COOLING AIR LOW COMPRESSOR

CAPACITY (Kw),(TR) RATE INPUT (Kw)


FLOOR DESIGNATION AREA SERVE (LPS)

FCU 1 UNIT 1 to UNIT 6 5.94 (1.69) 225 2.1


3rd floor
to
8th floor FCU 2 UNIT 7 to UNIT 9 8.21 (2.33) 280 2.9
FAN MOTOR ELECTRICAL CHARACTERISTICS
DRIVE
(W) REMARKS
VOLT PHASE HZ

171 220 1 60

212 220 1 60

0.1428001692 0.21269
sq m / ton h m l
residential 55.8 46.5 35.4
office 33.5 26.1 17.7

unit 1 unit 2 unit 3 unit 4 unit 5 unit 6 unit 7 unit 8


cooling load
make-up air
toilet exhaust
area of room area of toilet ee room reception
unit 1 20.25
unit 2 22.5
unit 3 22.5 2.5 5
unit 4 22.5
3rd flr to 8th unit 5 20.75
8
flr unit 6 21.5
unit 9 unit 7 27.25
unit 8 24.25 22.2 53.3
unit 9 28
hallway
store 1 79.24
store 2 64.25 8.75 5
room 1 15.75
ground floor room 2 10.5 8
room 3 13.95
room 4 13.95
77.8 53.3
lobby 10.5
hallway 24.75
2nd flr store space 268.5 8.75 5 8
bedroom 16.25

funtion room function 53.5


roofdeck toilet 1 2.25 20.0
toilet 2 3.75 33.3
toilet 3 2.5 22.2
Parking 362.4 4026.7
garbage 4.35 38.7
basement
storage 4.25 37.8
pump room 18.1 321.8

ELEVATOR

34 1.8 3

183.6 573.75
BTU/hr sensible latent total sq f
floor area 5200 7500.00 16000 150
occupants/person 600 30 9000.00 9000.00 18000 200
equipment and light/1000 wa 3414 1000 2731.20 546.24 3277.44 300
sun expose/15 sq f 1000 0 0.00 0 340
kitchen (average) 4000 0 0.00 0 450
550
19231.20 9546.24 37277.44 700
800
kw 1.60 0.80 3.11 850
1000
tr 5.64 2.80 10.93 1100
1400
0.6666666667 1500
1600

22.375
3.7291666667

7.4583333333
3.7291666667

4.4583333333
1.3541666667

533.33333
EXHAUST/SUPPLY 2800
JET FAN 700
sq m BTU/hr
13.9 up to 5200
18.6 6000
27.9 7500
31.6 8000
41.8 10000
51.1 12000
65.1 14000
74.4 15000
79.0 16000
93.0 18000
### 20000
### 24000
### 28000
### 32000
AIR COOLED CONDENSING UNIT
FLOOR QTY DESIGNATION TOTAL COOLING (Kw),(TR) COND EXT COMPRESSOR
Calculated Nominal (◦C) KW INPUT

1 ACCU G1 27.1 (7.41) 28.2 (8) 35 10

1 ACCU G2 18.7 (5.33) 21.1 (6) 35 7.5


GROUND
FLOOR
1 ACCU G3 12.3 (3.5) 14.1 (4) 35 5

1 ACCU G4 8.2 (2.3) 7.0 (3) 35 3.8

EER 12
1.25
9.6
G UNIT ELECTRICAL CHARACTERISTICS
COMPRESSOR COOL FAN VOLT PHASE HZ EER DESIGNATION
TYPE OUTPUT
(Kw)
FCU G1.1
SCROLL 380 3 60 9.6
FCU G1.2
FCU G2.1
SCROLL 380 3 60 9.6
FCU G2.2
FCU G3.1
SCROLL 380 3 60 9.6
FCU G3.2 & FCU G3.3

FCU G4.1
SCROLL 380 3 60 9.6
FCU G4.2
FAN COIL UNITS
AREA SERVE TOTAL HEAT (Kw),(TR) SUPPLY AIR ENT DB EVAPORATOR FAN
Calculated Nominal (LPS) (◦C) ESP (Pa) POWER (Watt)
13.1 (3.71) 14.1 (4) 706 22.7 45 150
STORE 1
13.1 (3.71) 14.1 (4) 706 22.7 45 150
9.4 (2.67) 10.6 (3) 570 22.7 45 150
STORE 2
9.4 (2.67) 10.6 (3) 570 22.7 45 150
RETAIL 1 6.7 (1.9) 10.6 (2) 140 22.7 45 150
RETAIL 2 & LOBBY 2.8 (0.8) 10.6 (1) 140 22.7 45 150

RETAIL 3 4.0 (1.2) 5.28 (1.5) 140 22.7 45 150


RETAIL 4 4.0 (1.2) 5.28 (1.5) 140 22.7 45 150
ELECTRICAL CHARACTERISTICS
VOLT PHASE HZ REMARKS

220 3 60
CEILING CASSETTE TYPE
220 3 60
220 3 60
CEILING CASSETTE TYPE
220 3 60
220 3 60
WALL MOUNTED
220 3 60

220 3 60
WALL MOUNTED
220 3 60
COOLING AIR LOW COMPRESSOR
CAPACITY (Kw),(TR) RATE INPUT (Kw)
FLOOR DESIGNATION AREA SERVE (LPS)

FCU 1 UNIT 1 to UNIT 6 5.94 (1.69) 225 2.1


3rd floor
to
8th floor FCU 2 UNIT 7 to UNIT 9 8.21 (2.33) 280 2.9
FAN MOTOR ELECTRICAL CHARACTERISTICS
DRIVE
(W) REMARKS
VOLT PHASE HZ

171 220 1 60

212 220 1 60

0.0357000423 0.03329