Escolar Documentos
Profissional Documentos
Cultura Documentos
Slide 1
2
Agenda
▫ Introduction
▫ Using Log-Log Paper & TCCs ▫ f
Transformer Overcurrent
O Protection
▫ Motor Overcurrent Protection
▫ Types of Fault Current
▫ Conductor Overcurrent Protection
▫ Protective Devices & Characteristic ▫ Generator Overcurrent Protection
Curves
▫ Coordinating a System
▫ Coordination Time Intervals (CTIs) ▫ Supplemental Material
▫ Effect of Fault Current Variations ▫ Coordination Quizzes
▫ Multiple Source Buses ▫ Hands-On Demonstration
▫ Partial Differential Relaying ▫ References
▫ Directional Overcurrent Coordination
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 2
I t d ti
Introduction
Slide 3
4
Protection Objectives
• Personnel Safety
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 4
5
Protection Objectives
• Equipment Protection
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 5
6
Protection Objectives
• p
Errors in either specification or setting
g
can cause nuisance outages.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 6
7
Types of Protection
•Distance
•High-Impedance
Hi h I d Differential
Diff ti l
•Current Differential
•Under/Overfrequency
•Under/Overvoltage
•Over Temperature
•Overload
Overload
•Overcurrent
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 7
8
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 8
9
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 9
10
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 10
11
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 11
12
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 12
13
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 13
U i Log-Log
Using L L Paper
P & TCCs
TCC
Slide 14
15
Log-Log Plots
Ti
Time-Current
C t Characteristic
Ch t i ti C Curve (TCC)
1000
effectively
steady state Why log-log paper?
100
1 minute I2t withstand
curves plot as
straight lines
• Log-Log scale compresses
values to a more manageable
Time In Secondss
10
typical motor range.
acceleration
0.1 5 cycles
(
(interrupting)
)
FLC = 1 pu Fs = 13.9 pu Fp = 577 pu
1 cycle
(momentary)
0.01
0.5 1 10 100` 1000 10000
Current in Amperes
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 15
16
Plotting A Curve
5000
000 hp Motor TCC
CC
1000
FLC = 598.9 A
13.8 kV
100
13.8/4.16 kV
10 MVA
Time IIn Secondss
10 6.5%
Accel. Time = 2 s
4.16 kV
1
0.1 M
4 kV 5000 hp
90% PF, 96% η, 598.9 A
LRC = 3593.5 A 3593.5 LRC, 2 s start
0.01
0.5 1 10 100` 1000 10000
Current in Amperes
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 16
17
100
13.8/4.16 kV
10 MVA
6.5%
Time In Seconds
10
Accel. Time = 2 s
4.16 kV
1 15 kA
0.1 4 kV 5000 hp
90% PF, 96% η, 598.9 A
3593.5 LRC, 2 s start
LRC = 3593.5 A 15 kA
0.01
0 01
0.5 1 10 100` 1000 10000
Voltage Scales
5000
000 hp Motor TCC
CC with Fault on Transformer
f Primary
45 kA @ 13.8 kV 1000
13.8 kV
= ? @ 4.16 kV
= (45 x 13.8/4.16) 100
45 kA
= 149.3 kA @ 4.16 kV 13.8/4.16 kV
10 MVA
6.5%
Time IIn Secondss
10
4.16 kV
1 15 kA
M
4 kV 5000 hp
0.1
90% PF
PF, 96% η, 598.9
598 9 A
3593.5 LRC, 2 s start
15 kA 149.3 kA
0.01
0.5 1 10 100` 1000 10000
Current in Amperes x 100
10 AA @ 4.16 kV
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 18
T
Types off Fault
F lt Currents
C t
Slide 19
20
Interrupting/Breaking
Momentary
Initial Symmetrical
ANSI IEC
• Momentary Symmetrical • Initial Symmetrical (Ik’’)
• Momentary Asymmetrical • Peak (Ip)
• Momentary Crest • Breaking (Ib)
• Interrupting Symmetrical • Asymmetrical Breaking (Ib,asym)
• Adjusted Interrupting Symmetrical
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 20
21
Interrupting/Breaking
Momentary
Initial Symmetrical
Slide 22
23
NDS
TIME IN SECON
1
10
Dial
ngs
Time D
Settin
3
2
0.1 1
½
0.01
1 10 100
MULTIPLES OF PICK-UP SETTING
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 23
24
Electromechanical Relays
Pickup Calculation
The relay should pick-up for current
values above the motor FLC ( ~ 600 A). 4.16 kV
IFC
For the IFC53 pictured, the available 800/5
53
Set AT = 4
ampere-tap (AT) settings are 0 0.5,
5 00.6,
6
0.7, 0.8, 1, 1.2, 1.5, 2, 2.5, 3, & 4.
