Escolar Documentos
Profissional Documentos
Cultura Documentos
GUIDELINES FOR
SMALL HYDRO DEVELOPMENT
3.4
Electro-Mechanical–
Selection of Control, Automation, Protection and Monitoring System
July 2012
Contact:
Dr Arun Kumar
Alternate Hydro Energy Centre,
Indian Institute of Technology Roorkee,
Roorkee - 247 667, Uttarakhand, India
Phone : Off.(+91 1332) 285821, 285167
Fax : (+91 1332) 273517, 273560
E-mail : aheciitr.ak@gmail.com, akumafah@iitr.ernet.in
DISCLAIMER
The data, information, drawings, charts used in this standard/manual/guideline has been drawn
and also obtained from different sources. Every care has been taken to ensure that the data is
correct, consistent and complete as far as possible.
3.2
The constraints of time and resources available to this nature of assignment, however do not
preclude the possibility of errors, omissions etc. in the data and consequently in the report
preparation.
Use of the contents of this standard/manual/guideline is voluntarily and can be used freely with
the request that a reference may be made as follows:
AHEC-IITR, “3.4 E&M Works – Selection of Control, Automation, Protection and Monitoring
System”, standard/manual/guideline with support from Ministry of New and Renewable Energy,
Roorkee, July 2012.
PREAMBLE
The experts have drawn some text and figures from existing standards, manuals,
publications and reports. Attempts have been made to give suitable reference and credit.
However, the possibility of some omission due to oversight cannot be ruled out. These can be
incorporated in our subsequent editions.
This series of standards / manuals / guidelines are the first edition. We request users to
send their views / comments on the contents and utilization to enable us to review for further
upgradation.
Standards/ Manuals/Guidelines series for Small Hydropower Development
General
1.1 Small hydropower definitions and glossary of terms, list and scope of different
Indian and international standards/guidelines/manuals
1.2 Planning of the projects on existing dams, Barrages, Weirs
Part I
1.2 Planning of the Projects on Canal falls and Lock Structures.
Part II
1.2 Planning of the Run-of-River Projects
Part III
1.3 Project hydrology and installed capacity
1.4 Reports preparation: reconnaissance, pre-feasibility, feasibility, detailed project
report, as built report
1.5 Project cost estimation
1.6 Economic & Financial Analysis and Tariff Determination
1.7 Model Contract for Execution and Supplies of Civil and E&M Works
1.8 Project Management of Small Hydroelectric Projects
1.9 Environment Impact Assessment
1.10 Performance evaluation of Small Hydro Power plants
1.11 Renovation, modernization and uprating
1.12 Site Investigations
Civil works
2.1 Layouts of SHP projects
2.2 Hydraulic design
2.3 Structural design
2.4 Maintenance of civil works (including hydro-mechanical)
2.5 Technical specifications for Hydro Mechanical Works
Drafting Group
Consultation Group
ITEMS PAGE NO
Section-I Introduction 1
1.1 Objectives 1
1.2 General 1
1.3 References and Codes 1
LIST OF ANNEXURES
1.1 SCOPE
This standard/ mannual guideline covers selection of systems for control, automation,
protection and monitoring for small hydropower (SHP) up to 25 MW by developers,
manufacturers, consultants, regulators and others. This includes selection of technology,
extent of automation and monitoring system for different categories of SHP (up to100
kW, up to 5 MW and 5 MW to 25 MW) which are economical, easy to adopt,
sustainable, feasible and essential for safe operation.
1.2 GENERAL
The generating units of a SHP plant may have its shaft vertical, horizontal or inclined
with the type of turbine selected to suit the site’s physical conditions. Small hydro
turbines may be selected as per site conditions, head and discharge available. Small
hydro-generator are of the alternating current type and may be either synchronous or
induction type. Usually SHP units up to 5 MW are expected to require minimum of field
assembly and installation work. While units having capacity from 5 MW to 25 MW may
have slow speed, large diameter and with split generator, stator that may require final
winding assembly in the field.
Mini & micro power stations are generally provided system suiting to these being run
unattended or with few attendants while bigger machines up to 25 MW capacity have
more elaborate arrangement of control monitoring and protection. Provision of parallel
operation with other systems will have more comprehensive control, monitoring &
protection system.
This guideline will serve as a reference document along with available national &
international codes, standards, guide and books. For the purpose of convenience this
standard / manual guidelines has been subdivided as follows:
(i). Control and Automation
(ii). Protection and Relaying
(iii). Metering and Monitoring
(R1). IEEE 1020:1988 - IEEE guide for control of small hydro electric
power plants
(R2). IEEE 1010:2006 - IEEE guide for control of hydro electric power
plants
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 1
(R3). IEEE 60545:1976 - Guide for commissioning operation and
maintenance of Hydraulic Turbines
(R4).IEC 61116:1992 - Electro mechanical guide for small
hydroelectric installations
(R5). IEC: 62270:2004 Hydroelectric power plant automation – Guide
for computer based control
(R6). IEEE 1046:1991 - IEEE application guide for distributed digital
control and monitoring for power plants
(R7). IEEE 1249:1996 - IEEE guide for computer–based control for
power plant automation
(R8). IEEE C 37.101:2006 - IEEE guide for generator ground protection
(R9). IEEE C37.1:2007 IEEE Standard for SCADA and Automation
systems
(R10). IEEE 421.4-2004 - IEEE guide for preparation of excitation system
specification
(R11). ANSI/ IEEE 242:1996 - IEEE recommended practice for protection and
coordination of industrial and commercial
power systems
(R12). ANSI/ IEEE C 372-1987 - IEEE standard electrical power systems device
function numbers
(R14).ANSI/ IEEE C 37.102:1987 - IEEE guide for generator protection
(R15) IEEE C37.102 :2006 - IEEE Guide for AC Generator Protection
(R16). AHEC IITR - Micro-Hydro Quality Standards-2005
For preparing this publication following published and unpublished documents were also
referred and contents used:
(i) AHEC, 1997,Technology recommended under UNDP-GEF Project for Himalayan
SHP project, Ministry of Non Conventional Energy Sources, Delhi
(ii) World Bank. 1991, “India - Mini-hydro development on irrigation dams and canal
drops pre-investment study”, Report ; no. ESM 139 91. Energy Sector Management
Assistance Programme. Vol. 1-3.
(iii) Thapar, R and Perrault DA, 1985 “Economic Computer Controls for Low Head
Hydro”; Waterpower’85, Las Vegas, USA, September 25-27, 1985
(ii) Thapar, R, 1986, “Microprocessor Controller for a small Hydroelectric System”,
IEE, October, 1986
(iii) DIGITEK INC , 1994, “Microcomputer Based Control and Monitoring Systems”;.
11807, North Creek Pkwy, So. Bothell, WA 98011 U.S.A. – Technical Literature.
(iv) Thapar OD, 1985, “Small Hydro Electric Technology for Economic Development”,
Proceedings of XI National Convention of Electrical Engineers on “Environmental
Friendly Electric Power Generation”, Nov. 1995, Roorkee. Allied Publisher pp 44-51
(v) AHEC 2002, Report on study and design and development of Model SHP based self
sustained projects - E & M Equipment standardization and cost reduction Vol. III,
Power finance corporation Ltd.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 2
Abbreviations:
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 3
SECTION-II
CONTROL AND AUTOMATION
2.1 GENERAL
For small hydro installation simplicity of control system is advised, however, the
sophistication of control should be based on the complexity and size of the installation,
without compromising unit dependability and safety of personnel. Simplicity of control is
desirable to keep total cost of installed equipment as well as cost of maintenance, repair
and testing at economical level. Moreover a simpler system is more reliable as compared
to complex one.
Up to 1980s, conventional control system was almost universally used. In this system
control of a hydro plant’s generating units was typically performed from governor panel
or unit control switchboard. If the plant had multiple units, a centralized control board
was provided. The unit control board and centralized control board using relay logic
contained iron vane meters, hardwired control switches, and hundreds of auxiliary relays
to perform the unit start/stop and other control operations. All the necessary sensors and
controls required to operate the unit or units were hardwired to the unit control board and/
or centralized control board, allowing operator to control the entire station from one
location. Stepped sequence control system was mostly followed. Large hydro stations
mostly had operators at two levels i.e. governor gallery and centralized control room.
Offsite supervisory control was by hardwires and not successful. Data acquisition was
manual. Modernization of the conventional control system using digital control
technology is now being undertaken.
