DIN 000 FUSES

6,9 gRB-URB SEMICONDUCTOR protection Fuses


GERMAN STANDARD
500 - 690 v ac
gRB-URB FROM 20 TO 400A
Size: 000
Features/Benefits
➤ Extremely high Interrupting rating Fuses:
Protection of power Semiconductors according
to269.1 and 4
➤ 500-690V Voltage Rating [Rating 20 to 400A]
➤ gR Class [gRB Ratings 20 to 125A] according to
VDE 636-23
-Full range protection
-Improved safety and protection
-Allows selective coordination
➤ aR Class [Current Rating 100A] According to VDE
636-23 and IEC 269.4
➤ 3 Models complying with DIN 43653-00C are:
-With or without blown fuse indication
-With trip indicator
➤ Model complying with DIN 43620 (00C) C US
-Standard with or without blown fuse indication
-With trip indicator

APPLICATIONS DATA
Voltage Current MELTING Total clearing Watt losses
rating Class rating I2t @ Tested Estimated
I2t @ 1 ms interrupting rating
UN( V ) IN( A ) 660 VAC 0.8 IN IN interrupting rating
(A2s) (A2s)

20 12 80 3.8 7
25 20 150 5.0 9
32 39 270 5.5 10
690 40 70 460 6.6 12 200 k A
gRB 50 102 730 7.7 14 300 k A
63 210 1500 8.8 16 @ 660 V
@ 660 V
80 475 2900 9.9 18
100 970 6000 11 20
125 1900 11800 11.6 21
80 390 2500 11.6 21
100 690 4200 12.7 23
125 1300 8900 14.3 26 200 k A
690 160 2700 16000 17.0 31
URB 300 k A
200 5250 31500 19.8 36 @ 660 V
@ 660 V
250 9900 52000 24.8 45
660 315 15500 82000 31.9 58
500 350 22400 110000 31.9 58 120 k A
URB
400 33200 160000 36.3 66 @ 500 V

Minimum operating voltage for blown fuse indicator: 20 V

D 50
DIN 000 FUSES

6,9 gRB-URB SEMICONDUCTOR protection Fuses

German Standard blade-type DIN 43620** I/IN


SIZE Catalog No.** REF #
16 6,9 GRB 000 PV 016 Y210609 1
20 6,9 GRB 000 PV 020 Z210610 1
25 6,9 GRB 000 PV 025 A210611 1
32 6,9 GRB 000 PV 032 B210612 1
40 6,9 GRB 000 PV 040 C210613 1
50 6,9 GRB 000 PV 050 D210614 1
63 6,9 GRB 000 PV 063 E210615 1
80 6,9 GRB 000 PV 080 F210616 1
100 6,9 GRB 000 PV 100 G210617 1
125 6,9 GRB 000 PV 125 H210618 1
80
100
125
6,9 URD
6,9 URD
6,9 URD
000
000
000
PV
PV
PV
0080
0100
0125
Q320059
V320063
X320065
1
1
0,95
D
160 6,9 URD 000 PV 0160 B320069 0,85
200 6,9 URD 000 PV 0200 D320071 0,85
250 6,9 URD 000 PV 0250 H320075 0,8
315 6,9 URD 000 PV 0315 M320079 0,7
Weight: 150 g 350 5 URB 000 PV 350 R210626 0,7
Packaging: 3 pieces 400 5 URB 000 PV 400 S210627 0,65
Microswitches
** These Fuses are not UL recognized
MS 4L 2-5 B6 + PRES Ref. F210156
MS 4L 2-5 B2 + PRES Ref. G210157
* Fuse Base: 41002-G

