Você está na página 1de 20

ANALYSIS OF BEAM SECTION UNDER FLEXURE

Flexural members are those subject to bending, e.g. beams and


slabs. EC2 also mentioned on other types of beam namely:

Deep Beams - Deep beams having a clear span of less than three times
their overall depth require special consideration and are outside the scope
of this module. EC2 gives design guidance.

Slender Beams- Slender beams, where the breadth of the compression face
b is small compared with the depth and length, have a tendency to fail by
lateral torsional buckling. If this buckling is prevented by, for example, a
slab attached to the compression face of the beam, then the beam is
considered as laterally restrained and it will be satisfactory if the depth h is
not more than 2.5 times the breadth b. If the compression face is
unrestrained, then the unrestrained length should not be more than 35 b .
In practice, slender beams are rare.

Stress- Strain Relations for the Design of Cross-sections

Downward loads on a simply supported beam induce sagging


bending moments which cause compressive stress in the material
fibres above the neutral axis and tensile stresses in those below.
Concrete is good at resisting compressive stresses but its resistance

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
to tension is so poor that it is ignored. Instead, steel reinforcing
bars are introduced to resist the tension.
A

Some of the parameters used to describe the cross-section of a


singly reinforced beam are shown below:

Cross-section A-A of rectangular singly reinforced beam

A singly reinforced beam will be adequate in bending if the ultimate


resistance moment Mu of a concrete beam must be greater than or
equal to the ultimate design bending moment Md i.e

Mu ≥ Md
The ultimate design bending moment Md is calculated under
ultimate design loads and will be greatest at or near the centre of
HJ ROSLAN BIN KOLOP
PUSAT PENGAJIAN DIPLOMA PPD
the beam.(For simply supported beam with uniformly distributed
load Md = wdL2/8)
To determine the Mu section analysis can be used as shown below:

Figure (b) above shows the strains in the beam when it is subject
to a sagging bending moment equal to M . The neutral axis is at

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
distance x from the top of the beam.
EC2 in Clause 3.1.7 allows the use of simplified stress-strain
relationship as in Fig (d) which can be used for the design at
ultimate limit state.
In the UK it is considered good practice that x should not be more
than d /2. This will ensure that the beam is under-reinforced and
will fail in a ductile manner by yielding of the reinforcement
giving a robust structural element with some warning of the
failure. If x is much greater than d /2 then the beam is over-
reinforced and may fail by crushing of the concrete, possibly
leading to a sudden collapse. Limiting K to 0.167, as described
later in this section, ensures that the beam is under-reinforced.

During steel yielding, the formation of plastic hinges allows


redistribution of maximum moment, resulting in a safer and
economical structure.
To ensure sufficient rotation of the plastic hinge and also to allow
for others factors, EC2 limits the depth of neutral axis to:
x ≤ 0.45 d for concrete class ≤ C50/60

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
Figure (c) shows the design values of the stresses at the ULS.

● The concrete cylinder strength f ck is multiplied by 0.85, a factor


which converts compressive strength into bending strength, and
divided by the partial safety factor γ m = 1.5.
● The reinforcement strength fyk is divided by the partial safety
factor γ m = 1.15.
Note that the stress in the concrete below the neutral axis is zero as
it is assumed to be cracked.

Figure (d) is a simplified version of Figure (c) with the curved


stress block replaced by a rectangular stress block of depth 0.8 x
for ease of calculation.

Figure (e) shows the stresses from Figure(d) converted to forces.


● Concrete force F cc = stress multiplied by area
= (0.567 fck )(0.8 x )( b ) = 0.453 xbfck
● Steel force F st = stress multiplied by area
= 0.87 fyk As

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
Analysis of a singly reinforced beam using stress block

Based on Cl 3.1.7 EN 1992-1-1

Design equations can be derived as follows:

0.85fck/γc = 0.567fck
0.0035
b

s/2
x s =0.8x Fcc
Neutral
d Axis
z=lad
As

Fst
εst

Section Strain Stress Block

Bending will induce a resultant tensile force Fst in the steel bar and
a resultant compressive force in the concrete Fcc.