Modern systems permit control of the entire plant from a single location. Modern control
rooms utilize the far more cost-effective supervisory control and data acquisition
(SCADA) systems (including programmable logic controllers (PLCs) and distributed
computer control systems with graphic display screens to implement a vast array of
control schemes. The SCADA control scheme also provides flexibility in control,
alarming, sequence of events recording, and remote communication that was not possible
with the hardwired control systems. Data acquisition, storage and retrieval is provided by
the computer.
For complete reference computerized automation, remote control and SCADA reference
be made to IEC 62270: 2004 “Hydroelectric power plant automation – Guide for
computer based control”.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 4
The main control and automation system in a hydroelectric power plant are associated
with following:
(i). Turbine governor for speed control (frequency) optimum running control for real
power generation and dynamic stability.
(ii). Generator excitation control for voltage reactive power control Plant automation to
cover such operation as start, stop, synchronizing and running control of the unit.
(iii). Supervisory control including off site control and centralized control room.
(iv). Data acquisition and retrieval is used to cover such operations as relaying plant
operating status, instantaneous system efficiency, or monthly plant factor, to the
operators and managers.
The control and monitoring equipment for a hydro power plant include control
circuits/logic, control devices, indication, instrumentation, protection and annunciation at
the main control board and at the unit control board for generation, conversion and
transmission operation including grid interconnected operation of hydro stations. These
features are necessary to provide operators with the facilities required for the control and
supervision of the station’s major and auxiliary equipment. In the design of these
features consideration must be given to the size and importance of the station with respect
to other stations in the power system, location of the main control room with respect to
the equipments to be controlled and all other station features which influence the control
system.
Modern control system employed for large power stations (above 5 MW) is distributed
computer control system with adequate redundancy.
Modern control of small hydro up to 5 MW is mostly PLC based integrated governor and
plant control systems.
Micro hydro modern controls are micro processor based non flow control electronic load
controller.
There are many functions to be controlled in a small hydropower system. For example
turbine governor controls the speed of turbine, plant automation covers operations as auto
start, auto synchronization, remote control startup or water level control and data
acquisition and retrieval covers such operation as relaying plant operating status,
instantaneous system efficiency or monthly plant factor.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 5
2.3.1 Turbine Control
This is the speed / load control of turbine in which governor adjusts the flow of water
through turbine to balance the input power with load.
In case small plants in the category of micro hydro (100 kW unit size), load controllers
are used, where excess load is diverted to dummy load to maintain constant speed. With
an isolated system, the governor controls the frequency of the system.
In interconnected system, the governor may be used to regulate unit load and may
contribute to the system frequency control. Figure -1 shows the different types of control
applicable to turbines.
MAIN DISCHARGE
SPEED - NEEDLE
CONTROL - GUIDE VANE
- WICKET GATE
FLOW
TURBINE LEVEL
CONTROL
CONTROL
CONTROL
(GOVERNOR
)
KW BY PASS
CONTROL DEFLECTOR
This is the excitation control of synchronous generator. The excitation is an integral part
of synchronous generator which is used to regulate operation of generator. The main
functions of excitation system of a synchronous generator are:
Plant control deals with the operation of plant. It includes sequential operation like
startup, excitation control, synchronization, loading unit under specified conditions,
normal shutdown, emergency shutdown etc. The mode of control may be manual or
automatic and may be controlled locally or from remote location. Plant control usually
includes monitoring and display of plant conditions. Different plant controls are given in
fig -3.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 6
Typical function of start, stop and sequence logic as specified for 4 x 4 MW project is
given in figure 4 to figure 7.
(INCLUDING CENTRALISED
CONTROL ROOM)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 7
PRE START CHECKS
BUTTERFLY VALVE OPEN
PROTECTIVE DEVICES RESET
WATER LEVEL NORMAL
GENERATOR BREAKER OPEN
WICKET GATES CLOSED
33kV
WICKET GATE LOCK RELEASED
PRESSURE OIL SYSTEMS FUNCTIONAL
GOVERNOR IN AUTOMATIC POSITION EXCIATION SYSTEM
ON VOLTAGE
STOP SEQUENCE RESET REGULATOR GENERATOR
AUXILIARY SYSTEM CHECKS CONTROL BREAKER
L
START SEQUENCE INITIATED VOLTAG
FREQUENCY
IF PRES START CHECK MATCHING
(NORMAL
P.B AN
___
GENERATOR
BREAKER
CLOSE AUXILIARY
UNIT ACCELERATES TO
NEAR SYNCHRONOUS
SPEE
UNI
RUNNING ___
AN
CONTROL
INITIAL EXCITATION
APPLIE
SYNCHRONIZING UNIT GENERATING
INITIATING AS REQUIRED
GENERATOR
VOLTAG P.B
BUILDU
GENERATOR
SPINING
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 8
Controlled action shut down shall be initiated by conditions shown in column -1 of Table -1 and
shall perform actions shown in Column-2 of Table -1. Control action shut down for a typical 5
MW generating unit is shown in Fig. 5.
Emergency shut down shall be initiated by conditions shown in column -1 of Table -2 and shall
perform actions shown in Column-2 of Table -2. Emergency shut down for a typical 5 MW
generating unit is shown in Fig. 6.
Electrical shut down shall be initiated by conditions shown in column -1 of Table -3 and shall
perform actions shown in Column-2 of Table -3. Electrical shut down for a typical 5 MW
generating unit is shown in Fig. 7.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 9
Fig. 5 : Controlled Action Shut Down (Typical for gen. units above 5 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 10
Fig. 6 : Emergency Shut Down (Typical for Gen. Units above 5 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 11
Table 3 : Electrical Shut Down
Governor and control systems for small hydro units especially in developing countries
have to be selected keeping in view the following:
(i) Traditional mechanical flow control governor with mechanical hydraulic devices is
complex demanding maintenance and high first cost. Further performance
requirements of stability and sensitivity i.e. dead band, dead time and dashpot time
especially for interconnected units may not be possible with mechanical governors.
(ii) The manpower as available for operation is unskilled and further adequate
supervision is not feasible.
(iii) Load factors for stand-alone micro hydro are usually low which affects economic
viability.
(iv) Cost of speed control and automation with electronic analog flow control
governors, unit control and plant control is high. These systems require attended
operation and are mostly based on large capacity hydro units. This is making most
of the units very costly and uneconomical to operate. Experience in successful
operation of analog electronic control system in India for SHP is not good.
(v) Electronic digital flow control governors can take up plant control functions.
(vi) Flow control turbine governors are expensive and not recommended for micro
hydro units. Electronic load control (ELC) governing system with water cooled hot
water tanks as ballast loads for unit size up to 100 kW be used. If the thyristor
control ELC is used then the generator be oversized up to 2% on kVA to cope with
the higher circulating current. Accordingly, in case of micro hydrol units up to 100
kW size elimination of flow control governors by digital shunt load governor
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 12
(electronic load controllers) for economically viability and eliminating of
continuous attendance is recommended.
viii) Analog electronic governors and plant controllers are also used for small hydro auto
synchronizing and for remote control and monitoring of system.
(x) Digital generation controllers were evolved to take care of speed control, unit
control and automation, unit protection and generation scheduling and have been
successfully in operation for over ten years.
(xi) PLC based system are reliable and suitable for harsh conditions. These have been in
operation in India and abroad.
(xii) Dedicated PC based systems for complete generation control can be easily adopted
for data acquisition and storage at low cost and can also be adapted to SCADA
system. Customized software is used in these systems which inhibits wide spread
use. Future systems using PC as controller and for SCADA with open architecture
and use of commercially available software is recommended for economy and wide
spread use.
Comparison of various options for for control system, including turbine governing
supervisory control and data acquisition are given in table-4.
As per Location:
a) Local
b) Centralized
c) Offsite
Relationship of local centralized and off site control function is shown in fig-8.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 13
Fig. 7 : Electrical Shut Down (Typical for Synchronizing Generator above 5 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 14
OFF SITE
CONTROL
Communication Link
Fig. 8 : Typical Relationship of local centralized and off site control function
Local area networks (LANs) should be configured to IEEE 802.3 (Ethernet) standard.
