED display and keyboard The CM series general
CM530-LED2
operation panel operation RJ45 interface

Standard May 8 core cable For 1 meter and 3 meters,


Extension cable CM-CAB CM5X0E - leds, CM5X0E - LCD 5 meters, 10 meters four
CM5X0E - LED2 connection specifications

If you need other function module extensions (such as I/O card, PG card, EPS card, etc.), please choose
CM580E series inverter, specify when ordering the function module card.

2.7 The daily maintenance and maintenance of the converter

2.7.1 Daily Maitenance


Due to environment temperature, humidity, dust and the influence of vibration, can cause converter internal device
aging, lead to frequency converter potential failure or reduce the service life of the converter.Therefore, it is
necessary to implement daily and regular maintenance and maintenance for frequency converter.

! Caution
Daily check items:
1) in the operation of the motor sound if an exception occurs
2) whether there was a vibration in the operation of the motor
3) whether frequency converter installation environment changes
4) converter cooling fan is working correctly
5) inverter is overheating

Daily cleaning:
Should always keep the inverter in a clean state.
Effectively remove the inverter on the Table area of dust, prevent dust from entering the internal frequency
converter, especially metal powder.
Effectively remove oil converter cooling fan.

2.7.2 Regular Examinations


Please check in the operation of the check on a regular basis.
Regular inspection items:
20
CM5X0E general magnetic flux vector control inverter user manual product information

1) check the air duct, and regularly clean


2) check if there is a loose screw
3) check the inverter from corrosion
4) check whether the terminal is a drawing arc trace
5)The main loop of the insulation test
Remind:In megohm Table megohm Table (please use dc 500 v) measuring insulation resistance, will release main
return route and converter, and don't use Table test control circuit insulation, insulation resistance without high
pressure test (factory) has been completed.

2.7.3 The inverter parts replacement


Inverter main parts, cooling fan and filter electrolytic capacitor, its life is closely related to the use of the
environment and the status of the maintenance.
General life time is:

Device names Life span

Fans 2~3years

Electrolytic Capacitor 4~5years

The user can according to the running time determine the change of fixed number of year.
1, the cooling fan may damage the reason: bearing wear, leaf aging.
Criteria: fan blade for cracks, such as whether there are abnormal vibration sound when the phone is switched on.
2, filtering electrolytic capacitor may damage the reason: the poor quality of the input power supply, the
environment temperature is higher, the frequent load jump, electrolyte aging.Judging criteria: presence of liquid
leakage, the relief valve is protruding, electrostatic capacitance measurement, the measurement of insulation
resistance。

2.7.4 the storage of inverters


Users to buy inverter, temporary storage and long-term storage must pay attention to the following:
1) according to the original packaging as far as possible when stored in the packing box of the company.
2) storage for a long time can lead to degradation of electrolytic capacitors, and must ensure that access within 2
years once electricity, electricity for at least 5 hours, the input voltage must use voltage regulator slowly rise to the
rating.

2.8 The inverter's warranty:

1,Reasonable maintenance fee will be charged;


2, in 18 months, such as the following event should charge a maintenance fee:
(1). The user does not, as stated in the manual, the machine damage;
(2). Such as fire, flood, abnormal voltage caused by the damage;
(3). The frequency converter is used for the damage caused by the abnormal function;
3, export overseas (excluding home), in accordance with the contract execution, such as not sign a contract do not
enjoy free maintenance), the relevant service fees in accordance with the manufacturer standard calculation,
contract, if any, to the principle of contract priority processing.

2.9 Selection Guide

CM series frequency converter of six kinds of control mode: the common V/F, open loop flux vector control 1, 2,
open-loop flux vector control open-loop torque control, the closed-loop flux vector control, the closed loop torque
control.

21
CM5X0E general magnetic flux vector control inverter user manual product information

When choosing the inverter must first clear system of variable frequency speed regulation technology requirements,
the application of frequency converter and the load characteristics of occasions, and from the adaptation motor, the
output voltage, rated output current factors such as comprehensive consideration, and then choose to meet the
requirements of aircraft and determine the operation mode.

The basic principle is: motor rated load current should not exceed the rated current of the inverter.Normally
according to the instruction of motor capacity to choose, the attention is rated current of the motor and frequency
converter.Overload capacity for starting and braking of frequency converter to be meaningful.Anything that
short-time overload in the running process, can cause changes in the velocity of the load.If the velocity accuracy
requirement is higher, please consider enlarge a class.

Fan and water pump type: in the low required overload ability, because the load is proportional to the square of the
torque and speed, so the load lighter during low speed running except roots blower () and load on the speed
accuracy because of this kind has no special requirements, so choose square torque V/F.

Constant torque load: most of the load with constant torque characteristics, but in terms of the accuracy of the speed
and the dynamic performance requirements are generally not high.For example: extrusion machine, mixer,
conveyor belt, in the factory the transport trolley, crane, translation agencies, etc.Optional model selection of the
multistage V/F control mode.

Controlled object has a certain dynamic and static index requirements: this type of load is sometimes a hard
mechanical properties at low speed, in order to meet the production process of the control system of static and
dynamic index requirements.Can choose the open-loop flux vector control mode.Controlled object with high
dynamic and static index requirements: for speed control precision and dynamic performance index has a high
requirement and high precision synchronous control occasions, can adopt closed-loop flux vector control mode
(please choose CM58 series inverter).

2.10 Brake component selection guide

Please choose according to the braking torque of brake resistance, power and braking unit types, and you can see
Table2-5 for details:
Please choose according to the braking torque of brake resistance, power and braking unit types, and the specific
see Table2-5:
The application of different industry, its braking torque is different:
1, the general reduction in the process of braking, the braking torque is 50% (such as: machine tools, punch press,
spindle servo, brick machine, etc.);
2, vertical load falling in the process of braking, the braking torque is between 100% ~ 150% (such as: construction
elevators, cranes, passenger elevator, centrifuges, etc.).

Braking torque by Braking torque by


Brake torque 150%, 5
100%, and 15 s 50%, and 15 s
The s recommended
recommended recommended
Inverters resistance tolerance of
resistance tolerance of resistance tolerance of
Types the power unit and
the power and the the power and the
brake model
braking unit model braking unit model
≥220Ω,0.4KW ≥300Ω,0.3KW ≥300Ω,0.3KW
R4GB Built-in brake units Built-in brake units Built-in brake units

R75GB ≥150Ω,0.6KW ≥150Ω,0.6KW ≥300Ω,0.3KW


Built-in brake units Built-in brake units Built-in brake units

1R5GB ≥60Ω,1KW ≥100Ω,0.8KW ≥150Ω,0.6KW


Built-in brake units Built-in brake units Built-in brake units

2R2GB ≥40Ω,1.2KW ≥60Ω,1KW ≥150Ω,0.6KW


Built-in brake units Built-in brake units Built-in brake units

22
CM5X0E general magnetic flux vector control inverter user manual product information

Braking torque by Braking torque by


Brake torque 150%, 5
100%, and 15 s 50%, and 15 s
The s recommended
recommended recommended
Inverters resistance tolerance of
resistance tolerance of resistance tolerance of
Types the power unit and
the power and the the power and the
brake model
braking unit model braking unit model

R75GB ≥300Ω,0.3KW ≥300Ω,0.3KW ≥300Ω,0.3KW


Built-in brake units Built-in brake units Built-in brake units
≥150Ω,0.5KW ≥220Ω,0.4KW ≥300Ω,0.3KW
1R5GB/2R2PB
Built-in brake units Built-in brake units Built-in brake units

2R2GB/4R0PB ≥150Ω,0.5KW ≥220Ω,0.4KW ≥300Ω,0.3KW


Built-in brake units Built-in brake units Built-in brake units

4R0GB/5R5PB ≥100Ω,0.8KW ≥130Ω,0.6KW ≥150Ω,0.5KW


Built-in brake units Built-in brake units Built-in brake units

5R5GB/7R5PB ≥75Ω,1.0KW ≥100Ω,0.8KW ≥130Ω,0.6KW


Built-in brake units Built-in brake units Built-in brake units

7R5GB/9R0PB ≥60Ω,1.2KW ≥75Ω,1.0KW ≥100Ω,0.8KW


Built-in brake units Built-in brake units Built-in brake units
≥40Ω,2KW ≥50Ω,1.5KW ≥60Ω,1.2KW
9R0GB/011PB Built-in brake units Built-in brake units Built-in brake units
≥40Ω,2KW ≥50Ω,1.5KW ≥60Ω,1.2KW
011GB/015PB Built-in brake units Built-in brake units Built-in brake units
≥30Ω,4KW ≥40Ω,2KW ≥50Ω,1.5KW
015GB/018PB Built-in brake units Built-in brake units Built-in brake units
≥24Ω,4KW ≥30Ω,4KW
≥40Ω,2KW
Built-in matching brake Built-in matching brake
018G/022P Built-in matching brake
units units
units
≥13.6Ω,8KW ≥30Ω,4KW ≥40Ω,2KW
022G/030P Built-in matching brake Built-in matching brake Built-in matching brake
units units units
≥13.6Ω,8KW ≥24Ω,6KW ≥30Ω,4KW
030G/037P Built-in matching brake Built-in matching brake Built-in matching brake
units units units
≥24Ω,6KW ≥24Ω,6KW
≥10Ω,12KW BR530E-4T037 BR530E-4T037
037G/045P BR530E-4T075 Built-in matching brake Built-in matching brake
units units
≥10Ω,12KW ≥13.6Ω,8KW
≥6.8Ω,12KW BR530E-4T075 BR530E-4T075
045G/055P BR530E-4T132 Built-in matching brake Built-in matching brake
units units
≥10Ω,12KW ≥13.6Ω,8KW
≥6.8Ω,12KW BR530E-4T075 BR530E-4T075
055G/075P BR530E-4T132 Built-in matching brake Built-in matching brake
units units

≥6.8Ω,12KW ≥10Ω,12KW ≥13.6Ω,8KW


075G/093P BR530E-4T132 BR530E-4T075 BR530E-4T075

23
CM5X0E general magnetic flux vector control inverter user manual product information

Braking torque by Braking torque by


Brake torque 150%, 5
100%, and 15 s 50%, and 15 s
The s recommended
recommended recommended
Inverters resistance tolerance of
resistance tolerance of resistance tolerance of
Types the power unit and
the power and the the power and the
brake model
braking unit model braking unit model
≥2*6.8Ω,12KW ≥6.8Ω,12KW ≥6.8Ω,12KW
093G/110P BR530E-4T200 BR530E-4T132 BR530E-4T132
≥2*6.8Ω,12KW ≥6.8Ω,12KW ≥6.8Ω,12KW
110G/132P BR530E-4T200 BR530E-4T132 BR530E-4T132
≥2*6.8Ω,12KW
132G/160P ≥6.8Ω,12KW ≥6.8Ω,12KW
BR530E-4T200
BR530E-4T132 BR530E-4T132
≥3*6.8Ω,12KW
160G/185P ≥2*6.8Ω,12KW ≥2*6.8Ω,12KW
BR530E-4T315
BR530E-4T200 BR530E-4T200
≥3*6.8Ω,12KW
185G/200P ≥2*6.8Ω,12KW ≥2*6.8Ω,12KW
BR530E-4T315
BR530E-4T200 BR530E-4T200
≥3*6.8Ω,12KW
200G/220P ≥2*6.8Ω,12KW ≥2*6.8Ω,12KW
BR530E-4T315
BR530E-4T200 BR530E-4T200
≥3*6.8Ω,12KW
220G/250P ≥2*6.8Ω,12KW ≥2*6.8Ω,12KW
BR530E-4T315
BR530E-4T315 BR530E-4T315
≥3*6.8Ω,12KW
250G/280P ≥2*6.8Ω,12KW ≥2*6.8Ω,12KW
BR530E-4T315
BR530E-4T315 BR530E-4T315
≥3*6.8Ω,12KW ≥2*6.8Ω,12KW
280G/315P ≥2*6.8Ω,12KW
BR530E-4T315 BR530E-4T315 BR530E-4T315
≥3*6.8Ω,12KW ≥2*6.8Ω,12KW
315G/355P ≥2*6.8Ω,12KW
BR530E-4T315 BR530E-4T315 BR530E-4T315
≥5*6.8Ω,20KW ≥4*6.8Ω,20KW
355G/400P ≥3*6.8Ω,20KW
BR530E-4T630 BR530E-4T450 BR530E-4T450
≥5*6.8Ω,20KW ≥4*6.8Ω,20KW
400G/450P ≥3*6.8Ω,20KW
BR530E-4T630 BR530E-4T450 BR530E-4T450
≥5*6.8Ω,20KW ≥4*6.8Ω,20KW
450G/500P ≥3*6.8Ω,20KW
BR530E-4T630 BR530E-4T450 BR530E-4T450
≥6*6.8Ω,20KW ≥5*6.8Ω,20KW
500G/550P ≥4*6.8Ω,20KW
BR530E-4T630 BR530E-4T630 BR530E-4T630
≥6*6.8Ω,20KW ≥5*6.8Ω,20KW
550G/630P ≥4*6.8Ω,20KW
BR530E-4T630 BR530E-4T630 BR530E-4T630
≥6*6.8Ω,20KW ≥5*6.8Ω,20KW
630G ≥4*6.8Ω,20KW
BR530E-4T630 BR530E-4T630 BR530E-4T630

Note:
24
CM5X0E general magnetic flux vector control inverter user manual product information

1, braking resistor value choice must not be smaller than the resistance tolerance of the recommended in the Table,
such as more than would be likely to damage the brake unit;
2, 2 Table shown in Table x braking resistor in parallel with the two groups, the Table in the x3 Table in three
groups of braking resistor in parallel with, and so on.
3,After 3, inverter type with "B" as the standard built-in brake unit type inverter, not the built-in brake unit, please
choose the corresponding according to its braking torque braking unit model;
4, 18.5 ~ 55 kw G type braking unit is a built-in optional, if you have any requirements, please specify when
ordering, standard configuration without braking unit;
5, 5 s, listed in the Table 15 s refers to the continuous braking time.

25
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

chapter3 installation of mechanics and electronics

3.1 Mechanics installation

3.1.1 Installation environments:


1) ambient temperature, ambient temperature has a great influence on the frequency converter life, do not allow
the inverter running environment temperature more than allowed temperature range (- 10 ℃ to 50 ℃).
2) install the inverter on the Table surface of the object to flame retardant, want to have enough space around the
cooling, frequency converter work easily generate a large amount of heat, and vertical screw is installed on the
installation pedestal.
3) please install where is not easy to vibration, the vibration should not greater than 0.6 G, pay special attention
to stay away from the punching machine and other equipment.
4) installed in avoid direct sunlight, moisture, where the water is.
5) to avoid installed in corrosive, flammable, explosive gas in the air.
6) to avoid in a more than oil, dirt, metal dust in many places.

Monomer installation map

State:When the inverter fluctuation when installation, please install the Map of insulation guide plate.

26
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

>100mm

Map3-1 CM5X0 Installation of the inverters sketch map

3.1.2 Machinery installation need to focus on is the cooling problem.So please note the
following points :
1) please install vertical frequency converter, facilitate upward heat, but not the horse.If there are more
contained in the inverter, it's best to install side by side.When installed up and down is required, please refer to
the Map3-1 schematic Map, install insulation guide plate.
2) follow the Map3-1 installation space, to ensure that the inverter heat dissipation space, but decorate, please
consider other components contained in the heat.
3) mounting bracket must be flame retardant material.
4) with metal powder applications, recommended the radiator tank installation, outside seal ark space should be
as large as possible at this time.

27
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

3.1.3 Keyboard, cover-plate disassembly and installation:

Activities cover the axis


of rotation

Rotary axis for position

Map3-2 Keyboard, cover-plate disassembly and installation

28
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

More than 9 kw CM series inverter adopts sheet metal enclosure, sheet metal shell plate disassembly see
Map3-3.Available tools will be directly under the cover of screws loosen.
! Danger

The cover board removed, avoid the cover off may cause harm to the equipment and the personal

Cover board hook

Hook mounting position

Operation Panel

Map3-3Sheet metal shell cover plate disassembly graph Map

29
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

3.2 installation of electronics

3.2.1 Peripheral electrical components selection guidance:


Table3-1CM5X0 Peripheral electrical components selection guidance of the invertex

The
main
loop of
cocon The main
Air-switch the Control Ground
tacto loop of the
circuit
The Inverter Types (MCCB) input output lead
conductor
r side wires
(mm²)
(A) side (mm²) (mm²)
(A)
wires
(mm²

220V R4GB 16 10 2.5 2.5 1 2.5

Voltage R75GB 16 10 2.5 2.5 1 2.5

Level 1R5GB 20 16 4 2.5 1 2.5

2R2GB 32 20 6 4 1 2.5

R75GB 10 10 2.5 2.5 1 2.5

1R5GB 16 10 2.5 2.5 1 2.5

2R2GB 16 10 2.5 2.5 1 2.5

4R0GB/5R 25 16 4 4 1 4
5PB

5R5GB/7R 32 25 4 4 1 4
5PB

7R5GB/9R 40 32 4 4 1 4
0PB
380V 9R0GB/01 40 32 6 6 1.5 6
Voltage 1PB
Level 011GB/01 50 40 6 6 1.5 6
5PB

015GB/01 50 40 6 6 1.5 6
8PB

018G/022P 63 63 10 10 1.5 10

022G/030P 80 63 16 16 1.5 16

30
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

The
main
loop of
cocon The main
Air-switch the Control Ground
tacto loop of the
circuit
The Inverter Types (MCCB) input output lead
conductor
r side wires
(mm²)
(A) side (mm²) (mm²)
(A)
wires
(mm²

030G/037P 100 100 16 16 1.5 16

125 10 25 25 1.5 25
037G/045P
0

160 12 25 25 1.5 25
045G/055P
5

180 12 35 35 1.5 25
055G/075P
5

200 16 50 50 1.5 25
075G/093P
0

093G/110P 225 225 70 70 1.5 25

110G/132P 250 225 120 120 1.5 25

132G/160P 400 330 150 150 1.5 25

160G/185P 500 400 185 185 1.5 25


380V
185G/200P 500 500 185 185 1.5 25
Voltage
200G/220P 630 500 240 240 1.5 25
Level
220G/250P 800 630 150*2 150*2 1.5 25

250G/280P 800 630 150*2 150*2 1.5 25

280G/315P 1000 630 185*2 185*2 1.5 25

315G/355P 1000 800 240*2 240*2 1.5 35

355G/400P 1200 800 240*2 240*2 1.5 35

400G/450P 1200 1000 185*3 325*2 1.5 35

450G/500P 1500 1500 185*3 350*2 1.5 35

500G/550P 1720 1500 185*3 350*2 1.5 35

550G/630P 1900 1500 185*3 350*2 1.5 35

630G 2200 1650 240*3 350*2 1.5 35

31
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

3.2.2 The using instruction of peripheral electrical components :


Table3-2 CM5X0 The using instruction of peripheral inverters

Installation
Parets Name function Instruction
Location
The input circuit
Air switch Equipment flow at the downstream power off
of the front-end
Empty opened
Inverter power operation.It should be avoided by contactor
between frequency
contactor frequent fluctuation of the frequency changer electrical operation
converter input
per minute (less than a second) or direct start operation.
side

1, improve the power factor of input side;


Frequency 2, effectively eliminate higher harmonic input side, prevent other
Ac input reactor converter input equipment damage caused by the voltage waveform distortion;
side 3, eliminate the power supply and imbalance caused by the
unbalanced input current.

75-132 - kw for 1, improve the power factor of input side;


matching, 160 kw 2, effectively eliminate higher harmonic input side,
Dc reactor
and above as the prevent other equipment damage caused by the
standard voltage waveform distortion.

1, reduce inverter foreign conduction and radiation interference;


Frequency 2, to reduce the flow from the power inverter of conduction
EMC input filter converter input interference, improve the anti-interference ability of frequency
side converter.

Generally it contains more higher harmonic inverter output


side.When the distance motor and frequency converter, because
have larger capacitance in circuit.During a harmonic may cause
Installation
resonance in the loop, which impact from two aspects:
between the motor
1, damage motor insulation performance,and long time will
Ac output reactor and inverter output
damage the motor.
side, near the
2, generate large leakage current, causing the inverter frequency
inverter.
protection.
General inverter and motor’s distance more than 100 meters, so it
is recommended that the reactor equip with ac output.

32
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

3.2.3 Wiring Methods

制动电阻
Brake resistor

R (-) (+) PB U
三相380V
AC three-phase
power supply
交流输入
380V
S V M
W
T
+24V
NPN PNP 485+
MODBUS接口
MODBUS interface
Default ON OFF
多功能数字输入端子1
Multifunctional digital input terminal 1 DI1 默认
FWDFWD
485-
Default
多功能数字输入端子2
Multifunctional digital input terminal 2 DI2 默认
REVREV
I U AO1 Analog output:
多功能数字输入端子3
Multifunctional digital input terminal 3 DI3 模拟量输出:
I U AO2 0/2-10V
0/2-10V
多功能数字输入端子4
Multifunctional digital input terminal 4 DI4 或0/4-20mA
Or0/4-20mA
GND
Multifunctional digital input terminal 5
多功能数字输入端子5 DI5
Y1
Multifunctional digital input terminal 6
多功能数字输入端子6 DI6
Multifunctional
多功能双极性 bipolar open
Multifunctional digital input terminal 7
多功能数字输入端子7 DI7
COM collector
开路集电极 output terminal
或 HDI
Or 输出端子
CME
COM
Y2
多功能双极 bipolar open
Multifunctional
性开路集电
collector output terminal
COM 极输出端子
Or FM pulse output
或 FM
脉冲输出
CME

TA
AI1 1 relay output
模拟量输入:
Analog Input: TB 继电器1输出
0-10V/4-20mA
0-10V/4-20mA I U TC
AI2
Analog
模拟量输入: Input: RA
I U
0-10V/4-20mA
0-10V/4-20mA
GND RB 2继电器2输出
relay output

RC

Map3-4 55KW and lower triple inverters

Note:this Map is suitable for CM5X0-A1X4TR75GB ~ CM5X0-B1X4T055GB series inverters

(18.5~55KW Parts of brake units match function, if you have any requirements, please specify when orde)。

33
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

制动电阻
Brake resistor

BR530

R (+) (-) U
三相380V 380V
AC three-phase
交流输入
power supply S V M
W
T
+24V
NPN PNP 485+
MODBUS接口
MODBUS interface
ON OFF
多功能数字输入端子1
Multifunctional digital input terminal 1
Default
DI1 默认
FWDFWD
485-
Default
多功能数字输入端子2
Multifunctional digital input terminal 2 DI2 默认
REVREV
I U AO1
Multifunctional digital input terminal 3
多功能数字输入端子3 DI3 模拟量输出:
Analog output:
I U AO2 0/2-10V
0/2-10V
Multifunctional digital input terminal 4
多功能数字输入端子4 DI4 或0/4-20mA
Or0/4-20mA
GND
Multifunctional digital input terminal 5
多功能数字输入端子5 DI5
Y1
Multifunctional digital input terminal 6
多功能数字输入端子6 DI6
多功能双极性
Multifunctional bipolar open
Multifunctional digital input terminal 7
多功能数字输入端子7 DI7
COM 开路集电极
collector output terminal
或 HDI
Or 输出端子
CME
COM
Y2
多功能双极 bipolar open
Multifunctional
性开路集电
collector output terminal
COM 极输出端子
Or FM pulse output
或 FM
脉冲输出
CME

TA
AI1 1继电器1输出
relay output
模拟量输入:
Analog Input: TB
0-10V/4-20mA I U
0-10V/4-20mA TC
AI2
Analog
模拟量输入: Input: RA
I U
0-10V/4-20mA
0-10V/4-20mA
GND RB 2继电器2输出
relay output

RC

Map3-5 37-55KW triple inverters

Note:18.5Kw ~ 55Kw if users don’t choose built-in brake unit,the wring is as Map3-5 above

34
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

制动电阻
Brake resistor

BR530

R P1 (+) (-) U
AC three-phase
三相380V380V
power supply
交流输入 S V M
W
T
+24V
NPN PNP 485+
MODBUS interface
MODBUS接口
ON OFF
多功能数字输入端子1
Multifunctional digital input terminal 1 DI1 默认 FWD 485-

多功能数字输入端子2
Multifunctional digital input terminal 2 DI2 默认 REV
I U AO1
多功能数字输入端子3
Multifunctional digital input terminal 3 DI3 模拟量输出:
Analog output:
I U AO2 0/2-10V
0/2-10V
多功能数字输入端子4
Multifunctional digital input terminal 4 DI4 或0/4-20mA
Or0/4-20mA
GND
多功能数字输入端子5
Multifunctional digital input terminal 5 DI5
Y1
多功能数字输入端子6
Multifunctional digital input terminal 6 DI6
多功能双极性bipolar open
Multifunctional
多功能数字输入端子7
Multifunctional digital input terminal 7 DI7
COM 开路集电极
collector output terminal
或 HDI 输出端子
CME
COM
Y2
多功能双极 bipolar open
Multifunctional
性开路集电
collector output terminal
COM 极输出端子
Or FM pulse output
或 FM
脉冲输出
CME

TA
AI1 1继电器1输出
relay output
模拟量输入:
Analog Input: TB
0-10V/4-20mA I U
0-10V/4-20mA TC
AI2
模拟量输入:
Analog Input: RA
I U
0-10V/4-20mA
0-10V/4-20mA
GND RB 2继电器2输出
relay output

RC

Map3-6 75KW and upper triple inverters

35
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

3.2.4 Main circuit terminals and wiring:


! Danger
1, confirm the power switch in the OFF state can only be wiring operation, otherwise electric shock accident may
occur.
2, wiring personnel must be trained professionals, or may cause harm to the equipment and the personal!
3, must be reliable grounding, otherwise there is an electric shock or fire danger!
! Caution
1, confirm the identity of the input power and frequency converter rating, otherwise it will damage the inverter!
2, confirm the motor and frequency converter adapter, otherwise it might damage the machine or cause the inverter
protection!
3, can't pick up the power supply to terminals U, V, W, otherwise it will damage the inverter!
4,Braking resistance is April and may not be directly to the dc bus (+), (-), or start a fire!
3.2.4.1 single phase inverter main circuit terminal:
Terminal
Names Instruction
Marks
Single-phase power input Single-phase 220 v ac power supply
L、N
terminals connection point
Dc bus positive and
(+)、(-) Common dc bus input point
negative terminals
Braking resistor connected
(+)、PB Connect braking resistor
terminals
The inverter output
U、V、W Connect three-phase motor
terminals

Safety earthing terminal Safety earthing terminal

3.2.4.2 Three-phase inverter main circuit terminal


7.5KW and lower:

9-15KW:

36
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

18.5-30KW:(Safety earthing terminal bottom on the outside of casing)

37-55KW:(Safety earthing terminal bottom on the outside of casing)

The main loop of the three-phase 75 ~ 93 kw terminal identification(Safety earthing terminal at the bottom
of the main circuit )
75-93KW:(Safety earthing terminal bottom on the outside of casing)

110-132KW(530type):

160-280KW(530type):

315-630KW(530type):

110-132KW(530Etype):

37
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

160-630KW(530Etype):

Terminal
Names Instruction
Marks
Single-phase power input Ac three-phase 380 v power supply
R、S、T
terminals connection point
Common dc bus input point
Dc bus positive and negative
(+)、(-) The junction of more than 75 kw and
terminals
external braking unit
Braking resistor connected 55 kw and under braking resistor
(+)、PB
terminals connection point
The inverter output
(+)、P1 75-132 - kw dc reactor is optional
terminals

U、V、W Safety earthing terminal Connect three-phase motor

Safety earthing terminal (frequency


Single-phase power input
converter belonging to class I
terminals
appliance,must be reliable grounding.)