At equilibrium , ultimate design moment M = moment of


resistance of the section

M = Fccz =Fstz ………… (1)

Where z is the lever arm.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
Fcc = stress x area of action = 0.567fck x b x s …………..(2)

and z = d – s/2

substitute in (2)

M = Fccz = 0.567fck x b x s x z

Replacing s, s=2(d-z)

M = 1.134fckb(d-z)z

Rearranging and substitute K = M/bd2fck

(z/d)2 - (z/d) + K/1.134 = 0

Solving the quadratic equation:

z = d {0.5 + √(0.25 – K/1.134)} (Also check z < 0.95d)

In equation (1) ,

Fst = (fyk/γs) x As γs - safety factor for steel = 1.15


= 0.87fykAs

Since M= Fstz = 0.87fykAs z

As = M
0.87fykz

This equation can be used to design the tension steel area for
singly reinforced beam section to resist an ultimate design
moment M.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
Balance Section

For a singly reinforced beam, EC2 allows the maximum value


for x (depth to neutral axis)= 0.45d (for C50/60 concrete) in
order to provide ductile section and a gradual tension type
failure. This is often referred as the balance section because at
ultimate limit state the concrete and tension in steel reach their
ultimate strain at the same time.

x bal = 0.45 d

The depth of the stress block,

s = 0.8xbal = 0.8 x 0.45d = 0.36d

The force on the concrete stress block is


Fccbal = 0.567fck x b x s = 0.204fckbd

For equilibrium the force in concrete = force in steel

Fstbal = 0.87fykAsbal = Fccbal = 0.204fckbd

Therefore,
Asbal = 0.234fckbd/fyk

So that
100Asbal = 23.4 fck percent
bd fyk

which is the steel percentage for a balanced section which should


not be exceeded for a ductile singly reinforced section.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
Example: If fck = 25 N/mm2 and fyk=500 N/mm2
100Asbal = 23.4 x 25 = 1.17 percent
bd 500

The ultimate moment of resistance of the balanced section is

Mbal = Fccbalzbal where


zbal = d – s/2 = 0.82d (s = 0.36d)

Substitue Fccbal and z (0.204fckbd)

Mbal = 0.167fckbd2

and

Md = 0.167 = Kbal
fckbd2

If

Md > K bal ( 0.167) than the section can no longer be singly


fckbd2 reinforced and compression steel is needed in the
Compression zone of the section

If the value of K for a singly reinforced beam is found to exceed


K lim > 0.167 then the beam is likely to fail by crushing of the
concrete before the tension reinforcement yields.(Over-
reinforced)

This should be avoided by either:


● using stronger concrete and so reducing K
● increasing the size of the beam and so reducing K
● providing compression reinforcement above the neutral axis
to form a doubly reinforced beam.
HJ ROSLAN BIN KOLOP
PUSAT PENGAJIAN DIPLOMA PPD
Moment of Resistance of a Section

Given a cross-section of a reinforced concrete beam, the moment


of resistance of the section can be calculated.

For equilibrium of the compressive force in the concrete and the


tensile force in the steel as shown below:

Fcc = Fst

therefore

0.567fckb x s = 0.87 fyk As

Therefore depth of stress block is

s = 0.87fykAs/0.567fckb

And x = s/0.8

Therefore moment of resistance of the section is

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
M = Fst x z

This equation assume the tension reinforcement has yielded, which


will be the case if x< 0.617d

Example:

Determine the moment of resistance of the cross-section shown


below. Given fyk=500 N/mm2; fck = 25 N/mm2.

b=300mm

d =520mm

As=1470 mm2

Fcc = Fst

Therefore
0.567fckb x s = 0.87 fyk As

0.567 x 25 x 300 x s = 0.87 x 500 x 1470

s = 150 mm
and

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
x = s/0.8 = 150/0.8 = 188 mm

This value(188/520=0.361) is less than 0.617. Therefore the steel


yielded and fst = 0.87fyk as assumed.

Therefore moment of resistance of the section is

M = Fst x z
= 0.87fykAs(d – s/2)
= 0.87 x 500 x 1470(520 – 150/2) x 10-6
= 284 kNm

Doubly Reinforced Concrete Section

When M > 0.167fckbd2 i.e when the design moment exceeds the
moment of resistance of concrete ( Mbal) then compression
reinforcement is required.