Commercially available software should be used as far as possible.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 15
Table 4 : Comparison of various options for control system, including turbine governing supervisory control and data acquisition
S. Turbine Gov. and Unit size Mode Suitability Cost including Gov. Recommendation Remarks
No. Controller Type of control, protection,
kW operati Turbine Unit Data storage SCADA SCADA data Aq.,
on Gov. Unit Prot. and Retrieval Storage and Retrieval
control (see note-1)
Capital O&M
1. Mech. Flow control Gov. 50-100 Iso. At high extra cost Very high High Not recommendation
without
Grid SCADA
100-500 & Iso.
above
Grid
2. Load control governor 50-100 Iso. Suitable At extra cost Low Low Not considered
Grid
Do not available
Digital load
100-500 Iso. See note 3 control
governor may
Grid Not feasible
be developed
for SCADA
3. Analogue, Electronic 50-100 Iso. Suitable At high extra cost Very high cost Not recommended
Gov. & Plant Controller Grid
Above 100 Iso. High Moderate
to high
Grid
4. PLC integrated controller SHP 100 Iso. Suitable Low Moderate Recommended
with SCADA by PC kW to 5
MW Grid
5. PLC digital governor with Above 5 Iso. Suitable High Moderate Recommended for units
plant controller and MW See note 2 above 5 MW
SCADA with redundant Grid
PC
6. Data Logger with ELC 5 to 100 kW Iso. Data not available Low Moderate Recommended
load controller Grid
7. PC based integrated 100 kW to Iso. Suitable – Indigenous system not available Low Medium Recommended with
system for governing; 2500 kW high speed PC suitable
plant control protection for harsh area
and metering
Grid
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 16
2.8 HUMAN-MACHINE INTERFACE (HMI)
The operator’s station of the station controller (SCADA system) should have an elaborate
and friendly man-machine interface. A 45.6 mm (19”) or larger monitor should be
provided for the display.. The screen displays should be suitably designed to provide
information in most appropriate forms such as text, tables, curves, bar charts, dynamic
mimic diagrams, graphic symbols, all in colour. An event printer should be connected to
PC of the SCADA system. Events should be printed out spontaneously as they arrive.
Provision should be made to connect and use another printer simultaneously. Touch
control screen, voice and other advanced modes of HMI are desired and should be
preferred. The entire customization of software for HMI and report generation should be
carried out. A window based operating system should be preferred.
2.9 HARDWARE
(i). Portability and the exchange of I/O cards from one I/O location to another. This
can reduce spare parts requirements.
(ii). Availability of I/O cards to be replaced under power. This avoids the need to
shutdown an entire I/O location to change one card.
(iii). Sequence-of-Events (SOE) time tagging at the I/O locations; accuracy and
resolution.
(iv). Availability of I/O signal types and levels that support the field device signals to
be used.
(v). Support of redundant field devices, capability for redundant I/O from field device
to the database and operator interface.
(vi). I/O diagnostics available at the card, e.g., card failure indicating LEDs, or through
software in the system.
2.10 GROUNDING
Each equipment rack in which automation system components are located should be
separately connected to the powerhouse ground mat by a large gauge wire.
Shielded cables should be used for analog signals between the transducers and the
automation system. Each shield should be tied to the signal common potential at the
transducer end of the cable. If there are terminations or junction boxes between the
transducers and automation system, each shield circuit should be maintained as a separate
continuous circuit through such junction or termination boxes.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 17
2.12 INFORMATION AND CONTROL SIGNALS
Information and control signal for proper control and monitoring will be acquired from
the main and auxiliary/associated equipment and shall be provided as tentatively detailed
along with the equipment as out lined in this paragraph. Deviation will be intimated in the
bid 25% spare capacity for inputs and output shall be provided.
The control system shall receive input signals from main equipment such as the turbine or
the generator, and from various other accessory equipments, such as the governor,
exciter, and automatic synchronizer. Status inputs shall be obtained from control
switches, level and function switches indicative of pressure, position etc, throughout the
plant. The proper combination of these inputs to the control system logic will provide
outputs to the governor, the exciter, and other equipment to start or shutdown the unit.
Any abnormalities in the inputs must prevent the unit’s startup, or if already on-line,
provide an alarm or initiate its shutdown.
(i). Generator
(ii). Generator field excitation equipment
(iii). Generator terminal equipment (Line and Neutral side)
(iv). Unit generator breaker equipment
(v). Turbine
(vi). Governor
(vii). Generator cooling
(viii). Service air(above 5MW)
(ix). Cooling water(above 5MW)
(x). DC power supply
(xi). AC auxiliary power supply
(xii). Water level monitoring
(xiii). Fire protection
Following four types of signals are provided between control board and particular
equipment:
(i). Analog inputs for variable signals from CTs, VTs, RTDs, pressure, flow, level,
vibration etc.
(ii). Digital inputs provides digitalized values of variable quantities from the
equipment
(iii). Digital outputs – command signals from control boards to equipment
(iv). Analog outputs – transmit variable signals from control to equipment e.g.
governor, voltage regulator etc.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 18
2.13 COMMUNICATION LINKS
2.13.1 Communication links with remote offsite control
Following methods are available for implementing control from a remote location:
(i). Hardwired communication circuits (telephone type line, optical cables etc.)
(ii). Leased telephone lines
(iii). Power line carries communication system
(iv). Microwave communication system
Metallic circuit in hardwired communication circuits and leased telephone lines, requires
special protection for equipments and personals against ground potential rise (GPR) due
to electric system fault, since the hydro-generator is source of fault current. GPR is also
caused by lightning transmitted through power lines entering the power plant. As such
suitable mitigation has to be provided.
Power line carrier including insulated ground wire system can be used for
communications purposes. This method couples a high frequency signal on the power
line or insulated ground wire and is decoupled at an offsite point.
Data and control signals will be required to be transmitted. The communication link
between control board and equipment should be reliable. Optical fiber cable, shielded
cable are various options. Communication links required are given in table 5:
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 19
2.14 CONTROL SYSTEMS FOR VARIOUS CATEGORIES OF SHP
2.14.1 Control for micro hydro power plant (Up to 100 kW)
2.14.2 Control for Small Hydro Power Plants (Above 100 kW and up to 5000 kW)
2.14.2.1 Integrated Governor and Plant Control System
Present and recommend modern practice is to have PLC based automatic control system
with manual control as backup. A common PC for Supervisory Control and data
Acquisition system (SCADA) may be provided. Redundant PLC for automation as
backup is not provided.
Microprocessor controller (PLC/PC) is used to provide following unit and plant control
functions.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 20
A dedicated controller for normal operation in isolated/interconnected operation is
required. This controller can perform all the control functions of unit control e.g. starting
sequence control, auxiliary control, emergency and normal shut down and governing.
In manual/maintenance control mode the control system controller can perform the
following control functions.
In addition the control system can monitor all critical items that are require for safe
operation.
Most small hydro powerhouses in the range have the control room at the same level as
the machine hall. The hard wired manual unit control and computer based (PLC)
automatic control system is provided in the control room. Supervisory control and data
acquisition system (SCADA) if required is provided by a common Personnel Computer
for all the units for Supervisory/Remote control functions in the control room.
2.14.2.3 Typical example of Computer (PLC) based control system for SHP (101 kW to
5000 kW) in the Country
The hard wired manual unit control and computer based (PLC) automatic control system
is provided in the control room.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 21
Supervisory control and data acquisition system (SACADA) if required is provided by a
common Personnel Computer for all the units for Supervisory/Remote control functions
in the control room for which one additional panel or desk is provided.
World Bank, 1991 recommendation for control of irrigation based SHP in this
range by a PLC based unit controller for the powerhouse with a common PC for
SCADA and offsite control provision for all units in this range.
PLC integrated unit controller with PC for supervisory control data acquisition
and remote control facilities for canal fall SHPs with provision for remote control
of three nearby canal fall power plants is shown in Fig.-9.
(iii) SHP – 4 x 4 MW
Control system unit control (manual/automatic) is from Turbine Auxiliary
Governor Panel (TAGP) along with Manual and Protection panel in control room
as shown in Figure-13.
2.14.3Control for small hydro power station (above 5000 kW)- (Distributed computer
control)
2.14.3.1 Introduction
Modern control system employed for power stations having capacity above 5 MW is
distributed computer control system with adequate redundancy as generally shown in fig-
14. Provision for hard wired manual control and modern for offsite control is also shown
in figure.
Main controllers that is turbine governor and excitation control are controlled by their
own microprocessor controllers (PLC based). The digital modules used in the controller
should belong to the same family hardware which is also being used in unit control
panels. Software used in the governors generally includes PID/temporary droop control
scheme for regulation; Start up and shutdown logic etc. Similarly excitation system
controls are microprocessor PLC based. Function block programming language to be
used should be same as in unit control panels.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 22
(ii) Local control may be provided by equipment preferably located near the generating
unit. The local unit computer should be part of the equipment.
(iii) Automatic unit start/stop control sequencing is part of computer based automation.