3.2.4.3 Notice for wiring:


The input power L, N/R, S, T:
Frequency converter input side of the connection, without phase sequence.
Dc bus (+) and (-) terminal:
Note after power dc bus (+), (-) terminal there are residual voltage, must wait to CHARGE off lights went out
and confirm that is less than 36 v rear can contact, otherwise there is risk of electric shock.
75 kw and above when choosing outer brake components, pay attention to (+), (-) polarity cannot reverse,
otherwise result in frequency converter damage and even fire.Braking unit wiring should not be more than 10
meters in length, but should use twisted pair or close double parallel wiring, it may not be directly connect
braking resistance on the dc bus, may cause damage of frequency converter and even fire.
Braking resistor connection terminal (+), PB:
55 kw and below and confirmed the built-in braking unit model, the braking resistor terminals.Braking resistor
type selection reference recommended value and wiring distance should be less than 5 meters.Otherwise may
cause damage of frequency converter.
The inverter output side of U, V, W:
Inverter side out side cannot be connected capacitor or surge absorber, otherwise it will cause inverter often
protect and even damaged.
38
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

The motor when the cable is too long, because of the influence of the distributed capacitance, easy to produce
electrical resonance, causing the motor insulation damage or produce larger leakage current transducer
over-current protection.Electrical cable length is more than 100 meters, the reactor with ac output.

Earthing terminal PE:


Terminal must be reliable grounding, grounding line resistance must be less than 0.1Ω, otherwise it will lead to
abnormal equipment work or even damage.

May not be Shared by earthing terminal and power line and N terminal.
3.2.5 Control terminals and the terminal:
3.2.5.1 Control circuit terminal layout map is as follows:
Map3-5 Control circuit terminal layout map

GND AO1 AO2 GND DI1 DI2 DI3 DI4 DI5 DI6 COM R/A R/B R/C
Y2/ DI7/
10V AI1 AI2 485+ 485- CME COM Y1 24V T/A T/B T/C
FM HDI

CM5x0control terminal sketch map(x represents Table 3or8)

3.2.5.2 control terminal’s function instruction:(x presents Table 3or8)


Table3-3 CM5x0E functioninstruction of frequency converter control terminal
Terminal Terminal
Types function Instruction
Signs Names
To provide + 10 v power supply, the maximum
Power
+10V-G External + 10 v output current: 10 ma, generally used as an
Supply
ND power supply external potentiometer working power supply,
potentiometer resistance range :1~5kΩ
To provide + 24 v power supply, generally used as
24V-CO External + 10 v a digital input/output terminals work power and
M power supply external sensor power, maximum output current :
200mA
AI1-GN 1, input range: DC0 ~ 10 v / 4 ~ 20 mA
Analog input
D Determined by the CN1 dial the code switch
terminal 1
Analogous on the control panel to choose
Input The factory to voltage mode.
AI2-GN Analog input
2, input impedance, voltage type 100 kΩ, 500 Ω
D terminal 2
current input.
DI1-CO Digital
1, optical coupling isolation, compatible with
M Input1
bipolar input, through DI dial the code switch,
Digital DI2-CO Digital
factory to NPN mode
Input M Input2
2, input impedance: 3.3 k 惟
DI3-CO Digital
3, level of input voltage range: 9 ~ 30 v
M Input3

39
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

Terminal Terminal
Types function Instruction
Signs Names
DI4-CO Digital (DI6 DI7 terminal function CM530E machine
M Input4 only
DI5-CO Digital
M Input5
DI6-CO Digital
M Input6
DI7-CO
M Digital
/HDI-C Input7
OM
AO1-G Analogous Respectively by the panel on CN2, CN3 dial the
ND Output1 code switch selection decision output voltage or
current.
Analogous
The output voltage range: 0 ~ 10 v
Output AO2-G Analogous
Output current range: 0 to 20 mA
ND Output2
(AO2 terminal function only CM530E CM530
three-phase 380 v 37 kw or more
Optical coupling isolation, bipolar open collector
output
The output voltage range: 0 ~ 24 v
Output current range: 0 ~ 50 mA
Y1-CM Digital Note: digital output of CME from the digital input
E Output1 fields COM is internal, but when they leave the
CME and COM has external nipple (Y1 for + 24
Digital
v drive by default) at this time.When Y1 think
Output
with external power drive, you have to disconnect
the CME and COM external short answer.

Digital
Output2 The same as the function of Y1
Y2/FM
High-speed High-speed pulse output
pulse output

Modbus communication interface, can choose


whether to need to communication through dial
Modbus
Communication 485+ - the code switch CN1 matching resistance.
Communication
interface 485- For Profibus communication function, please
interface
choose CM530E or 580 series inverter, and
selects the Profibus DP.

40
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

Terminal Terminal
Types function Instruction
Signs Names
Normally closed
TA-TB Contactand drive ability:AC250V,3A,
terminals
Relay output 1 COSφ=0.4。
Normally closed
TA-TC DC30V,1A
terminals

Normally closed Contact and drive ability:


RA-RB
terminals AC250V,3A,COSφ=0.4。
Relay output 2
Normally closed DC30V,1A,only CM530E or CM530 above 37
RA-RC
terminals kw three-phase 380 v

Keyboard Irfpa keyboard, copy and keyboard interface, take


outer keyboard
extension interface CN6 out the bidirectional crystal head, the standard
interface
Ethernet cable can be used for the extension

3.2.5.3 Control terminal wiring instructions:


A、Analogous input terminals:
Due to the weak analog voltage signals are particularly vulnerable to external interference, so generally need to use
shielded cable, and wiring short distance as far as possible, not more than 20 meters, such as Map3-7.In some of the
analog signal severely disrupted, analog signal source is add filter capacitor or ferrite core.

10V
AI1
电位器
Potentiome CM
ter AI2 5X0E
GND
屏蔽电缆单点接地
Shielded cables single point grounding

Map3-7 Analog input terminal connection sketch map

41
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

B、Digital input terminals:

DI terminal connection Mode 1(Default):


DI接线模式一(出厂默认接线方式):当 DI接线模式二:当DI拨码开
DI terminal connection Mode2:
CN1 inDI拨码开关为NPN模式没有使用外部电源
the NPN mode and use an internal power supply CN1 in the PNP关为NPN模式使用外部电源
mode and use an external power supply

DC9-
24V 24V
30V
(Factory Default FWD)
DI1(出厂默认FWD)
(Factory Default FWD)
DI1(出厂默认FWD)
(Factory Default REV)
DI2(出厂默认REV)
(Factory Default REV)
DI2(出厂默认REV)
DI3
CM5X0E DI3
DI4 CM5X0E
DI4
DI5
DI5
DI6
DI6
Shielded cables 屏蔽电缆单端接地
single point grounding
COM Shielded cables屏蔽电缆单端接地
single point grounding
COM

DI terminal DI接线模式三:当DI拨码开关
connection Mode 3: DI terminal connection Mode 4:
DI接线模式四:当DI拨码开
为PNP模式没有使用外部电源
CN1 in the PNP mode and use an internal power supply CN1 in the PNP关为PNP模式使用外部电源
mode and use an external power supply

24V 24V

(Factory Default FWD)


DI1(出厂默认FWD) DI1(出厂默认FWD)
(Factory Default FWD)
(Factory Default REV)
DI2(出厂默认REV) (Factory Default REV)
DI2(出厂默认REV)

DI3 DI3

DI4 CM5X0E DI4 CM5X0E

DI5 DI5

DI6 DI6
Shielded cables屏蔽电缆单端接地
single point grounding
DC9-
COM 30V COM

Shielded cables屏蔽电缆单端接地
single point grounding

Map3-8 Four different modes digital input terminal connection sketch map

Generally need to use shielded cable, and wiring short distance as far as possible, not more than 20 meters.
When the user drive in active way, for the power of the crosstalk of filter necessary measures.
The proposal chooses way contact control. C、digital output terminals:
When digital output terminals need to drive the relay, you should add absorb diode side of the relay coil, otherwise
it will be easy to cause damage of dc 24 v power supply.
Note:Must be properly installed to absorb the polarity of the diode.As the following Map3-9.Otherwise when
digital output terminals output, 24 v dc power supply will be burn out immediately.

42
CM5X0E general magnetic flux vector control inverter user manual installation of mechanics &electronics

24V 24V
CM5X0E 继电器
Relay CM5X0E DC9-
Y1 Y1
30V
继电器
Relay
CME CME
External control
控制端子外部短接片 去掉控制端子
Remove the control
COM terminal jumper COM 外部短接片
terminal external jumpers

内部供电接线图
Internal Power Supply 外部供电接线图
External Power Supply

Map3-9 Digital output terminal Y wiring sketch map

43
CM5X0E general magnetic flux vector control inverter user manual operation and display

Chapter4 operation and display

4.1 peration and display interface introduction

Use operation panel, can function parameters change of the frequency changer, inverter working condition
monitoring and frequency converter operation control (such as start, stop) operation, its appearance and function as
shown in figure 4-1 :

Hz
Uint RPM Digital
indicator A display
%
V

Function
RUN L/D/C FWD/REV TUNE/TC indicator

ENTER
Program EPG
- + QUICK QUICK/
key ESC JOG
JOG Key

Run RUN STOP Stop/Reset


SHIFT RESET
key key

Shift
key
Figure 4-1 operation panel diagram 1 (standard LED keyboard 1)

Hz
Uint Digital
RPM
indicator display
A
%
V
Function
indicator
RUN L/D/C FWD/REV TUNE/TC

Program EPG QUICK QUICK/


key ESC JOG JOG Key

DOWN ENTER UP

STOP
Stop/Reset
RUN
Run SHIFT RESET key
key

Shift
key

ENTER
Operation panel diagram 2 (optional LED 2 keyboard, if you want to select the keyboard, in order to show)
Keyboard 1 and 2 switching operation mode for: press.prg key and STOP at the same time wait for a "-" let go,
switch is successful.

44
CM5X0E general magnetic flux vector control inverter user manual operation and display

4.1.1 Indicator light show


Light sign name meaning color

Unit Light - current parameters as frequency


Hz Frequency unit green
values
Indicator Light - the current parameters for the
A Current unit green
current value
Light Light - the current parameters for the
V Voltage unit green
voltage value
RP Light - the current parameters for the
Drive units green
M speed value
Light - the current parameters as
% The percentage green
percentage
unit Light - frequency converter in the running
RU Running status state
green
function N indicator Out - frequency converter in the stop state

Light Out - frequency converter in the keyboard


control mode
Light - the inverter is in terminal control
L/D
Light control way mode red
/C
Flash - frequency converter in a remote
communication control mode

FW Turn out - said it was


Running direction
D/R Light - reverse state said red
indication
EV

TU Light - enter a state of tuning


Tuning/torque
NE/ Bright and light - the RUN button is tuned red
indicator
TC

4.1.2 Digital display area:


Five LED display, can display setting frequency, output frequency, all kinds of monitoring data and alarm code,
users can according to the function code F7-29 / F7-30 free Settings requires data, detailed see function code F7-29
/ F7-30, also can be directly set FE - 00 (running monitor display parameters FE - 01 (downtime monitoring display
parameters).
4.1.3 The keyboard button instructions
Table 4-1 keyboard function table
Button Name function
PRG/ESC Programming key/exit Level 1 menu to enter or exit, returned to the parent menu

Confirm key (ENTER) Step by step into the menu screen, set parameter confirmation
ENTER
- +
Increasing key (+) Increasing data or function code

Descending key (-) Data or function code

Under the outage display interface and operation interface,


can choose according to cycle parameters, the specific
》 The shift key
meaning according to see F7-29, F7-30; When modifying
parameters, can choose the parameter changes
RUN The operation key Under the keyboard operation, used to run the operation
Running state, press this button can be used to stop running
STOP/RESET Stop/reset operation; Fault alarm state, can be used to rehabilitate
operation, the key features of the function code F7-27.
QUICK/JOG Inching operation F7-28 was set to 0 point operation buttons, F7-28 is set to 1
45
CM5X0E general magnetic flux vector control inverter user manual operation and display

key/direction for the direction key, press the key direction of the not

4.2function code view, modify method

CM series general magnetic flux vector control frequency converter operation panel in operation such as level 3
parameter Settings menu structure.
Three-level menu are: parameter set (menu) - function code (level 2) - function code value (level 3) menu.
Operation process is shown in figure 4-2.

Change改变参数组
Parameter Group Change改变参数组
Parameter Group Change Function code value
改变功能码数值

PRG ENTER ENTER


50.00 F0 F0-11 050.00
PRG PRG PRG/
一级菜单
One menu 二级菜单
Two menu ENTER 三级菜单
Three menu

Figure 4-2 submenus operation flow chart Explanation: the three-level menu operation, can press.prg key or the
ENTER key to return to the secondary menu.
The difference between the two is: press ENTER to save setting parameters after returning to the secondary menu,
and automatically move to the next function code; While press.prg returned directly the secondary menu, not
storage parameters, and returns to the current function code.

Example: the function code F2-02 from 50.00 Hz change the sample set is 20.00 Hz. (gray boxes represent flashing
digits)
PRG ENTER
50.00 F0 F2 F2-00 F2-02

PRG ENTER

PRG ENTER >>


F2 F2-03 020.00 050.00 050.00

Figure 4-3 parameter edit operation example


Note: in the condition of the third level menu, if the parameter is not flashing, said the function code cannot be
modified, possible reasons
1) the function code to modify parameters. Such as the actual testing parameters, operation records, etc.;
2) the function code in the running state cannot be modified, need to modify.

4.3The check method of parameters’ monitoring

Under the outage or running state, can display various state parameters, by function code F7-29 (LED display
parameters) operation and F7-30 (LED stop display parameters), according to a choice whether the parameters
according to the binary you define see chapter 6 F7-29 and function of F7-30 yards.
In stop state, with a total of seven parameters can choose whether show stop condition respectively: set frequency,
busbar voltage, DI input state, the DO output state, voltage analog input AI1, AI2 analog input voltage steps, PLC
running, press the shift key sequence to switch display the selected parameter (the F7-30 display parameters into
binary choice).
In running state, a total of 13 parameters can be displayed, including five fixed display running status parameters:
operating frequency, set frequency, busbar voltage, output voltage, output current is fixed, according to the eight
other display parameters, output power, DI input state, the DO output state, voltage analog input AI1, AI2 analog
input voltage, PID, PID feedback, PLC steps is displayed by the function code F7-29 bitwise (converted to binary)
selection, switch input sequences show that the selected parameters.
Inverter power again to electricity, the display parameter is the default for inverter power lost before the choice of
parameters.

4.4password

Frequency converter provides a user password protection function, when set to zero, F7-51 is the user's password,
set the password before the F7-51 all parameters can be 0 cases according to determine the key, if all have said the

46
CM5X0E general magnetic flux vector control inverter user manual operation and display

current password can be set. If the password is valid, must enter the user password correctly, can enter the ordinary
menu operation, or to enter the show will be 0, twinkle and finally a digital tube, prompt the user must enter the
correct password to action.
If you want to cancel the password protection function, it is only through the password to enter, and F7-51 to 0
press determine key can cancel password protection.
User password protection monitoring parameters, the user password protection situations to normal view
monitoring parameters.
Note: if user forgot password to use the frequency converter, please contact the manufacturer.
Specific cryptographic operations figure see below:

47
CM5X0E general magnetic flux vector control inverter user manual operation and display

CM系列
K1 K2 运行命令
0 0 停止
1 0 停止
K1
0 1 正转 FWD
K2 REV
1 1 反转 COM/+24V

Figure 4-4: password process

CM系列

SB2 FWD
SB1 DIn
SB3 REV
COM/+24V

Figure 4-5: remove password process

48
CM5X0E general magnetic flux vector control inverter user manual operation and display

4.5 motor parameter automatic tuning steps

Choose the vector control operation mode, in front of the frequency converter operation, must be accurate input
motor nameplate parameters, CM5X0E frequency converter on the basis of standard motor nameplate parameters
matching parameters; Vector control method of motor parameters dependence is very strong, to get good control
performance, must be charged with the accurate parameters of the machine.

Motor parameters automatic tuning steps are as follows:


Will first command source (F0-04) choice for operation panel command channel.
Then the actual parameters according to the motor, please input the following parameters:
F4-01: motor rated power F4-02: motor rated voltage
F4-04: the motor rated current F4-05: motor rated frequency
F4-06: motor rated speed

If the motor can be completely off load, and then the F4-00 please select 2 (complete tuning), and then press the
RUN key on the keyboard panel, the inverter will automatically calculate the motor of the following parameters:
F4-07: no-load current F4-08: stator resistance
F4-09: rotor resistance F4-10: mutual inductance resistance
F4-11: leakage inductance

Complete the motor parameter automatic tuning.

If the motor and load off completely, the F4-00 please select 1 (static tuning), and then press the RUN key on the
keyboard panel, also can obtain needed parameters.

Note: manufacturers recommend using tuning completely, this will help you to obtain more accurate parameters of
motor.

49
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Chapter 5 Parameter Description

5.1 F0 The basic functional group

Software version The factory value ###.##


F0-00
Set the range
Only for the user to see the software version, may be changed.

Models show The factory value Related to the aircraft

G type (constant torque load models)


F0-01 0
Set the range
P type (fan, water pump load models)
1
Only for the user to see the software version, may be changed.
0: is suitable for the specified rated parameters of constant torque load
1: is suitable for the specified variable torque load rated parameters of fan, water pump (load)

Rated current The factory value Related to the aircraft


F0-02
Set the range 0.1A~3000.0A
Only for the user to see the software version, may be changed.

The control mode


The factory value 0
Open loop flux vector control 1
0
(SVC1)
Open loop flux vector control 2
1
(SVC2)
F0-03 2 VFcontrol
Set the range A closed-loop vector
3
(FVC)/TQC Additional purchase of PG card
Torque control
4
(TQC) only for CM580 and CM580E use
PG Torque control
5
(TQCPG) only for CM580 and CM580E use
0: open-loop vector control
The vector control method is not sensitive to the motor parameters, typically require static to motor parameter
tuning can be stable and reliable operation, most of the motor can automatic correction in the process of operation
parameters, such as no-load current, minimum operating frequency of 1 hz, and can only be run under the
fundamental frequency, suitable for requiring higher performance, a frequency converter can only drive a motor.
1:2 open loop vector control
Applicable to the usual high performance control occasions, such as machine tools, centrifuge, wire drawing
machine, injection molding machine, such as load, can control the weak magnetic, can run above the fundamental
frequency (2 times).
2: VF control
Suitable for load demand is not high, or a frequency converter drive motor, such as fan and pump load, can be used
in the occasion of a frequency converter drive motor.
3: the closed-loop vector
A speed sensorless vector control operation mode, suitable for torque corresponding faster, higher torque and speed
control precision, drag the position control of the asynchronous motor can be completed with certain accuracy,
simple servo positioning control.
The following two kinds of control mode CM580 and CM580E use only
4: torque control
50
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Output torque converter control, need to have a speed sensorless vector control to achieve better control effect.

5: PG torque control
Torque control + coder can improve the accuracy of torque control.
Tip: choose the vector control method must be done when the motor parameter tuning process, only accurate motor
parameters can give a full play to the superiority of the vector control mode. Motor parameter tuning steps, see
tuning instructions, by adjusting the vector control regulator parameters (F3) can obtain better performance.

The source is set to run


The factory value
commands 0

Operation panel command channel


0
F0-04
Terminal command channel
Range set 1
Serial port communication command channel
2
Choose inverter control command channel, inverter control commands include: start, stop, forward, inversion,
points, etc.
0: operation panel command channel (" lights out L/D/C ");
By the operation panel on the RUN, the STOP/RES button to RUN the command control.
1: terminal command channel (" L/D/C "lights).
By the multifunctional input terminals FWD, REV, JOGF, JOGR to run the command control, etc.
2: serial port communication command channel (" L/D/C "lights flashing)
Run the command by the upper machine is given by way of communication.

The main frequency


The factory value 1
source X option
Digital set UP and DOWN to adjust (
0
No memory)
Digital set UP and DOWN to adjust (
1
Keep memory)
2 AI1
3 AI2
F0-06
Multistage speed
Range set 4
5 PLC
6 PID
7 Communications given
8 AI3
PULSE Set the pulse
9
Choosing the frequency converter input channel of a given frequency, a total of eight kinds of main a given
frequency channel:
0: digital set (memory)
The initial value for the F0-11 "digital frequency setting preset values.
Can increase or decrease by a keyboard key (or the input terminal of the UP and DOWN) to change the set
frequency value of the frequency converter.
No memory refers to the frequency converter after power off, set frequency values revert to F0-11 "digital
frequency setting preset values.

1: digital set (memory)


The initial value for the F0-11 "digital frequency setting preset values.
Can increase or decrease by a keyboard key (or the input terminal of the UP and DOWN) to change the set
frequency value of the frequency converter.
Memory refers to the frequency converter after power off back to electricity, set the frequency for the last time out
before the set frequency.

2: AI1

3: AI2
51
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Refers to the frequency by the analog inputs to determine. CM5X0E drives provide two analog input terminals, AI1,
AI2 can be 0 ~ 10 v voltage input, can also be used for 4 ~ 20 ma current input, choose by CN1 dial the code switch
on the control panel.
More than 4: period of speed
Choose the way to multistage speed operation. You need to set up F5 "inputs" and FC group "more speed and PLC"
parameter to determine if a given signal and the corresponding relation of a given frequency.

5: simple PLC
Select the simple PLC mode. PLC frequency source is simple and easy, you need to set up the FC group "more
speed and PLC" parameter to determine if a given frequency.

6: PID
The selection process PID control. At this point, you need to set up "PID" FA group, the frequency of the inverter
frequency for PID function after values, including PID given source, refer to quantitative, feedback source meaning
"PID" FA group is introduced.

7: communications given
Refers to the main frequency source by the upper machine through communications given (specific see CM5X0
series inverter serial communication protocol).

8: AI3 given
Refers to the frequency determined by the analog input terminal AI3, the input voltage is 0 ~ 10 v.

9: PULSE, PULSE frequency, given by the control board HDI6 terminal input but need to set DI terminal become
high-speed PULSE input.

Y choose auxiliary frequency


The factory value
sources 0

0 Digital set UP and DOWN to adjust (no memory)


1 Digital set UP and DOWN to adjust (Keep memory)
2 AI1
F0-07 3 AI2
4 Multistage speed
Range set
5 PLC
6 PID
7 Communications given
8 AI3
9 PULSE Set the pulse
Auxiliary frequency source as a separate frequency for a given channel, its usage is the same as the main frequency
source X.
When the auxiliary source used as frequency superposition given (i.e. frequency source selection for X + Y or X to
X + Y) switch from time to tome special as follows:
1, when the auxiliary frequency source for digital timing, preset frequency (F0-11) doesn't work, through the
increase or decrease in the keyboard keys (or multi-function input terminal of the UP and DOWN) can be
conducted on the basis of the Lord given frequency adjust UP and DOWN.
2, when the auxiliary frequency source for analog input given (AI1, AI2), 100% of the input set corresponding
auxiliary frequency source range (see F0-08 and F0-09), if need to be in the main on the basis of a given frequency
fluctuation adjustment, please set the analog input corresponding scope set to ~ + - n % n % (see F5 to 15 ~ F5-24).
Tip: auxiliary frequency source selection and the main frequency source X Y value cannot be the same, namely
advocate complementary frequency source cannot use the same frequency for a given channel.

Y relative auxiliary
The factory value 0
frequency sources
Relative to the maximum frequency
F0-08 0
Range
Relative to the main frequency source X
1

52
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Y relative auxiliary
The factory value 100%
F0-09 frequency sources
Range set 0%~100%
When selecting frequency source for frequency superposition given (F0-10 to 1 or 3), used to determine the
adjusting range of auxiliary frequency source. F0-08 relative object is used to determine the range, if compared
with the maximum frequency (F0-14), its scope is a fixed value, if the relative to the main frequency source X, then
the scope will change as the change of main frequency X.

Frequency source
selection The factory value 0

0 The main frequency source X


1 The main frequency source X Y + auxiliary frequency sources
The main switch frequency source and auxiliary frequency source
2
XY
3 Main frequency source with X (X + Y) switch
F0-10
4 Auxiliary frequency source with Y (X + Y) switch
Range set Main frequency source and the auxiliary frequency source take
big (Max (X, Y))
5
Note: in such a mode of auxiliary frequency source Y range
relative to the maximum frequency, F0-08 will no longer work
The main frequency source and the auxiliary frequency source in
6
small (Min (X, Y))
7 The main frequency source, the auxiliary frequency source
A given channel through which the parameter selection. Through the main frequency of source and auxiliary
frequency source X Y compound to achieve a given frequency.
When the option 1, frequency source "master frequency source X + auxiliary frequency source Y", which can
realize frequency superposition of a given function.
When choose 2, frequency source as the main source and auxiliary frequency source X Y switch by multi-function
input terminal terminal to switch "switching frequency source".
When choose 3, frequency source as the main frequency source with X (main frequency source X + auxiliary
frequency source Y) when switching by multi-function input terminal terminal to switch "switching frequency
source".
When selecting 4, frequency source for auxiliary frequency source with Y (main frequency source X + auxiliary
frequency source Y) when switching by multi-function input terminals "frequency source switch"
The terminal to switch. Which can realize frequency given way between mutual switch such as PID operation with
normal operation, simple PLC and general
Through running switch, analog switch is configured to run with normal switch.
When selecting 5, in the main frequency source and auxiliary frequency selection of maximum frequency source is
carried out.
When selecting 6, in the main frequency source and auxiliary frequency selection of minimum frequency source is
carried out.
When selecting 7, the main frequency source, auxiliary frequency source

The preset
The factory value 50.00Hz
F0-11 frequency
Range set 0.00 Hz~F0-14
When the main frequency source selection set for "digital" or "terminal UP/DN", the function code values for the
frequency of the inverter digital setting the initial value.