C US
German Standard without blown fuse indicator SIZE Catalog No. REF # I/IN*
20 6,9 GRB 000 D08 / 020 D330030 1
25 6,9 GRB 000 D08 / 025 E330031 1
32 6,9 GRB 000 D08 / 032 F330032 1
40 6,9 GRB 000 D08 / 040 G330033 1
50 6,9 GRB 000 D08 / 050 H330034 1
63 6,9 GRB 000 D08 / 063 J330035 1
80 6,9 GRB 000 D08 / 080 A330073 1
100 6,9 GRB 000 D08 / 100 S330112 1
125 6,9 GRB 000 D08 / 125 T330113 0,9
80 6,9 URB 000 D08 / 080 K330036 1
100 6,9 URB 000 D08 / 100 L330037 1
125 6,9 URB 000 D08 / 120 M330038 0,9
160 6,9 URB 000 D08 / 160 N330039 0,85
200 6,9 URB 000 D08 / 200 P330040 0,85
250 6,9 URB 000 D08 / 250 Q330041 0,8
315 6,9 URB 000 D08 / 315 R330042 0,7
Weight: 110 g 350 5 URB 000 D08 / 350 V330114 0,7
Packaging: 6 pieces 400 5 URB 000 D08 / 400 D330191 0,65
* Fuse Base: SI 000 DIN 80
Ref. Number: C 220710

D 51
DIN 000 FUSES

6,9 gRB-URB SEMICONDUCTOR protection Fuses

C US
German Standard with blown fuse indication I/N FUSE BASE*
Current Rating Catalog No. REF #
20 6,9 gRB 000 DO8V/020 P330017 1
25 6,9 gRB 000 DO8V/025 Q330018 1
32 6,9 gRB 000 DO8V/032 R330019 1
40 6,9 gRB 000 DO8V/040 S330020 1
48 50 6,9 gRB 000 DO8V/050 T330021 1
63 6,9 gRB 000 DO8V/063 V330022 1
80 6,9 gRB 000 DO8V/080 G330102 1
38.5 100 6,9 gRB 000 DO8V/100 Q330110 1
8. 125 6,9 gRB 000 DO8V/125 R330111 0,9
5
80 6,9 URB 000 DO8V/080 W330023 1
100 6,9 URB 000 DO8V/100 X330024 1
8.5 125 6,9 URB 000 DO8V/125 Y330025 0,95
5 160 6,9 URB 000 DO8V/160 Z330026 0,85
77. 00
1 200 6,9 URB 000 DO8V/200 A330027 0,85
20 250 6,9 URB 000 DO8V/250 B330028 0,8
315 6,9 URB 000 DO8V/315 C330029 0,7
350 5 URB 000 DO8V/350 W330115 0,7
400 5 URB 000 DO8V/400 E330192 0,65
* Fuse Base: SI 000 DIN 80
Ref. Number: C 220710

C US
German Standard with separate blown fuse Current Rating Catalog No. REF # I/N FUSE BASE*
trip-indicator
20 6,9 gRB 000 DO8L/020 J330173 1
25 6,9 gRB 000 DO8L/025 K330174 1
32 6,9 gRB 000 DO8L/032 L330175 1
48 40 6,9 gRB 000 DO8L/040 M330176 1
50 6,9 gRB 000 DO8L/050 N330177 1
63 6,9 gRB 000 DO8L/063 P330178 1
80 6,9 gRB 000 DO8L/080 Q330179 1
55.5 100 6,9 gRB 000 DO8L/100 R330180 1
125 6,9 gRB 000 DO8L/125 S330181 0,9
80 6,9 URB 000 DO8L/080 T330182 1
8. 100 6,9 URB 000 DO8L/100 V330183 1
5
125 6,9 URB 000 DO8L/125 W330184 0,9
160 6,9 URB 000 DO8L/160 X330185 0,85
8.5 200 6,9 URB 000 DO8L/200 Y330186 0,85
5
77. 250 6,9 URB 000 DO8L/250 Z330187 0,8
1 0
0 315 6,9 URB 000 DO8L/315 A330188 0,7
20 350 5 URB 000 DO8L/350 B330189 0,7
400 5 URB 000 DO8L/400 F330193 0,65
Microswitch
MC 4L 2-5 B6 + PRES Ref. Number: F210156
MC 4L 2-5 B2 + PRES Ref. Number: G210157
*Fuse Base: SI 000 DIN 80 Ref. Number: C220710

D 52
DIN 000 FUSES

6,9 gRB-URB/5URB SEMICONDUCTOR protection Fuses


Total Clearing I t 2

1,5 ms (0,3 ms)