Automation system should include capability to provide diagnostic information so
as to isolate the problem and get the unit on line as fast as possible.
(iv) Auto synchronizing is computer based. There is no objection to provide
synchronizing function as internal to the automation system. Check synchronizing
relay is provided for security.
(v) The computer system should optimize individual unit turbine operation to enhance
unit operation in respect of following:
(a) Efficiency maximization - gate position, flow, unit kW output, unit reactive
power output.
(b) Minimization unit vibration or rough running zone - gate position, unit
vibration.
(c) Minimization of cavitation: Adjust Gate position, flow, and Hydraulic head
as per turbine manufacturers’ cavitation curve.
(d) Black start control - This may include starting the unit in emergency.
(vi) Centralised Control – Individual units, switchyard, station service control, plant
voltage/VAR control, water and power optimization; Fore bay level control.
(vii) Provide Data acquisition capabilities
(viii) Provide Alarm processing and diagnostics
(ix) Provide Report generation
(x) Provide Maintenance and management interface
(xi) Provide Data acquisition and retrieval
(xii) Provide Data access
(xiii) Provide Operator simulation training
(xiv) Provision of operation in stand alone or in an isolated island by frequency relays
The recommended control system is shown in Fig-15. Manual control facility is provided
on PLC panel if in control room or by or special panel as shown in the figure 14 and
Figure 15.
A typical block diagram of computer based control system for a 2 x 10 MVA power
house with offsite control is shown in Fig. 15. A provision for a programming station
with back up for operation is also included as redundant system.
Main controllers that is turbine governor (PLC based) and excitation control are
controlled by their own microprocessor controllers. The digital modules used in the
controller belong to the same family hardware which is also being used in unit control
panels. Software used in the governors generally includes PID/temporary droop control
scheme for regulation; Start up and shutdown logic etc. Similarly excitation system
controls are microprocessor based. Function block programming language to be used
should be same as in unit control panels.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 23
(i). Each of these elements should be capable of being replaced by or communicate
with system elements provided by other vendors.
(ii). Distributed control system is used
(iii). Adequate redundancy is provided
2.14.3.3 Description
Basic manual control of drives is made possible from control boards. The local starter
panels can be used in case of failure of control boards or for test and maintenance
purposes.
The control system should be suitable for manual and automatic start-up, running & shut-
down of the generating units and the station auxiliary systems.
In the system each unit is controlled by a unit control board for automatic start-stop
sequence. In the automatic mode the unit is started and stopped by computer control or by
push buttons which actuates the complete sequence with all interlocks while in the
manual mode only the plant safety requirements is actuated.
The unit control should be responsible for the overall sequence of operation, for example
when the machine is started or shutdown, it takes the process criteria as its input and
execute a sequence program and issues commands to the drive control. It checks for the
presence of all the required criteria before it issues a particular command. Also time
taken for the execution of the command is monitored and an alarm or trip is generated if
command execution takes more than stipulated time.
Control of all auxiliaries and drives pertaining to the unit is carried out. It is possible to
control either by the commands received by the sequence control or commands from
push buttons mounted on the panel. All required logic and interlocks for each drive
should be built up by software logic in the system.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 24
Fig. 9 : Typical System Configuration Canal SHP project (Punjab)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 25
TO 33 kV SUBSTATION TO 33 kV SUBSTATION
(APPROX. 30 km (APPROX. 30 km
GARIYABAND S/S) GARIYABAND S/S) NOMENCLATURE
L.A.
40 -------- LOSS OF EXCITATION RELAY
L.A. 41G -------- EXCITATION BREAKER
45G -------- FIELD SURGE PROTECTION
51 -------- OVER CURRENT RELAY
51V -------- OVER CURRENT VOLTAGE RESTRAINT RELAY
51D -------- DIRECTIONAL OVER CURRENT RELAY
E/F -------- EARTH FAULT RELAY
59 -------- OVER VOLTAGE RELAY
63 -------- BUCHHOLZ RELAY
CT 250/125/1A
CORE-1, 5P10
64F -------- ROTOR EARTH FAULT RELAY
64G -------- STATOR EARTH FAULT RELAY
CT 250/125/1A 64T -------- BACKUP POWER SYSTEM E/F RELAY
CORE-2, M ETERING 87G -------- GENERATOR EARTH FAULT RELAY
CT 250/125/1A ACC.CLASS 1-0 87GT -------- GEN. TRANSFORMER E/F RELAY
CORE-1, 5P10
25 -------- CHECK SYNCHRONISING
CT 250/125/1A 46 -------- NEGATIVE SEQUENCE RELAY
CORE-2, M ETERING
ACC.CLASS 1-0
// / 52-3 52-5 //
/
33k V
/3 / 110V
/3
33kV
/3 / 110V
/3
ISOLATING SWITCH
HV CIRCUIT BREAKER
TRANSFORMER
CURRENT TRANSFORMER
CT 75/1A, 5P10 CT 75/1A, 5P10
5000 k VA, 3.3/33 k V
GENERATOR POTENTIAL TRANSFORMER
TRANSFORM ER-1 87GT 87GT
64T 51
5000 k VA 3.3/33, kV 64T
GENERATOR 51
TRANSFORM ER-1
LIGHTNING ARRESTOR
FUSE
87GT 87GT
EARTH
3.3 KV CUBICLE 3.3 KV CUBICLE
11 KV BREAKER
RECTIFIER RECTIFIER
50/5A TRANSFORM ER 50/5A TRANSFORM ER
11-1 11-2
CT 775/5A
CT 775/5A
AVR AVR
RECTIFIER RECTIFIER
M BRIDGE M BRIDGE
P.T. P.T.
CT 775/5A CT 775/5A
P.T. P.T.
41G
41G
3500 k W 0.8 PF 3.3 k V 3500 kW 0.8 PF 3.3 kV
GENERATOR-1 G1 GENERATOR-2 G2
45G
PS CT 775/5A PS CT 775/5A
PS CT 775/1A CT 775/1A
PS
DISTRIBUTION DISTRIBUTION
TRANSFORM ER TRANSFORM ER
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 26
UNIT-1 UNIT-2
MMI MMI
DIGITAL INPUT DIGITAL OUTPUT SPARE DIGITAL INPUT DIGITAL OUTPUT SPARE
DC POWER SUPPLY
DC POWER SUPPLY
DC POWER SUPPLY
DC POWER SUPPLY
ANALOG MIXED
ANALOG MIXED
DIGITAL INPUT
DIGITAL INPUT
ANALOG INPUT
ANALOG INPUT
ANALOG INPUT
ANALOG INPUT
RK2 RK2
RK1 RK1
CPU
CPU
MODULE
MODULE
10 POINT I/O RACK 10 POINT I/O RACK 10 POINT I/O RACK 10 POINT I/O RACK
MODBUS (COM3)
SIGNAL
CONVERTOR
SCADA
(PC BASED) MULTI FUCNTION MULTI FUCNTION MULTI FUCNTION MULTI FUCNTION TEMPERATURE TEMPERATURE TEMPERATURE TEMPERATURE
TRANSDUCER-1 TRANSDUCER-2 TRANSDUCER-1 TRANSDUCER-2 RECORDERS-1 RECORDERS-2 RECORDERS-1 RECORDERS-2
Fig. 11 : Typical PLC Controller with PC SCADA (Control & Protection System) for a (2 x 3.5 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 27
Fig. 12 : Typical General Arrangement of Control & Protection
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 28
Fig. 13 : Typical Control and Protection of a SHP (4 x 4 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 29
Fig. 14 : Typical Configuration for Computerized Hydro Station (above 5 MW)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 30
Fig. 15 : Typical HMI System for a 2 unit Computerized Station with offsite Control
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 31
(ii) Sequence Control
Master/Stepped sequence control performs the functions of sequential start up, shut down
and / or changeover of the status of the machine. The status of unit is stand still, shut
down, spin and generate. Master control type control is preferred.
In the automatic mode the operator gives the command only once to start the program.
No further intervention is needed for normal execution. Normally the unit is operated in
this mode. At each step, specified process criteria is to be checked and the program
continues if the criteria is satisfied. A time monitoring of each step execution is provided
and if this time is exceeded, the program stops and display the missing criteria. During
the program execution if any protection operates, program execution stops and the
machine brought to shut down.
This mode is used to execute the program in steps. Every time a step is ready to be
executed, the operator initiates the step through a push button command. This mode is
used during commissioning and test phases. All indications of the sequence control and
display of missing criteria is available in this mode. If timing of the step exceeds the set
time, execution is blocked. On completion of each step, an indication for the readiness to
execute the next step is available. The commands to functional group and drive control is
issued during execution of the relevant steps. The drive control is also possible by
operating push button command in this mode of operation.