M
4 kV
For this type of relay, the primary pickup 5000 hp
current was calculated as: FLC = 598.9 A
SF = 1.0
PU = CT Ratio x AT
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 24
25
Electromechanical Relays
100
4.16 kV
IFC 53
RELAY
ONDS
53 TD = ??
10
10 kA
15 kA
M
1.21 4 kV
1 5000 hp
1.05 10
598.9 A, SF = 1
ettings
0.34 IFC 53 Relay Operating Times
Time Dial Se
0.30
3
2 Fault Current 15 kA 10 kA
0.1 15000/640 10000/640
1
0.08 Multiple of Pick-up
0.07 ½ = 23.4 = 15.6
Time Dial ½ 0.07 s 0.08 s
Time Dial 3 0.30 s 0.34 s
0.01 15.6 23.4 Time Dial 10 1.05 s 1.21 s
1 10 100
MULTIPLES OF PICK-UP SETTING
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 25
26
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 26
27
Microprocessor-Based Relays
2000/5 52B
01-52B
41-SWGR-01B
41 SWGR 01B
13.8 kV
400/5 OCR F15B
01-F15B
52B
OC1
ANSI-Normal Inverse
Seconds
Pickup = 2.13 (0.05 – 20 xCT Sec)
Time Dial = 0.96
Inst = 20 (0.05 – 20 xCT Sec)
F15B Time Delay = 0.01 s
OC1
ANSI-Extremely Inverse
Pickup = 8 (0.05 – 20 xCT Sec)
Time Dial = 0.43
Inst = 20 (0.05 – 20 xCT Sec)
Time Delay = 0.02 s
52B – 3P
F15B – 3P
30 kA @ 13.8 kV
Seconds
LT Pickup = 1 (3200 Amps)
LT Band = 4
ST Pickup = 2.5 (8000 Amps)
Power FCB ST Band = 0.3 (I^x)t = OUT
Cutler-Hammer RMS 520 Series
Sensor = 1200 ST Pickup
LT Pickup = 1 (1200 Amps)
LT Band = 2
ST Pickup = 4 (4500 Amps) ST Band
ST Band = 0.1 (I^x)t = OUT
Seconds
LT Pickup = Fixed (1200 A)
LT Band = Fixed
ST Pickup = 4 x (4000 A)
ST Band = Fixed (I^2)t = IN
Override = 14000 A
Molded Case CB
HKD
Size = 250 A
Terminal Trip = Fixed
Magnetic Trip = 10
Fault current
< Inst. Override
Seconds
LT Pickup = Fixed (1200 A)
LT Band = Fixed
ST Pickup = 4 x (4000 A)
ST Band = Fixed (I^2)t = IN
Override = 14000 A
Molded Case CB
HKD
Size = 250 A
Terminal Trip = Fixed
Magnetic Trip = 10
Fault current
> Inst. Override
MCC 1
4.16 kV
Mtr Fuse
Mtr Fuse
JCL (2/03)
Standard 5.08 kV
5R
Seconds
Total
T t l
Clearing
Minimum
Melting
Mtr Fuse
15 kA @
4.16 kV
Slide 32
33
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 33
34
What typical
Wh i l CTI wouldld we
want between the feeder and
Feeder
the main breaker relays?
30 kA
Main
Seconds
It depends.
depends Feeder
?s
30 kA
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 34
35
It is continuously adjustable
and not exact.