0.85fck/γc = 0.567fck
0.0035
b
s/2
d’
Fsc

As’ x s =0.8x Fcc


Neutral
Axis
d
z bal
As

Fst
εst

Section Strains Stress Block

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
For this condition the maximum depth of neutral axis allows in
EC2 is x <0.45d to ensure ductile failure of the section.

Using equilibrium, Fst = Fcc + Fsc


0.87fykAs = 0.567fckbs +0.87fykA’s

And taking moments about the centroid of the tension steel


M = Fcc x zbal + Fsc (d – d’)

It can be proved that:

( K  K bal ) f ck bd 2
As’ =
0.87 f yk (d  d ' )
and

K bal f ck bd 2
As = + As’
0.87 f yk z bal

M
Where Kbal = 0.167 and K=
bd 2 f ck
If d’/d < 0.171 than the compression yielded

EXAMPLE

The section shown below is to resist an ultimate design moment of


285 kNm. Given fyk=500 N/mm2; fck = 25 N/mm2. Determine the
area of reinforcement required.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
d’=50
mm
As’
d =440
mm
As

b=260
mm
M
K=
bd 2 f ck
= 285 x 106/260x4402x25 = 0.226 >0.167
Therefore compression steel is required.

Check d’/d = 50/400 = 0.11 < 0.171


Compression steel will have yielded

Compression steel:

( K  K bal ) f ck bd 2
As’ =
0.87 f yk (d  d ' )
= (0.226 – 0.167) x 25 x 260 x 4402
0.87 x 500 x (400 – 50)
= 438 mm2

Tension steel:

K bal f ck bd 2
As = + As’
0.87 f yk z bal
= 0.167 x 25 x 260 x 4402 + 438
0.87 x 500(0.82 x 400)
= 1339 + 438 = 1777 mm2

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
HJ ROSLAN BIN KOLOP
PUSAT PENGAJIAN DIPLOMA PPD
Moment of Resistance of Doubly Reinforced Beam

Example

Determine the ultimate moment of resistance of the cross


section shown below. Given fyk = 500 N/mm2 and fck = 25
N/mm2

0.85fck/γc = 0.567fck
b=280
s/2
d’=50
Fsc

As’=628 x s =0.8x Fcc


Neutral
Axis
d=510
z bal
As=2410

Fst

Section Stress Block

Using equilibrium
(tension) (compression)
Fst = Fsc + Fcc

0.87fykAs = 0.567fckbs + 0.87 fykAs’

s = 0.87fyk(As – As’)/ 0.567fckb

= 0.87 x 500 (2410 – 628)/0.567 x 25 x 280


= 195 mm

x = s/0.8 = 244 mm

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
x/d = 244/510 = 0.48 < 0.617

so tension steel yielded.

d’/d = 50/510= 0.098 < 0.171

so compression steel yielded.

Taking moment about tension steel:

Moment of resistance = Fcc(d – s/2) + Fsc(d – d’)


= 0.567fckbs(d-s/2) + 0.87fykAs’(d-d’)
={ 0.567x25x280x195(510-195/2) + 0.87x500x620(510-50)}x10-6
= 443 kNm

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
TUTORIAL

S1 The singly reinforced concrete beam shown below


is made of C30/37 concrete. Using stress block as
recommended in EC2, check whether the section can
resist an ultimate sagging bending moment of 525 kNm.

Given As = 2348 mm2

S2 The singly reinforced concrete beam shown below is


made of C35/45 concrete and is required to resist an
ultimate sagging bending moment of 150 kNm. The
breadth b is 250 mm. Choose a suitable beam depth and
determine the area of reinforcement required.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
ASSIGNMENT 3

A simply supported reinforced concrete beam with an effective


span of 7.0 m is 500 mm deep overall by 250 mm wide. It
supports the following characteristic loads:

Permanent dead loads: 12.0 kN/m plus beam self-weight


Variable imposed loads: 11.0 kN/m.

The concrete is grade C40/50, and 25-mm cover is required to


all reinforcement. Assuming that the shear links are H10 and
the main bars are H25, check whether the beam size is
adequate for the bending ULS and determine suitable tension
reinforcement.

HJ ROSLAN BIN KOLOP


PUSAT PENGAJIAN DIPLOMA PPD
HJ ROSLAN BIN KOLOP
PUSAT PENGAJIAN DIPLOMA PPD

Você também pode gostar