The driver output


The factory value 0
direction
F0-13 0 In the same direction
Range set 1 In the opposite direction
2 Ban reversal
By changing the function code can under the condition of without changing any other parameters change the
steering motor, its effect is equivalent to adjust motor (U, V, W) any two lines for motor direction of rotation
transformation.
Tip: after initialization parameter will restore the original state of the motor running direction. Good for system
debugging after careful is forbidden to change the motor to occasion
53
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

The largest operating


The factory value 50.00Hz
frequency
F0-14
Range set 50.00Hz~400.00Hz
Upper limit frequency
The factory value 0
source
0 F0-16
1 AI1
F0-15 2 AI2
Range set 3 Communications given
4 AI3
5 PULSEset
Define the upper limit frequency source. Upper limit frequency can be from digital set (F0-16), can also be from the
analog input channel. When was capped with analog input frequency, 100% of the analog input set corresponding
F0-14.
For example: when the torque control, speed control is invalid. Break a "flying car" in order to avoid material, can
use analog frequency cap, when the inverter running to the upper limit frequency value, the torque control is invalid,
frequency converter continuous maximum frequency operation.

Upper limit frequency The factory value 50.00Hz


F0-16
Range set F0-18~F0-14
Maximum frequency offset The factory value 0.00Hz
F0-17 0.00Hz~Maximum frequency
Range set
F0-14
When the upper limit frequency for analog to the timing, this parameter as the analog offset, its basic value is F0-14,
is the upper limit frequency offset frequency on the simulation value as the final cap on frequency value.

The lower frequency The factory value 0.00Hz


F0-18 0.00Hz~Upper limit frequency
Range set
F0-16
Started from the start, when the inverter running frequency, if during the operation of a given frequency is less than
the lower frequency, the frequency converter has been run in the lower frequency, until the inverter stop or a given
frequency is greater than the lower limit of frequency.

Deceleration reference The factory value 0


0 Maximum frequency
F0-22 Range set 1 Maximum frequency
2 Aim frequency
Deceleration time reference object.
Acceleration time 1 The factory value 30.0s
F0-23
Range set 0.0s~3000.0s
Deceleration time 1 The factory value 20.0s
F0-24
Range set 0.0s~3000.0s
Acceleration time 1 refers to the frequency converter from 0 hz to maximum output frequency required time t1
(F0-14).
Deceleration time 1 refers to the frequency converter (F0-14) from the maximum output frequency to slow down to
0 hz time t2.

54
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

CM5X0E

K 运行方向选择
SB2 FWD
0 正转 SB1 DIn

反转 K REV
1
COM/+24V

Figure 5-1 deceleration time

Pay attention to the actual deceleration time and set the deceleration time difference.
CM530E, 580 e series frequency converter of four groups of deceleration time choice
The first group: F0-23, F0-24;
The second group: F7-03, F7-04;
The third group: F7-05, F7-06;
The fourth group: F7-07, F7-08.
By multi-function digital input terminals (F5-00 ~ F5-04) choose deceleration time.

Overmodulation
choice The factory value 0
F0-25
0 invalid
Range set
1 valid
Carrier frequency The factory value Determination of models
F0-26
Range set 1.0kHz~15.0kHz
This function adjusting carrier frequency converter. By adjusting the carrier frequency can reduce electrical noise,
to avoid the resonance point of the mechanical system, reduce the line of floor drain current and reducing
interference caused by frequency converter.
When the carrier frequency is low, the output current of higher harmonic component increases, motor loss increase,
the motor temperature increase.
When high carrier frequency, the motor loss is reduced, the motor temperature rise reduced, but the loss of the
inverter increases, the frequency converter temperature increase, the interference

Adjust the impact of carrier frequency for the following properties:


Carrier frequency low → high
The motor noise big → small
The output current waveform bad → good
The motor temperature rise high → low
The temperature rise of the
low → high
frequency converter
Leakage current small → big
Foreign radiated interference small → big
Carrier frequency low → high
The motor noise big → small
The output current waveform bad → good
The motor temperature rise high → low
Note: the above factory set the carrier frequency is running, every increase 1 KHZ, inverter need derating 5% use.

55
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Carrier frequency
adjustment
The factory value 0
options

Fixed PWM carrier frequency temperature adjustment is


F0-27 0
invalid
Random PWM carrier frequency temperature adjustment
Range set 1
is invalid
2 Fixed PWM carrier effective temperature adjustment
3 Random PWM carrier effective temperature adjustment
Provide fixed and random PWM carrier frequency adjustment way. Random PWM motor noise frequency domain
wide, the fixed frequency PWM motor noise is fixed.
Carrier frequency temperature adjustment effectively, to automatically adjust the carrier frequency inverter can
according to their own temperature. Select the function may reduce the possibility of inverter overheat alarm.

Initialization parameter
The factory value 0

0 No operation
F0-28
Range set 1 Restore the factory Settings
2 Restore the last user preferences
3 Clear the fault record
To restore frequency parameters

Parameters of the copy


The factory value 0

0 Don't move
F0-29
Range set 1 Parameters to upload
Parameters to download
2
This parameter is only suitable for LCD keyboard

5.2 F1group Start-stop control

Start way
The factory value 0
F1-00 0 Direct start
Range set 1 Speed tracking start
2 Preliminary field start
0: direct start
If start the dc braking time is set to 0, from start frequency to start.
Start the dc braking time set to 0, a dc brake first, then start, applicable to small inertia load reversal may be
produced at startup.
1: the speed tracking and start again
Frequency converter for motor speed and direction first judge, again with tracking to the motor speed of the
corresponding frequency start, no impact on the smooth implementation of rotation of motor start, applicable to
large inertia load of the instantaneous power failure to start again. .

Fast track way The factory


0
value
0 Starting from the stop frequency
F1-01
1 Start from zero velocity
Range set
Starting from the maximum frequency
2
To use the shortest possible time to complete speed tracking process, choosing the way of frequency converter

56
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

motor speed tracking:


Zero: track down from the frequency of the power failure, usually choose this way;
1: start from zero frequency tracking upwards, in the case of power failure for a long time to start using;
2: the maximum frequency tracking down, general power load

Speed tracking current The factory


100%
F1-02 value
Range set 30%~180%
Speed tracking speed The factory
20.0
F1-03 value
Range set 1.0~100.0
When speed tracking startup mode again, choose the speed tracking speed, the parameters, the greater the tracking
speed faster, but too much can cause tracking is unreliable.

Start frequency The factory


0.00Hz
F1-04 value
Range set 0.00Hz~10.00Hz
Start frequency keep time The factory
0.0s
F1-05 value
Range set 0.0s~36.0s
The dc braking current The factory
0%
F1-06 value
Range set 0%~100%
Start the dc braking time The factory
0.0s
F1-07 value
Range set 0.0s~36.0s
Start the first generally used for dc brake motor completely stop and start.
If start way for direct start, starts first started in the setting of the dc inverter braking current on dc brake, after a set
start dc braking time and then started to run, if set dc braking time is 0, without dc brake boot directly.
Dc braking current, the greater the braking force, the greater the startup dc braking current refers to the percentage
of the relative frequency converter rated current.

S curve acceleration start time The factory


1.00s
F1-09 value
Range set 0.00s~25.00s
S curve acceleration over time The factory
1.00s
F1-10 value
Range set 0.00s~25.00s
S curve slow start time The factory
1.00s
F1-11 value
Range set 0.00s~25.00s
S curve to slow down over time The factory
1.00s
F1-12 value
Range set 0.00s~25.00s
This parameter can be used to set the drive in start began to accelerate without impact of slow start, the deceleration
curve changed from set point.
Different degrees of S curve acceleration and deceleration. Start the S curve slow deceleration, drive is on the basis
of the original deceleration rate of deceleration curve for different time.
Deceleration time = 0, S curve function is invalid

57
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Fmax

F1-09 F1-10 F1-11 F1-12


Figure 5-2 S deceleration curve diagram

Stop way
The factory value 0
Slowing down
F1-13 0
Range set
Free downtime
1
0: slow down parking
After downtime command effective, frequency converter according to the definition of deceleration mode and the
deceleration time to reduce the output frequency, frequency drop to zero after downtime.
1: free parking
After downtime command effective, inverter immediately put an end to the output. According to the mechanical
load inertia free parking

Stop dc brake starting


frequency The factory value 0.00Hz
F1-14
0.00Hz~Maximum frequency
Range set
Dc braking current
downtime The factory value 0%
F1-16
Range set 0%~100%
Stop dc braking time
The factory value 0.0s
F1-17
Range set 0.0s~36.0s
Outage dc brake starting frequency: slow down in the process, when arrived at the frequency, dc braking process
downtime.
Outage dc braking current: refers to the amount of direct current braking and, this value, the greater the dc braking
effect.
Outage dc braking time: time for dc brake quantity, this value is 0 means no dc braking, parking inverter according
to the set by slowing down the process.

Brake unit usage


The factory value 100%
F1-18
Range set 0%~100%
Built-in braking unit converter effectively. The braking effect of adjustable brake unit.

The instantaneous power


The factory value 0
failure to start again
F1-19 0 invalid
Range set 1 By the power cut speed tracking speed as before
2 From the minimum output frequency for speed tracking
Allow time when power
The factory value 1.0s
F1-20 supply drop
Range set 1.0s~5.0s
Power supply recovery
The factory value 1.0s
F1-21 waiting time
Range set 1.0s~50.0s

58
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Fmax

F1-09 F1-10 F1-11 F1-12

Map5-2 S Deceleration Curve Map

Stop way The factory value 0


F1-13 0 Decelerating down
Range set
1 Free down
0:decelerating parking
After downtime command effective, frequency converter according to the definition of deceleration mode and the
deceleration time to reduce the output frequency, frequency drop to zero after downtime.
1:free parking
After downtime command effective, inverter immediately put an end to the output.According to the mechanical
load inertia free parking.

Stop dc brake starting


Factory 0.00Hz
F1-14 frequency
Range set 0.00Hz~maximum frequency
Dc braking current
Factory 0%
F1-16 downtime
Range set 0%~100%
Stop dc braking time Factory 0.0s
F1-17
Range set 0.0s~36.0s
Outage dc brake starting frequency: slow down in the process, when arrived at the frequency, dc braking process
downtime.
Outage dc braking current: refers to the amount of direct current braking and, this value, the greater the dc braking
effect.
Outage dc braking time: time for dc brake quantity, this value is 0 Table shows no dc braking, parking inverter
according to the set by slowing down the process.

Brake unit usage Factory 100%


F1-18
Range set 0%~100%
Built-in braking unit converter effectively.The braking effect of adjustable brake unit.

The instantaneous power


Factory 0
failure to start again
F1-19 0 invalid
Range set 1 By the power cut speed tracking speed as before
2 From the minimum output frequency for speed tracking
F1-20 Allowing time when Factory 1.0s
59
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

power supply drop


Range set 1.0s~5.0s
Power supply recovery
Factory 1.0s
F1-21 waiting time
Range set 1.0s~50.0s
When the inverter power, inverter power supply recovery after startup option, when set to 0, F1-19 Table in inverter
power lost after power supply recovery, the inverter will not start automatically, until have run a command.Other
Settings, if after power off within the time allowed power - 20 (F1), power supply recovery after waiting time - 21
(F1) according to the set way to start again.

After power supply


Factory 0
recovery action choice
0 Stop running

F1-22 By the speed of tracking before


1
Range set useing
From the minimum output
2
frequency for speed tracking
3 Direct start
Instantaneous stop
Factory 1
function
F1-23
0 Instantaneous stop is invalid
Range set
1 Instantaneous stop keep effective

Instantaneous frequency
decrease rate mode
Factory 1
selection to stop
constantly
Choose the deceleration time1
0
(F0-23/F0-24)
F1-24 Choose the deceleration time2
1
(F7-03/F7-04)
Range set
Choose the deceleration time3
2
(F7-05/F7-06)
Choose the deceleration time4
3
(F7-07/F7-08)
When applications in instantaneous power, can use this function to motor with slow way to slow down to zero
speed, if the power recovery at this time, also can again start the motor after recovery time.

Instantaneous stop time to


Factory 1.0s
F1-25 recover
Range set 0.0~60.0s

5.3 V/F controls parameter of F2 group

The group function code only for V/F control mode, the V/F control for general load such as fan, water pump, or
one inverter with more motor, inverter power is smaller than the motor power level or big 2 above.
V/F curve set Factory 0
0 Linear VF curve
F2-00 1 Multipoint VF curve
Range set 2 Square VF curve
3 1.7 the power curve
4 1.3 the power curve
Fan pump type load, can choose square V/F control:
1: V/F more curve, is suitable for centrifuge dewatering machine, and other special load;
2: square curve of V/F, such as fans and pumps suitable for centrifugal load.
60
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

3 ~ 4: V/F curve for many times, such as fans and pumps suitable for centrifugal load.

Torque increase Factory 2.0%


F2-01
Range set 0.0%~30.0%
Torque increase the
Factory 5.0Hz
F2-02 cut-off frequency
Range set 0.0Hz~50.0Hz
To compensate for low frequency torque characteristics, V/F control the low frequency inverter output voltage
when do some compensation.
Ascension too large torque, motor easy to overheat, inverter is easy to flow.In general, a torque not more than 8.0%.
Effective adjustment of the parameters, which can effectively avoid starting over current situation, for large load,
suggest increase this parameter, when the load is lighter can decrease this parameter is set, when the torque is set to
0.0, automatic torque converter for.
Torque increase torque cut-off frequency: the frequency, torque increase torque effectively, more than the set
frequency, torque increase failure, specific see Map5-3。

内 F7-09
部 F7-10
频 F7-11
率 F7-12
指 F7-13
令 F7-14

设定频率指令
Map5-3 Manual torque Map

V/FFrequency Factory 0.00Hz


F2-03 point1(Hz)
Range set 0.00Hz~50.00Hz
V/FVoltage point1(%) Factory 0.0%
F2-04
Range set 0.0%~100.0%
V/FFrequency Factory 0.00Hz
F2-05 point2(Hz)
Range set 0.00Hz~50.00Hz
V/FVoltage point2(%) Factory 0.0%
F2-06
Range set 0.0%~100.0%
V/FFrequency Factory 0.00Hz
F2-07 point3(Hz)
Range set 0.00Hz~50.00Hz
V/FVoltage point3(%) Factory 0.0%
F2-08
Range set 0.0%~100.0%

F2-03 ~ F2-08 more than six parameters defined section V/F curve.
The value of V/F curve usually set according to the load characteristic of the motor.
Note: V1 V2 < < V3, F1 F2 < F3, low-frequency voltage set too high may lead to motor overheating or even
burning, the inverter may be a loss of speed or over current protection.

61
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

死区时间

Map5-4 V/F Curve Set Map


Slip compensation
Factory 0.0%
F2-09 coefficient
Range set 0.0%~200.0%
Based on V/F control effectively.Set this parameter to compensate for load application of V/F control slip, make the
V/F control motor speed changing with load variation decreases, and the general was 100% when the motor with
rated load rating of the slip.
Slip coefficient adjustment may refer to the following principles: when the load is rated load, slip compensation
coefficient was 100%, the inverter with the speed of the motor base close to the given speed.

AVR choice Factory 64


F2-10
Range set 0 ~ 200
Easily over voltage alarm, the process of converter reduction need to improve the magnetic flux brake gain, but
magnetic flux brake profit is too big, easy to cause the output current increases, need to weigh in the application.
On the occasion of moment of inertia is small, do not show up in the motor speed voltage rise, suggested setting
flux brake gain to zero;To places that have requirements of braking resistor, also suggested that magnetic flux brake
gain is set to 0.

The oscillation Factory 20


F2-11 suppression gain
Range set 0 ~ 100
Vector 1 low frequency Factory 100
F2-12 torque increase gain
Range set 0 ~ 200

In 1 cases improve the low frequency torque vector control mode, the greater the F2-12 torque is bigger, the big but
high electric current may cause damage of motor.

Vector 1 low frequency Factory 700


F2-13 torque cutoff frequency
Range set 0 ~ 1000
Low frequency Factory 200
compensation filter
F2-14
coefficient vector 1
Range set 1 ~ 9999
Vector 1 filter coefficient Factory 100
F2-15 of torque electric current
Range set 1 ~ 2000

62
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5.4 F3 group vector control parameters

F3 group function code applies only to the vector control, namely the F0-03 = 1.

Switching frequencyF1 Factory 5.00Hz


F3-00
Range set 1.00Hz~F2-02Hz

Switching frequencyF2 Factory 10.00Hz


F3-02
Range set F3-00~F0-14
Low frequency speed proportional
Factory 2.000
F3-04 gain
Range set 0.001~10.000
Low frequency speed integration
Factory 0.500s
F3-05 time
Range set 0.001s~10.000s
High frequency speed
Factory 1.000
F3-06 proportional gain
Range set 0.001~10.000
High frequency speed integration
Factory 1.000s
F3-07 time
Range set 0.001s~10.000s

Speed loop integral attribute Factory 0


F3-08 0:Points are not isolated
Range set
1:Points are isolated
By setting the speed regulator of the proportional coefficient and integral time, can adjust the speed of dynamic
response characteristics of vector control, increase the proportional gain, decrease the integration time, all can speed
up the speed loop dynamic accordingly, the proportional gain is too large or too little integration time could make
the system produce oscillation.

Suggestion adjustment method:


If Factory parameters can't meet the requirements, the Factory parameters based on fine-tuning, to increase the
proportional gain, ensure no oscillation system;And then reduce the integration time, make the system has faster
response, smaller overshoot

63
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

F3-04
F3-05

F3-06
F3-07

F3-00 F3-02
频率
. Frequency

Map5-5 Switching speed loop PI parameters Map

Torque current regulator


Factory 1000
F3-11 Kp
Range set 30000Kp
Torque current regulato
Factory 1000
F3-12 Ki
Range set 0~30000
Torque current regulator
Factory 1000
F3-13 Kp
Range set 0~30000
Torque current regulator
Factory 1000
F3-14 Ki
Range set 0~30000
The open loop vector
Factory 2
function of AVR
0 The whole is invalid
F3-15
Range set 1 The whole is valid

2 Invalid when just slow down

Vector control loop current PI control parameters, the parameters in the asynchronous machine will automatically
receive after complete tuning, generally does not need to be modified, current loop integral controller, integration
time is not used as the dimension, but directly setting the integral gain.Current loop PI gain setting is too big, can
lead to the control loops oscillation, so when the oscillation or greater torque ripple current, can be manually reduce
the PI proportional gain and integral gain here.
AVR function, vector control system with AVR function of V/F control

Weak magnetic curve gain Factory 100%


F3-16
Range set 50%~150%
The output voltage of the into the weak magnetic area, users can adjust the F3-16.
The applications of in speeding, adjust way:
64
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

1: let the motor run to the maximum frequency point;


2: to observe the output voltage;
3: adjust the parameter F3-16, make the output voltage to the motor rated voltage;
4: the greater the value, the greater the output voltage;

Slip the senders gain(%) Factory 100%


F3-17
Range set 50%~200%
To the speed sensorless vector control, this parameter is used to adjust motor steady speed precision, when the
speed is larger, the parameter tuning is small, and large

Speed loop feedback Factory 0.000s


low-pass filtering time
F3-18
constant
Range set 0.000s~0.100s

Speed loop output filter Factory 0.000s


F3-19 time constant
Range set 0.000s~0.100s
Vector control mode, the output of the speed loop controller for the torque current instruction, the parameters used
for torque command filter, generally do not need to adjust the parameters, the speed when the volatile can be
appropriately increase the filtering time, if the motor appear oscillation, this parameter should be reduced.
Speed loop output filter time constant is small, the inverter output torque may change is bigger, but the response is
fast.

The electric torque limit


Factory 0
source
0 F3-21

1 AI1(Analog scaleF3-21)

F3-20 2 AI2(Analog scaleF3-21)


Range set
3 AI3(Analog scaleF3-21)

4 PLUSE GIVEN

5 COMMUNICATION GIVEN
Electric torque limit Factory 150%
F3-21
Range set 0%~200%
Brake torque limit Factory 0
0 Brake torque limit F3-23
1 AI1
F3-22 2 AI2
Range set
3 AI3
4 PLUSE GIVEN
5 COMMUNICATION GIVEN
Brake torque limit Factory 150.0%
F3-23
Range set 0.0%~200%

65
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

F3-21 for electric torque setting, F3-23 for selecting braking torque setting, other set maximum F3-21 and F3-23.

5.5 F4 set motor parameters

Motor parameters Factory 0


tuning
F4-00 0 No function
Range set 1 Static tuning
2 Totola tuning

Tip: before tuning, you must set up the correct motor rated parameters (F4-01 ~ F4-06)
0: no operation, namely the tuning is prohibited.
1: static tuning, applicable to the motor and load is not easy to release and cannot rotate the occasion of tuning.
Action: in F0-04 equals 0 mode, set up the function code is 1, and press the RUN button confirmation, inverter will
conduct static tuning.
2: complete tuning
In order to guarantee the dynamic control of the frequency converter performance, please select a rotary tuning,
rotating tuned motor must and load off (light).
Choose rotation after tuning, tuning frequency converter to rest, rest after the tuning machine in accordance with
the acceleration of the F4-12 accelerated to 80% of the rated frequency motor, and maintain a period of time, and
then in accordance with the reduction of the F4-13 speed slowed to zero speed, rotating end of tuning.
Action: set the function code is 2, and press the RUN button confirmation, inverter will rotate the tuning.
Tuning instructions:
When the F4-00 to 0 and then press ENTER, flashing "most cerebral sci-film" and right now, and then press the
RUN button to start the parameters tuning, flashing "most cerebral sci-film" stop at this time.When after the tuning,
display interface back to stop state.In the process of tuning can press the STOP button to suspend the tuning.When,
after the completion of tuning the F4-00 value automatic recovery of 0.

The rated power Factory modules determination


F4-01
Range set 0.4kw~1000.0kw
The rated voltage Factory 380V
F4-02
Range set 0V~440V
The number of motor Factory modules determination
F4-03
Range set 2~64
The Factory modules determination
F4-04 rated current
Range set 0.1A~3000.0A
The rated frequency Factory 50.00Hz
F4-05
Range set 0.00Hz~maximum frequency
The rated speed Factory 1460rpm
F4-06
Range set 0 rpm~30000rpm
The no-load current Factory modules determination
F4-07
Range set 0.1A~1500.0A
The stator resistance Factory modules determination
F4-08
Range set 0.001Ω~65.535Ω
The rotor resistance Factory modules determination
F4-09
Range set 0.001Ω~65.535Ω

66
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Mutual inductance
Factory modules determination
F4-10 resistance
Range set 0.1mH~6553.5mH
Leakage inductance Factory modules determination
F4-11
Range set 0.01 mH~655.35mH
Fully tuned acceleration Factory 100
F4-12
Range set 1~60000
Tuned in full speed
Factory 100
F4-13 reduction
Range set 1~60000
The encoder pulse
number Factory 1024
F4-14
Range set 1~9999
The encoder input form Factory 0
F4-15
Range set 0~1
The encoder to choose Factory 0
0 ABZ Incremental encoder
1 UVW Incremental encoder
F4-16 Province line UVW incremental
Range set 2 encoder
3 Rotating transformer
4 sin/cos coder
Spiral pole changing
logarithmic Factory 2
F4-17
Range set 1~65535
Rotary encoder
excitation signal Factory 7.0KHz
F4-19 frequency setting
Range set 2.0 KHz~20.0 KHz

! Caution
1,please according to the motor nameplate parameters are set.
2,good control performance of vector control, need accurate motor parameters, accurate parameter identification
from the motor rated parameters is set up correctly.
3,in order to ensure that controlling, please according to the standard of frequency converter adapter motor for
motor configuration, if the motor power and the standard adapter gap is too large, the control performance of
transducer will be markedly reduced.

5.6 F5 group of input terminals

CM5X0E series inverter standard cell with 5 multi-function digital input terminals, two analog input terminal, if the
system needs more input/output terminals, can choose our expansion card.(X represents Table 3or8)
DI1 terminal function choice Factory 1
F5-00
Range set 0~34
DI2 terminal function choice Factory 2
F5-01
Range set 0~34
F5-02 DI3 terminal function choice Factory 3

67
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Range set 0~34


DI4 terminal function choice Factory 9
F5-03
Range set 0~34
DI5 terminal function choice Factory 12
F5-04
Range set 0~34
DI6 terminal function choice Factory 13
F5-05
Range set 0~34
DI7/HD Iterminal function
Factory 14
F5-05 choice
Range set 0~34
DI7 terminal function choice
(IO-1 expansion card) Factory 0
F5-06
Range set 0~34
DI8 terminal function choice
Factory 0
F5-07 (IO-1 expansion card)
Range set 0~34
DI9 terminal function choice
(IO-1 expansion card) Factory 0
F5-08
Range set 0~34

Note: when DI7 choice for high-speed pulse input is set F5-05 to 34.

This parameter is used to set digital multi function input terminal corresponding to the function.
The set
Function Explanation
value
Even with the signal input transducer is not action, but will not use jokes
0 No function
set the function to prevent misoperation
Running forward
1
(FWD) Through the external terminals to control the inverter forward and
Reverse running inversion
2
(REV)
Three-wire system Through the terminal to determine the frequency converter operation mode
3
operation control are the three line control mode
turning point move
4
(FJOG) FJOG run for point to move forward, RJOG for dynamic inversion
Reversal point move operation
5
(RJOG)
By external terminal changes when a given frequency increasing frequency
6 Terminal UP
instructions, decreasing.When set the frequency source as digital set set
7 Terminal DOWN frequency can be adjusted up and down
Blockade and output frequency converter, motor parking process is not
8 Free parking controlled by the frequency converter.For large inertia of load and there is
no requirement on parking time, often taken by the method
External fault reset function.With the RESET key on the keyboard function
9 Failure reset RESET)
is the same
Frequency converter and stop, but all operation parameters for the memory
state.Parameters such as PLC, frequency parameters, the PID
10 Run to suspend
parameters.The signal disappears, the inverter back to the front of the
parking status
Normally open input When external fault signal to frequency converter, frequency converter
11
External fault reported failures and downtime
68
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

The set
Function Explanation
value
Multistage speed
12
termina l1
Multistage speed
13 It can be combined by the four terminal state of digital setting of a total of
terminal 2
16 segment speed can be realized
Multistage speed
14 See Table1 detailed combination
terminal 3
Multistage speed
15
terminal 4
Ac-deceleration time
16 Through the state of digital combination of the two terminals to choose
choosing terminal 1
four deceleration time
Ac-deceleration time
17 Detailed portfolio see Table2
choosing terminal 2
Switching frequency Through the terminal to the main frequency source and auxiliary switch
18
source frequency source Y and X
Give a figure for timing when frequency, the terminal can change
Set UP/DOWN reset
19 frequency values of clearing UP/DOWN, return to make a given frequency
(terminal, keyboard)
F0-11 set of values
When the command source for the keyboard, through the terminal to
Run the command terminal control and keyboard control switch
20
switch terminals When for communication, through this terminal can communicate with the
keyboard control
Deceleration is Ensure the inverter is not affected by external signal (except halt
21
prohibited command), to maintain the current output frequency
PID temporary failure, frequency converter to maintain the current
22 PID failure
frequency output
PLC in the execution of suspension, the runtime can be effectively easy to
23 PLC state reset
restore to the PLC through the terminal of the initial state
The pendulum
24 Inverter with center frequency output.The pendulum frequency suspended
frequency suspended
Timer when the input signal effective time to achieve timing time when
25 Timer trigger input
closed, the timing output function effectively.
26 Dc brake command Dc brake command.
External input fault When external fault signal to frequency converter, frequency converter
27
normally closed reported failures and downtime
28 Counter input Count pulse input terminals
29 Counter reset To counter reset
Counting the length
30 The input terminals of length count
of the input
The length of the
31 The length of the reset
reset
Torque control is
32 Ban inverter torque control mode
prohibited
PULSE(pulse)
33 For the pulse input terminals
frequency
34 PID switch Two groups of PID switch terminals

Table1Multistage speedfunction explanation

K4 K3 K2 K1 The frequency set Corresponding parameters

OFF OFF OFF OFF Multistage speed0 FC-00

OFF OFF OFF ON Multistage speed1 FC-01

69
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

K4 K3 K2 K1 The frequency set Corresponding parameters

OFF OFF ON OFF Multistage speed2 FC-02

OFF OFF ON ON Multistage speed3 FC-03

OFF ON OFF OFF Multistage speed4 FC-04

OFF ON OFF ON Multistage speed5 FC-05

OFF ON ON OFF Multistage speed6 FC-06

OFF ON ON ON Multistage speed7 FC-07

ON OFF OFF OFF Multistage speed8 FC-08

ON OFF OFF ON Multistage speed9 FC-09

ON OFF ON OFF Multistage speed10 FC-10

ON OFF ON ON Multistage speed11 FC-11

ON ON OFF OFF Multistage speed12 FC-12

ON ON OFF ON Multistage speed13 FC-13

ON ON ON OFF Multistage speed14 FC-14

ON ON ON ON Multistage speed15 FC-15

Table2 Ac-deceleration function explanation

Terminal 2 Terminal 1 Ac-deceleration Corresponding parameters


time choice

OFF OFF To speed up the F0-23、F0-24


time 1

OFF ON To speed up the F7-03、F7-04


time 2

ON OFF To speed up the F7-05、F7-06


time 3

ON ON To speed up the F7-07、F7-08


time 4

70
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

DI Filtering time Factory 10ms


F5-10
Range set 0 ms~3600 ms
Set DI terminal sensitivity, if encounter digital input terminals are susceptible to interference caused by
misoperation, this parameter can be increased, the anti-interference ability enhancement, but the cause of DI
terminal lower sensitivity.