FIELD TESTING !
(not just hand set)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 35
36
Feeder
Seconds
“3x” means 3 times pickup
3 * 8 = 24 A (9.6 kA primary) 5x (16 kA), 1.24 s
5 * 8 = 40 A (16 kA primary)
i ) 8x (25
(25.6
6 kA)
kA), 0
0.63
63 s
8 * 8 = 64 A (25.6 kA primary)
30 kA
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 36
37
b ?
be?
0.4 s Feeder
30 kA
Main w/ testing
Seconds
Main w/o testing
But, if test points are provided
what should the CTI be? Feeder
30 kA
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 37
38
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 38
39
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 39
40
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 40
41
Seconds
Feeder (SS) Feeder EM
0.3 s
0.2 s
Amps X 100 (Plot Ref. kV=13.8) Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 41
42
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 42
43
Seconds
0.22 s 0.12 s
25 kA 25 kA
Amps X 100 (Plot Ref. kV=0.48) Amps X 100 (Plot Ref. kV=0.48)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 43
44
• There is no intentional/
additional time delay needed
between two banded devices.
Seconds
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 44
45
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 45
46
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 46
Eff t off F
Effect Fault
lt C
Currentt V
Variations
i ti
Slide 47
48
Main
Relay Operating
Current Time Feeder
F1 = 10 kA
Main F2 = 20 kA
Seconds
For a fault current of 10 kA the
CTI is 0.2
0 2 ss.
Feeder 0.2 s
For a fault current of 20 kA the 0.06 s
CTI is 0.06 s.
Consider a main-tie-main
F1 = 10 kA F2 = 20 kA
arrangement with a N.O. tie
b k
breaker Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 48
49
10 kA
15 kA
1.2 kA 0.8 kA 2 kA 1 kA
M M M
• For a typical distribution bus all feeder relays will see a slightly different
maximum fault current.
• Years back, the simple approach was to use the total bus fault current as
the basis of the CTI,
CTI including main incomer
incomer.
• Using the same current for the main led to a margin of conservatism.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 49
50
10 kA
Using
g Total Bus Using Actual
Fault Current of 15 kA Maximum Relay
15 kA Current of 10 kA
Feeder Feeder
M
Main
Main
Seconds
0.8 s
0.2 s
15 kA 10 kA 15 kA
Amps X 100 (Plot Ref. kV=13.8) Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 50
51
Curve Shaping
Seconds
current levels.
0.2 s
20 kA
15 kA
10 kA
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 51
52
Seconds
• Under certain setting conditions, such
as with an extremely inverse
characteristic, the intended definite 0.2 s
time delay can be undercut and higher 0.1 s
fault levels.
40 kA
20 kA
15 kA
10 kA
Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 52
M lti l Source
Multiple S Buses
B
Slide 53
54
• y should be plotted
Source relays p onlyy to their respective
p fault
currents or their “normalized” plots.
