Circuit Breaker Time/Current Curves (Phase Current)
6000
5000 Magnum Circuit Breakers
Response: Very Inverse & Short Delay Trip
1 Hour
3000 Notes:
1. This curve is shown as a multiple of the PICKUP setting (Ir). The TimeDial setting
2000 combined with SHORT PU and SHORT TIME setting (shown in heavy lines) depict
the IEC-B response. The Instantaneous, shown as a separate response, can be
set to OFF.
4. The actual pick up point (indicated by rapid flashing of Unit Status LED on the
100 product) occurs at 110% of the Ir, current, with a ±5% tolerance. The SHORT PU
90
80 Adjustable PICKUP settings have conventional 100% ± 5% as their pick up point.
0.4 to 1.0x In = Ir
1 Minute
70
with 0.05 increments 5. SHORT PU also has a M1 setting, which may extend out where the SHORT PU
60
See Note 4 will become active.
50
Adjustable Range M1 setting
40 Narrow Frame:
200A through 1250A 1.5 to 14x Ir M1=14x In
30 1600A 1.5 to 12x Ir M1=12x In
2000A (IEC only) 1.5 to 10x Ir M1=12x In
Standard Frame:
20
100A through 1250A 1.5 to 14x Ir M1=14x In
1600A, 2000A, 2500A 1.5 to 12x Ir M1=12x In
3000A, 3200A 1.5 to 10x Ir M1=10x In
Double Wide Frame:
10 2000A, 2500A 1.5 to 14x Ir M1=14x In
9 3000A, 3200A, 4000A, 5000A 1.5 to 12x Ir M1=12x In
8
6000A, 6300A (IEC only) 1.5 to 10x Ir M1=10x In
7
6
6. The end of the curve is determined by the interrupting rating of the circuit breaker.
5 See Adjustable TimeDial
Note 6 Setting 0.10 to 1.00 7. SHORT TIME: FLAT only
4
With 0.05 increments Tolerance is +0/ -80 ms of setting except
See Note 2 0.10s setting is 0.06 to 0.13
3 0.15s setting is 0.10 to 0.17
0.20s setting is 0.15 to 0.22
2 8. Curve applies from -20°C to +55°C ambient. Temperatures above +85°C cause
automatic trip.
Adjustable 9. These curves are comprehensive for the complete family of Magnum breakers,
TIME IN SECONDS
SHORT TIME including all frame sizes, ratings, and constructions. The total clearing times shown
1.00 0.10s to 0.50s are conservative and consider the maximum response times of the trip unit, the
1 With 0.05 increments
.9 0.90 circuit breaker opening, and the interruption of the current under factors that
0.80 See Note 7 contribute to worst case conditions, like: maximum rated voltages, single phase
.8
.7 0.70 interruption, and minimum power factor. Faster clearing times are possible
0.60 depending on the specific system conditions, the type of Magnum Circuit Breaker
.6
0.50 applied, and if any arc reduction settings are employed. Contact Eaton for additional
.5 0.50 s information.
0.40
.4
0.30
.3
0.20
.2
0.15
0.10
.1
.09
.08
.07
.06
.05
.02
.01
1
.7
30
.9
10
3
50
4
70
20
40
60
.6
100
80
90
.8
.5