Terminal command mode Factory 0


0 two-wire system 1
F5-11 1 two-wire system 2
Range set
2 three-wire system 1
3 three-wire system 2
This parameter defines the external terminal control frequency converter running four different ways.

0:two-line operation mode


1: this pattern is most commonly used mode of two lines, by FWD, REV terminal command to determine the
positive and reverse of the machine.

CM Series
CM530
K1 K2 Running Commanc
0 0 Stop
1 0 Forward Rotation
K1
0 1 Reverse Rotation K2
FWD
REV
1 1 Stop COM/+24V

Map5-7 Two-line operation mode 1


1: two line operation mode 2: use this mode when the REV for the terminal, to determine the direction by FWD.

CM530
CM Series
K1 K2 Running Commanc
0 0 Stop
1 0 Stop
K1
0 1 Forward Rotation K2
FWD
REV
1 1 Reverse Rotation COM/+24V

Map5-8 Two-line operation mode 2


2: three line operation pattern 1: can the model Din to make terminal, direction by FWD, REV control
respectively.But when parking pulse effectively, must be done through disconnect Din terminal signal.

71
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

CM Series
CM系列

SB2 FWD
SB1 DIn
SB3 REV
COM/+24V

Map5-9 Three-line operation mode 1

And:

SB1:Stoping button

SB2:Forward button

SB3:Reverse button
Din is DI1 ~ DI6 function input terminals, at this time should be the corresponding terminal function is defined as 3
function "three-wire system operation control.

3: three line operation mode 2: this pattern can make terminal for Din, run the command given by FWD, direction is
determined by the state of the REV.
The shutdown is commanded by disconnecting Din signal to complet.

CM 5X0E

bit1 bit0

T1 T0

DO0 REL1

Map5-10 Three-line operation mode 2

And:
SB1: Stoping button
SB2: running button
Din is DI1 ~ DI6 function of input, at this time should be the corresponding terminal function is defined as 3
function "three-wire system operation control.
Terminal change rate UP/DOWN Factory 1.00
F5-12
Range set 0.01~100.00
0:The target frequency
F5-13 UP/DOWN frequency of reference
1:The running frequency

terminalUP/DOWN To adjust the rate of change of the set frequency.

72
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

AI1 minimum input (V) Factory 0.00v


F5-15
Range set 0.00~10.00
AI1 minimum input corresponding
Factory 0.0%
F5-16 set (%)
Range set -100.0%~100.0%
AI1 maximum input (V) Factory 10.00v
F5-17
Range set 0.00~10.00
AI1 input corresponding to the
Factory 100.0
F5-18 largest set (%)
Range set -100.0~100.0
AI1 input Filtering time (S) Factory 0.10
F5-19
Range set 0.00~10.00
The above function code defines The analog input voltage and analog input and The relationship between The set
value of The Table, when The analog input voltage more than set The range of maximum input or minimum input,
outside part will be calculated to maximum or minimum input.
Current input for analog input, 1 ma current equivalent to a 0.5 V voltage.(AI3, AI2, AI1 Settings the same)
In different applications, the simulation's 100% of the nominal value is different, specific please refer to the various
parts of the application.
The following Map example illustrates several set of conditions:

Corresponding Settings Corresponding Settings


(Frequency, Torque, etc.) (Frequency, Torque, etc.)
100.0% 100.0%

0V 10V
(0mA) (20mA)
AI

AI -100.0%
0.0%
0V
(0mA)

Map5-11 Set to a given and quantitative corresponding relations

AI2 The minimum input(V) Factory 0.00v


F5-20
Range set 0.00~10.00
AI2 The minimum input
Factory 0.0
F5-21 corresponding set(%)
Range set -100.0~100.0
AI2 The maximum input(V) Factory 10.00v
F5-22
Range set 0.00~10.00
AI2 The maximum
Factory 100.0
F5-23 inputcorresponding set(%)
Range set -100.0~100.0
AI2 The input filtering time(S) Factory 0.10
F5-24
Range set 0.00~10.00
AI3 The minimum input(V) Factory 0.00v
F5-25
Range set 0.00~10.00
AI3 The minimum
Factory 0.0
F5-26 inputcorresponding set(%)
Range set -100.0~100.0
73
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

AI3 The maximum input(V) Factory 10.00v


F5-27
Range set 0.00~10.00
AI3 The maximum
Factory 100.0
F5-28 inputcorresponding set(%)
Range set -100.0~100.0
AI3 The input filtering time(S) Factory 0.10
F5-29
Range set 0.00~10.00
PULSE(impluse)input
Factory 0.00
F5-30 the minimum frequency(KHz)
Range set 0.00~50.00
PULSE(impulse )input
the minimum Factory 0.0
F5-31 frequencycorresponding set(%)
Range set -100.0%~100.0%
PULSE(impulse )input
Factory 50.00
F5-32 maximum frequency(KHz)
Range set 0.00~50.00
PULSE(impulse )input
maximum frequencycorresponding Factory 0.0
F5-33 set(%)
Range set -100.0%~100.0%
PULSEinputFiltering time(S) Factory 0.10
F5-34
Range set 0.00~10.00
DI3Open the delay time Factory 0.0S
F5-35
Range set 0.0S~3600.0S
DI3close the delay time Factory 0.0S
F5-36
Range set 0.0S~3600.0S
DI4Open the delay time Factory 0.0S
F5-37
Range set 0.0S~3600.0S
DI4close the delay time Factory 0.0S
F5-38
Range set 0.0S~3600.0S
DI5Open the delay time Factory 0.0S
F5-39
Range set 0.0S~3600.0S
DI5close the delay time Factory 0.0S
F5-40
Range set 0.0S~3600.0S
DI3terminal effective model Factory 0
F5-41 0 close-valid
Range set
1 cut-valid
DI4terminal effective model Factory 0
F5-42 0 close-valid
Range set
1 cut-valid
DI5terminal effective model Factory 0
F5-43 0 close-valid
Range set
1 cut-valid
Analog AI1 input way more choice Factory 0
0 F5-15~F5-19
F5-44
Range set 1 FA-00~FA-07
2 FA-08~FA-15
Analog AI2 multipoint input mode
Factory 0
selection
F5-45 0 F5-15~F5-19
Range set 1 FA -00~FA -07
2 FA -08~FA -15
Is used to set DI terminal state changes, frequency converter for different state the delay time of change, at present
only DI3 ~ DI5 have this function.

74
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5.7 input terminal of F6 group

CM5X0E series inverter standard unit has more than two function digital output terminals, more than two function
relay output terminals, more than two function analog output terminals, such as the need to increase the relay output
terminal and analog output terminals, can choose and buy the company's expansion card.
Control board relay RELAY1
Factory 2
F6-00 output option
Range set 0~21
Control board relay RELAY2
Factory 1
F6-01 output option
Range set 0~21
Y1 output option Factory 0
F6-02
Range set 0~21
FM terminal output mode
Factory 1
selection:
0 impulse output(FMP)
F6-04
Range set 1 Open collector output switch
2 Used as AO3 output
FMR output option Factory 0
F6-05
Range set 0~21
FMP output selection, impulse
Factory 0
F6-06 output
Range set 0~21
IO - 2 extension board relay Factory 0
F6-07
Range set 0~21
IO - 2 extension board relay Factory 0
F6-08
Range set 0~21

Multifunctiooutput terminal function choiceas followed:


This parameter is used to set digital multi function output terminal corresponding to the function.

The set value Function Explanation

0 No function No function for teminal output

In the operation of the


1 In the operation of the converter
converter
2 The fault output When the inverter failure occurs, the output ON signal
Frequency level detection
3 Frequency level detection of FDT arrive
of FDT arrive

4 Frequency arrival Frequency arrival


In the operation of the
5 When the inverter failure occurs, the output ON signal
zero speed
Electronic motor thermal protection action before, according to
Motor overload
6 the overload forecast value judgment, after more than forecast
forecasting warning
value output ON signal

7 Inverter overload After checking the inverter overload, in premise before 10 s in


75
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

The set value Function Explanation


forecasting warning protection, output ON signal

The PLC cycle to After completing a cycle when simple PLC output impulse
8
complete signal of a width is 250 ms

9 Runing time arrival Total run time more than set time output ON signal
When set to the frequency of more than, lower limit and lower
10 In the frequency limit limit of frequency inverter output frequency to reach, frequency,
output ON signal

Main circuit and control circuit of power supply, frequency


11 Ready to run converter to protect the function action, frequency converter in
the runnable state, output ON signal
When analog inputAI1 value is greater than the other way
12 AI1>AI2
inputAI2, output ON signal
The high frequency
13 When operating frequency to limit frequency output ON signal
arrival

When the operation frequency to the lower frequency output


14 The low frequency arrival
ON signal
15 Undervoltage state output The inverter is in a state of undervoltage output ON signal
16 communication set communication set

When setting the input a terminal for the timer inputfunction


17 Timer output function after F7-39 time this function terminal close - valid, such as the
input is invalid after F7-40 this function terminal disconnection

Direction of rotation
18 Direction of rotation speed value
speed value

19 Current limit Current limit

When testing the actual length of more than set length, output
20 Length arrival
ON signal
When the torque limit function, stalling protection function
21 The torque limit
automatic action

AO1 output choice Factory 0


F6-09
Range set 0~7
AO2 output choice Factory 0
F6-10
Range set 0~7
FMP output maximum frequency(KHz) Factory 50.0
F6-11
Range set 0.0~50.0

Analog output to standard output (zero bias of 0, gain is 1) to 0 ~ 20 ma (or 0 ~ 10 v).

76
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

AO、FM output functionTable:

The set
Function Range
value
Running
0 0~max output frequncey
frequency
Setting
1 0~max output frequncey
frequency

2 Output current 0~2double Inverter rated current

3 Output power 0~2double Inverter rated current

4 Output voltage 0~1.2double Inverter rated voltage

5 AI1 0~10V

6 AI2 0~10V/0~20mA

Communicaiton For details, refer to <the attachment CM5X0E series inverter communication
7
set protocol>
The Table below the scope of corresponding to the amount shown in the Table below:
AO1Zero bias coefficient(%) Factory 0.00%
F6-12
Range set -100.0%~100.0%
AO1 increase Factory 1.00
F6-13
Range set -10.00~10.00
AO2Zero bias coefficient(%) Factory 0.00%
F6-14
Range set -100.0%~100.0%
AO2 increase Factory 1.00
F6-15
Range set -10.00~10.00
If use "b" Table to show zero, gain with kTable, actual output with YTable, standard output with XTable, actual
output is Y = kX + b;
AO1, AO2Zero bias coefficient100 corresponding 10 v % (20 ma).
Standard output is 0 ~ 10 v (20 ma) corresponding to the analog output Table shows the amount of 0 ~ is the largest.
Commonly used for correction of analog output zero drift and the deviation of the output amplitude output curve
can also be customized for any need:

For example: if the analog output content for running frequency, hope that when the frequency of 0 8 v output 16
(ma) and frequency for maximum frequency, output 3 v (ma), the gain should be set to "0.50", zero bias should be
set to "80%".
AO1min output voltage Factory 0.00v
F6-16
Range set 0.00~10.00
AO1max output voltage Factory 10.00v
F6-17
Range set 0.00~10.00
AO2min output voltage Factory 0.00v
F6-18
Range set 0.00~10.00
AO2max output voltage Factory 10.00v
F6-19
Range set 0.00~10.00

AO output for direct limit output, for part of the customers' need to directly set minimum and maximum effective
FE - 23 set to 1.

77
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5.8 F7 group auxiliary function and user-machine interface function

Inching operation
Factory 6.00Hz
frequency
F7-00
Range set 0.00Hz~F0-14
Inching to speed up
Factory 1.0s
F7-01 the time
Range set 0.00s~3000.0s
Point move to slow
Factory 1.0s
down time
F7-02
Range set 0.00s~3000.0s
Defining point move when given the frequency of frequency converter and ac - decelaration time, inching process
according to the startup mode 0) (F1-00, direct start and stop the way 0 (F1-13, and stop) to stop.
Point move to speed up the time refers To the frequency converter from 0 hz accelerated To time needed for
maximum output frequency (F0-14).
Inching deceleration time refers to the frequency converter (F0-14) reduction from maximum output frequency to
the time needed for 0 hz.

To speed up the time2 Factory 3.0s


F7-03
Range set 0.0s~3000.0s
Deceleration time2 Factory 2.0s
F7-04
Range set 0.0s~3000.0s
To speed up the time3 Factory 3.0s
F7-05
Range set 0.0s~3000.0s
decelaration Factory 2.0s
F7-06 time3
Range set 0.0s~3000.0s
To speed up the time4 Factory 3.0s
F7-07
Range set 0.0s~3000.0s
decelaration time4 Factory 2.0s
F7-08
Range set 0.0s~3000.0s
Ac - decelaration time can choose F0-23 and 24 and the above three kinds of ac - decelaration F0 - time, its
meaning are the same, please refer to the F0-23 and F0-24 related instructions.
Can more than through the different combination of the function of digital input terminals DI to select the inverter
ac - in the process of running decelaration time1 ~ 4.Please refer to the function code F5-00 ~ F5-04.

Hopping frequency1 Factory 0.00Hz


F7-09
Range set 0.00Hz~300.00 Hz
Hopping frequency2 Factory 0.00Hz
F7-10
Range set 0.00Hz~300.00 Hz
Hopping frequency3 Factory 0.00Hz
F7-11
Range set 0.00Hz~300.00 Hz
Hopping frequency4 Factory 0.00Hz
F7-12
Range set 0.00Hz~300.00 Hz
Hopping frequency5 Factory 0.00Hz
F7-13
Range set 0.00Hz~300.00 Hz
Hopping frequency6 Factory 0.00Hz
F7-14
Range set 0.00Hz~300.00 Hz

78
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

When a set frequency Hopping frequency range, the actual operation frequency will be run in closer from the set
frequency Hopping frequency boundary, by setting the Hopping frequency, the frequency converter to avoid negtive
mechanical resonance point.This converter can be set up three jumping Frequency point, if the adjacent two
Hopping Frequency is set to the same value, the Frequency of this function does not work.

PID参数

PID参数1
FA-06 ~ FA-08

PID参数1
FA-18 ~ FA-20

FA-22 FA-23
PID偏差
Map5-12 Hopping Frequency Map

Positive & negative dead


Factory 0.0s
F7-15 zone
Range set 0.0s~3000.0s
Set the frequency converter and reversing transition in the process, in the output at zero frequency over time.As
followed map displays:

Dead zone time

Map5-13 Positive & Negative Dead Zone Map

Rotate the keyboard control


Factory 0
precision
0 Normal acceleration
1 0.1Hz
2 0.5Hz
F7-16 3 1Hz
Range set 4 2Hz
5 4Hz
6 5Hz
7 8Hz
8 10Hz
Set the frequency is lower than the Factory 0
lower limit frequency
In the lower frequency
F7-17 0
operation
Range set
1 downtime
2 Running with 0 speed
Choose when setting frequency is lower than the lower limit frequency converter running state.
In order to avoid the motor under low speed running for a long time, can use this function to select downtime.action

79
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Droop control Factory 0.00Hz


F7-18 Range set 0.00Hz~10.00Hz

When more than one inverter drive negtive load caused by different speeds negtive uneven load distribution, load
speed larger inverter with heavier negtive.Droop control features to make the speed droop change as negtive load,
can make the negtive load equilibrium.
This parameter adjustment speed droop of the frequency change of the frequency converter.

Delay time of frequency is lower Factory 0s


than the minimum downtime
F7-19
Range set 0.0s~600.0s

When setting frequency is lower than the lower limit frequency action choice for downtime, delay F7-19 action
time.

Setting running time Factory 65535H


F7-20
Range set 0h~65535h
Terminal point dynamic priority
Factory 0
choice
F7-21
Range set 0~1
Preset frequency converter running time.
When the total run time (F7-34, F7-35) reach the set run time, inverter output function digital DO run more time
signal.

A frequency values (FDT level) Factory 50.00Hz


F7-22
Range set 0.00Hz~maximum frequency
A frequency values (FDT level) Factory 5.0%
F7-23
Range set 0.0%~100.0%
A set of output frequency values and cancel the lag value of the output motion.

Output Frequency

FDT Level
FDT Hysteresis

Frequency Detection t
Signal(DO1 RELAY)

ON

Map5-14 FDT Level Map

Frequency to check out the width Factory 0.0%


F7-24
Range set 0.0%~100.0%
Inverter output frequency reaches a set frequency value, the function can adjust the amplitude detection。As
followed Map displays:

80
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Output Frequency

Detected
Amplitude

Frequency
Detection Signal ON ON
(DO1 RELAY)

Map5-15 Frequency To Detect Amplitude Map

0:runing with 0 speed


F7-25 Negtive frequency choice
1:reverse-positive running

Running time to action Factory 0


F7-26 0 Continue running
Range set
1 downtime
STOP/RESET keyboard function Factory 0
Only valid at the time of the keyboard
0
control way
In the terminal control STOP STOP
F7-27 1
function effectively
Range set
When the terminal control STOP reset
2
function effectively
Terminal control when the STOP button
3
down and fault reset function are effective
Keyboard JOG function choice Factory 0

F7-28 0 Inching function keyboard


Range set
1 Forward/reverse switch function keys

LED runing display parameters Factory 4095

R
a
n
Y2 +24V AO2 AO3
F7-29 1~8191
g
e
s
et
T/A2 T/B2 T/C2 T/A3T/B3T/C3 CME COM GND GND

81
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

If you need to display the parameters above in the operation, the


corresponding position is set to 1, the binary number to a decimal in
F7-29.For example to show linear velocity, the calculation of 213 =
8192, sets the F7-29 to 8192.If you want to display the PID feedback
value, the calculation of 211 = 2048, sets the F7-29 to 2048.If you
want to show other, calculation method for the same.

LED downtime display Factory 127


parameters
低8位含义of lower 8 digits
Meanings
bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0
Digit
数字预置频率set frequency
Bus voltage
母线电压
DI input state
DI状态
DO output state
DO状态
AI1 Voltage
AI1输入值
AI2 Voltage
AI2输入值
PLC阶段
PLC steps
PID setting
PID设置
R Meanings
高8位含义of higher 8 digits
a bit15 bit14 bit13 bit12 bit11 bit10 bit9 bit8
F7-30 n
g 1~127 PID feedback
PID反馈
保留
Reserved
e 保留
Reserved
保留
Reserved
s 保留
Reserved
保留
Reserved
et 保留
Reserved
保留
Reserved

If you need to display the parameters above in the downtime, its


corresponding position 1, will be in after the binary number to a
decimal F7-30.
For example: the need to display and digital PID feedback value preset

frequency F7-30 setting value is 28  20  257 。


Negtive load speeding Factory 1.000
F7-31 display parameters
Range set 0.000~6.500

Through this parameter will output frequency of frequency converter and negtive load speed.When need to display
negtive load speed set, negtive speed = 120 * * F7 - the number of 31 / motor running frequency.

The radiator temperature Factory -


F7-32
Range set 12℃~100℃
Cumulative on time Factory -
F7-33
Range set 0~65535

Showed that the temperature of the IGBT inverter module, different models of IGBT inverter modules over
temperature protection value might be different.

Accumulation running
Factory -
F7-34 itme(minute)
Range set 0~1440

82
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Accumulation running
Factory -
F7-35 itme(day)
Range set 0~65535

Record the motor running time (frequency converter drive enabled), set to 0 can be removed, when running time is
less than 60 seconds is not recorded

Fan controlling choice Factory 1


0 Fan keeps runing
F7-36 1 Stop running stop in a minute
Range set 2 Along with the drive run/stop action
Detect heat sink temperature to move again after
3
about 50 ℃

Water-supply dormancy
Factory 0
function
F7-37
0 invalid
Range set
1 valid

Parameters are used to realize the application of water supply in sleep and wake up function.
Frequency converter running process, set when the frequency is less than or equal to F1-18 when the lower limit of
frequency and differential pressure less than wake up, after F7-19 delay time, frequency converter to enter a
dormant state, and automatically stop.
If the frequency inverter dormant, and run the current effective, is when set to sleep wake up, wake up dormant.
Process of converter dormancy is valid from stop to the target frequency acceleration by user Settings, and
decelaration time limit, such as the user to select add and subtract time 0, is affected by the F0-23, F0-24.So in the
process of dormancy start user should according to the actual need to adjust ac - decelaration time.

Sleep wake up value Factory 3.0%


F7-38
Range set 0.0% ~ 100.0%
The reference value that the maximum stress value of the reference object, arouse the function of the application of
the above parameters are used to realize water supply.
This parameter is used to determine The sensei pressure limit, The set value for The percentage of The maximum
pressure.
Lower limit value = PIgiven value - wake up differential pressure value;
Wake up the differential value = maximum pressure value * F7-38
When the PID regulator feedback is less than lower limit (pressure value is less than lower limit) converter out of
hibernation is up and running, generally can be set to 3.0% ~ 10.0%.
Water supply dormancy set steps:
1, select frequency source F0-06 = 6, for PIDgiven.
2, choose the lower frequency F0-18 = dormancy frequency values, is used to set the frequency of dormancy.
3, choose below the lower limit frequency F7-17 = 1, choose below the lower limit frequency downtime.
4, set the lower limit frequency operation delay time F7-19
5, choose water dormancy function open F7 to 37 = 1, choose to 1 water dormancy function to take effect.
6, choose to sleep wake up value F7-38 = according to the calculated value of pressure difference, such as given3
kilograms force, pressure is less than 2.5 kilograms of awakening dormant function, FA - 01 = 30.0%, F7-38 =
16.0%.

7, set the PID parameters (FA) group.


Regular time when
Factory 2.0s
F7-39 closing
Range set 0.0s~6000.0s
Regular time when
Factory 2.0s
F7-40 cutting
Range set 0.0s~6000.0s
When the timer input terminals "connected" is longer than F7-39, the timer function output through.
When the timer input terminals "disconnection" is longer than F7 to 40, the timer function output disconnect.

83
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

A B Z 15V COM OUTA COM OUTB COM


Map5-16 Timer Input/Output Action Map

Start protecting
Factory 1
function
F7-41 invalid(Start the terminal command
0
Range set effective direct start)
1 valid
If this parameter is used to improve the safety coefficient, is set to 1, there are two functions:
1) inverter power run command is, you must first run command will remove to avoid running protection state.
2) if the frequency converter fault reset run command still exist, you must first run command will remove to avoid
running protection state.
This prevents motor in unwittingly to run automatically, dangerous.
If set to 0, and frequency converter on the electricity run command exists, namely after F7-42 set the time,
frequency converter directly.。

On electricity directly
Factory 1.0s
F7-42 start delay
Range set 1.0s~60.0s
Any sorts of current
Factory 100.0%
F7-45 arrivals
Range set 0.0% ~ 200.0%
The width of current
Factory 3.0%
F7-46 arrivals
Range set 0.0% ~ 100.0%
When detected current reaches the F7-45, any current to output the function effectively, can choose the relay output
or the output Y.
Any current reaches the width range for any current output function does not change.

F7-47 The agent setting time


F7-48 The agent setting password
F7-49 The agent password status
User’s password Factory 0
F7-51
Range set 0~65535
Users through this function code set the password, specific Settings refer to chapter iv operation and display -
password section, agents set password please contact our technical service department.

5.9 F8 group communication function

Baud rate(bps)choice Factory 5


0 300BPS
F8-00 1 600BPS
Range set 2 1200BPS
3 2400BPS
4 4800BPS

84
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5 9600BPS
6 19200BPS
7 38400BPS
This parameter is used to set data transfer rate between the PC and inverter.Note that set the baud rate of upper
machine and converter must agree, otherwise, the communication can't be, the greater the baud rate, the faster the
communication.

The data format Factory 0


F8-01 0 No check
Range set 1 Parity checking
2 odd checking
PC and inverter set The data format must agree, otherwise, The communication can't be.

The machine address Factory 1


F8-02
Range set 0~247,0is broadcast address
When the machine address set to 0, the broadcast address, PC radio function.
Note: the machine address has uniqueness (except radio), which is to achieve the basis of upper machine and
inverter point-to-point communication conditions.

Response time(s) Factory 10ms


F8-03
Range set 0ms~20ms
Response latency, refers to the frequency converter data receiving end up to a machine to send data in the middle of
the interval of time.If the response time delay is less than the system processing time, the response time delay will
be subject to system processing time, if the response delay processing time is longer than the system, the system
after processing the data, to delay waiting for, until the response delay time, up to a machine to send data.