10 ms (2,5 ms)
I2t (A2s)

8 ms (1,8 ms)
7 ms (1,5 ms)
6 ms (1,3 ms)

3 ms (0,6 ms)

2 ms (0,4 ms)
10 ms (5 ms)

4ms (0,8 ms)


5 ms (1 ms)
10 6

10 5

10 4
D
10 3
10 2 10 3 10 4 10 5
Ip (A)

Above: Horizontal curves show, for each rated current, values of total
clearing I2t as a function of prospective current Ip. @ UN with cosj =
0.15. Horizontal lines indicate total clearing duration It, with associated
pre-arcing duration in brackets.

Clearing I2t vs. AC Operating Voltage Maximum Arc voltage vs. System Voltage

K
Um(V)
1.4
Correction Factor for I2t

Max Peak Arc Voltage

1.2
1400
1

0.8 1200 Determines the peak arc


voltage across the fuse
0.6 terminals as a function of
applied voltage
0.4 800

0.2
600

0
0 200 400 500 660 U (V)

Operating Voltage 0 200 400 600 700 U (V)

Correction factor to determine I2t value for a fuse Circuit Voltage


operating below its rated voltage.

D 53
DIN 000 FUSES

6,9 gRB-URB SEMICONDUCTOR protection Fuses

Melting Time - Current data

t (s) t (s)
URB

200
315
gRB
100
50

100
125
160
250
350
400
125

80
20
25
32
40
63
80

10 4 10 4

10 3 a=130 10 3 a=130
A2=0.6 A2=0.6
B1=1.25 B1=1.25
10 2 10 2 B2=0.6
B2=0.6
Cf3=0.8

Time in Seconds
Cf3=0.8
Time in Seconds

C C'

C C'
10 10

1 1

10-1 10-1

10-2 10-2

10-3 10-3

10-4 10-4
10 10 2 10 3 10 4 I (A) 10 10 2 10 3 10 4 10 5 I (A)

Current in Amperes Current in Amperes

Curves show, for each rated current, pre-arcing (melt) time vs. R.M.S. pre-arcing current.

Peak Let Tru Data

Ip(A)
Max Instantanious Peak Let Thru Current

Max Instantanious Peak Let Thru Current

Ia(A)
10
2.5

5
Ip
2
=

gRB URB
E
Ic

=
2.5

Ip

400 A
350 A
Ic
2
=

315 A
E

250 A
Ic

200 A
=

10 4 125 A 160 A
Ic

100 A 125 A
80 A
63 A 100 A
50 A 80 A
40 A
32 A
25 A
20 A

10 3

10 2
10 2 10 3 10 4 10 5 10 6 10 2 10 3 10 4 10 5 10 6

Available Current in RMS Symmetrical Amperes Available Current in RMS Symmetrical Amperes

Curves show, for each rating, value of peak-let-through current Ic as a function of availible fault current lp.

D 54
DIN 000 FUSES

6,9 gRB-URB SEMICONDUCTOR protection Fuses

DC Voltage Capability vs. Time Constant DC Peak Arc Voltage

L/R (ms) Um (V)


100 d c b a
1400 L/R =80 ms
90
L/R =25 ms
80 1200
Time Constant L/R

Peak Arc Voltage


70 L/R =10 ms
1000
60
800
50
40 600
30
20
400 D
200
10
0 0
U (V) U (V)

0
100
200
300
400
500
600
700
0
100
200
300
400
500
600
700

DC Voltage Capabilities System Voltage

Provides the DC voltage capability of a fuse as a Above: Curve indicates peak arc
function of circuit time constant (L/R ratio). voltage Um which may appear across
Curve a: Ratings from 20 to 160 A fuse terminals at DC working voltage U.
Curve b: Ratings 200 A
Curve c: Ratings from 250 to 315 A
Curve d: Ratings from 350 to 400 A

Watts Loss Correction Factor

P/Pn
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
I/In
0.5
0.6
0.7
0.8
0.9
1.0
1.1

Above: Correction factor to determine watts loss value


for a fuse operating below its rated current.

D 55