• Plotting the source curves to the total bus fault current will lead to
much larger than actual CTIs.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 54
55
1 30 kA 1 1
Seconds
1.1 s
0.2 s
12 kA 30 kA 12 kA 30 kA
Amps X 100 (Plot Ref. kV=13.8) Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 55
56
Curve Shifting
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 56
57
Curve Shifting
25x
2.5
1
30 kA 1 1 2
2
12 kA 30 kA 30 kA
Amps X 100 (Plot Ref. kV=13.8) Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 57
58
10 kA 10 kA 5 kA
Bus A Bus B
15 kA (Fa)
10 kA (Fb)
Fa = 25 kA Fb = 25 kA
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 58
P ti l Differential
Partial Diff ti l Relaying
R l i
Slide 59
60
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 60
61
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 61
62
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 62
Di ti
Directional
l Overcurrent
O t Relaying
R l i
Slide 63
64
67 67
Bus A Bus B
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 64
T
Transformer
f Overcurrent
O t Protection
P t ti
Slide 65
66
Transformer Overcurrent Protection
NEC Table 450.3(A) defines overcurrent setting requirements for primary &
secondary protection pickup settings.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 66
67
Transformer Overcurrent Protection
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 67
68
Transformer Overcurrent Protection
Relay pickup
Primary
FLC = 2.4 MVA/(√3 x 13.8) = 100.4 A PWR-MCB
Relay PU must be ≤ 600% FLC = 602 602.4
4A
Using a relay setting of 2.0 x CT, the relay
PU = 2 x 200 = 400 A
400 / 100.4 = 398% so okay 2.4 MVA, 5.75% Z
∆-Y
∆ Y Resistor Ground
Secondary
Seconds
FLC = 2.4 MVA / (√3 x 0.48) = 2887 A
R-Primary
MCB Trip must be ≤ 250% FLC = 7217 A 13.8 kV
optional
ti l time
ti
Breaker Trip = 3200 A per bus rating R-Primary
delay settings
3200 / 2887 = 111% (okay)
13.8/0.48 kV
2.4 MVA
Time d
Ti delay
l ddepends
d on llevell off protection
t ti 5 75%
5.75%
desired. PWR-MCB
3200 A
480 V
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 68
69
Transformer Overcurrent Protection
∆-Y Connections – Phase-To-Phase Faults
0.5 a
A
1.0 0
0.866
B b
0.5 c
C 0.866
Seconds
• Setting the CTI based on a three
three- 0.3 s 0.25 s
phase fault is not as conservative as
for a phase-phase fault.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 69
70
Transformer Overcurrent Protection
∆ Y Connections
∆-Y C ti – Phase-To-Ground
Ph T G d Faults
F lt
1.0 2.4 MVA, 5.75% Z
0.577 a
A ∆-Y Resistor Ground
0.577
0 0 0
B b 2.4 MVA, 5.75% Z
0.577 c ∆-Y Solid Ground
58%
C
R-Primary
y
PWR-MCB
• A one per unit phase-ground fault on
Seconds
the secondary appears as a 58%
((1/√3)
√ )pphase fault on the p
primary.
y 13 8 kV
13.8
PWR-MCB
3200 A
45 kA @ 0.48 kV
480 V
PWR-MCB
• Use of 8-12 times FLC @ 0.1
0 1 s is an
empirical approach based on EM
relays.
2.4 MVA, 5.75% Z
∆-Y
∆ Y Resistor Ground
• The instantaneous peak value of the
inrush current can actually be much
Seconds
higher than 12 times FLC. 13.8 kV
R-Primary
• The inrush is not over at 0.1 s, the dot
just represents a typical rms 13.8/0.48 kV
2.4 MVA 8-12 x FLC
equivalent of the inrush from 5 75%
5.75%
(typical)
energization to this point in time. PWR-MCB
3200 A
480 V 45 kA @ 0.48 kV
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 71
72
Transformer Overcurrent Protection
Setting the primary inst. protection
PWR-MCB
• The primary relay instantaneous
(50) setting should clear both the
inrush & the secondary fault current.
2.4 MVA, 5.75% Z
∆-Y
∆ Y Resistor Ground
• It was common to use the
asymmetrical rms value of
Seconds
secondary fault current (1.6 x sym) 13.8 kV
t establish
to t bli h th
the iinstantaneous
t t
pickup, but most modern relays filter R-Primary
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 72
73
Transformer Overcurrent Protection
• A secondary L-G fault is not sensed by the ground (zero sequence) devices on
the primary (∆) side.
• L
Low-resistance
i t and
d solidly-grounded
lidl d d systems
t on th
the secondary
d off a ∆-Y
Y
transformer are therefore coordinated separately from the upstream systems.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 73
74
Transformer Overcurrent Protection
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 74
M t O
Motor Overcurrentt Protection
P t ti
Slide 75
76
Motor Overcurrent Protection
• Fuse provides short-circuit GE Multilin 469
Standard O/L Curve
protection. Pickup = 1.01 X FLC
Curve Multiplier = 3
Hot
1000 hp
• Overload pickup depends on 4 kV
650% LRC
motor FLC and service factor.
Seconds
• The time delay for the 49/51
protection is based on motor
stall time.
3 kA @
M 4.16 kV
Seconds
interrupting rating.