A common control board for the control & monitoring of common station auxiliaries,
Feeders and Bus coupler is also required to be provided. The panel may consist of the
required number of switches, ILPBS, relays, indicating meters etc. as required.
(i). A dual channel auto synchronizer with voltage and frequency matching units which
issues voltage adjustment and speed adjustment commands and releases breaker
closing command when the frequency, voltage and phase of the generate and grid
are matched within limits.
(ii). Manual synchronizing equipment consisting of synchroscope, voltmeter and
frequency meters for incoming and running bus and a check synchronizing relay is
also provided.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 32
2.14.3.5 Engineering Work Station (Programming & Training Console)
The programming tool included in the Engineering Station is used for accessing &
modifying logic programs of the processor modules, reading the status of binary &
analog signals with their addresses, simulating signals to the processor.
Two numbers battery chargers, common battery bank and direct current distribution
boards (DCDB) are provided for the stabilized power supply requirement of electronic
panels of control boards. Lead acid / Nickel Cadmium batteries of sufficient capacity
should be provided. The battery charger should be provided with its associated float and
boost charger. For small power station where one battery set is selected the charger
should have provision of redundant float charger. For power station where two battery
sets and two chargers have been selected, interchangeability of chargers should be
ensured.
Two no. UPS system having common battery and common AC Distribution Board &
manual by-pass are provided for giving regulated Uninterrupted Power Supply to
SCADA.
The system should be solid state type with silicon controlled rectifiers to convert mains
input to DC for charging the battery. The UPS works on a 1-phase 230 volts supply.
Supervisory control and data acquisition system for control and monitoring of the plant
should be provided using Man Machine Interface (MMI) & (Data Acquisition System)
DAS computers. The system is intended to meet total operating functions of the plant,
which are normally performed by plant operators.
The SCADA system should be complete with all primary sensors, cables, analyzers/
transmitters, monitors, system hardware/ software and peripherals etc. to monitor/ control
the parameters for control, protection, annunciation, event recording for different
equipments including. List of essential sensors and type of sensors are given in the
following table 7:
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 33
Bearing oil level high/low Sensors for each oil reservoir high/low
Cooling air each cooler Temperature detector at inlet and outlet
Rotor temperature Temperature monitoring system for continuous monitoring field
temperature
Fire detection & protection Sensors as required are provided for detection and fire fighting
system
Thrust bearing high pressure Pressure switches
oil system start/stop interlock
Brake position As per IEEE 1010-2006
Electrical measurements and Microprocessor based transducer for
protection interface with CTs & PTs
B.Excitation Type of Sensors
Static excitation system Generally in accordance with IEEE 1010-2006
C.Turbine Type of Sensors
Turbine guide bearing temperature RTD for indication and recorder
in each segment TSD Thermo signaling device for alarm
& trip
Turbine guide bearing oil RTD for indication & alarm
temperature
Oil pressure in accumulator Level switch
Turbine guide bearing level Level switch
High/low
Other sensors as considered As per IEEE 1010-2006
necessary for the unit
D.Governor Type of Sensors
Speed indication
Synchronous speed, Electrically actuated speed relays by comparing the
under speed & over speed speed signal to reference signal
Centrifugal device mounted on the turbine shaft to mechanically
actuate over speed switch
Wicket gate position indication/ As per IEEE 1010-2006
position switches for control &
indication
Governor oil pressure unit switches As per IEEE 1010-2006
for oil level/pressure and sump oil
temperature
Governor power supply failure, As per IEEE 1010-2006
E. Generator Transformer. Transducers as required
F. High Voltage Circuit Breaker Transducers as required
G. Instrument Transformers Transducers as required
H. Auxiliary System Transducers as required
Without SCADA: All Control functions for the generating units are through the
electronic panels of control boards, with the associated interlocks, sequential operation
and protection trip functions being met by the software programs in the processor
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 34
modules. Overall monitoring may be through the indications, meters and annunciation
features provided on the control boards. Station operators may take care of the data
logging.
With SCADA: In this mode, each and every control functions provided on Unit Control
Panel and Line control panel is through the HMI of SCADA system. Further, the joint
control of units for overall control of active, reactive power and voltage is carried out
from HMI of SCADA. Commands from SCADA is dispatched to respective unit control
boards through Ethernet bus. Further, processing of commands is done by the DPUs of
unit control panels through their software logic.
Automatic logging of periodical logs, event logs and alarm summaries may be achieved
in the SCADA system along with overall plant monitoring through data acquisition in the
form of alarms, mimics, trends, bar charts etc. Total plant operation, monitoring, logging
etc. should be possible from SCADA without any need of attendance elsewhere in the
plant.
A separate grounding system should be provided for the plant and static control as
generally shown in figure-16.
2.14.3.10 Testing
Factory Assembly and Test, Field Test should be performed as given in the typical
specifications.
A training programme for the operators and maintenance personnel should be included in
the procurement specifications.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 35
Fig. 16: Typical Computerized Control & Monitoring System - Grounding Scheme
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 36
SECTION-III
PROTECTION AND RELAYING
3.1 GENERAL
The abnormal operating conditions that may arise should be detected automatically and
corrective action taken in a timely fashion to minimize the impact. Relays (utilizing
electrical quantities), temperature sensors, pressure or liquid level sensors, and
mechanical contacts operated by centrifugal force, etc., may be utilized in the detection of
abnormal conditions. These devices in turn operate other electrical and mechanical
devices to isolate the equipment from the system.
Where programmable controllers are provided for unit control, they can also perform
mechanical protection including hydraulic and thermal protection.
Operating problems with the turbine, generator, or associated auxiliary equipment require
an orderly shutdown of the affected unit while the remaining generating units (if more
than one is in the plant) continue to operate. Alarm indicators could be used to advise
operating personnel of the changed operating conditions.
Loss of individual items of auxiliary equipment may or may not be critical to the overall
operation of the small plant, depending upon the extent of redundancy provided in the
auxiliary systems. Many auxiliary equipment problems may necessitate loss of generation
until the abnormal conditions has been determined and corrected by operating or
maintenance staff.
The type and extent of the protection provided will depend upon many considerations,
some of which are:
Overall, though, the design of the protective systems and equipment is intended to detect
abnormal conditions quickly and isolate the affected equipment as rapidly as possible, so
as to minimize the extent of damage and yet retain the maximum amount of equipment in
service.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 37
Small hydroelectric power plants generally contain less complex systems than large
stations, and therefore tend to require less protective equipment. On the other hand, the
very small stations may be unattended and under automatic control, and frequently have
little control and data monitoring at an off-site location. This greater isolation tends to
increase the protection demands of the smaller plants.
An inherent part of the power plant protection is the design of the automatic controls to
recognize and act on abnormal conditions or control failures during startup. Close
coordination of the unit controls and other protection is essential.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 38
4. Bearing problems 4. Fire
5. Motoring
6. Fire
7. Excessive vibration
8. Cooling failure
9. Over speed
Table 11 : Abnormal conditions of Auxiliaries and grid
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 39
with alarm and trip contacts.
5. Water level A measuring system incorporating level sensors and monitoring
equipment, to alarm, trip, or control turbine output on limiting
values of headwater or tail water level, or head
6. Fire Sensors located in areas where fire can occur and connected to a
central fire monitor for alarm. Small generators usually do not
have fire sensors or suppression equipment, since they are not
usually enclosed.
7. Miscellaneous Sensing devices are integral to the protected systems, such as
mechanical system automatic greasing system, wicket gate shear pins, cooling water
system and drainage system.
The protective relays stand watch and in the event of failures short circuits or abnormal
operating conditions help de-energize the unhealthy section of power system and restrain
interference with rest of it and limit damage to equipment and ensure safety of personnel.
The essential features of protective relays are shown in table 13.
S. Feature Purpose
No.
i. Reliability To ensure correct action even after long period of inactivity and
also to offer repeated operation under sever condition
ii. Selectivity To ensure that only the unhealthy part of system is disconnected
iii. Sensitivity Detection of short circuit or abnormal operating condition
iv. Speed To prevent and minimize damage and risk to instability of
rotating plant.
v. Stability The ability to operate only under those conditions that calls for its
operation and to remain either passive or biased against operation
under all other conditions.
Protective relay technology has changed significantly in recent years. Induction disk
relays for each individual protective function were normally used. Individual solid state
static relays for protective function were introduced in the decade 1980 – 1990 and IS:
3231 – 1965 was accordingly revised in 1987.
