FA/116-08R
Revised: 11/2008
A technical bulletin for engineers, contractors and students in the air movement and control industry.
reduces the possibility of contact between any offer power roof ventilators and inline fans that
stationary and rotating component. Typically, this is are designed to meet AMCA standard 99-0401.
satisfied with the use of an aluminum wheel and an These alternative construction options provide
aluminum rub ring. If there is a mechanical failure of more flexibility to meet unique needs of each
the fan, the aluminum wheel will contact a steel inlet ventilation application.
cone. Similar to Spark C construction, the aluminum
Which type should I use?
rub ring will protect against contact of the steel fan
shaft and steel fan housing. Spark B falls between The main criteria to keep in mind are whether
Spark A and C with regards to pricing. the airstream will be normally hazardous or
not normally hazardous. A normally hazardous
AMCA Type C Spark airstream may require type A or B. A fan handling
Type C offers a minimal level of spark resistance gases that are not normally hazardous might be of
and only requires that possible contact between construction type B or C.
stationary and rotating components be reduced.
An example of a system that is not normally
Typically, this construction includes the use of an
hazardous would be a high school chemistry lab.
aluminum inlet cone and an aluminum rub ring.
Although a spark resistant construction is warranted
The aluminum inlet cone will be the first point of
for this application, the degree of spark resistance
fan wheel contact if there is a mechanical failure.
would lessen as ambient classroom air dilutes the
The aluminum rub ring placed at the opening of
flammable materials. When the level of construction
the housing where the shaft passes, protects against
is in question, go with the higher degree of
contact of the steel fan shaft and steel fan housing.
protection. One example might be a gasoline storage
Spark C is the least expensive alternative.
facility. Based on the high level of fumes, this would
Other considerations constitute as a normally hazardous airstream. For
Electrical motors, disconnect switch, bearings and this application, Spark A or B should be considered.
drive components may require some consideration Keep in mind that having a safe SRC fan system
depending on the type of fan. does not end with the fan selection, purchase,
AMCA standard 99-0401 does not require that and installation. Proper maintenance and regular
an explosion resistant motor and disconnect be inspection of SRC fans is important. The US Bureau
used to attain spark resistant construction as of Mines along with others has shown that
long as these components are located out of the aluminum impellers rubbing on steel which
airstream. AMCA 99-0401 states that the motor or has been allowed to rust may result in high
any electrical devices should not be placed in the intensity sparking.
flammable airstream. If mounting these devices in Summary
the airstream is required, then a suitable explosion
Although factory representatives can help suggest
resistant construction or enclosure is required
what might best serve their customer, ultimately it
to prevent igniting the airstream. For additional
is up to the system designer to specify appropriate
information on the selection of these components,
levels. For more information, we recommend
refer to Product Application Guides FA/107-
purchasing AMCA Standard 99-0401. If needed,
00 (Explosion Resistant Disconnect Switches) or
Greenheck’s application engineers are also available
FA/113-01 (Motors for Ventilation Products).
to provide additional assistance.
Spark Resistant Fan Types
Spark resistant construction is available on many
types of commercial and industrial blowers. Along
with scroll type centrifugal fans, most manufacturers