Contactor
6 kA Int.
3 kA @
M 4.16 kV
Seconds
• Can be done using a lower pickup and
time delay to allow the DC component
to decay out.
3 kA @ 4.16 kV
M
Slide 79
80
LV Cables
NEC 240.4 Protection of Conductors – conductors shall be protected against
overcurrent in accordance with their ampacities
(B) Devices Rated 800 A or Less – the next higher standard device rating
shall be permitted
(C) Devices Rated over 800 A – the ampacity of the conductors shall be ≥ the
device rating
NEC 240.6
240 6 Standard Ampere Ratings
(A) Fuses & Fixed-Trip Circuit Breakers – cites all standard ratings
(B) Adjustable Trip Circuit Breakers – Rating shall be equal to maximum
setting
tti
(C) Restricted Access Adjustable-Trip Circuit Breakers – Rating can be
equal to setting if access is restricted
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 80
81
MV Motor
M t Conductors
C d t
NEC 430.224 Size of Conductors
Conductors ampacity
p y shall be g
greater than the overload setting.
g
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 81
82
Seconds
To = 90 deg. C
Slide 83
84
Momentary contribution
(FLC/X”d) • The pickup at no restraint must be
< FLC/Xd.
Amps X 10 (Plot Ref. kV=12.47)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 84
85
12.47 kV
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 85
86
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 86
87
30 kA
Slide 88
89
Coordinating a System
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 89
90
Coordinating a System
• Showing a vertical
slice of the system
y
can reduce
crowding, but still
be hard to read.
• Upstream
equipment is
shown on multiple
and redundant
TCCs.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 90
91
Coordinating a System
• A set of overlapping TCCs can be used to limit the amount of
information on each curve and demonstrate coordination of the
system from the bottom up.
TCC-6
TCC-3
TCC-2 TCC-Comp
TCC-5
TCC-1
TCC-4
TCC-307J
TCC-101J TCC-212J
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 92
93
Seconds
• Motor starting & protection is adequate.
• Cab
Cablee withstand
s a d protection
p o ec o is s adequa
adequate.
e
• The MCC main breaker may trip for faults
above 11 kA, but this cannot be helped.
• The switchgear feeder breaker is selective
with the MCC main breaker, although not
necessarily required
Amps X 100 (Plot Ref. kV=0.48)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 93
94
Seconds
• The switchgear feeder breaker settings
established on TCC-1 set the basis for this curve.
• The main breaker is set to be selective with the
feeder at all fault levels.
• A CTI marker is not required since the
characteristic curves include all margins and
breaker operating times.
• The main breaker curve is clipped at its through-
fault current instead of the total bus fault current
to allow tighter coordination of the upstream relay.
(See TCC-3)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 94
95
Seconds
• The LV switchgear
g main breaker settings
g
established on TCC-2 set the basis for this curve.
• The transformer damage curve is based on frequent
faults and is not shifted since the transformer is
resistance grounded.
• The primary side OC relay is selective with the
secondary main and provides adequate transformer
and feeder cable protection.
• The OC relay instantaneous high enough to pass
the secondary fault current and transformer inrush
current. Amps X 100 (Plot Ref. kV=0.48)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 95
96
Seconds
• Thi
This curve setst the
th basis
b i ffor th
the upstream
t d
devices
i
since its motor is the largest on the MCC.
• Motor starting and overload protection is
acceptable.
• Motor feeder cable protection is acceptable
• The motor relay includes a definite time unit to
provide enhanced protection.
• The definite time function is delay to allow the
asymmetrical inrush current to pass
pass.
Amps X 10 (Plot Ref. kV=4.16)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 96
97
Seconds
• The 307J motor relay settings established on
TCC-307J set the basis for this curve.
• The tie breaker relay curve is plotted to the total
b ffault
bus lt currentt to
t be
b conservative.
ti
• The main breaker relay curve is plotted to its
let-through current.
• A coordination step is provided between the tie
and main relay although this decision is
discretionary.
• All devices are selectively coordinated at all
fault current levels.
• The definite time functions insulate the CTIs
from minor fault current variations.