The old conventional electromagnetic relays were replaced with static relays which are
much faster and maintenance free. These relays are more reliable and sensitive. These
days microprocessor based multifunction relays are available which have different
protections elements and therefore, a separate relay for each protection is not required.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 40
3.3.2.3 Isolation of Digital Control and Protection System
Solid state digital control and protection system is fast replacing hard wired control and
electro-mechanical relaying systems in hydro stations. These systems working on 4 to 5
volts with respect to ground are susceptible to damage/malfunction from induced voltage
from switching surges, rise of ground grid voltage on ground faults and lightning surges
etc.
Isolation of the digital system for protection and control is very important to avoid
damage. A design that provide complete isolation from the high frequency surges is vital
to maximize plants on line availability.
Standards addressing these problems for the control and protection equipment have been
issued by IEC and other standards organization which can be referred
Programmable logic controller (PLC) input/output racks used in hydro plants are suitable
for use in harsh environment of the hydro plants. PLCs input/output racks and solid state
components are designed to withstand the surges. Isolation is by optical coupling I/O
racks and cards so as to provide isolation and withstand surge voltage capability.
There are many standards for surge protection, grounding and acceptable installation
procedures which can be referred.
(i). Control Power: The operating energy for most electromechanical relays is
obtained from the measured currents and/or voltages, but most microprocessor
relays require a source of control power.
(ii). Multi Protective Functions: Digital relays provide multiple protective functions
in one relay. In contrast, older relay system required an individual relay for each
protective function. Consequently, multifunction digital relays reduce panel space
and wiring costs while providing equivalent protection. Multifunction feature can
result in a loss of redundancy. For instance, the failure of a single-phase over
current relay is backed up by the remaining phase and neutral relays. In a
microprocessor scheme, the phase and neutral elements are frequently combined in
one package and a single failure can disable the protection.
(iii). Self Monitoring: microprocessor-based digital relays have “watchdog timers” to
monitor their own operating status on a continual basis. Any potential malfunction
will be indentified and communicated to the control system. The self monitoring
feature eliminates the possibility of a non functioning relay in the plant protective
relay system. In previous protective relay systems, a non functional induction disk
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 41
or solid state relay would not normally be discovered until the next maintenance
test of the protective relay system.
The self-monitoring capability of these relays is only effective if the alarm output
can be communicated to a manned location such as a control room. Also, the
remote communication ability assumes there is a communication channel available
to the relay.
(iv). Communication: The digital relay uses a digital communication scheme which
allows the relay to communicate directly with the plant control system. The digital
relays are provided with serial data ports based on established protocols, which
should be compatible with the DCS (Distributed Computer System)/PLC
communication protocol used at the plant.
(a) Microprocessor transformer package that has both differential and over current
relaying provide less redundancy than a scheme comprising separate relays. The
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 42
self-diagnostics ability of the microprocessor relay, and its ability to communicate
failure alarms, mitigates some of the loss of redundancy. It may also be
economical to use multiple microprocessor relay.
(b) Microprocessor relays require more engineering in the application and setting of
the relay though less work in the panel design and wiring. The increased relay
setting flexibility is accompanied by an increase in setting complexity that requires
proper care to avoid setting errors.
(c) Some relays have experienced numerous software upgrades in a short period of
time.
(d) Microprocessor relays have relatively shorter product life cycles because of the
rapid advance in technology. As a result, a specific microprocessor relay model
may only be available for a relatively short period of time. As a failure may require
replacement rather than repair, it may not be possible to use an exact replacement,
which may require more engineering and installation work. Although less frequent
testing may be required, when it is, it requires a higher level of training for the
technician and more test equipment than is normally used with electromechanical
relays in order to obtain the full benefit of all the features of the microprocessor
relay.
Due to these reasons back up protection with conventional relays is provided with
microprocessor relays in hydroelectric plants. Various protection elements of a
Microprocessor based relay are shown in table 14.
Symbol Description
21 Under Impedance
24 Over Fluxing
26 Field Winding Temp
27 Under Voltage
27NT 100% Stator E/F
32 Reverse Power
38 Bearing Temp
40 Loss of Field
46 Negative Phase Sequence
49 Stator Winding Temp
50BF Breaker Failure
50P Instantaneous Phase Over Current
50N Instantaneous Neutral Over Current
50/27 Unintentional Energisation at Stand Still
51P Time Delayed Phase Over Current
51N Time Delayed Neutral Over Current
51N Voltage Controlled Over Current
59 Over Voltage
59N Residual Over Voltage
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 43
64R Restricted E/F
78 Pole Slipping Protection
81 Over/ Under Frequency
87G Generator Differential
CTS Current Transformer Supervision
VTS Voltage Transformer Supervision
(i). The application of relays must be coordinated with the partitioning of the electrical
system by circuit breakers, so that least amount of equipment is removed from
operation following a fault, preserving the integrity of the balance of the plant’s
electrical system.
(ii). Generally, SHP Owners protection engineer will coordinate with the grid owners
protection engineer to recommend the functional requirements of the overlapping
zones of protection for the main transformers and high voltage bus and lines. The
grid owners protection engineer will determine the protection required for the
station service transformers, main unit generators, main transformers, and
powerhouse bus.
(iii). Electromechanical protective relays, individual solid state protective relays, multi-
function protective relays, or some combination of these may be used for protection
system requirements.
(iv). Individual solid state protective relays and/or multifunction protective relays offer a
single solution for many applications plus continuous self diagnostics to alarm
when unable to function as required. Multi-function protective relays may be cost-
competitive for generator and line protection where many individual relays would
be required.
(v). When multi-function relays are selected, limited additional backup relays should be
considered based upon safety, cost of equipment lost or damaged, repairs and the
energy lost during the outage or repairs.
(vi). When redundancy is required, a backup protective relay with a different design and
algorithm should be provided for reliability and security.
(vii). Generators, main transformers, and the high voltage bus bar are normally protected
with independent differential relays (above 1000 kW unit size).
The designer must balance the expense of applying a particular relay against the
consequences of losing a generator. The total loss of generator may not be catastrophic if
it represents a small percentage of the investment in an installation. However, the impact
on service reliability and upset to loads supplied must be considered. Damage to
equipment and loss of product in continuous processes can be dominating concern rather
than generating unit. Accordingly there is no standard solution based on MW-rating.
However, it is rather expected that a 100 kW, 415 V hydro machines will have less
protection as compared to 25 MW base load hydro electric machine.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 44
With increasing complications in power system, utility regulation, stress on cost
reduction and trends towards automation, generating unit protection has become a high
focus area. State of the art, micro processor based protection schemes offer a range of
economical, efficient and reliable solution to address the basic protection and control
requirements depending upon the size and specific requirement of the plant.
Applying brakes at a particular speed (30% of full speed) is done to reduce time to
achieve stand still position of machine.
It is recommended two independent devices must be provided for over speed shut down
on larger machines. One for alarm mostly at 110% and other for tripping at 140%.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 45
S. Element Alarm & annunciation Trip
No.
c. Earth fault with current limits (stators Alarm and annunciation Immediate
& rotor) tripping
d. Maximum and minimum voltage Alarm and annunciation Immediate
tripping
e. Power reversal Alarm and annunciation Immediate
tripping
f. Over/ under frequency Alarm and annunciation Immediate
tripping
g. Oil level in bearing sumps Alarm and annunciation Immediate
tripping
h. Pad & oil temperature of bearings First alarm and Then tripping
annunciation
i. Cooling air temperature First alarm and Then tripping
annunciation
In view of the economy and plant requirements generator protection for small
hydropower stations is categorized a follows:
Transient over-voltages and lightning surges are controlled by lightning arrestors. Surge
capacitors are provided to restrict rate of rise of surge voltages and their magnitudes.
Every generator is provided with a set of lightning arrestors / surge diverter of
appropriate rating and generated voltage.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 46
Table 17 : Monitoring and protection scheme
Note: Use of DC source for control, monitoring and protection in MHP is costlier option as such
AC operated protection system is adopted (e.g. AC with shunt trip coil of generator breaker)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 47
It is recommended that two independent over speed shut-down devices be used on larger
units which might not be designed for continuous runaway.
3.5.4.2 Generator
It is advisable to consider differential protection when the size of the generator and/or its
environment justifies it.
The instruments and devices generally recommended for monitoring and protection are as
follows: voltmeter, ammeter, wattmeter, energy meter, power factor meter, tachometer,
hours of operation counter, synchronizer, water-level and/or pressure indicator, turbine
wicket gate position indicator, emergency stop device, short-circuit current protection,
over current protection, reverse power relay, frequency monitor, voltage monitor, bearing
monitor.