Communication
Factory 0.0s
F8-04 timeout time
Range set 0.0s(invalid)~60.0s
When this function code is set to 0.0 s, communication timeout parameter is invalid.
When the function code set to valid values, if a communication and the interval time of the next communication
beyond the communication timeout, system error will be reported to the communication failures, under normal
circumstances, will be set to null and void, if this parameter is set in the continuous communication system, can
monitor the communication status.

communication pattern
Factory 1
choice
F8-05
0 Free pattern
Range set
1 Standard MOBUS protocol
Linkage proportion
Factory 1.00
from the machine
F8-06
Range set 0.00% ~ 10.00%

This value to adjust the communication frequency ratio, the actual frequency conversion rate = * F8-06
communication frequency

Master-slave machine
Factory 0
selection
F8-07 0:slave machine
Range set
1:master machine
When the set is given priority to, can be achieved by 485 from the machine and the host communication with
frequency and follow actual operation frequency of frequency for the host.

85
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5.10 F9 group fault and protection

Motor overload protection option Factory 1


Frequency converter to the negtive
0 banned load motor overload protection,
F9-00 before the motor heating relay;
Range set
The frequency converter for motor
1 allowed overload protection function.See
F9-01 protection value
Motor overload protection time
Factory 1.00
coefficient
Motor overload protection time coefficient is F9.01 x
motor overload protection
F9-01 Time, the default protection is 220% by the motor rated
Range set 0.20~10.00 current 1 minute,
Such as: F9-01 set to 0.5, then the time into the motor
overload protection
220% x motor rated current 30 s.
Motor overload coefficient of
Factory 80%
warning
This value is the amount of reference for motor overload
F9-02 current.When the inverter to detect the current output to
Range set 50%~100% meet F9-02 x motor overload current and continuous
inverse time curve after the prescribed time, from the
DO or RELAY output forecasting warning signals.
Over voltage protection stalled
Factory 100%
gain
Adjust the frequency converter overvoltage stall control
capability.This value is, the greater the ability to
suppress overvoltage.
For a small moment of inertia of negtive, this value
F9-03
should be smaller, otherwise slow dynamic response in
Range set 0%~100%
the system.For large inertia negtive load, this value
should be large, otherwise the inhibition effect is bad,
overvoltage faults that may occur.Line after the
prescribed time, from the DO or RELAY output
forecasting warning signals.
Over-voltage protection of stall Factory 150%
F9-04 Choose overvoltage protection function point
Set range 100%~200% stalled.More than this value converter implemented
overvoltage protection function of stall.
Loss of speed protection gain Factory 100%
Adjust the frequency converter of erosion speed
ability.This value is, the greater the inhibition of flow
ability.
F9-05 For a small moment of inertia of negtive, this value
Range set 0%~100% should be smaller, otherwise slow dynamic response in
the system.
For large inertia negtive load, this value should be large,
otherwise the inhibition effect is not good, may occur
over current fault.
Over current protection current
Factory 150%
stalled
F9-06 Choose a loss speed protection function.More than this
Range set 100%~200% value converter implemented stall over current
protection function.
F9-09 Encoder bolt testing time Factory 5

86
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Range set 0~100


Encoder bolt processing: Factory 2
0 Warning, but continue to run
F9-10
Range set 1 Warning, slow down
2 Warning, free downtime

Automatic reset failure time Factory 0


F9-11
Range set 0~3 Just lying and overvoltage fault self-recovery.
During the fault self-recovery
Factory 0
Fault relay action choice
After choosing converter fault self-recovery function,
F9-12 fault reset during the implementation, and through this
0:no action
Range set parameter setting, can determine whether a fault relay
1:action action will be needed, to block and fault alarm, make the
equipment to continue running.
Fault self-recovery time interval Factory 1.0s
F9-13 Fault alarm to the waiting time between automatic reset
Range set 0.1~100.0s
the fault.

The input phase protection option Factory 1


F9-14
0:banned
Range set Choose whether to protect the input phase.
1:allowed
The output phase protection
Factory 1
option
F9-15
0:banned
Range set Choose whether to protect the input phase.
1:allowed

F9-16 The first fault types


F9-17 the second fault types 0~29
F9-18 the third fault types
Record inverter recently three times The fault types: 0 for trouble-free, 1 ~ 29 is ERR01 ~ ERR29.Detailed
description see chapter 7.

F9-19 The lastest fault types Show the lastest fault frequency
F9-20 The lastest fault frequency Show the lastest fault frequency
F9-21 The lastest fault current Show the lastest fault current
F9-22 The lastest fault bus voltage Show the lastest fault bus voltage

87
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

This value is a decimal number.According to a recent


failure all digital input terminal of the state, the order is:
bit4 bit3 bit2 bit1 bit0

T4 T3 T2 T1 T0

DI4 DI3 DI2 DI1 DI0


A recent failure state of the input
F9-23
terminals According to each state is transformed into the
corresponding decimal display.
When the input terminal to ON, its corresponding to 1.OFF
to 0.
Through this value to understand the current state of the
digital output signal.

This value is a decimal number.According to a recent


failure all the input terminal of the state, the order is:
bit1 bit0

T1 T0

DO0 REL1
F9-24 A recent failure output terminals
According to each state is transformed into the
corresponding decimal display.
The input terminal to ON at the time, its corresponding to
1.OFF to 0.
Through this value to understand the current state of the
digital output signal.

5.11 FA group process controlling PID function

PID control is a common method for process control, based on the charged amount of feedback signal and the target
signal dispersion of proportion, integral, differential operation, to adjust the output frequency of frequency
converter, a negtive feedback system, have been accused of stability in the target amount.Suitable for flow control,
pressure control, temperature control process control, etc.Basic principle of control box, the Map is as follows:

A+ B+ Z+ +5V1 OA+ OB+ OZ+


A- B- Z- COM OA- OB- OZ-

Map5-17 Process PID Principle Of Frame Map

PID given origination Factory 0


FA-00 0 PID keyboard given
Range set
1 AI1

88
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

2 AI2

3 Communication given

4 AI3

5 PULSE given

6 Multi-level command given


When the PID frequency source choice, namely F0-06 or F0-07 choice for 6, the group function.(please refer to the
function code F0-06, F0-07).
The decision process of PID parameters given channel target quantity.
Process PID amount of goal setting for the relative value, of 100% of the set corresponds to the 100% of the
feedback signal.
Range of PID (FA - 05) is not required, because, no matter how much range is set to system are to be carried out
according to the relative value (0 ~ 100%) operation.But if setting the PID range, can be observed visually through
the keyboard display parameters PID given and feedback the actual value of the corresponding signal.

PID keyboard given Factory 50.0%


FA-01
Range set 0.0%~100.0%
Choose FA - 00 equals zero, namely the target source for keyboard is given, the need to set this parameter, the
parameter of the basic value for the amount of feedback system.

PID given changing time Factory 0.0s


FA-02
Range set 0.0s~3000.0s
PID given change time refers to the actual PID values vary from 0.0 to 100.0% of the time required.
When change PIDgiven PIDgiven actual values will not be as the response immediately.But according to the given
time linear change, prevent given mutations.

PID feedback
Factory 0
origination
0 AI1
1 AI2
2 AI1-AI2
FA-03 3 Communication given
Range set
4 AI3
5 PULSE given
6 AI1+AI2
Through this parameter to select the PID feedback channel.

PID working direction Factory 0


FA-04 0 Positive effect
Range set
1 Reverse effect

Positive effect:When feedback signal is greater than the given PID for the inverter output frequency drops, can
make PID equilibrium.Such as winding tension of PID control.

Reverse effect:When feedback signal is greater than the given PID for the inverter output frequency is rising, to
make PID equilibrium.Such as rolling tension of PID control.
PID given feedback unit Factory 1000
FA-05 Range is dimensionless PID given
Range set 0~65535 feedback unit.Used as PID given
and feedback shows.

89
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

The proportion grainP1 Factory 20.0


FA-06
Range set 0.0~100.0
Integration timeI1 Factory 2.00s
FA-07
Range set 0.01s~10.00s
differential timeD1 Factory 0.000s
FA-08
Range set 0.00s~10.00s
The proportion grainP:Decide the intensity of the adjustment of PID controller, the bigger the P, adjust the intensity,
the parameters of 100 table shown when the PID feedback quantity deviation was 100%, and the given amount of
PID regulator to adjust the amplitude of output frequency instructions for maximum frequency (ignore the integral
action and derivative action).
Integration timeI:Determining PID regulator for PID feedback and given the amount of deviation to adjust how
quickly the integral, the Integration time is when the PID feedback and given the amount of deviation was 100%,
integral controller (ignore the proportional action and derivative action) after the time continuous adjustment, adjust
quantity to achieve maximum frequency (F0-14).The shorter the Integration time adjustment, the greater the
intensity.
differential timeD:Decision of PID feedback PID regulator and adjusted the rate of change of the intensity of the
given amount of deviation.If differential time refers to the amount of feedback to change within the time 100%,
adjust the amount of differential controller for maximum frequency (F0-14) (ignoring scale function and the
integral action).The longer the differential time adjust the intensity

PID inversion of cut-off


Factory 0.00Hz
FA-09 frequency
Range set 0.00Hz ~ maximum frequency
Deviation limits Factory 0.00%
FA-10
Range set 0.00% ~ 100.00%

Deviation limits:When the deviation in the range, the PID feedback PID stop adjustment.

Differential limiter Factory 5%


FA-11
Range set 0.00% ~ 100.00%
Differential limiter: PID controller, the effect of differential is more sensitive, easy to cause system oscillation,
therefore, generally limit the effect of differential PID in a smaller range, FA - 11 is used to set the PID differential
output range.

PID output filtering time Factory 0.00s


FA-12
Range set 0.00s~60.00s
PID feedback missing values Factory 0.0%
FA-13
Range set 0.0% ~ 100.0%
When PID feedback value less than PIDgiven - (PIDgiven * FA - 13) after the FA - 14 times PID fault, lost 0.0%
doesn't work.

PID feedback detection lost time Factory 1.0s


FA-14
Range set 0.0s ~ 60.0s
This value is used with FA - 13.

Start the PID loss detection delay Factory 0.0s


FA-15
Range set 0.0s ~ 120.0s
The value for the variable frequency start to PID feedback delay time lost judgement, suitable for feedback to build
slower.

90
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

PID given changing time Factory 0.0s


FA-16
Range set 0.0s ~ 60.0s
When to the PID value, actual inverter PIDgiven change time.

PIDpattern top menu can be modified


Factory 0
FA-17 FA-01
Range set 0~ 1
When the FA - 17 set as 1, can be directly modified in monitoring menu group FA - 01, PIDgiven value, convenient
users don't have to enter the parameters to modify PIDgiven values.

The proportion grainP2 Factory 20.0


FA-18
Range set 0.0~100.0
Integration timeI2(s) Factory 2.00
FA-19
Range set 0.01~10.00
Differential timeD2(s) Factory 0.000
FA-20
Range set 0.000~10.000
The second set of PID parameter values, parameter adjustment and FA - 06 - FA - 08.

0:no switch
1:switching through DI terminal
PID Parameters of switching 2:switching according to deviation
FA-21
conditions
3:automatic switch accroding to the running
frequency
PID switch deviation1 Factory 0.0%
FA-22
Range set 0.0% ~ 100%
PID switch deviation2 Factory 0.0%
FA-23
Range set 0.0% ~ 100.0%
In some applications, a set of PID parameters can not meet the needs of the whole operation process, need to adopt
different PID parameters under different conditions.
This group of the function code is used to switch of the two groups of PID parameters, the controller parameters of
FA - 18 ~ FA - 20 set mode, and the parameters of FA - 06 - FA - 08, two groups of PID parameters can be achieved
by many digital DI terminal switching function, can also according to the deviation of PID automatic switching.
Select multiple functionDI terminal switch more functionterminal function choice should be set up to 35 (PID
parameter switch terminal), when the terminal was invalid selection parameters group 1 (FA - 06 - FA - 08),
terminal effective choosing parameters in group 2 (FA - 18 ~ FA - 20).

Choosing to automatic switching, given and feedback the deviation between the absolute value is less than PID
parameter deviation switch 1 FA - 22, PID parameters selection group 1.Given feedback and deviation between the
absolute value is greater than the PID switch deviation 2 FA - 23, PID parameters selection in group 2.Deviation in
a given and feedback between switch deviation between 1 and switch 2, the PID parameters for PID parameters of
the linear interpolation values in both groups, as shown in Map5-18.

PID参数
PID Parameters
PID Parameters
PID参数11
FA-06 ~ FA-08

PID Parameters 1
PID参数1
FA-18 ~ FA-20

FA-22 FA-23
PID Deviation
PID偏差

Map5-17 PID Switch Parameters

91
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

PIDinitials Factory 0.0%


FA-24
Range set 0.0% ~100.0%
PIDinitials keeping time Factory 0.00s
FA-25
Range set 0.00s ~ 650.00s
Frequency converter starts up, the PID output fixed for PID initial FA - 24, after continuous PID initial keep time
FA - 25, PID closed-loop adjustment operation.

Two output is maximum Factory 0.00%


FA-26
Range set 0.00% ~ 100.00%
Two output is maximum Factory 0.00%
FA-27
Range set 0.00% ~ 100.00%
This function is used to limit the PID output duple (2 ms/take) the difference between, in order to suppress the PID
output changes too fast, make the inverter running stable.FA - 26 and FA - 27 correspond to the forward and reverse
the output of the deviation of absolute value maximum.

PID downtime axiom Factory 0


FA-28 Downtime without
Range set 0
axiom
1 Downtime with axiom
Stop condition is used to select the PID, PID whether to continue operation, general applications, PID should stop
operation under the stop condition.

92
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

5.12 FB group pendulum frequency function

Pendulum frequency function is suitable for the textile, chemical fiber and other industries and the need to traverse,
winding function.
Pendulum frequency function refers to the inverter output frequency at a set frequency (frequency instruction by
F0-06 and F0-07) as a center for bobbing up and down, the operating frequency in time axis trajectory shown in the
Map below, the oscillation amplitude are set in the FB - 00 and FB - 01, when FB - 01 to 0, the swing is 0, the
pendulum frequency doesn't work.
Setting Frequency Hz

Aw=Fset*FB-01
Frequency
Upper Limit FH
Center +Aw
Frequency Fset -Aw
Frequency
Lower Limit FL Textile Kick Triangular Rising Time
Frequency =FB-03 * FB-04
=Aw*FB-02
Accelerate by Decelerate by
Acceleration Frequency CycleFB-03
Running Deceleration Time
Time
Command
Stop
Command

Map5-18 The Pendulum Frequncy Map

Swing set Factory 0


FB-00 0 Relative to the center frequency
Range set
1 Relative to the maximum frequency

hrough this parameter to determine the swing of the benchmark.


0: relative center frequency (or F0 F0-06-07 frequency source), for the swing system, swing along with the change
of center frequency set (frequency) change.
1: the relative maximum frequency (the maximum operating frequency F0-14), as the system for swing, swing.

The pendulum frequency range(%) Factory 0.0%


FB-01
Range set 0.0%~100.0%
A sudden jump frequency range(%) Factory 0.0%
FB-02
Range set 0.0%~50.0%

Through this parameter to determine the frequency amplitude and kick.


The pendulum frequency operation frequency, lower frequency constraint on.
Swing relative to the center frequency (variable swing, select the FB - 00 = 0) : swing AW = FB - 01 x swing
amplitude frequency sources.
Swing relative to the maximum frequency (swing, choose the FB - 00 = 1) : swing AW = maximum frequencyF0
FB - 01-14 x swing range.
Tu rate = swing AW * kick frequency amplitude FB - 02.The pendulum frequency is run, tu rate relative value of
the swing.
If choose swing relative to the center frequency (variable swing, select the FB - 00 = 0), tu value rate is change.
If choose swing relative to the maximum frequency (swing, choose the FB - 00 = 1), the rate is a fixed value.

93
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Pendulum length(s) Factory 10.0s


FB-03
Range set 0.1s~3000.0s
Rise time coefficient triangular
Factory 50.0%
FB-04 wave(%)
Range set 0.1%~100.0%
Setting length (m) Factory 1000
FB-05
Range set 0~65535
Real length (m) Factory 0
FB-06
Range set 0~65535
Every impluse numbers Factory 1000
FB-07
Range set 01~65535
Setting the count Factory 1000
FB-08
Range set 1~65535
Setting the count Factory 1000
FB-09
Range set 1~65535

Pendulum frequency cycle: a complete frequency cycle time value.


FB - 04 triangle wave rise time coefficient is relatively FB - 03 pendulum frequency cycle.
Triangle wave rise time = pendulum frequency cycle FB - FB 03 by triangle wave rise time coefficient - 04 (unit:
second)
Triangle wave fall time = pendulum frequency cycle FB - 03 x (1 - a wave of triangle rise time coefficient FB - 04)
(unit: second)
Note: for fixed length and counting function please select CM580E series high performance magnetic flux vector
control frequency converter.
Set length and practical length, each mimpulse number three function code is mainly used for fixed-length control,
length calculation by impulse the switch quantity input terminal input signal, the need to set the corresponding
input terminals for counting the length of the input terminals.
The actual length = length counting inputimpulse number per mimpulse number.
When the actual length more than set length FB FB - 06-05, the function more digital output terminals "length
reaches the terminal output ON signal" (please refer to the F6 group DO output function).
Count by multiple function switch input terminal of the counter input terminals inputimpulse signal counting.
When the count value to set meter value, switch output terminals output signal set count arrived, counter to stop.
When the count value reaches the specified count, switch output terminals output signal specified count arrived,
counter to count, to set the "count" stop.
Count value specified FB - 09 don't set count value should be greater than FB - 08.

5.13 FC group Multistage speed function and simple PLC function

Simple PLCfunction inverter's a built-in programmable controller (PLC) to complete the multistage frequency
automatic control logic, can set up running time, direction and operation frequency, in order to meet the process
requirements.
CM530E series general magnetic flux vector control frequency converter can achieve 16 segment speed change
control, there are four kinds of deceleration time for choice.
When set by PLC after completion of a cycle can be made of the function more digital output terminal Y1, multiple
function relay RELAY1 output ON signal.Details see F6-00 ~ F6-02.

94
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Multistage speed0 Factory 0.0Hz


FC-00
Range set negtivemaximum frequency~maximum frequency
Multistage speed1 Factory 0.0Hz
FC-01
Range set negtivemaximum frequency~maximum frequency
Multistage speed2 Factory 0.0Hz
FC-02
Range set negtivemaximum frequency~maximum frequency
Multistage speed3 Factory 0.0Hz
FC-03
Range set negtivemaximum frequency~maximum frequency
Multistage speed4 Factory 0.0Hz
FC-04
Range set negtivemaximum frequency~maximum frequency
Multistage speed5 Factory 0.0Hz
FC-05
Range set negtivemaximum frequency~maximum frequency
Multistage speed6 Factory 0.0Hz
FC-06
Range set negtivemaximum frequency~maximum frequency
Multistage speed7 Factory 0.0Hz
FC-07
Range set negtivemaximum frequency~maximum frequency
Multistage speed8 Factory 0.0Hz
FC-08
Range set negtivemaximum frequency~maximum frequency
Multistage speed9 Factory 0.0Hz
FC-09
Range set negtivemaximum frequency~maximum frequency
Multistage speed10 Factory 0.0Hz
FC-10
Range set negtivemaximum frequency~maximum frequency
Multistage speed11 Factory 0.0Hz
FC-11
Range set negtivemaximum frequency~maximum frequency
Multistage speed12 Factory 0.0Hz
FC-12
Range set negtivemaximum frequency~maximum frequency
Multistage speed13 Factory 0.0Hz
FC-13
Range set negtivemaximum frequency~maximum frequency

Multistage speed14 Factory 0.0Hz


FC-14
Range set negtivemaximum frequency~maximum frequency
Multistage speed15 Factory 0.0Hz
FC-15
Range set negtivemaximum frequency~maximum frequency

Description: FC - 00 ~ FC - 15 symbol determines the simple PLC running direction, if the negtive value, is the
Table in reverse direction.。

95
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Simple PLC Map:

FC-02 FC-14
FC-19 define FC-21 define
accelerate FC-00 decelerate FC-15

FC-21 define FC-23 define


accelerate decelerate
FC-01
DO or RELAY
FC-18 FC-20 Output

Map5-19 Simple PLC Map

PLC running way Factory 0


FC-16 0 One end of the run down
Range set 1 Single run end of final value
2 Keep circuiting

0: single end stop operation, after completing a single inverter automatic stop, need operation command given to
start again.
Keep the final end of the 1: a single run, after completing a single frequency converter automatically keep running
frequency and direction of the last paragraph.
2: always circulation, the frequency converter to complete a automatically begin the next cycle after cycle, until a
stop command, system downtime.

PLC lose memory choice Factory 0


Don't memory and stop interrupt reset when
0
power supply drop
FC-17 1 Power lost memory reset and stop interrupt
Range set Useing don't memory and from interrupt no
2
downtime
No longer a power lost memories and from
3
downtime interrupt

0: after power off memory and not stopping to restore 0 period began
After power off memory and not stop after the restart PLC 0 section from the beginning.
1: power lost memories and stop 0 period began to recovery
After power off memory and downtime after restart from zero start.
2: power lost memories and starting from the break point
Useing not memory and restart from the outage time after downtime PLC to segment.
3: power lost memory and starting from the break point
Useing PLC memory and restart from the outage time after downtime period of execution.

PLC 0 segment running time Factory 0.0s(h)


FC-18
Range set 0.0s(h)~6553.5s(h)
PLC 0 segment ac-deceleration time
Factory 0
FC-19 choice
Range set 0~3
PLC 1 segment running time Factory 0.0s(h)
FC-20
Range set 0.0s(h)~6553.5s(h)
PLC 1 segment ac-deceleration time
Factory 0
FC-21 choice
Range set 0~3
FC-22 PLC 2 segment running time Factory 0.0s(h)
96
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Range set 0.0s(h)~6553.5s(h)


PLC 2 segment ac-deceleration time
Factory 0
FC-23 choice
Range set 0~3
PLC 3 segment running time Factory 0.0s(h)
FC-24
Range set 0.0s(h)~6553.5s(h)
PLC 3 segment ac-deceleration time
Factory 0
FC-25 choice
Range set 0~3
PLC 4 segment running time Factory 0.0s(h)
FC-26
Range set 0.0s(h)~6553.5s(h)
PLC 4 segment ac-deceleration time
Factory 0
FC-27 choice
Range set 0~3
PLC 5 segment running time Factory 0.0s(h)
FC-28
Range set 0.0s(h)~6553.5s(h)
PLC 5 segment ac-deceleration time Factory 0
FC-29
Range set 0~3
PLC 6 segment running time Factory 0.0s(h)
FC-30
Range set 0.0s(h)~6553.5s(h)
PLC 6 segment ac-deceleration time Factory 0
FC-31
Range set 0~3
PLC 7 segment running time Factory 0.0s(h)
FC-32
Range set 0.0s(h)~6553.5s(h)
PLC 7 segment ac-deceleration time Factory 0
FC-33
Range set 0~3
PLC 8 segment running time Factory 0.0s(h)
FC-34
Range set 0.0s(h)~6553.5s(h)
PLC 8 segment ac-deceleration time Factory 0
FC-35
Range set 0~3
PLC 9 segment running time Factory 0.0s(h)
FC-36
Range set 0.0s(h)~6553.5s(h)
PLC 9 segment ac-deceleration time Factory 0
FC-37
Range set 0~3
PLC 10 segment running time Factory 0.0s(h)
FC-38
Range set 0.0s(h)~6553.5s(h)
PLC 10 segment ac-deceleration time Factory 0
FC-39
Range set 0~3
PLC 11 segment running time Factory 0.0s(h)
FC-40
Range set 0.0s(h)~6553.5s(h)
PLC 11 segment ac-deceleration time Factory 0
FC-41
Range set 0~3
PLC 12 segment running time Factory 0.0s(h)
FC-42
Range set 0.0s(h)~6553.5s(h)
PLC 12 segment ac-deceleration time Factory 0
FC-43
Range set 0~3
97
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

PLC 13 segment running time Factory 0.0s(h)

Multistage speed、PLC directly modify Factory 0


FC-53
FC-44 Range set 0~1
Multistage speed 、 PLC directly modify if
Factory 1
FC-54 saved
Range set 0~1
Range set 0.0s(h)~6553.5s(h)
PLC 13 segment ac-deceleration time Factory 0
FC-45
Range set 0~3
PLC 14 segment running time Factory 0.0s(h)
FC-46
Range set 0.0s(h)~6553.5s(h)
PLC 14 segment ac-deceleration time Factory 0
FC-47
Range set 0~3
PLC 15 segment running time Factory 0.0s(h)
FC-48
Range set 0.0s(h)~6553.5s(h)
PLC 15 segment ac-deceleration time Factory 0
FC-49
Range set 0~3
PLC running time unit choice Factory 0
FC-50 0 S
Range set
1 H
Multistage speed pefect way to choose Factory 0

FC-51 0 Multistage speed is after


Range set
1 Multistage speed is first

Multistage speed priority is when Multistage speed terminal is not complete to 0, prioritise Multistage speed
command value.

Multistage speed first ac-deceleration


Factory 0
time choice
FC-52 0 ac-decelaration time1
Range set 1 ac-decelaration time2
2 ac-decelaration time3

When multistage speed first,doing multistage speed ac-decelaration time choice.

5.14 FD group torque controlling parameters

Torque command source selection Factory 0


0 Mubers given(FD-01)
1 AI1
2 AI2
FD-00 3 AI3
Range set 4 PULSEimpulse frequency given
5 communication given
6 MIN(AI1,AI2)
7 MAX(AI1,AI2)
98
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Torque numbers given Factory 100%


FD-01
Range set -200%~200%
Torque FD - 00 set is used to select torque source, a total of seven kinds of torque setting.
Torque setting USES the relative value, corresponding to 100.0% rated torque converter.Range set to 200% ~ 200%,
and the Table Ming inverter torque capacity of 2 times the rated torque converter.
When using 1 ~ 7 torque setting, communication, analog input, and 100% of impulse input corresponding FD - 01.
Note:when choosing PLUSE impulse given,need to use terminal function choice as impulse input.

Maximum torque limit Factory 100%


FD-02
Range set 0%~200%
Torque control is used to set the upper limit of torque command.

Torque controlling positive maximum


Factory 50.00Hz
FD-03 frequency
Range set 0.00Hz~ FMAX
Torque controlling reverse maximum
Factory 50.00Hz
FD-04 frequency
Range set 0.00Hz~FMAX
Used to set the torque control mode, forward or reverse maximum operation frequency converter.
When the inverter torque control, if negtive load is less than the motor output torque, torque motor speed will rising,
to prevent it
Accidents, such as mechanical system appear coasters must limit the highest torque control of motor speed.

Torque command filtering time Factory 0.000s


FD-06
Range set 0.000s~1.000s
Set the parameter values, can make the torque command more smooth, make the control more submissive, but
slower response group strain.

Torque command to speed up the time Factory 0.00s


FD-07
Range set 0.00s~600.00s
Torque command deceleration time Factory 0.00s
FD-08
Range set 0.00s~600.00s
This parameter is used to set the torque control, torque instruction of ac - decelaration time, can make the torque
command linear change, to meet different applications.