Amps X 10 (Plot Ref. kV=4.16)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 97
98
Seconds
• The MV MCC main breaker settings established on
TCC-4 set the basis for this curve.
• The transformer damage curve is based on frequent
faults and is not shifted since the transformer is
resistance grounded.
grounded
• The primary side OC relay is selective with the
secondary main and provides adequate transformer
and feeder cable protection.
• The OC relay instantaneous high enough to pass the
f
secondary fault f
current and transformer inrush current.
Amps X 10 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 98
99
Seconds
• Due to the compressor size, this curve may set
the basis for the MV switchgear main breaker.
• Motor starting and overload protection is
p
acceptable.
• Short-circuit protection is provided by the
relay/breaker instead of a fuse as with the 1000
hp motor.
• The short-circuit protection is delayed 50 ms to
avoid nuisance tripping.
Amps X 10 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 99
100
Seconds
• The feeder breaker settings established on
TCC-3, TCC-4, and TCC-Comp are shown as
the basis for this curve.
• The
Th settings
tti for
f feeder
f d 52A1 (t (to th
the 2
2.4
4 MVA)
could be omitted since it does not define any
requirements.
• A coordination step is provided between the tie
and main relay although this decision is
discretionary.
• All devices are selectively coordinated at all fault
current levels.
• The definite time functions insulate the CTIs from
minor fault current variations.
Amps X 10 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 100
101
TCC-G1
TCC-G2
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 101
S
Supplemental
l t l Material
M t i l
Slide 102
103
103
51 51
50 50
51 51
50 50
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 103
104
104
51
ia
ib
ic ia+ib+ic
51 51
50 N
Protected
Residual CT connection Bus
ia+ib+ic
Ia
Ib 51
Ic G 51
Zero sequence
q CT
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 104
105
105
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 105
106
106
Suggested “Rules
Rules of Thumb
Thumb” for MV Equipment
• Transformers
• Bus
• Feeders
• Motors
• Capacitors
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 106
107
107
Suggested
gg “Rules of Thumb” for MV Equipment
•The intent of this section is to provide a range of “typical” settings. It is the
engineer’s responsibility to verify the application on an individual basis.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 107
108
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 108
109
Generally use E-rated fuses. Note that TOC characteristics of fuses are not all
the same.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 110
111
Example: 2000 A main breaker (2000:5 CTs), it may make sense to specify
an 400 A ground resistor with a continuous rating of 50% (200 A) such that a
2000:5 residually connected CT input can be used with a minimum pickup
(0.1 x CT = 0.5 A secondary, 200 A primary).
•Set
Set the time dial such that at the time to trip is 2.0
2 0 seconds at maximum
ground fault
•Protect
Protect resistor using I²t
I t curve.
curve Typical resistor is rated for 10 seconds at
nominal current (to be specified at time of order).
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 111
112
•Decrease the primary phase element by 58% (to account for transformer
damage curve shift). This is the equivalent current seen on the primary
(delta) for a secondary ground fault (refer to the Symmetrical Components
presentation
t ti on Oct
O t 5th,
5th 2010 bby D
Dr. KKurtt Ed
Ederhoff).
h ff)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 112
113
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 113
114
Primary
P i Side
Sid Wye-Grounded
W G d d Transformer
T f
If primary is solidly grounded and neutral relay is available, set pickup at
approximately 50% of phase element. This must coordinate with upstream
line p
protection devices ((i.e. 21P,, 21G,, 67,, 67G …).
) If it’s at the utilityy level,,
they will review and provide settings.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 114
115
For a fault
F f lt between
b t the
th
51B transformer and main
breaker, the partial
differential bus relays will
not detect current (other
than motor contribution).
ection
ction
Trip Dire
Trip Direc
on
Trip Directio
The tie
Th ti breaker
b k will ill ttrip
i ffollowed
ll d
Trip Direction
n
67
N.C. 67 by the respective transformer
primary overcurrent. A directional
overcurrent relayy is required
q
to prevent loss of one bus.
Set 67 pickup at 40% of transformer FLA.
Coordinate with time curve with 51Tie
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 116
117
Feeder Relays:
Set pickup to comply with NEC 240-100 (limited to 600% of
rated ampacity of conductor). Actually, pickup permitted by NEC is slightly higher.
Keep it down in the neighborhood of 200%. The intent is NOT to provide
overload protection. The intent is to provide short-circuit protection.
Set time dial as required to coordinate with downstream devices while protecting
conductor against damage.
Enable instantaneous element only if the load has a notable impedance (i.e.
transformer,
f motor, capacitor, etc)) or iff the load is the end off a radial circuit.
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 117
118
Ground Overcurrent. For Zero Sequence CT (BYZ) set ground Trip at 10A primary and
Alarm at 5A primary. Set for instantaneous if using electromechanical and set at 20 msec
delayy ((minimum)) if using
g digital
g relays.
y
For solidly grounded systems, ensure that the ground trip setting will not cause a motor
starter to attempt interrupting a fault beyond its rating.
For feeder protection, set Pickup at 135% of FLA, set Time Dial at 1.0,
set 50P element above maximum inrush and include a slight time delay to
coordinate with individual fuse clear time. Plot TOC to protect the capacitor
case rupture curve.
Slide 120
C
Coordination
di ti Quizzes
Q i
Slide 121
122
Coordination Quiz #1
2000/5 OCR
400/5
/ OCR
600/5 OCR • There is no need to maintain a
TR-FDR1 TR-FDR2
coordination interval between
feeder breakers.
TR-FDR2-P
Main-P • The CTI between the main and
OC1
Seconds
Coordination Quiz #2
SWGR-3
SWGR 3 • The CTIs shown between main
400/5 OCR
600/5 OCR and both feeders are sufficient.
FDR-1 FDR-2
Main-P
Main P • Assuming testing EM relays, the
OC1 0.62 s CTI cannot be reduced
Seconds
Coordination Quiz #3
2000/5 OCR
400/5 OCR
600/5 OCR
• The marked CTIs are okay,
okay but….
but
FDR--1 FDR--2
Main-3-P
OC1 • Fix – delete the instantaneous on
FDR--1-P
0 47 s
0.47
the main relayy and raise the time
OC1
delay to maintain a 0.2s CTI at
FDR--2-P 0.33 s
50 kA.
OC1
Main-3-3P
FDR--2-3P
FDR--1-3P
13 8 kV
50 kA @ 13.8
Coordination Quiz #4
Coordination Quiz #5
0.08 s
• Fix – raise Relay14 time delay
setting and add CTI marker.
marker
Coordination Quiz #6
LVMain
a • There is no need to maintain an
intentional time margin between
Seconds
LVFDR1
0.21 s
• Fix – lower the main breaker
short-time delay band.
LVFDR2 – 3P
LVMain – 3P LVFDR1 – 3P
30 kA @ 0.48 kV 45 kA @ 0.48 kV
Coordination Quiz #7
10 kA 5 kA
Does this TCC look okay??
• The source relays should not be
plotted to the full bus fault level
unless their plots are shifted
Source1 - P
based on:
OC1 SF = Total fault current / relay
Source2 - P current.
Seconds
OC1
Feeder - P
OC1 • Assuming each relay actually
sees only half of the total fault
0.3 s
current, the CTI is actually much
higher than 0.3 s.
Source1 - 3P
Source2 – 3P • Fix – plot the source relays to
Feeder – 3P their actual fault current or apply
15 kA @ 13.8 kV
SF
SF.
Amps X 100 (Plot Ref. kV=13.8)
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 128
129
Coordination Quiz #8
OC1
tightly with the feeder.
FDR-5 - P
OC1
0.30 s
• Th
The 51V curve willill shift
hift lleft
ft and
d
lose selectivity with the feeder if a
close-in fault occurs and the
voltage
g drops.
p
51V – 3P
• Fix – show both 51V curves and
FDR-5 – 3P raise time delay.
15 kA @ 13.8 kV
Slide 130
131
Selected References
Overcurrent Coordination for Industrial Applications IEEE IAS 2010 - Copyright: IEEE
Slide 131