Typical single line diagram for Asynchronous and synchronous generators are attached as
figure -17 and figure-18 respectively based on recommendations by IEC: 61116 for SHP
up to 5 MW units.
Typical single line diagram is at figure-19 and unit metering and relaying is shown in
figure-20.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 48
Fig. 17 : Typical single line diagram for asynchronous generators
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 49
Fig. 18 : Typical single line diagram for synchronous generators
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 50
OUTGOING LINES NOMENCLATURE
OUTGOING LINES
40 -------- LOSS OF EXCITATION RELAY
41G -------- EXCITATION BREAKER
L.A. 45G -------- FIELD SURGE PROTECTION
L.A.
51 -------- OVER CURRENT RELAY
51V -------- OVER CURRENT VOLTAGE RESTRAINT RELAY
51D -------- DIRECTIONAL OVER CURRENT RELAY
E/F -------- EARTH FAULT RELAY
//
/ P.T.
/// P.T.
59 -------- OVER VOLTAGE RELAY
63 -------- BUCHHOLZ RELAY
64F -------- ROTOR EARTH FAULT RELAY
64G -------- STATOR EARTH FAULT RELAY
PS CLASS FOR BUS
64T -------- BACKUP POWER SYSTEM E/F RELAY
PS CLASS FOR BUS
DIFFERENTIAL DIFFERENTIAL 87G -------- GENERATOR EARTH FAULT RELAY
87GT -------- GEN. TRANSFORMER E/F RELAY
CT CT 25 -------- CHECK SYNCHRONISING
CORE-1, 5P10 CORE-1, 5P10 46 -------- NEGATIVE SEQUENCE RELAY
CT CT
CORE-2, M ETERING CORE-2, M ETERING
ACC.CLASS 1-0 ACC.CLASS 1-0
52-3 52-5
LEGEND
33/66/132 kV BUS 52-6
ISOLATING SWITCH
HV CIRCUIT BREAKER
LINK
CT CT
TRANSFORMER
41G
EXCITATION BREAKER WITH
52-1
DISCHARGE RESISTOR
52-2
CURRENT TRANSFORMER
51 EARTH
87GT 87GT
11 KV BREAKER
DG SET
11 KV CIRCUIT 11 KV CIRCUIT
BREAKER 11-1 BREAKER 11-2
CT TO P.T.
CT TO P.T.
P.T. P.T.
41G
41G
GENERATOR-
G1 GENERATOR-2 G2
45G
PS CT PS CT
5P10 CT
5P10 CT
PS CT CT
PS
DISTRIBUTION DISTRIBUTION
TRANSFORM ER TRANSFORM ER
Fig. 19 : Typical Single Line Diagram for generating Units above 5MW
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 51
33 K.V. BUS NOMENCLATURE
GENERATORS
CT
NOTES 12 CENTRIFUGAL SPEED SWITCH
12G ELECTRICAL OVERSPEEDC RELAY
25 CHECK SYNCHRONISING RELAY
1.THE SCHEM E M AY BE M ODIFIED TO SUIT ACTUAL 26AU/AI AIR COOLER (OUTLET/INLET)
BREAKER EQUIPM ENT ORDERED AIR TEMPERATURE
52-1
2.COM M ON TRIPPING RELAYS FOR SIM ILAR 26G TEMPERATURE DETECTORS FOR
FUNCTIONS WILL BE PROVIDED WITH LOCK FIRE PROTECTION SYSTEM
OUT FACILITIES, SIGNAL TYPE CURRENT 26GS STATOR WINDING TEMPERATURE
RELAYS FOR DISCRIM INATION OF FAULTS ARE
PROPOSED TO BE PROVIDED IN THE 32 REVERSE POWER RELAY
87T INDIVIDUAL CIRCUITS OF COM M ON TRIPPING 33AB AIR BRAKE POSITION INDICATION
RELAYS . 33CW/80CW COOLING WATER VALVE POSITION/FLOW
64T
3.TRIPPING BLOCK DIAGRAM DOES NOT INCLUDE 38 BEARING TEMPERATURE DEVICE
63T FIRST STAGE ALARM S 38-2
5P10
TEM PERATURE
4.DETAILS OF R.T.D. (RESISTANCE 38GT GUIDE BEARING TEMPERATURE
CT
DETECTORS) ARE AS UNDER : 38QB BEARING OIL TEMPERATURE
(A) GENERATOR STATOR WINDINGS - 12 NO. 38THT THRUST BEARING TEMPERATURE
38T (B) GENERATOR THRUST BEARING - 2 NO.
87 GT (C) TURBINE GUIDE BEARING - 2 NO. 40 FIELD FAILURE RELAY
GEN.TRANSFORM ER
50/51 5. UNIT-2 IS SAM E AS UNIT-1 45F FIELD SURGE PROTECTION
CT 46 NEGATIVE PHASE SEQUENCE RELAY
PS 47 PHASE SEQUENCE CHECK RELAY
LINK (FOR SYNCHRONIZING)
48 INCOMPLETE SEQUENCE RELAY
C.T. 5P10 50/51 T TARNSFORMER OVERCURRENT RELAY
51V INSTANTANEOUS OVERCURRENT
250 k VA
WITH VOLTAGE RESTRAINT RELAY
11/.415 kV
TO 86 EB 11 KV 60 VOLTAGE BALANCE RELAY
11-1 GENERATOR 63 GOVERNOR LOW OIL PRESSURE SWITCH
BREAKER 51/64 63FG
87 GT FIRE EXTIGUISHING SYSTEM OPERATION
51 EX C.T. 63QTH THRUST BEARING HIGH PRESSURE OIL
SYSTEM START INTERLOCK/FAILURE ALARM
RECTIFIER 63 T MAIN TANK OVER PRESURE SWITCH
TRANSFORM ER 63 TX AUXILIARY RELAY
64G GROUND VOLTAGE RELAY - STATOR
25 64F ROTOR EARTH FAULT RELAY
47
TO P.T. 65SN SOLENOID SPEED NO LOAD
65SL SOLENOID SHUT DOWN
59 71QBH/L BEARING OIL LEVEL(HIGH/LOW)
THYRISTOR STATIC 86 EA LOCKOUT RELAY ELECT. GROUP "A"
BRIGES EXCITATION LOCKOUT RELAY ELECT. GROUP "B"
86 EB
SYNCH.
VOLTAGE
REGULATOR 86 MA LOCKOUT RELAY MECH. GROUP "A"
AND CONTROL 86 MB LOCKOUT RELAY MECH. GROUP "B"
87G GENERATOR DIFFERENTIAL RELAY
S.S.
FROM EXCITOR 2 87T TRANSFORMER DIFFERENTIAL RELAY
F F SYNCHRONISING
TO 86 EB EXCITERS
. VAR.COM P
PT PT L
SOCKET
L
27
V
31
41G
51 EX
EXCITATION RELAY
GENERATOR FIELD BREAKER
INSTANTANEOUS TIM E OVER
CURRENT RELAY
FROM BATTERY
..
31
EQUIPMENT
.. S.S.
KWH
F F
PAR COM P PARALLEL COM PENSATION
METERING
.. S.S.
38THT
THERM OSTAT
R.T.D.
38QB
60
BLOCKS 50/51V
& 40 ON LOSS
OF RELAY
FM
KVAR
SYN
LINK 86 EA
TRIP 52-1 & 41 G
RELEASE CO2,
TURBINE SHUT
2
1
RESISTOR
RATED 15 SEC.