Torque controlling acceleration way Factory 0


FD-09 Using torque command as an
0
Range set ac-decelaration way
1 Using speed limit as ac-decelaration way
This parameter is used to select the choice of the ways of torque control acceleration.
0: torque instruction with FD - 07, FD - 08 deceleration parameter setting.
1: torque instruction during deceleration limited by speed limiting value, for deceleration.

Positive frequency limit Factory 0


0:Numbers given
FD-10 1:AI1given
Range set
2:AI2given
3:communication given
99
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Reverse frequency limit Factory 0


0:Numbers given
FD-11 1:AI1given
Range set
2:AI2given
3:communication given

5.15 FE group function enhancement

AIcurve1The minimum input Factory 0.00V


FE-00
Range set 0.00V~10.00V
AIcurve1The minimum inputcorresponding
Factory 0.0%
FE-01 set
Range set -100.0%~100.0%
AIcurve1the secondinput Factory 0.00V
FE-02
Range set 0.00V~10.00V
AIcurve1the secondinputcorresponding set Factory 0.0%
FE-03
Range set -100.0%~100.0%
AIcurve1the thirdinput Factory 0.00V
FE-04
Range set 0.00V~10.00V
AIcurvethe thirdinputcorresponding set Factory 0.0%
FE-05
Range set -100.0%~100.0%
AIcurve1The maximum input Factory 0.00V
FE-06
Range set 0.00V~10.00V
AIcurve1The maximum inputcorresponding
Factory 0.0%
FE-07 set
Range set -100.0%~100.0%
AIcurve2The minimum input Factory 0.00V
FE-08
Range set 0.00V~10.00V
AIcurve2The minimum inputcorresponding
Factory 0.0%
FE-09 set
Range set -100.0%~100.0%
AIcurve2the secondinput Factory 0.00V
FE-10
Range set 0.00V~10.00V
AIcurve2the secondinputcorresponding set Factory 0.0%
FE-11
Range set -100.0%~100.0%
AIcurve2the thirdinput Factory 0.00V
FE-12
Range set 0.00V~10.00V
AIcurve2the thirdinputcorresponding set Factory 0.0%
FE-13
Range set -100.0%~100.0%
AIcurve2The maximum input Factory 0.00V
FE-14
Range set 0.00V~10.00V
AIcurve2The maximum inputcorresponding
Factory 0.0%
FE-15 set
Range set -100.0%~100.0%
0:LEDkeyboard with coder
FE-17 Keyboard choice 1:LEDkeyboard without coder
2:LCDkeyboard
Input lack of a sensitivity Factory 10
FE-18
Range set 0~5000
FE-19 The output powe
FE-20 Total power consumption

100
CM5X0E general magnetic flux vector control inverter user manual Parameter Description

Top menu display Factory 0


0 Display the frequency
1 Display the rorating speed
FE-22 2 Display the output current
Range set
3 Display the output voltage
4 Display PID return
5 Display PID given

101
CM5X0E general magnetic flux vector control inverter user manual Electromagnetic compatibility

Chapter 6 Electromagnetic compatibility

6.1 Definition
Electromagnetic compatibility refers to the electrical equipment in the electromagnetic interference environment,
the interference of the electromagnetic environment such as stable but also the ability to achieve its function.

6.2 EMC Standard Introduction


According to the requirements of national standard GB/T12668.3 inverter need to conform to the two aspects of
electromagnetic interference and electromagnetic interference.
We perform existing products are the latest international standards:
IEC/EN61800-32004 (Adjustable speedelectricalpowerdrivesystemspart3:
MCrequirementsandspecifictestmethods), equivalent to the national standard GB/T12668.3.
IEC/EN61800-3 mainly from two aspects of electromagnetic interference and electromagnetic interference of
frequency converter, electromagnetic interference is mainly for the inverter radiation interference, the conducted
interference and harmonic interference test (corresponding to the frequency converter has the demand for
civil).Main converter on the conduction resistance to electromagnetic interference immunity, radiation immunity
and surge immunity, rapid mutation impulse moisturiser group of immunity, ESD immunity and low frequency
power supply noise immunity (specific test projects are: 1, the input voltage sag, the interrupt and the change of the
interference resistance test; 2, the perturbation resistance commutation gap test; 3, harmonic input disturbance
resistance test; 4, frequency of input change test; 5, unbalanced input voltage test; 6, the input voltage fluctuation
test) test.
According to the above the strict requirements of IEC/EN61800-3 test, our products guide for installation, as shown
in 6.3 in the general industrial environment will have a good electromagnetic compatibility.

6.3 EMC guidance


6.3.1The influence of the harmonic:
Higher harmonic power supply will be damages to the inverter, so in some grid quality is poorer, suggest reactor
with ac input.

6.3.2Electromagnetic interference and installation considerations:


There are two kinds of electromagnetic interference, one kind is the environment of electromagnetic noise
interference with frequency converter, another type of interference on the surrounding equipment produced by
frequency converter.
Install the matters needing attention:
Inverter and other electrical products grounding line should be good grounding;
Inverter power input and the output power and the weak current signal line (such as: control circuit) try not to
parallel arrangement, vertical arrangement when conditional;
Inverter output power line it is recommended to use shielded cable, or the use of steel tube shielded power line, and
shielding layer should be reliable grounding, wire for interference device it is recommended to use twisted-pair
shielding line, and will be screened and reliable grounding;
Requirements for motor cable length of more than 100 meters, equipped with output filter or reactor.

6.3.3Electromagnetic equipment surrounding the processing method of frequency


converter to produce interference:
Generally the cause of the electromagnetic influence on the inverter is installed near the inverter have a large
number of relay, contactor, or electromagnetic brake.When the inverter so disturbed and misoperation,
recommended the following solution:
A, the disturbance of devices on the surge suppressor;
Add filter B, inverter input end, specific reference to 7.3.6, operate;
C, the inverter control signal line and test line with lead shielding cable shielding layer and reliable grounding.

6.3.4Treatment method of the frequency converter of interferences with peripheral


devices:
This part of the noise can be divided into two kinds: one kind is radiated interference frequency converter, converter
and the other is the conducted interference.Both interfere with the surrounding electrical equipment by
electromagnetic or electrostatic induction, then make the device produces the misoperation, according to several

102
CM5X0E general magnetic flux vector control inverter user manual Electromagnetic compatibility

different interference, refer to the following solution:


A, used to measure the Table, A receiver and its sensors, and general signal is weak, if and when inverter in
relatively close distance or in the same control cabinet, susceptible to interference and misoperation, recommended
the following solution: away from disturbance sources as far as possible;Don't will signal lines and power lines
parallel to decorate special don't equal banding together;Signal line and the power line with shielded cable, and
good grounding;On the output side of the converter plus ferrite beads (select inhibition in 30 ~ 1000 MHZ
frequency range), and 2 ~ 3 turns around, and for the bad, can choose EMC output filter;
B, interference equipment and frequency converter using the same power, cause the conducted interference, if the
above method can't eliminate interference, it should be between the inverter and the power supply with EMC filter
(specific reference to selection of 7.3.6);
C, peripheral equipment grounding alone, can rule out common ground with the frequency converter of leakage
current on the grounding line interference.

6.3.5The leakage current and processing:


Leakage current when using frequency converter has two forms: one is a leakage current to ground;Another is
the line between line and leakage current.
Influence factors of floor drain current and solution:
Distributed capacitance between conductor and earth, the greater the capacitance, the greater the leakage current,
effectively reduce the distance between the inverter and motor to reduce the distributed capacitance.The carrier
frequency, the greater the leakage current is larger, can reduce the carrier frequency to reduce the leakage current,
but reduce the carrier frequency can cause motor noise increased, please note that adding reactor is also an effective
way to solve the leakage current.
Leakage flow increases with the loop current, so do the motor power, the corresponding leakage current.
Causes of leakage current between line and line and solutions:
Inverter output wiring between the distributed capacitance, if through the lines containing higher harmonic current,
leakage current may cause resonance, at this time if the use of thermal relay may make its misoperation.
The solution is to reduce the carrier frequency or reactor with output.Advice before the use of frequency converter
motor is not equipped with thermal relay, the use of frequency converter electronic over-current protection function.

6.3.6 input power supply add EMCinput filter matters needing attention:
Add EMCinput filter on the power input end, please pay attention to the following;
1, please use in strict accordance with the rating when using filter.Belongs to class I appliance due to the filter, filter
to metal case should be large and install ark metal contact is good, and require good conductive continuity,
otherwise there will be a shock hazard and seriously affect the EMC effect;
2, through the EMC test found that PE filter to must and converter end to receive the same public ground, otherwise
will seriously affect the EMC effect;
3, filter close to the power input end of the frequency converter installation;
April and may not be EMCinput filter used in inverter output filter.

103
CM5X0E general magnetic flux vector control inverter user manual Troubleshootiong and countermeasures

Chapter7 Troubleshooting and countermeasures

7.1 Fault alarm and countermeasures

CM5X0E inverter with a total of 29 warning information and the protection function, once the abnormal failure,
protection function, frequency converter to stop output, frequency converter fault relay contact action, and in the
frequency converter fault code shown on the display panel. User before seeking service, can according to this
section suggests checking first, analysis the cause of the problem, find out the solution. If belong to contact the
factory problem, please seek service, with you purchased inverter agents or direct contact with our company.

Fault code Fault types Possible causes The solution


1、U/V/W phase to phase short 1、 check the wiring
circuit or short circuit to ground 2、 equipped with reactor or output
Inverter unit 2、The motor line is too long filter
ERR01
protection 3、Module is overheating 3、 check the air duct or fan
4、Components or internal 4、 contact the manufacturers,
wiring fault agents or sales Table
1、Under the heavy load small 1、 change right type inverter
inverter power selection 2、 motor rotation, stop and start
2、In the operation of the motor 3、 test line motor and motor
Hardware over
ERR02 directly fast start 4、 contact the manufacturers,
current
4、Motor for short circuit agents or sales Table
5、The driver board and control
board cable fault
1、Abnormal input power 1、 test input power supply
2、Moment of inertia of load is 2、 use the appropriate energy
Hardware over
ERR03 too large consumption braking
voltage
3、Motor for short circuit components
3、 test line motor and motor
1、Low power grid voltage 1、 test input voltage of power grid
2、Acceleration time is too short 2、 extend the acceleration time
3、Start frequency set on the reduce the load mutation
high side 3、 to reduce the starting frequency
Accelerated ov 4、V/F control curve ratio is too 4、 adjust the V/F curve
ERR04
ercurrent large 5、 extend the acceleration time and
5、Big moment of inertia of the reduce the load mutation
load and impact load 6、 check the motor parameter
6、Abnormal motor parameter Settings
Settings
1、Low power grid voltage 1、Detection of input power grid
2、Deceleration time setting is voltage
too short 2、Prolonged slowdown
Slow down
ERR05 3、Big moment of inertia of the 3、Extend the deceleration time,
over current
load and impact load reduce the load mutation
4、Abnormal motor parameter 4、Check the motor parameter
Settings Settings
1、In the operation of the 1、 to reduce the load mutation
constant speed over current load frequency and amplitude
mutation 2、 check the motor parameter
Constant speed Settings
ERR06 2、Abnormal motor parameter
over current
Settings 3、 change more suitable inverter
3、Small inverter power model
selection
Stop over 1、Driver board or panel of 1、Contact the manufacturer, agent or
ERR07
current failure sales generation Table

104
CM5X0E general magnetic flux vector control inverter user manual Troubleshootiong and countermeasures

1、Power grid voltage is too 1、 check the input voltage of


high power grid
Accelerate the 2、Excessive load inertia 2、 equipped with appropriate
ERR08
overvoltage braking components
3、Speed up the time is too short
3、 extend the acceleration time
1、Power grid voltage is too 1、Check the input voltage of power
high grid
Deceleration
ERR09 2、Excessive load inertia 2、Equipped with appropriate braking
overvoltage
3、Deceleration time is too short components
3、Prolonged slowdown
1、Power grid voltage is too 1、Check the input voltage of power
Constant speed high grid
ERR10
over voltage 2、Excessive load inertia 2、Equipped with appropriate braking
components
Stop the 1、Power grid voltage is too 1、Check the input voltage of power
ERR11
overvoltage high grid
1、The supply voltage is lower 1、 check the input voltage of
than the lowest working power grid
Under-voltage 2、 Contact the manufacturer, agent
ERR12 voltage
fault or sales generation Table
2、Internal abnormal switching
power supply
1、The input voltage is low 1、Check the input power
2、Motor in high speed rotating 2、Motor rotation stop and start
fast start 3、Shorten the overload time, reduce
The inverter 3、For a long time under the the load
ERR13
overload heavy load 4、Prolonged deceleration
4、Deceleration time is too short 5、Change is more appropriate model
5、Small inverter power converter
selection
1、The input voltage is too low 1、Detection of input power
2、Motor blocked or serious 2、Prevent motor stalling, reduce the
mutation load load mutation
ERR14 Motor overload 3、Motor overload protection 3、Increase the motor overload
time setting is too small protection
4、Dc braking current set is too 4、Reduce the dc current braking
large
1、The environment temperature 1、Reduce the environment
is too high temperature
Module is 2、Air duct blockage 2、Clean up the air duct
ERR15
overheating 3、If the fan in bad 3、Replace the fan
4、Damage to the device 4、Contact the manufacturer, agent or
sales generation Table
1、Control panel fault 1、Contact the manufacturer, agent or
AD transform 2、Driver board failure sales generation Table
ERR16
fault 2、Contact the manufacturer, agent or
sales generation Table
1、Current anomaly detection Contact the manufacturer, agent or
IU current device sales generation Table
ERR17
detection fault 2、Control board is damaged
3、Driver board is damaged
With the similar IU fault Contact the manufacturer, agent or
ERR18 IV current fault
sales generation Table
1、Current anomaly detection Contact the manufacturer, agent or
IW current device sales generation Table
ERR19
fault 2、Control board is damaged
3、Driver board is damaged

105
CM5X0E general magnetic flux vector control inverter user manual Troubleshootiong and countermeasures

1、Testing whether the 1、Replace the motor or cable


Short circuit to
ERR20 motor short circuit to ground 2、Contact the manufacturer, agent or
ground
2、Driver board damage sales generation Table
1、Motor parameter is set 1、Check the actual motor parameters
Motor tuning
ERR21 correctly 2、Check the inverter and motor
fault
2、Motor tuning timeout connection
1、Inverter power supply end 1、According to the procedures, check
connection exception, leak or the power supply wiring bobble,
break break
The input side 2、Serious unbalanced 2、Check the input power three-phase
ERR23
lacks three-phase input power imbalance degree meets the
3、Inverter capacitance aging requirement
3、Contact the manufacturer, agent or
sales generation Table
1、Inverter output side 1、According to the procedures, check
connection exception, leak or the power supply wiring bobble,
The output
ERR24 break break
phase
2、The output three-phase 2、Contact the manufacturer, agent or
imbalance sales generation Table
1、Memory chip on board 1、Contact the manufacturer, agent or
ERR25 Memory fault
failure sales generation Table
Password 1、User password input error 1、Please enter the password correctly
ERR26
mistake three times
1、485 line fault 1、Check whether the 485 line
Communicatio 2、485 communication port normally
ERR27
n failure failure 2、Contact the manufacturer, agent or
sales generation Table
1、External terminal for a given 1、Check the wiring and terminals set
ERR28 External fault
fault parameters
External PID feedback failure Detection of external PID feedback
ERR29 PID bolt
status

7.2 The common faults and processing methods

The following fault of converter may be encountered in the process of using,please refer to the
following simple fault analysis method:
1、Electricity no display:
1)By using Table to check the input power supply converter million rated voltageand frequency
converter is consistent, if the power supply has the question please check and eliminate.
2)Check whether the three-phase rectifier bridge is in good condition, if the rectifier bridge has been
damaged, please seek service.
3)Check whether the charge lamp is lit, if the light is not bright, the fault generally focus on the rectifier bridge
or buffer resistance, if the light is bright, the fault may be in part of switch power supply. Please seek service。
2、Jumped on electric power supply air switch:
1)Check whether there is between the input power grounding or short circuit conditions, eliminate the problems
2)Check whether the bridge rectifier has breakdown, ifdamaged, for services.

3、The motor does not rotate after the operation of the transducer:
1)Check U, V, W between whether there is a balanced three-phase output, if any, for the motor line or itself is
damaged, or the motor due to mechanical causes blockage. Please exclude.
2)Output but the three-phase imbalance, should be damaged for frequency converter drive plate or output
module, please seek service.
3)If there is no output voltage, output module is likely to be driven plate or damaged, please seek service.
4、On electrical inverter show normal, jumped after the operation power supply air
106
CM5X0E general magnetic flux vector control inverter user manual Troubleshootiong and countermeasures

switch:
1)Check whether there is a short circuit between the output module, if so, please seek service。
2)Check whether there is a short circuit or ground between motor fuses, if yes, please exclude..
3)If the trip is occasionally between the motor and the inverter and the distance is far, consider adding the
output AC.

107
CM5X0E general magnetic flux vector control inverter user manual communication protocols

Chapter8 CM5X0E series inverter serial communication protocol

CM5X0E series inverter to provide the RS485 communication interface, and USES MODBUS communication
protocol, the user can through the computer or PLC central control, set the inverter running commands, modify or
read function code parameter, to read the inverter working condition and fault information, etc.

8.1 The contents of the agreement

The serial communication protocol defines the content and use the information in the serial communication
format, including host polling (or broadcast) format and host encoding method. Host encoding method including
action function code,the data transmission, error checking, etc. From the machine response is also using the
same structure, its contents include: action confirmation, return data, error checking, etc. If there was an error in
receiving information from machine or cannot fulfill the requirements of the host, it will launch a fault feedback
information in response to the host.

8.2 Application mode

The frequency converter with RS485 bus access "single from" PC/PLC controlnetwork.

8.3 Bus structure

8.3.1 The interface way


RS485 interface hardware

8.3.2 Transmission mode


Asynchronous serial port , a half-duplex transmission mode. At the same time the host and the only one to send
data from the machine and the other can only receive data, the data in the process of serial asynchronous
communication, is a frame of a frame in the form of message sending.

8.3.3 Topological structure


From single host machine system . From the machine address set in the range of 1 ~ 247, 0 for broadcast
communication address, from machine in the network address must be unique.

8.4 Protocol specification

CM5X0E series inverter when an asynchronous serial port communication protocol of master-slave ModBus
communication protocol, the network has only one device (host) to establish agreement (called
"query/command"). Other equipment (machine) can only through the provision of data query/command
response of the host, or "query/command" according to the host to respond to action. Host in this refers to the
personal computer (PC), industrial control equipment or programmable logic controller (PLC), etc., from
machine refers to CM5X0E inverter, the host can communicate to a separate from the machine, can also be
released to all the lower machine from broadcast information. For access to the host alone "query/command",
from the machine to return to a information (called response), for radio host information, from the machine
without feedback response to the host.

8.5 Communication frame structure

CM5X0E series inverter using MODBUS RTU mode communication protocol


Use the RTU mode, the message is sent at least to begin with a pause interval of 3.5 characters of time, in a
variety of different characters of time under the network baud rate, it is very easy to implement. Message
transmission equipment is the first domain address, you can use the transmission character of is the hex 0 ~ F.

108
CM5X0E general magnetic flux vector control inverter user manual communication protocols

Network equipment continuously detect network bus (including pause time interval), when the first domain
(domain), after receiving each equipment decoding to judge whether the data sent to yourself. Last transmission
character, after a pause at least 3.5 characters time calibration for the end of the message, a new message can be
started after the pause.
The entire message frames must be as a continuous flow of transmission, if the time frame to complete more
than 1.5 characters before the pause time, receiving equipment will refresh incomplete message and assume that
the next byte is the address of the new message domain, likewise, if a new message in less than 3.5 characters of
time and then a message before, receiving equipment will think it is a continuation of the previous message, this
will lead to an error, because the back of the CRC field value can't be right.

RTU frame format:


The frame header START >=3.5 characters of time
From the machine 1~247(0 for the broadcast address)
address
The command codeCMD 03:Read the parameter
06:Write parameters
The content of the The content of the DATA:
DATA(N-1) Function code parameters address, function code, function code
The content of the DATA number parameter values
(N-2)
………..
The content of the
DATA0
CRC CHK High Calibration value:CRC value
CRC CHK Low
End of the frame >=3.5 characters of time

109
CM5X0E general magnetic flux vector control inverter user manual communication protocols

Command command (CMD) and DATA description (DATA)


Command code: 3 h, read the N Word (Word), can read up to 12 characters and N = 1 ~ 12. Specific format is as
follows:
Frame From the The High Lower The The CR C END
Head machine comman address addres numb numbe C R
START address d code s er of r of low chec C
CMD high functio k ch
functi n code high ec
on parame k
code ters lo
para w
meter
s
>=3.5 >=3.5
Address_ Addres
characte 1~247 03 00 N<=12 * * charact
H s_L
rs ers

Example: reading from the machine address for inverter F0 01-03 began for two
consecutive parameters
The host sends commands
Frame Fro The High Lower The The CR C END
Head m comma address address numbe numbe C R
START the nd code r of r of low chec C
mac CMD high functio k ch
hine functio n code high ec
addr n code parame k
ess parame ters lo
ters w
>=3.5 >=3.5
0x
character 0x01 0x03 0xf0 0x03 00 0x02 0x07 characte
0b
s rs

Reply from machine inverter


Frame From The Read F0 high F0-0 F0-0 F0-0 CR CR END
Head the comma the - 03 3 4 4 C C
START machin nd code numbe parame para para para chec chec
e CMD r of ter mete mete mete k k
address parame values r rs of r high low
ters valu high valu
e is valu e is
low e low
>=3.5 >=3.5
character 0x01 0x03 0x04 0x00 0x00 0x00 0x00 0x43 0x07 chara
s cters

110
CM5X0E general magnetic flux vector control inverter user manual communication protocols

If change the control mode F0-03 to VF (F0-03 = 1), run the command source instead of
terminal control (F0-04 = 1), the corresponding data for:
Frame From The Read F0 F0-0 F0-0 F0-0 CR CR END
Head the comma the high 3 4 4 C C
START machin nd code numbe - 03 para para para chec chec
e CMD r of para mete mete mete k k
address parame mete r rs of r high low
ters r valu high valu
valu e is valu e is
es low e low
>=3.5 >=3.5
0xD
characters 0x01 0x03 0x04 0x00 0x01 0x00 0x01 0x07 characte
3
rs

The command code: 6 h, writing a parameter data.


Frame Fro The High Lower Writin Writin CR CR END
Head m comma address address g g C C
START the nd code content content chec chec
mac CMD high low k k
hine high low
addr
ess
>=3.5 >=3.5
1 ~
characters 0x06 Address_H Address_L Data_H Data_L * * characte
247 rs

Example: write from the machine address 01 inverter control mode function code for VF
control mode and F0-03 = 1.
The host sends commands
Frame Fro The High Lower Writin Writin CRC CRC END
Head m comma address address g g check check
START the nd code content content high low
mac CMD high low
hine
addr
ess
>=3.5 >=3.5
characters 0x01 0x06 0xf0 0x03 0x00 0x01 0x8B 0x0A characte
rs

Reply from machine inverter


Frame Fro The High Lower Writin Writin CRC CRC END
Head m comma address address g g check check
START the nd code content content high low
mac CMD high low
hine
addr
ess
>=3.5 >=3.5
characters 0x01 0x06 0xf0 0x03 0x00 0x01 0x8B 0x0A characte
rs
Note: if no success will write command is not successful reason.

111
CM5X0E general magnetic flux vector control inverter user manual communication protocols

8.6 Parity (CRC check way)

Using RTU frame format, message includes a calibration method based on CRC error detection domain, CRC field
tested the content of a message. CRC domain is two bytes, containing 16 bit binary value, after it is calculated by
the transmission equipment, added to the message. Receiving device to calculate the CRC messages are received,
and comparing with receives the CRC in the domain of value, if the two CRC value is not equal, then there is an
error in transmission.
CRC register into 0 XFFFF first, and then call a process to continuous 8-bit bytes of the message and the values in
the current register for processing, only 8 bit data in each character of CRC, effective start bit and stop bit and
parity bits are invalid.
CRC produced in the process, each 8-bit characters individually with register contents exclusive or (XOR), the
results to the lowest effective direction, MSB to 0. LSB can be extracted, if the LSB is 1, register and preset value
dissimilarity or alone, if the LSB is 0,, is not. The whole process will repeat 8 times. At the last one (8) is completed,
the next eight bytes and separate and register the current value of the alien or xa001 (0). The values in the final
register, is all the bytes in the message after execution of CRC value.
CRC were added to the message, the low byte first, then add the high byte. CRC simple function is as follows:
Unsigned int Crc_Cal_Value (Unsigned int *data, Unsigned int length)
{
Unsigned int crcValue = 0xffff;
int I;
while (length--)
{
crcValue ^= *data++;

for (I = 8 – 1; I >= 0; i--)


{
if (crcValue & 0x0001)
{
crcValue = (crcValue >> 1) ^ 0Xa001;
}
else
{
crcValue = crcValue >> 1;
}
}
}
return (crcValue);
}

112
CM5X0E general magnetic flux vector control inverter user manual communication protocols

8.7 Commands and status

Stop/operation parameters (0 x1000)


Parameter address Parameter description
0x1000 or 0x9000 Communication set data (10000 ~ 10000) (decimal) (write) (write 0
x1000 address content as a percentage, 0 x9000 content for the actual
frequency values)
1:Communication baud rate set point
2:Operating frequency
3:Bus voltage
4:The output voltage
5:The output current
6:The output power
7:DI input symbol
0x100x
8:DO output symbol
9:The PID Settings
A:PID feedback
B:AI1 voltage
C:AI2 voltage
D:AO1 output voltage
E:PLC steps
For example: read operation frequency 0 x01 0 x03 0 x10 0 x02 0 x00 0 x01 + CRC check.
At the same time read operation frequency, busbar voltage, output voltage: 0 x01 0 x03 0 x10 0 x02 0 x00 0 x03 +
CRC check.

Note: in the condition of communication written address 0 x9000 parameters for the actual
frequency values, such as written to 4000 to 40.00 Hz
Control command input to the inverter (0 x2000) (write) only
Parameter address Parameter description
0001:Running forward
0002:Reverse run
0003:Is turning point move
0004:Reversal point move
0x2000 0005:Free downtime
0006:Slowing down
0007:Failure reset
1000:Restore the factory parameter
1001:Eliminate malfunction records

Reading the inverter status (0 x3000) (read-only)


Parameter address Parameter description
0001:Running forward
0x3000 0002:Reverse run
0003:downtime

Prompt, data must be 0 x01 after sending commands


Example: 0 x01 0 x03 0 x30 0 x00 0 x00 0 x01 + (CRC check)
Lock password checking (4000) (0 x8888, Table password by) password

Parameter address Parameter description

113
CM5X0E general magnetic flux vector control inverter user manual communication protocols

0x4000 *****

Lock the password parameter (5000) (write) only


Lock the password Lock the password command
command addresses
0x5000 0x0001

Digital output terminal control (6000) (write) only


Parameter address Parameter description
BIT0:The control board relay RELAY1 output
BIT1:Y1 output control
0x6000 BIT2:FMR output option
BIT3:RELAY1 expansion card relay output option
BIT4: Y2 output option

Analog AO1 output control (7000) (write) only


Parameter address Parameter description
0x7000 0 ~ 7 FFF Table: 0% ~ 100%

Inverter current fault information read (8000) (read-only)


Parameter address Parameter description
0000:keep

0x8000
Other: fault code, and the digital tube display fault code

0000:trouble-free

0001:Password mistake

0002:The command code error

0003:CRC check error


0x8001
0004:Invalid address

0005:Invalid parameter

0006:Parameter is invalid

0007:Password lock

Prompt, read-only case, data must be 0 x01 after sending commands

114
CM5X0E general magnetic flux vector control inverter user manual Appendix

Appendix A:Function parameter Table

F7-51 set to non-zero value, that is, password protection, set the parameters parameter menu operations must be
after the correct password to enter, in the condition of decryption will F7-51 to 0, cancel the password.
Monitoring parameter is not protected by password.
Function code symbol stated below:
“☆”:Table said the inverter parameters during downtime, operation can be modified
“★”:Table immutable said inverter is in operation
“○”:Table said the parameters is the manufacturer, the user may be changed
“●s”:Table said a frequency converter in the actual values or manufacturer curing value, cannot be changed

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F0 he basic functional group

F0-00 Software version - 0xF000 #.# ●

0:G model
F0-01 The inverter model 0xF001 0 ●
1:P model

Model to
F0-02 Rated Current 0.1A~3000.0A 0xF002 ●
determine
0:open-loop vector one (SVC1)/SVC1
1:open-loop vector two (SVC2)/SVC2
2:common VF control /common VF
F0-03 Control Method 0xF003 0 ★
3:close-loop vector control (FVC)/TQC
4:PG torque control (TQCPG)
5:torque control (TQC)
0:run the command channel operation panel
Command source
F0-04 1:Terminal command channel 0xF004 0 ☆
selection
2:serial port command channel

115
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

0:Digital set UP and DOWN to adjust (not a


memory)
1:Digital setting UP and DOWN to adjust
(memory)
2:AI1
The main frequency 3:AI2
F0-06 0xF006 1 ★
source X option 4:Multistage speed
5:PLC
6:PID
7:Communications given
8:AI3
9:PULSE setting
0:Digital set UP and DOWN to adjust (not a
memory)
1:Digital setting UP and DOWN to adjust
(memory)
2:AI1
Y choose auxiliary 3:AI2
F0-07 0xF007 0 ★
frequency sources 4:Multistage speed
5:PLC
6:PID
7:Communications given
8:AI3
9:PULSE setting
Auxiliary frequency 0:Relative to the maximum frequency
F0-08 0xF008 0 ☆
source Y range 1:Relative to the frequency source X
Auxiliary frequency
F0-09 0%~100% 0xF009 100% ☆
source Y range

116
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

0:The main frequency source X


1:The main frequency source X Y + auxiliary
frequency sources
2:The main switch frequency source and auxiliary
frequency source X Y
3:Main frequency source X with (main frequency
source X + Y) switch
4:Auxiliary frequency source with Y switch (main
Frequency source frequency source X + Y)
F0-10 0xF00A 0 ★
selection 5:Main frequency source and the auxiliary
frequency source take big (Max (X, Y)) note: in
such a mode of auxiliary frequency source Y range
relative to the maximum frequency, F0-08 will no
longer work
6:The main frequency source and the auxiliary
frequency source in small (Min (X, Y))
7:The main frequency source, the auxiliary
frequency source
F0-11 The preset frequency 0. 00 hz ~ maximum frequency F0-14 0xF00B 50.00Hz ★
0:In the same direction
The driver output
F0-13 1:In the opposite direction 0xF00D 0 ★
direction
2:Ban reversal
The largest operating
F0-14 50.00Hz~400.00Hz 0xF00E 50.00 Hz ★
frequency
0:F0-16 set
1:AI1
Upper limit 2:AI2
F0-15 0xF00F 0 ★
frequency source 3:Ban reversal
4:AI3
5:Set the PULSE
Upper limit The lower frequency F0-16 ~ maximum frequency
F0-16 0xF010 50.00Hz ☆
frequency F0-14
Maximum frequency
F0-17 0. 00 hz ~ maximum frequency F0-14 0xF011 0.00Hz ☆
offset

F0-18 The lower frequency 0. 00 hz ~ limit frequency F0-16 0xF012 0.00Hz ☆


Add and subtract 0: Maximum frequency
F0-22 speed reference 1:Reference frequency 0xF016 0 ☆
object 2:The target frequency

117
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F0-23 Acceleration time 1 0.0s~3000.0s 0xF017 30.0s ☆


F0-24 Deceleration time 1 0.0s~3000.0s 0xF018 20.0s ☆
Overmodulation 0:invalid
F0-25 0xF019 0.0
choice 1:effective
Models to
F0-26 Carrier frequency 1.0kHz~15.0kHz 0xF01A ☆
determine
0:Fixed PWM carrier frequency temperature
adjustment is invalid
1:Random PWM carrier frequency temperature
Carrier frequency adjustment is invalid
F0-27 0xF01B 0 ☆
adjustment options 2:Fixed PWM carrier effective temperature
adjustment
3:Random PWM carrier effective temperature
adjustment
0:No operation
1:Restore the factory Settings
Initialization
F0-28 2:Restore the last power before the user 0xF01C 0 ☆
parameter
preferences
3:Eliminate malfunction records
0: Don't move
Parameters of the
F0-29 1:Parameters to upload 0xF01D 0 ★
copy
2:Parameters to download
F1 start-stop control group

0:Directly start
F1-00 Boot mode 1:Speed tracking start 0xF100 0 ☆
2:Preliminary field start
0:Starting from the stop frequency
F1-01 Speed tracking way 1:Start from zero velocity 0xF101 0 ★
2:Starting from the maximum frequency
Speed tracking
F1-02 30%~180% 0xF102 100% ☆
maximum current
F1-03 Speed tracking speed 1.0~100.0 0xF103 20.0 ★
F1-04 Start frequency 0.00Hz~10.00Hz 0xF104 0.00Hz ★
Start frequency keep
F1-05 0.0s~36.0s 0xF105 0.0s ★
time
The dc braking
F1-06 0%~100% 0xF106 0% ★
current

118
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Start the dc braking


F1-07 0.0~36.0s 0xF107 0.0s ★
time
S curve acceleration
F1-09 0.00s~25.00s 0xF109 1.00s ★
start time
S curve acceleration
F1-10 0.00s~25.00s 0xF10A 1.00s ★
over time
S curve slow start
F1-11 0.00s~25.00s 0xF10B 1.00s ★
time
S curve to slow down
F1-12 0.00s~25.00s 0xF10C 1.00s ★
over time
0:Slowing down
F1-13 Stop way 0xF10D 0 ☆
1:Free downtime
Stop dc brake starting
F1-14 0. 00 hz ~ maximum frequency 0xF10E 0.00Hz ☆
frequency
Dc braking current
F1-16 0%~100% 0xF110 0% ★
downtime
F1-17 Stop dc braking time 0.0s~36.0s 0xF111 0.0s ★
F1-18 Brake unit usage 0%~100% 0xF112 100% ☆
0:invalid
Instantaneous power 1:By the power cut speed tracking speed as before
F1-19 0xF113 0 ☆
failure restart 2:From the minimum output frequency for speed
tracking
Allow the outage
F1-20 1.0s~5.0s 0xF114 1.0s ☆
time
Power supply
F1-21 1.0s~50.0s 0xF115 1.0s ☆
recovery waiting time
0:stop
After power supply 1:By the speed of tracking before useing
F1-22 recovery action 2:From the minimum output frequency for speed 0xF116 0 ☆
choice tracking
3:Direct start
Instantaneous stop 0:invalid
F1-23 0xF117 1 ☆
function 1:effective
Instantaneous stop
keep frequency
F1-24 0~3 0xF118 1 ☆
decrease rate of
choice

119
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Instantaneous stop
F1-25 0.0~60.0s 0xF119 1.0 ☆
time to recover

F2 V/F control parameters

0:Linear V/F curve


1:Multipoint V/F curve
F2-00 V/F curve set 2:V/F square curve 0xF200 0 ★
3:1.7 the power curve
4:1.3 the power curve
F2-01 Torque increase 0.0%~30.0% 0xF201 1.0% ☆
Torque increase the
F2-02 0.0Hz~50.0Hz 0xF202 5.0Hz ★
cut-off frequency
V/F frequency point
F2-03 0.00Hz~50.00Hz 0xF203 0.00Hz ★
1
F2-04 V/F voltage point 1 0.0%~100.0% 0xF204 0.0% ★
V/F frequency point
F2-05 0.00Hz~50.00Hz 0xF205 0.00Hz ★
2
F2-06 V/F voltage point 2 0.0%~100.0% 0xF206 0.0% ★
V/F frequency point
F2-07 0.00Hz~50.00Hz 0xF207 0.00Hz ★
3
F2-08 V/F voltage point 3 0.0%~100.0% 0xF208 0.0% ★
Slip compensation
F2-09 0.0%~200.0% 0xF209 0.0% ☆
coefficient
F2-10 AVR choice 0~200 0xF20A 64 ☆
The oscillation
F2-11 0~100 0xF20B 20 ☆
suppression gain
Vector 1 low
F2-12 frequency torque 0~200 0xF20C 100 ★
increase gain
Vector 1 low
F2-13 frequency torque 0~1000Hz 0xF20D 700Hz ★
cutoff frequency
Low frequency
F2-14 compensation filter 1~9999 0xF20E 200 ★
coefficient vector 1
Filter coefficient
F2-15 vector 1 low 0~2000 0xF20F 100 ★
frequency current
120
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F3 vector control parameters

The switching
F3-00 1.00Hz~F2-02 0xF300 5.00 Hz ★
frequency F1
Switching frequency
F3-02 F3-00~F0-14 0xF302 10.00 Hz ★
F2
Low speed
F3-04 The proportional gain 0.001~10.000 0xF304 2.000 ☆

Low frequency speed


F3-05 integration time 0.001s~10.000s 0xF305 0.500s ☆
(0.001 s)
High frequency speed
F3-06 The proportional gain 0.001~10.000 0xF306 1.000 ☆

High frequency speed


F3-07 integration time 0.001s~10.000s 0xF307 1.000s ☆
(0.001 s)
The torque current
F3-11 30000 0xF30B 1000 ★
regulator Kp
The torque current
F3-12 0~30000 0xF30C 1000 ★
regulator Ki
The excitation
F3-13 0~30000 0xF30D 1000 ★
current regulator Kp
The excitation
F3-14 0~30000 0xF30E 1000 ★
current regulator Ki

0- The whole is invalid


The open loop vector
F3-15 1- The whole effective 0xF30F 2 ☆
function of AVR
2- Invalid when just slow down

Weak magnetic curve


F3-16 50%~150% 0xF310 100% ☆
gain
Slip the senders gain
F3-17 50%~200% 0xF311 100 ☆
(%)
Speed loop feedback
F3-18 low-pass filtering 0.000~0.100 0xF312 0.000 ★
time constant

121
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Speed loop output


F3-19 0.000~0.100 0xF313 0.000 ☆
filter time constant

0 - F3-21
1 - AI1
2 – AI2
The electric torque
F3-20 3 – AI3 0xF314 0 ★
limit source
4 - PLUSE given
5 - Communications given
(analog range corresponding to the F3-21)

Electric torque limit


F3-21 0.0%~200.0% 0xF315 150.0% ☆
(%)

0 - F3-23
1 - AI1
2 – AI2
F3-22 Brake torque limit 3 – AI3 0xF316 0 ★
4 - PLUSE given
5 - Communications given
(analog range corresponding to the F3-23)

Brake torque limit


F3-23 0.0%~200.0% 0xF317 150.0% ★
(%)

F4 set motor parameters

0:There is no function
Motor parameters
F4-00 1:Static tuning 0xF400 0 ★
tuning
2:Completely tuned

Models to
F4-01 Motor 1 rated power 0.4kw~1000.0kw 0xF401 ★
determine
(kW)
Motor rated voltage
F4-02 0V~440V 0xF402 380V ★
(V) 1
The number of motor Models to
F4-03 2~64 0xF403 ★
1 determine

122
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Motor 1 rated current Models to


F4-04 0.1A~3000.0A 0xF404 ★
(A) 0.1 determine
Motor 1 rated
F4-05 0. 00 hz ~ maximum frequency 0xF405 50.00 ★
frequency (Hz)
Motor 1 rated speed
F4-06 0rpm~30000rpm 0xF406 1460 ★
(RPM)
1 motor no-load Models to
F4-07 0.1A~1500.0A 0xF407 ☆
current (0.1 A) determine
Motor stator Models to
F4-08 0.001Ω~65.535Ω 0xF408 ☆
resistance 1 ohm determine
Motor rotor Models to
F4-09 0.001Ω~65.535Ω 0xF409 ☆
resistance 1 ohm determine
Motor 1 mutual Models to
F4-10 0.1Mh~6553.5 Mh 0xF40A ☆
inductance of mH determine
Motor 1 leakage Models to
F4-11 0.01Mh~655.35Mh 0xF40B ☆
inductance mH determine
Fully tuned
F4-12 1~60000 0xF40C 100 ☆
acceleration
Tuned in full speed
F4-13 1~60000 0xF40D 100 ☆
reduction
The encoder pulse ☆

F4-14 number before 4 1~9999 0xF40E 1024


times (frequency)
The encoder input ☆
F4-15 0~1 0xF40F 0
form
0 - ABZ incremental encoder ☆

1 - UVW incremental encoder

The encoder to 2 - Province line UVW incremental encoder


F4-16 0xF410 3
choose 3 - Rotating transformer
4 - Sine/cosine encoder
0 - ABZ incremental encoder

Spiral pole changing ☆


F4-17 1~65535 0xF411 2
logarithmic
Rotary encoder

F4-19 excitation signal 2.0KHz~20.0KHz 0xF413 7.0KHz
frequency setting

123
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F5 set of input terminals

0:There is no function ☆
F5-00 DI1 terminal function 1
1:Forward to run (FWD) 0xF500
2:Reverse operation (REV)
3:Three-wire system operation control
4:Forward some dynamic (FJOG)
F5-01 DI2 terminal function 0xF501 2 ☆
5:Reverse point move (FJOG)
6:Terminal UP
7:Terminal DOWN
8:Free parking
F5-02 DI3 terminal function 9:Failure RESET (RESET 0xF502 3 ☆
10:Run to suspend
11:The external input normally open fault
12:Multistage speed terminal 1
13:Multistage speed terminal 2
F5-03 DI4 terminal function 14:Multistage speed terminal 3 0xF503 4 ☆
15:Multistage speed terminal 4
16:Deceleration time choose terminal 1
F5-04 DI5 terminal function 17:Deceleration time choose terminal 2 0xF504 5 ☆

DI6 terminal 18:Switching frequency source


F5-05 function/HDI6 19:Set UP/DOWN reset 0xF505 0 ☆
function (terminals, keyboard)
DI7 terminal function 20:Run the command switch terminals 0xF506
F5-06 selection (expansion 21:Deceleration is prohibited 0 ☆
card IO - 1) 22:PID failure
DI8 terminal function 23:PLC state reset 0xF507
F5-07 selection (expansion 24:The pendulum frequency suspended 0 ☆
card IO - 1) 25:Timer trigger input

DI9 terminal function 26:Dc brake command 0xF508


F5-08 selection (expansion 27:External input fault normally closed 0 ☆
card IO - 1) 28:Counter input
29:Counter reset 0xF509
30:Counting the length of the input
DI9 terminal function 31:The length of the reset
selection (expansion 32:Torque control is prohibited ☆
F5-09 0
card IO - 1) 33:Input PULSE frequency
34:PID switch

124
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F5-10 DI filtering time 0ms~3600ms 0xF500A 10ms ☆

0 - Two wire1
Terminal command 1 - Two wire 2
F5-11 0xF50B 0 ☆
mode 2 - Three wire system 1
3 - Three wire system 2
Terminal change rate
F5-12 0.00V~100.00V 0xF50C 1.00V ☆
UP/DOWN
UP/DOWN reference 0:The target frequency ☆
F5-13 0xF50D
frequency = 1 :Operating frequency
AI1 minimum input ☆
F5-15 0.00 V~10.00V 0xF50E 0.00
(V)
AI1 minimum input ☆

F5-16 corresponding set -100.0%~100.0% 0xF510 0.0


(%)
AI1 maximum input ☆
F5-17 0.00 V~10.00V 0xF511 10.00
(V)
AI1 input ☆

F5-18 corresponding to the -100.0%~100.0% 0xF512 100.0


largest set (%)
AI1 input filtering ☆
F5-19 0.00S~10.00S 0xF513 0.10
time (S)
AI2 minimum input ☆
F5-20 0.00V~10.00V 0xF514 0.00
(V)
AI2 minimum input ☆

F5-21 corresponding set -100.0%~100.0% 0xF515 0.0


(%)
AI2 maximum input ☆
F5-22 0.00V~10.00V 0xF516 10.00
(V)
AI2 maximum input ☆

F5-23 corresponding set -100.0%~100.0% 0xF517 100.0


(%)
AI2 input filtering ☆
F5-24 0.00S~10.00S 0xF518 0.10
time (S)
AI3 minimum input ☆
F5-25 0.00V~10.00V 0xF519 0.00
(V)
AI3 minimum input ☆

F5-26 corresponding set -100.0%~100.0% 0xF51A 0.0


(%)

125
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

AI3 maximum input ☆


F5-27 0.00 V~10.00V 0xF51B 10.00
(V)
AI3 maximum input ☆

F5-28 corresponding set -100.0%~100.0% 0xF51C 100.0


(%)
AI3 input filtering ☆
F5-29 0.00S~10.00S 0xF51D 0.10
time (S)
PULSE input ☆

F5-30 minimum frequency 0.00KHz~50.00KHz 0xF51E 0.00


( KHz)
PULSE frequency ☆

corresponding to the
F5-31 -100.0%~100.0% 0xF51F 0.0
minimum input set
(%)
PULSE input ☆

F5-32 maximum frequency 0.00KHz~50.00KHz 0xF520 50.00


( KHz)
PULSE input ☆

frequency
F5-33 -100.0%~100.0% 0xF521 0.0
corresponding to the
largest set (%)
PULSE input ☆
F5-34 0.00S~10.00S 0xF522 0.10
filtering time (S)
Opening the DI3 0.0S~3600.0S ★
F5-35 0xF523 0.0s
delay time
0.0S~3600.0S 0xF524 ★
F5-36 DI3 trip delay time 0.0s
Opening the DI4 0.0S~3600.0S 0xF525 ★
F5-37 0.0s
delay time
0.0S~3600.0S 0xF526 ★
F5-38 DI4 trip delay time 0.0s
Opening the DI5 0.0S~3600.0S 0xF527 ★
F5-39 0.0s
delay time
0.0S~3600.0S 0xF528 ★
F5-40 DI5 trip delay time 0.0s
DI3 terminal 0- Make effective
F5-41 0xF529 0 ★
effective model 1- Disconnect the effective
DI4 terminal 0- Make effective
F5-42 0xF52A 0 ★
effective model 1- Disconnect the effective
DI5 terminal 0- Make effective
F5-43 0xF52B 0 ★
effective model 1- Disconnect the effective

126
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Analog AI1 0:F5-15~F5-19


F5-44 multipoint input 1:FA-00~FA-07 0xF52C 0 ☆
mode choice 2:FAE-08~FA-15
Analog AI2 0:F5-15~F5-19
F5-45 multipoint input 1:FA-00~FA-07 0xF52D 0 ☆
mode choice 2:FA-08~FA-15
F6 set of output terminals

Control board relay 0:There is no function


F6-00 RELAY1 output 1: in the operation of the converter 0xF600 2 ☆
option 2: fault output
Level 3: frequency detection of FDT arrive
Control board relay 4: frequency to
F6-01 RELAY2 output 5: in the operation of the zero speed 0xF601 1 ☆
option 6: motor overload forecasting warning
7: inverter overload forecasting warning
8: PLC cycle is complete
9: run time
10: frequency limit
F6-02 Y1 output option 0xF602 0 ☆
11: run ready
12: AI1 > AI2
13: limit frequency reached
14: the lower frequency to arrive
15: undervoltage state output
16: communication is set
17: timer function, of output
Y2 output option
F6-03 18: direction of rotation speed value 0xF603 0 ☆
19: current limit
20: length to reach
21: torque limit

0 - pulse output (FMP)


FM terminal output
F6-04 1 - open collector output switch 0xF604 0 ☆
mode selection
2 - as AO3 output
F6-05 FMR output option 0xF605 0 ★

F6-06 FMP output option 0xF606 0 ☆


IO - 2 extension
F6-07 With the DO function selection 0xF607 0 ☆
board relay
IO - 2 extension
F6-08 0xF608 0 ☆
board relay

127
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

0: operating frequency
F6-09 AO1 output option 0xF609 0 ☆
1: set frequency

2: output current

3: the output power

4: the output voltage


F6-10 AO2 output option 0xF610A 0 ☆
5: AI1

6: AI2

7: newsletter set

FMP output
F6-11 maximum frequency 0.0~50.0 0xF60B 50.0 ☆
( KHz)
AO1 zero bias
F6-12 -100.0%~100.0% 0xF60C 0.00% ☆
coefficient (%)
F6-13 AO1 gain -10.00~10.00 0xF60D 1.00 ☆

AO2 zero bias


F6-14 -100.0%~100.0% 0xF60E 0.00% ☆
coefficient (%)
F6-15 AO2 gain -10.00~10.00 0xF60F 1.00 ☆

AO1 minimum
F6-16 0.00~10.00V 0xF610 0.00 ☆
output voltage
AO1 maximum
F6-17 0.00~10.00V 0xF611 10.00 ☆
output voltage
AO2 minimum
F6-18 0.00~10.00 V 0xF612 0.00 ☆
output voltage
AO2 maximum
F6-19 0.00V~10.00V 0xF613 10.00V ☆
output voltage
AO3 minimum
F6-20 0.00V~10.00V 0xF614 0.00V ☆
output voltage
AO3 maximum
F6-21 0.00V~10.00V 0xF615 10.00V ☆
output voltage
F7 set of auxiliary functions and man-machine interface function

Inching operation
F7-00 0.00Hz~F0-14 0xF700 6.00 ☆
frequency
Some dynamic
F7-01 0.0s~3000.0s 0xF701 ☆
acceleration time 1.00s
Point move to slow
F7-02 0.0s~3000.0s 0xF702 ☆
down time 1.00s
128
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F7-03 Acceleration time 2 0.0s~3000.0s 0xF703 3.00s ☆


F7-04 Deceleration time 2 0.0s~3000.0s 0xF704 2.00s ☆
F7-05 Acceleration time 3 0.0s~3000.0s 0xF705 3.00s ☆
F7-06 Deceleration time 3 0.0s~3000.0s 0xF706 2.00s ☆

F7-07 Acceleration time 4 0.0s~3000.0s 0xF707 3.00s ☆


F7-08 Deceleration time 4 0.0s~3000.0s 0xF708 2.00s ☆
Hopping frequency
F7-09 0.00Hz~300.0Hz 0xF709 ☆
point 1 0.00Hz
Hopping frequency
F7-10 0.00Hz~300.0Hz 0xF70A ☆
point 2 0.00Hz
Hopping frequency
F7-11 0.00Hz~300.0Hz 0xF70B ☆
point 3 0.00Hz
Hopping frequency
F7-12 0.00Hz~300.0Hz 0xF70C ☆
point 4 0.00Hz
Hopping frequency
F7-13 0.00Hz~300.0Hz 0xF70D ☆
point 5 0.00Hz
Hopping frequency
F7-14 0.00Hz~300.0Hz 0xF70E ☆
point 6 0.00Hz
Positive &negative
F7-15 0.0s~3000.0s 0xF70F 0.0s ☆
dead band time (S)
0: Normal speed
1:0.1Hz
2:0.5Hz
3:1Hz
Rotate the keyboard
F7-16 4:2Hz 0xF710 0 ☆
control precision
5:4Hz
6:5Hz
7:8Hz
8:10Hz
Set the frequency is
0:In the lower frequency operation
lower than the lower
F7-17 1:downtime 0xF711 0 ☆
limit frequency
2:Zero speed operation
action:
F7-18 Droop control (Hz) 0.00Hz~10.00Hz 0xF712 0.00Hz ☆
The length of delay
time s a frequency is
F7-19 0.0s~600.0s 0xF713 0.0s ☆
lower than the lower
limit
129
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

F7-20 Set the running time 0h~65535h 0xF714 65535h ☆


Terminal point
0:Continue to run
F7-21 dynamic priority 0xF715 0
1:downtime
choice
Hz frequency values
F7-22 0.00Hz~Maximum frequency 0xF716 50.00Hz ☆
(FDT level)
Check frequency
F7-23 hysteresis values 0.0%~100.0%(FDT level) 0xF717 5.0% ☆
(FDT lag) %
Frequency to detect
F7-24 the width (maximum 0.0%~100.0%(Maximum frequency) 0xF718 0.0% ☆
frequency)
The negative 0:Zero speed operation
F7-25 0xF719 ☆
frequency selective 1:Anyway, run
Running time to 0:Continue to run
F7-26 0xF71A 0 ★
action 1:downtime
0: only valid at the time of the keyboard control

1: the terminal control, STOP key STOP function


effectively

The STOP/RESET 2: the terminal control, the STOP button fault reset
F7-27 0xF71B 0 ☆
function function effectively

3: the terminal control, the STOP button STOP


function and fault reset is valid

0: dynamic function keys


Keyboard worldwide
F7-28 0 ☆
function selection 1: forward/reverse switch function keys

F7-29 Run the LED display 1~8191 0xF71D 4095 ☆

F7-30 Stop LED display 1~127 0xF71E 127 ☆


The coefficient of
F7-31 0.000~6.500 0xF71F 1.000 ☆
load speed display
The radiator -
F7-32 12℃~100℃ 0xF720 ●
temperature
F7-33 Cumulative on time 0~65535 0xF721 -
Cumulative run -
F7-34 0~1440 0xF722 ●
minutes

130
CM5X0E general magnetic flux vector control inverter user manual Appendix

Functi
Contact Mod
on Name Setting range Factory
address ify
Code

Cumulative days -
F7-35 0~65535 0xF723 ●
running
0:the fan running
1: stop running stop in a minute
F7-36 Fan control: 2: with the drive run/stop action 0xF724 1 ☆
3: the radiator temperature more than about 50 ℃