Fig. 20 : Typical Unit Metering Single Line Diagram for generating Units above 5MW
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 52
3.5.5.1 Various protections of Generator
Following additional back up electromagnetic/ static relays from different set of CTs and
PTs be also provided.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 53
Fig. 21 : Typical Functional Overview - Numerical Generator Protection Relay
Cat.-I may be used for small generators not requiring differential protection; Cat.-II can
be used for SHP generators up to 25,000 kW.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 54
Device Functions overview Cat-I Cat-II
No. Settings
21 Under impedance 2 2
59N Neutral voltage displacement/residual overvoltage, inter 2M/2D 2M/2D
turn – measured (M), derived (D)
27/59 Under/over voltage 2/2 2/2
81U/81O Under/over frequency 2/4 2/4
81AB Turbine abnormal frequency 6 6
32R/32L/ Reverse/Low Forward/Over power 2 2
32O
40 Loss of field 2 2
46T Negative phase sequence thermal 2 2
46OC Directional/Non directional, negative phase sequence over 4 4
current
47 Negative phase overvoltage 1 1
49 Stator thermal overload 2 2
24 Over fluxing 5 5
78 Pole slipping - 1
27TN/59 100% stator earth fault - 1
TN 3rd harmonic neutral under/over voltage)
50/27 Unintentional energisation at standstill - 1
50BF CB fail 2 2
Current transformer supervision 1 1
Voltage transformer supervision 1 1
RTDS x 10 PT 100 Option Option
Generator transformers up to 132 kV class may be used. The protection in SHP for 25
MW protection for transformers up to 132 kV class as per Central Board of Irrigation and
Power Manual on transformers is as follows:
i) Percentage biased differential relay (without harmonic restraint).
ii) High speed differential relay with harmonic restraint feature ) for power
transformer of capacities above 100 MVA
iii) Back up over current relay on primary side
iv) Back up over current and earth fault relay on the secondary side
v) Oil temperature indicator with alarm and trip contact.
vi) Buchholz relay with alarm and trip contact
vii) Winding temperature indicator with alarm and trip contact. (For transformer
having capacity up to 10 MVA)
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 55
viii) Winding temperature indicator with three contacts one each for alarm, trip and
control of fans (for transformer having capacities above 10 MVA)
ix) Magnetic oil gauge with low level alarm contacts
x) Lightning arrestors on both primary and secondary sides when the transformer is
located outdoors and is connected to overhead lines
xi) Oil surge protection for on load tap changer diverter tank with trip contact
xii) Pressure release device with trip contact for transformer rated 100 MVA and
above
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 56
Fig. 23 : Typical Generator Control Panel
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 57
vi) Oil temperature indicator with alarm one electrical contact for alarm or trip
contact.
vii) Buchholz relay with alarm and trip contact
viii) Winding temperature indicator with three electrical contacts for (a) alarm (b) trip
& (c) Fan control for transformers above 10 MVA
ix) Lightning arrestors on both primary and secondary sides when the transformer is
located outdoors and is connected to overhead lines
x) Oil surge protection for on load tap changers (OLTC) (if provided) diverter tank
with trip contact
xi) Pressure release device with trip contact for transformer rated 100 MVA and
above
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 58
Fig. 24 : Typical Functional Overview – Transformer Differential Protection
Whenever generators are running parallel to grid, a synchronizing & grid islanding
scheme will be required. This scheme will help in synchronizing the generator to the bus
and opening the incomer breaker of the plant whenever there is a severe grid disturbance,
thus protecting the generator from ill effects of disturbed grid.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 59
Fig. 25 : Schematic Drawing – 6 MVA, 11/33 kV Gen. Trans. Protection
Single Line Diagram
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 60
Generator may not be able to operate below a certain power-factor. At low power-factor,
reverse reactive power flow may damage the generator.
66kV FEEDER-1
NOMENCLATURE
25 CHECK SYNCHRONIZING RELAY
62 27 UNDER VOLTAGE RELAY
62
PLCC 40 LOSS OF EXCITATION RELAY
50Z LOCAL BREAKER BACKUP PROTECTION
67 DIRECTIONAL OVER CURRENT
RELAY
27 LMU
F 62 TIMING RELAY
81L 81H CVT
81L/H FREQUENCY RELAY (LOW, HIGH)
WAVE TRAP 185 PHASE COMPARISON RELAY
25
67N DIRECTIONAL EARTH FAULT RELAY
TZ Vs FREQUENCY METER
FM
185 PF POWER FACTOR METER
KV V TRIPS 52-3
TZ TRANSDUCER
SUPV.
67N 67 LEGEND
LIGHTNING ARRESTOR
KWH KW KVAR 3
A 50Z 5 P 10
EARTH
5 P 10
ISOLATOR
V Vs CURRENT 11 KV CIRCUIT
TRANSFORMER BREAKER
200/1
CLASS 1 66 KV CIRCUIT
BREAKER
TO UNIT
SYNCHRONISING FUSE
PS
A AMMETER
P.T. PS
/ 52-3
V VOLTMETER
RECORDING
INSTRUMENT
66KV 110V
/ / //
11O V. CURRENT
3 3 TRANSFORMER
POTENTIAL
TRANSFORMER
Primary Protection: Pilot aided (carrier communication) High speed 3 step directional
distance protection for phase to phase and phase to earth and three phase faults (digital)
or phase comparison type carrier relaying for short important lines.
Secondary Protection: Directional over current and earth fault relays (static).
A typical example is shown in figure-26 for 66 kV line interconnecting grid by short lines.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 61
Fig. 27 : Schematic Drawing for 33 kV Line Protection for 4 x4 MW Project
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 62
3.8 RECOMMENDATIONS FOR PROTECTION AND RELAYING
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 63
SECTION-IV
METERING AND MONITORING
Monitoring of operating parameters of the generating unit and their auxiliaries is very
important for the life and optimum utilization of available discharge for generation. The
efficient running of unit requires regular monitoring. The primary input data and
generation output data are monitored periodically.
The details of data required for monitoring performance of a generating station are as
shown in table 23 below:
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 64
v Power factor (PF)
vi Frequency (Hz)
vii Excitation voltage (Volts)
viii. Excitation current (Amp)
3 Transformer
i. Winding temperature i. Tap position
ii. Oil temperature ii. HV/LV current
iii. Oil level iii. Primary/ secondary
iv. Cooling water temperature voltage
and pressures
4 Grid system &
transmission line
i. Grid voltage
ii. Grid frequency
iii. Power export/import (kW)
Current (Amp)
iv. Kilowatt hour (kWh)
v. export / import
5 Station auxiliaries
i. Voltage and current on LT
AC system
ii. Kilowatt hour (kWh)
iii. Diesel generator running
hour, kWh & other
parameters
iv. Drainage & dewatering
system
a. Running hours of
pumps
b. Water level in sump
v. Fire extinguisher –
periodical testing
vi Battery set- Regular
monitoring as per
manufacturers
recommendations
vii. Battery chargers &
distribution boards –
voltage current etc.
viii. OPU system
a. Running hours of
pumps
b.Level in pressure
accumulators
c. Pressure of oil
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 65
4.2 REQUIREMENTS OF MONITORING SYSTEM
4.2.1 Instrument Transformers & Sensors
Current and voltage transformers of rated voltage and appropriate ratio, class of accuracy
are selected as per the requirement of the system.
(ii). Sensors
The sensors for temperatures, pressures, levels and speed are installed at the proper
location.
Analogue type of meters, separate for each parameter with selector switches etc were
being used earlier installed on control panels. Now a days digital meters are being used
for such parameters. Digital multifunction meters are now in use, only one meter
provides several parameters on selection, as well as provides routine display.
Digital temperature scanners indicating the temperatures of stator winding, bearing pads,
oil coolers etc. are provided and installed on the generator control panels. These scanners
get the signals from the sensor installed at specific locations preferably through screened
cables.
Indicating lamps of suitable colours as per code and practices should be provided on
control panels for indication status of machine and various auxiliaries, pumps, electrical
equipment like breaker, isolator, AC/DC supply system etc. Lists of such indication and
relays are enclosed as Annexure-1 and Annexure-2.
The protection system relays and auxiliary relays also provide signals to alarm and
annunciation system. A set of annunciation windows are provided on control panels for
each fault clearing relay with accept test and reset facility through push buttons. Alarm
and trip annunciation indicate the fault and advise operating personnel of the changed
operating conditions.
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 66
4.3 RECOMMENDATIONS FOR METERING AND MONITORING OF SHP
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 67
ANNEXURE-1
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 68
ANNEXURE-2
Symbol Description
21 Under Impedance
24 Over Fluxing
26 Field Winding Temp
27 Under Voltage
27NT 100% Stator E/F
32 Reverse Power
38 Bearing Temp
40 Loss of Field
46 Negative Phase Sequence
49 Stator Winding Temp
50BF Breaker Failure
50P Instantaneous Phase Over Current
50N Instantaneous Neutral Over Current
50/27 Unintentional Energisation at Stand Still
51P Time Delayed Phase Over Current
51N Time Delayed Neutral Over Current
51N Voltage Controlled Over Current
59 Over Voltage
59N Residual Over Voltage
64R Restricted E/F
78 Pole Slipping Protection
81 Over/ Under Frequency
87G Generator Differential
CTS Current Transformer Supervision
VTS Voltage Transformer Supervision
AHEC-IITR/MNRE/SHP Standards/E&M Works- Guidelines for Selection of Control, Automation, Protection and Monitoring System 69