0: invalid
Dormancy of water
F7-37 0xF725 0 ☆
supply 1: effective

F7-38 Sleep wake up value 0.0%~100.0% 0xF726 3.0% ☆

Timing time when


F7-39 0.0s~6000.0s 0xF727 2.0s ☆
closed
Disconnected time
F7-40 0.0s~6000.0s 0xF728 2.0s ☆
regularly
0: invalid
Start the protection (terminal command effective direct start)
F7-41 0xF729 1 ☆
function 1: effective

Electricity directly
F7-42 1.0s~60.0s 0xF72A 1.0s ☆
start delay time

F7-45 To current 0.0% ~ 200.0s% 0xF72D 100.0%
Any current reaches
F7-46 0.0% ~ 100.0% 0xF72E 3.0% ☆
the width
The agent setting ☆
F7-47 - 0xF72F -
time
The agent set ☆
F7-48 - 0xF730 -
password

F7-49 The agent password - 0xF731 -

F7-51 The user password 0~65535 0xF733 0

131
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

F8 group communication parameters


0:300BPS
1:600BPS
2:1200BPS
3:2400BPS
F8-00 Baud rate setting 0xF800 5 ☆
4:4800BPS
5:9600BPS
6:19200BPS
7:38400BPS
0:No check<8,N,2>
F8-01 The data format 1:Parity checking<8,E,1> 0xF801 0 ☆
2:odd checking<8,O,1>
The machine address
F8-02 0 for the broadcast 0~247(0 is broadcast address) 0xF802 1 ☆
address
F8-03 Response time (ms) 0ms~20ms 0xF803 10ms ☆
communication
F8-04 overtime time (s) 0.0s~60.0s 0xF804 0.0s ☆
communication patter
F8-05 choice 0 ~ 1 0xF805 0 ☆
Linkage proportion
F8-06 from the machine 0.00%~ 10.00% 0xF806 1.00 ☆

Master-slave machine
F8-07 0 ~ 1 0xF807 0 ☆
model choice

F9 group failure and protection

Motor overload 0:banned


F9-00 0xF900 1 ☆
protection option 1:allowed
Motor overload
F9-01 protection time 0.20~10.00 0xF901 1.00 ☆
coefficient
Motor overload
F9-02 coefficient of 50%~100% 0xF902 80 ☆
warning
The overpressure
F9-03 0%~100% 0xF903 100% ☆
stall gain
Overvoltage
F9-04 protection voltage 100%~200% 0xF904 150% ☆
stalled
F9-05 Loss of speed gain 0%~100% 0xF905 100% ☆

132
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

Over current
F9-06 protection current 100%~200% 0xF906 150% ☆
stalled
Encoder bolt testing ☆
F9-09 0~100 0xF909 5
time

0: warning, but continue to run
Encoder Wire
F9-10 1: warning, slow down 0xF90A 2
processing
2: warning. Free downtime
Automatic reset
F9-11 0~3 0xF90B 0 ☆
failure time
During the fault
self-recovery 0:no action
F9-12 0xF901C 0 ☆
Fault relay action 1:action
choice
Fault self-recovery
F9-13 0.1s~100.0s 0xF90D 1.0 ☆
time interval
The input phase 0:banned
F9-14 0xF90E 1 ☆
protection option 1:allowed
The output phase 0:banned
F9-15 0xF90F 1 ☆
protection option 1:allowed
F9-16 The first fault types 0:trouble-free 0xF910 ●
The second fault 1: inverter unit protection (ERR01)
F9-17 0xF911 ●
types 2: hardware flow (ERR02)

F9-18 The third fault types 3: hardware overvoltage (ERR03) 0xF912 ●


4: to accelerate the over-current (ERR04)
F9-19 Thelatest fault types 0xF913 ●
5: slow down over current (ERR05)
A recent failure
F9-20 6: constant speed over current (ERR06) 0xF914 ●
frequency
7: stop current (ERR07)
The latest fault
F9-21 8: accelerate the overvoltage (ERR08) 0xF915 ●
current
9: slow overvoltage (ERR09)
A recent failure 10: constant speed overvoltage (ERR1)
F9-22 0xF916 ●
busbar voltage 11: stop overvoltage (ERR11)

133
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

12: under-voltage fault (ERR12)


13: inverter overload (ERR13)
14: motor overload (ERR14)
15: module overheating (ERR15)
16: AD transform fault (ERR16)
17: IU current fault (ERR17)
The latest output
18: IV current fault (ERR18)
F9-23 terminal input 0xF917 ●
19: IW current fault (ERR19)
terminal
20: ground fault (ERR20)
21: motor parameter tuning fault (ERR21)
22: Encoder failure (ERR22)
23: the input phase (ERR23)
24: output phase (ERR24)
25: memory fault (ERR25)
26: password input error more than 3 times
(ERR26)
The latest output
F9-24 27: communication failure (ERR27) 0xF918 ●
terminal
28: external fault (ERR28)
29: PID single-line breakdown (ERR29)
FA group PID function
0:PID keyboard given
1:AI1
2:AI2
FA-00 PID given original 3:communication given 0xFA00 0 ☆
4:AI3
5:PULSEgiven
6:muti-level order given
FA-01 PID keyboard given 0.0%~100.0% 0xFA01 50.0% ☆

PID given changing


FA-02 0.0s~3000.0s 0xFA02 0.0s ☆
time
0:AI1 ☆
0xFA03 0
1:AI2
2:AI1-AI2
PID feedback
FA-03 3:communication given
original
4:AI3
5:PULSEgiven
6:AI1+AI2
PID working 0:positive effect
FA-04 0xFA04 0 ☆
direction 1:negative effect

134
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

PIDgiven feedback
FA-05 0~65535 0xFA05 1000 ☆
value
The proportion
FA-06 0.0~100.0 0xFA06 20.0 ☆
grainP
FA-07 Integration timeI 0.01s~10.00s 0xFA07 2.00s ☆

FA-08 differential timeD 0.000s~10.000s 0xFA08 0.00s ☆

The cut-off frequency


FA-09 0.00Hz~maximum frequency 0xFA09 0.0Hz ☆
inversion

FA-10 Deviation limits(℅) 0.0%~100.0% 0xFA0A 0.01% ☆


Differential
FA-11 limiting(℅) 0.0%~100.0% 0xFA0B 5% ☆
PID output filtering
FA-12 time 0.00S~60.00S 0xFA0C 0.00S ☆
PID A feedback is
FA-13 missing values 0.0% ~ 100.0% 0xFA0D 0.0% ☆
PID Feedback is
FA-14 missing detection 0.0s ~ 60.0s 0xFA0E 1.0s ☆
time
Start the PID loss
FA-15 detection delay 0.0s ~ 120.0s 0xFA0F 0.0s ☆
PID given changing
FA-16 time 0.0s ~ 60.0s 0xFA10 0.0s ☆
Top menu can be
FA-17 modified FA - 01 PID 0 ~ 1 0xFA11 0 ☆
mode
The proportion
FA-18 grainP2 0.0%~100.0% 0xFA12 20.0% ☆

FA-19 Integration timeI2(s) 0.01s~10.00s 0xFA13 2.00s ☆

FA-20 differential timeD2(s) 0.000s~10.000s 0xFA14 0.000s ☆


0:don't switch
1: through DIterminal switching
PID Parameters of
FA-21 2: according to the deviation of automatic 0xFA15 0 ☆
switching conditions
switching
3: according to the frequency automatic switching
PID switching
FA-22 deviation1 0.0% ~ 100% 0xFA16 0.0% ☆
PID switching
FA-23 deviation2 0.0% ~ 100.0% 0xFA17 0.0% ☆

FA-24 PIDinitials 0.0% ~ 100.0% 0xFA18 0.0% ☆


PIDinitials keeping
FA-25 time 0.00s ~ 650.00s 0xFA19 0.0s ☆
Two positive
FA-26 maximum output 0.00% ~ 100.00% 0xFA20 0.00% ☆

135
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy
Two reverse
FA-27 maximum output 0.00% ~ 100.00% 0xFA21 0.00% ☆

0:Don't stop operation


FA-28 PID Stop operation 0xFA22 0 ☆
1:Stop operation
FB group the pendulum function
0:Relative to the center frequency
FB-00 Swing set 0xFB00 0 ☆
1:relative to maximum frequency
The pendulum
FB-01 frequency range (℅) 0.0%~100.0% 0xFB01 0.0% ☆
A sudden jump
FB-02 frequency range (℅) 0.0%~50.0% 0xFB02 0.0% ☆
The pendulum
FB-03 frequency cycle (s) 0.1s~3000.0s 0xFB03 10.0s ☆
Rise time coefficient
FB-04 triangular wave (℅) 0.1%~100.0% 0xFB04 50.0% ☆

FB-05 Setting length (m) 0~65535 0xFB05 1000

FB-06 Real length (m) 0~65535 0xFB06 0

FB-07 Every impluse nubers 0.1~65535 0xFB07 1000

FB-08 Setting count 1~65535 0xFB08 1000

FB-09 Specifying count 1~65535 0xFB09 1000

FCgroup Multistage speed、PLC


negtivemaximum frequency ~ maximum
FC-00 Multistage speed0 0xFC00 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-01 Multistage speed1 0xFC01 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-02 Multistage speed2 0xFC02 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-03 Multistage speed3 0xFC03 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-04 Multistage speed4 0xFC04 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-05 Multistage speed5 0xFC05 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-06 Multistage speed6 0xFC06 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-07 Multistage speed7 0xFC07 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-08 Multistage speed8 0xFC08 0.0Hz ☆
frequency
FC-09 Multistage speed9 negtivemaximum frequency ~ maximum 0xFC09 0.0Hz ☆
136
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

frequency
negtivemaximum frequency ~ maximum
FC-10 Multistage speed10 0xFC0A 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-11 Multistage speed11 0xFC0B 0.0Hz ☆
frequency
negtivemaximum frequency ~ maximum
FC-12 Multistage speed12 0xFC0C 0.0Hz ☆
frequency
negtivemaximum frequency~maximum
FC-13 Multistage speed13 0xFC0D 0.0Hz ☆
frequency
negtivemaximum frequency~maximum
FC-14 Multistage speed14 0xFC0E 0.0Hz ☆
frequency
negtivemaximum frequency~maximum
FC-15 Multistage speed15 0xFC0F 0.0Hz ☆
frequency

0:One end of the run down

FC-16 PLC running way 1:Single run end of final value 0xFC10 0 ☆
2:keep cycling

0: no memory reset and stop interrupt when power


supply drop
1: power lost memory reset and stop interrupt
PLC Power lost
FC-17 2: power lost no memory and no longer a stop 0xFC11 0 ☆
memories choice
interrupt
3: power lost memory and no longer a stop
interrupt

PLC 0 segment
FC-18 0.0s(h)~6553.5s(h) 0xFC12 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 0 segment
1:ac-decelaration time2
FC-19 ac-deceleration time 0xFC13 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 1 segment
FC-20 0.0s(h)~6553.5s(h) 0xFC14 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 1 segment
1:ac-decelaration time2
FC-21 ac-deceleration time 0xFC15 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4

137
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

PLC 2 segment
FC-22 0.0s(h)~6553.5s(h) 0xFC16 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 2 segment
1:ac-decelaration time2
FC-23 ac-deceleration time 0xFC17 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 3 segment
FC-24 0.0s(h)~6553.5s(h) 0xFC18 0.0s(h) ☆
running time

0:ac-decelaration time1

PLC 3 segment 1:ac-decelaration time2


FC-25 0xFC19 0 ☆
ac-deceleration time 2:ac-decelaration time3
3:ac-decelaration time4
PLC 4 segment
FC-26 0.0s(h)~6553.5s(h) 0xFC1A 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 4 segment
1:ac-decelaration time2
FC-27 ac-deceleration time 0xFC1B 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 5 segment
FC-28 0.0s(h)~6553.5s(h) 0xFC1C 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 5 segment
1:ac-decelaration time2
FC-29 ac-deceleration time 0xFC1D 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 6 segment
FC-30 0.0s(h)~6553.5s(h) 0xFC1E 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 6 segment
1:ac-decelaration time2
FC-31 ac-deceleration time 0xFC1F 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 7 segment
FC-32 0.0~6553.5s(h) 0xFC20 0.0s(h) ☆
running time

PLC 7 segment 0:ac-decelaration time1


FC-33 0xFC21 0 ☆
ac-deceleration time 1:ac-decelaration time2
138
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

choice 2:ac-decelaration time3


3:ac-decelaration time4
PLC 8 segment
FC-34 0.0s(h)~6553.5s(h) 0xFC22 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 8 segment
1:ac-decelaration time2
FC-35 ac-deceleration time 0xFC23 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 9 segment
FC-36 0.0s(h)~6553.5s(h) 0xFC24 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 9 segment
1:ac-decelaration time2
FC-37 ac-deceleration time 0xFC25 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 10 segment
FC-38 0.0s(h)~6553.5s(h) 0xFC26 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 10 segment
1:ac-decelaration time2
FC-39 ac-deceleration time 0xFC27 0.0s(h) ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 11 segment
FC-40 0.0s(h)~6553.5s(h) 0xFC28 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 11 segment
1:ac-decelaration time2
FC-41 ac-deceleration time 0xFC29 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 12 segment
FC-42 0.0s(h)~6553.5s(h) 0xFC2A 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 12 segment
1:ac-decelaration time2
FC-43 ac-deceleration time 0xFC2B 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 13 segment
FC-44 0.0s(h)~6553.5s(h) 0xFC2C 0.0s(h) ☆
running time
139
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

0:ac-decelaration time1
PLC 13 segment
1:ac-decelaration time2
FC-45 ac-deceleration time 0xFC2D 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 14 segment
FC-46 0.0s(h)~6553.5s(h) 0xFC2E 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 14 segment
1:ac-decelaration time2
FC-47 ac-deceleration time 0xFC2F 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC 15 segment
FC-48 0.0s(h)~6553.5s(h) 0xFC30 0.0s(h) ☆
running time

0:ac-decelaration time1
PLC 15 segment
1:ac-decelaration time2
FC-49 ac-deceleration time 0xFC31 0 ☆
choice 2:ac-decelaration time3
3:ac-decelaration time4
PLC running time 0:s(second)
FC-50 0xFC32 0 ☆
unit choice 1:h(hour)
Multistage speed 0:Multistage speed not first
FC-51 0xFC33 0 ☆
first-way choice 1:Multistage speed first
Multistage speed 0:ac-decelaration time1
level first 1:ac-decelaration time2
FC-52 0xFC34 0 ☆
ac-decelaration time 2:ac-decelaration time3
choice 3:ac-decelaration time4
Multistage speed、
FC-53 PLC directly 0~1 0xFC35 0 ☆
modified
Multistage speed、
PLC directly
FC-54 0~1 0xFC36 1 ☆
modified whether
saved
FD group torque controls parameters group
0:digital setting(FD-01)
Torque command 1:AI1
FD-00 0xFD00 0 ☆
source selection 2:AI2
3:AI3
140
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy

4:PULSEimpulse frequency setting


5:communication given
6:MIN(AI1,AI2)
7:MAX(AI1,AI2)

Torque numbers
FD-01 -200%~200% 0xFD01 100% ☆
given %
FD-02 Max torque limits % 0%~200% 0xFD02 100% ☆
Torque controns
positive direction
FD-03 0.00~FMAX 0xFD03 50.00Hz ☆
maximum
frequency(Hz)
Torque controns
reverse direction
FD-04 0.00~FMAX 0xFD04 50.00Hz ☆
maximum
frequency(Hz)
Torque order filtering
FD-06 0.000~1.000s 0xFD06 0.000 ☆
time(s)
Torque command
FD-07 0.00s ~ 600.00s 0xFD07 0.00s ☆
speeding up time
Torque order
FD-08 0.00s ~ 600.00s 0xFD08 0.00s ☆
decelaration time
Torque controls
0:For deceleration mode with torque command
FD-09 ac-decelaration 0xFD09 0 ☆
1:With speed limit values for deceleration mode
choice
Positive frequency
FD-10 0~3 0xFD0A 0 ☆
limit
Reverse frequency
FD-11 0~3 0xFD0B 0 ☆
limit
FE group enhancement function group
AIcurve1The
FE-00 0.00V~10.00V 0xFE00 0.00V ☆
minimum input
AIcurve1The
minimum
FE-01 inputcorresponding -100.0%~100.0% 0xFE01 0.0% ☆
set
AIcurve1The
FE-02 minimum input 0.00V~10.00V 0xFE02 0.00V ☆
AIcurve1The
FE-03 minimum -100.0%~100.0% 0xFE03 0.0% ☆
inputcorresponding

141
CM5X0E general magnetic flux vector control inverter user manual Appendix

Funct M
Contact
ion Name Setting range Factory odi
address
Code fy
set

AIcurve1The
FE-04 minimum input 0.00V~10.00V 0xFE04 0.00V ☆
AIcurve1The
minimum
FE-05 inputcorresponding -100.0%~100.0% 0xFE05 0.0% ☆
set
AIcurve1The
FE-06 minimum input 0.00V~10.00V 0xFE06 0.00V ☆
AIcurve1The
minimum
FE-07 inputcorresponding -100.0%~100.0% 0xFE07 0.0% ☆
set
AIcurve2The
FE-08 minimum input 0.00V~10.00V 0xFE08 0.00V ☆
AIcurve2The
minimum
FE-09 inputcorresponding -100.0%~100.0% 0xFE09 0.0% ☆
set
AIcurve2The
FE-10 minimum input 0.00V~10.00V 0xFE0A 0.00V ☆
AIcurve2The
minimum
FE-11 inputcorresponding -100.0%~100.0% 0xFE0B 0.0% ☆
set
AIcurve2The
FE-12 minimum input 0.00V~10.00V 0xFE0C 0.00V ☆
AIcurve2The
minimum
FE-13 inputcorresponding -100.0%~100.0% 0xFE0D 0.0% ☆
set
AIcurve2The
FE-14 minimum input 0.00V~10.00V 0xFE0E 0.00V ☆
AIcurve2The
minimum
FE-15 inputcorresponding -100.0%~100.0% 0xFE0F 0.0% ☆
set
0:LED keyboard
FE-17 Keyboard choice 0xFE11 0 ☆
1:LCD keyboard
Input lack of a
FE-18 sensitivity 0~5000 0xFE12 10 ☆

FE-19 Output power - 0xFE13 - ☆


Total waste power
FE-20 value - 0xFE14 - ☆

FE-22 Top menu displays 0 ~ 5 0xFE15 0 ☆

FE-23 AO directly set 0 ~ 1 0xFE16 0 ☆

142
CM5X0E general magnetic flux vector control inverter user manual Appendix

Appendix B:card specification

A、CM580IO1expansion card usage explanation


1、overview
Output current range: 0 mA ~ 50 mA
Note: the digital output CME and digitalinput COM is internal isolation, users should be the CME and COM
external short sub.When DO2 think with external power drive, you have to disconnect the CME and COM.
2、installation and contron of machines terminalfunctionexplanation
1, installation, appearance size, jump line port, CN3signal defined respectively appendixB: Map1, Map2, Map3:
1) please under the condition of power inverter complete installation;
2) on the I/Oexpansion card and inverter control panel expansion cardport and positioning hole;
3) with screws.

appendixB:Map1 CM580IO Installation Way

143
CM5X0E general magnetic flux vector control inverter user manual Appendix

DIP switch

appendixB:Map2 CM580IO1 Installation Dimensions

U:0/2~10V U:0/2~10V PNP:PNP MODE

AI3 A03 DI

I:0/4~20mA I:0/4~20mA NPN:NPN MODE

appendixB:Map3 CM580IO1 Dialing Code Switch Map

AI3 AO2 DI7 DI8 DI9 DI10 24V


T/A2 T/B2 T/C2
GND -10V +10V Y2 CME COM COM

appendixB:Map4 CM580IO1 Controlling Loopterminal

144
CM5X0E general magnetic flux vector control inverter user manual Appendix

2、CM580IO1 controlling terminalfunctionexplanation:


Terminal Terminal
Types Function explanation
Signal Name
To provide + 10 v power supply, the maximum output
+10V-GN current: 10 mA
+10V-GND Generally used as an external potentiometer work power,
D
potentiometer resistance range:1kΩ~10kΩ
To provide - 10 v power supply, the maximum output current:
Power -10V-GND -10V-GND 10 mA
supply Commonly used as an external sensors work power

To provide + 24 v power supply, generally used as a digital


+24V-CO External + 24 v input and output terminal work power supply or external
M power supply sensor power supply.
Maximum output current: 200 mA

1. The range of input voltage: DC 0 v ~ 10 v/ma ~ 20 ma, 0


Analogous by the expansion card JK4 jumper selection decision on v
Analogous
AI3-GND value input (factory default to 0 ~ 10 v).
input
terminal3 2.Input impedance:when voltahe input 100kΩ,when current
input 500Ω
Multifuncti DI7-COM Digital input7
DI8-COM Digital input8 1, optical coupling isolation, compatible with bipolar input
on digital
DI9-COM Digital input9 2, the input impedance: 4.4 kΩ
input
3, level when the input voltage range: 9 ~ 30 v
terminal DI10-COM Digita linput10

By the expansion card of JK3 jump line voltage or current


Analogous analogous output choices (factory default for voltage output).
AO2-GND
output output2 The amount of output voltage specifications: 0 v to 10 v
The output current specifications: 0 mA ~ 20 mA

Optical coupling isolation, bipolar open collector output;The


output voltage range: 0 v ~ 24 v;Output current range: 0 mA
~ 50 mA;Note: the digital output CME and digitalinput COM
Digital Y2-CME Digital output2
is internal isolation, users should be the CME and COM
external short sub.When DO2 think with external power
drive, you have to disconnect the CME and COM.

触点驱动能力:
Relay T/A-T/B 常闭 terminal
AC250V,3A,COSφ=0.4。
output DC 30V,1A
T/A-T/C 常开 terminal
Auxiliary
J1 控制板 port 28 芯 terminal,与 CM580 系列变频器的控制板连接用
port

145
CM5X0E general magnetic flux vector control inverter user manual Appendix

B、CM580IO2 expansion card(output function expansion)usage explanation

DIP switch

appendixB:Map5 CM580IO2 Installation Dimensions

Y2 +24V AO2 AO3


T/A2 T/B2 T/C2 T/A3 T/B3 T/C3 CME COM GND GND

appendixB:Map6 CM580IO2 Controlling Loop Terminal

I:0/4~20mA I:0/4~20mA

A02 A03

U:0/2~10V U:0/2~10V

appendixB:Map7 CM580IO2 Dialing Code Switch Map

146
CM5X0E general magnetic flux vector control inverter user manual Appendix

CM580IO2 controlling terminal function explanation:

By the expansion card toll on CN4 dial the code


AO2-GND analogous output2 switch voltage or current output choices (factory
Analogous default for voltage output).
output The amount of output voltage specifications: 0 v to
10 v
AO3-GND analogous output3 The output current specifications: 0 mA ~ 20 mA

Optical coupling isolation, bipolar open collector


output
The output voltage range: 0 v ~ 24 v
Output current range: 0 mA ~ 50 mA
Digital
Y2-CME Digitao output 2 Note: the digital output CME and digital input to
output
COM is internal isolation, users should be the CME
and COM external short sub.When DO2 think with
external power drive, you have to disconnect the
CME and COM.

Normally closed
T/A2-T/B2
terminal
Normally
T/A2-T/C2 Contact the drive ability:
openterminal
Relay output AC250V,3A,COSφ=0.4。
Normally closed
T/A3-T/B3 DC 30V,1A
terminal
Normally open
T/A4-T/C4
terminal

Auxiliary 28 core terminal, and CM580 series inverter control


J1 Controling panel port
port panel connected with

C、PG card usage explanation


1、abstract:
CM5X0E equipped with three general Encoderexpansion card (namely PGcard), used as options, is made a
closed-loop vector control frequency converter or the closed loop torque control option, according to choose
corresponding PGcard Encoder output form, specific models are as follows:

Options Description
Open collector signalinput (compatible complementary output, the output
CM580PG1 voltage NPN Encoder, through dial the code switch), open collector with 1:1 the
frequency signal output
Differential signalinput (applicable to line driver output Encoder), including U
CM580PG2
V Wdifferential signal, open collector with 1:1 the frequency signal output
Differential signalinput (applicable to line driver output Encoder), differential
CM580PG3
with 1:1 the frequency signal output

147
CM5X0E general magnetic flux vector control inverter user manual Appendix

2、CM580PG1 usage explanation:

A B Z 15V COM OUTA COM OUTB COM

appendixB:Map8 CM580PG1terminalMap

CM:互补或NPN电压输出
Complementary or NPN output voltage

PG

OC:开路集电极
Open collector

appendixB:Map9 CM580PG1 Dialing Switch Map

PG card1terminalfunctionexplanation:

Terminal
Function Response Speed Max Current remark
Mark
Encoder working
15V,COM ―― 100mA ――
power supply
Open collector
electrodesignal or
EncoderA B Zsignal Complementary
ABZ 0~100kHz ――
input port (push-pull) output
signal or NPN voltage
output signal
OUTA,COM
1:1 A Bsignal output 0~100kHz 100mA Open collector signal
OUTB,COM
remark:
1, PGcard1 can only be used in asynchronous machine;
2, compatible complementary output, the output voltage NPN Encoder, through dial the code switch,
specific see Map9.

3、CM580PG2 usage explanation:

U+ V+ W+ A+ B+ Z+ OUTA OUTB +5V1


U- V- W- A- B- Z- COM COM COM

appendixB:Map10 CM580PG2 Terminal Map

PG card 2(differential signalinput PG card)terminal function explanation:


Terminal
Function Response Speed Max Current Remark
Mark
Encoder working
+5V1,COM ―― 100mA ――
power supply

148
CM5X0E general magnetic flux vector control inverter user manual Appendix

A+,A- Encoder A B
B+,B- Zdifferential 0~500kHz ―― ――
Z+,Z- signalinputport
For the use of
U+,U- encoder U V asynchronous machine
V+,V- Wlocation differential 0~20kHz ―― ordinary encoder, the
W+,W- signalinputport terminal is not
connection
OUTA,COM
1:1 A Bsignal output 0~500kHz 100mA Open collector
OUTB,COM
remark:
1, apply to line driver output form of the encoder;
2, PGcard2 can be applied to asynchronous machine, connected to the differential signal encoder, at
this point, the connection terminal without U V W;
3, PGcard2 can also be applied to the synchronous machine, can be connected with the rotor pole
testing U V W encoder, and the number of requirements of U V W encoder and the number of
synchronous machine is the same, only the number of the same.

4、CM580PG3 usage explanation:

A+ B+ Z+ +5V1 OA+ OB+ OZ+


A- B- Z- COM OA- OB- OZ-

appendixB:Map11 CM580PG3terminalMap

PG card 3 terminal function explanation:


Terminal Response
Function Max current Remark
Mark Speed
Encoder working power
+5V1,COM ―― 100mA ――
supply
A+,A-
The encoder A B
B+,B- 0~500kHz ―― ――
Zdifferential signal input port
Z+,Z-
OA+,OA-
1:1 A B Z differential signal The differential
OB+,OB- 0~500kHz ――
output signal output
OZ+,OZ-
remark: