Você está na página 1de 9

Construction and Building Materials 182 (2018) 637–645

Contents lists available at ScienceDirect

Construction and Building Materials


journal homepage: www.elsevier.com/locate/conbuildmat

Bond-slip behavior between pre-corroded rebar and steel fiber


reinforced concrete
Lijun Hou, Bingxuan Zhou, Shang Guo, Ning Zhuang, Da Chen ⇑
College of Harbour, Coastal and Offshore Engineering, Hohai University, Nanjing 210098, China

h i g h l i g h t s

 The bond between pre-corroded rebar and SFRC simulated the retrofit condition.
 A slip plateau was observed near the peak stress for specimens with c/d of 5.75.
 The effect of corrosion ratio on bond behavior was related to c/d and failing mode.
 A bond strength model was proposed considering coupling effect of corrosion and c/d.

a r t i c l e i n f o a b s t r a c t

Article history: For the corroded reinforced concrete (RC) members repaired using steel fiber reinforced concrete (SFRC),
Received 1 January 2018 bonding between corroded rebar and SFRC greatly affected the mechanical performance of repaired
Received in revised form 18 May 2018 members. In the present paper, the central pull-out tests were carried out to investigate the bond behav-
Accepted 14 June 2018
ior of SFRC and pre-corroded steel bar obtained in concrete specimens. The varied parameters included
corrosion ratio and cover thickness to rebar diameter ratio (c/d). The experimental results revealed that
the confinement and bridging action of fiber can improve the bond strength and transform the failure
Keywords:
mode from splitting to pull-out or combined splitting and pull-out. Bond strength decreased with
Bond
Pre-corrosion
increasing corrosion ratio and decreasing c/d, whereas the residual bond strength remained no less than
SFRC that of non-corroded rebar especially for specimens with a small c/d. Bond strength degradation, bond
Pull-out toughness variation and bond-slip descending behaviors with corrosion ratio were correlated to c/d
Strength and failing mode. A modified bond strength model considering the coupling effect of corrosion and c/d
Toughness was proposed, and the calculated strength agreed well with the tested.
Ó 2018 Published by Elsevier Ltd.

1. Introduction by corrosion effectively [4]. Moreover, the reverse loading greatly


aggravated the corrosion-induced bond degradation, especially
Bonding between rebar and concrete is a foundation in rein- within the first five cycles and for the unconfined rebar [5]. In addi-
forced concrete (RC) structures. For RC structures subjected to tion, the corrosion-induced bond degradation decreased with
long-term carbonation and chloride corrosion, bond of steel bar increasing strain rate, but strain rate effect was gradually weak-
and the surrounding concrete is first improved due to the filling ened with increasing corrosion level [6].
effect of corrosion product, and then reduces due to corrosion- More severely, the structural performance of corroded RC mem-
induced cover cracking [1,2]. For unconfined rebar, a rebar mass bers at the service and ultimate limit states degraded apparently
loss of about 0.5% resulted in about 50–60% enhancement in bond due to the deteriorated bond as well as reduced rebar area, ductility
strength, whereas a mass loss of 3.9% led to a sharp reduction up to and strength of rebar, etc. And thus, the patch repair for
54% [3]. In contrast, for confined rebar with around 4–6% corrosion corroded RC members is usually applied to improve the load-
ratio, the bond strength was almost 30–65% larger than that of carrying capacity, stiffness and durability for extending the service
unconfined rebar at a similar corrosion level, and the confinement age. Steel fiber reinforced concrete (SFRC), showing good mechani-
of transverse reinforcement can counteract the bond loss induced cal properties in tension, flexure, shear, impact and fatigue, etc.
[7–11] and durability in freezing and thawing, permeability and
⇑ Corresponding author. carbonation, etc. [11–13], has been used in retrofit and strengthening
E-mail address: chenda@hhu.edu.cn (D. Chen). of old and damaged structures as well as the construction of new

https://doi.org/10.1016/j.conbuildmat.2018.06.116
0950-0618/Ó 2018 Published by Elsevier Ltd.
638 L. Hou et al. / Construction and Building Materials 182 (2018) 637–645

structures [14]. Note that the property of SFRC subjected to chloride


corrosion is of great significance for the engineering application in
marine environment. The review on SFRC [15] confirms that the
steel fiber in uncracked SFRC had a superior chloride corrosion
resistance compared with rebar in concrete mainly due to the
discontinuity and the uniform steel surface of fibers along with
the dense and uniform fiber-matrix interface. For cracked SFRC
with crack width below the critical width (i.e., 0.2 mm), the crack
and damaged fiber-matrix interface can heal eventually [16,17].
In the meantime, fiber-matrix interface bond was improved due
to the increasing fiber roughness, healing fiber-matrix interface
and accumulated chemical binding products [18]. The study con-
ducted by Granju and Balouch [19] indicated that the flexural
Fig. 1. Details of the pre-corroded specimen.
strength of pre-cracking SFRC specimens was enhanced under chlo-
ride corrosion for one year. The fibers across the crack within a 2–3
mm rim from the specimen surface suffered severe corrosion,
whereas the fibers located out of this rim exhibited a light corrosion sleeve. Fig. 1 shows the detailed configuration of pre-corroded
without section loss. Balouch et al. [20] further revealed that the specimens. The variable of pre-corrosion test included rebar diam-
minimum cover of 0.1 mm or 0.2 mm can prevent the surface eter and corrosion ratio. The deformed rebar with 12, 16 and 20
corrosion of SFRC with w/c no larger than 0.5. Therefore, SFRC mm in diameter was used and, the corresponding center distance
may be used in the repair of marine engineering structures if a between crescent ribs was 8.48, 9.94 and 10.05 mm for these three
certain thickness of cover can be provided for fiber. types of rebar. The target corrosion ratio was designed as 5%, 10%
When corroded RC members were repaired using SFRC, the and 15%. Thus these 27 specimens can be divided into 9 groups
cracking cover, damaged and chloride-rich concrete surrounding with 3 specimens each group.
the corroded rebar and corrosion products bonded on rebar must The accelerated corrosion test using applied direct-current was
be removed before repair [21,22]. Accordingly, bonding between employed for pre-corrosion. Concrete cylinders were immersed
corroded rebar and SFRC is of great importance for the mechanical into 3.5% NaCl solution covering the whole pre-corrosion region
property of repaired members. However, the related studies con- of rebar. The reinforcement was connected with the anode of
cerning the bond between rebar and SFRC mainly concentrated power, and stainless steel bars with a diameter of 8 mm were con-
on the non-corroded rebar and the effect of fiber fraction and nected with the cathode. The corrosion current density applied was
parameters. The experimental results reported by Yazici et al. 300 lA/cm2, and corrosion age can be estimated according to
[23] revealed that bond strength was enhanced with increasing Faraday’s law,
fraction and fiber length to diameter ratio (lf/df). In detail, for steel
fiber with lf/df of 40–60, the addition of 60 kg/m3 fiber resulted in zF Dm
6–9% bond strength enhancement [23]. The bond experiment con- t¼ ð1Þ
MiS
ducted by Campione et al. [24] indicated that the use of steel fiber
in volume fraction within 0.5–2% produced 7–38% improvement in
bond strength. For pre-stressing strands, the bond strength where, F is Faraday’s constant (96,500 C/mol), z is the ionic charge
increased by 30% when using 15 kg/m3 steel fiber, and the optimal number (z = 2) of iron, Dm is the mass loss of corroded reinforce-
fiber fraction was related to the strand diameter and fiber param- ment (g), M is the molar mass of iron (56 g/mol), i is the corrosion
eters [25]. In contrast, the experimental study conducted by Gao current density (A/cm2), and S is the superficial area of rebar within
et al. [26] indicated that the addition of steel fiber within 2% vol- the corrosion region (cm2). After the pre-corrosion, the corroded
ume fraction merely resulted in a 3% increase in bond strength. rebar was removed though splitting cylinders. Further, corrosion
However, the bond behavior of corroded rebar embedded in product and concrete bonded on the rebar were cleaned up using
SFRC remains unclear, especially for the corroded rebar on which steel wire brush to obtain a similar rebar surface to that in an actual
corrosion products bonded are removed under the retrofit condi- repair condition.
tion. In the present paper, the pre-corroded rebar, obtained in con-
crete specimens through accelerated corrosion test, was cleaned
and used for pull-out specimens to simulate the actual repair con- 2.2. Pull-out specimens
dition. The effect of corrosion ratio and cover-rebar diameter ratio
on bond behaviors was discussed concerning failure modes, bond- The 150 mm cube with a centrally placed rebar was used as the
slip curves, bond strength and bond toughness, etc. The experi- pull-out specimen. A total of 45 pull-out specimens were cast
mental results can provide a reference for the retrofit of corroded including 9 concrete comparison specimens and 36 SFRC samples.
RC members using SFRC. The variable parameters included corrosion ratio (q) and cover
thickness to rebar diameter ratio (c/d). In this test, corrosion ratio
was taken as 0% and the actual pre-corrosion ratio. c/d was
2. Experimental program designed as 5.75, 4.19 and 3.25 with increasing rebar diameter
from 12 to 20 mm. Note that the actual pre-corrosion ratio was
2.1. Pre-corrosion of rebar measured after pull-out tests, and the details were presented in
the following section.
For simulating the retrofitting condition of corroded RC mem- Fig. 2 shows the details of pull-out specimen. The bond length-
bers, a total of 27 steel bars used for bond test were pre- rebar diameter ratio (l/d) was taken as 5.0 with bond length of 60,
corroded in concrete cylinders. The pre-corrosion region was taken 80 and 100 mm for 12, 16 and 20 mm rebar respectively. A pair of
as 150 mm in the middle of concrete cylinder, and concrete cover PVC sleeves was used at two ends to obtain a precise bond length.
thickness was 25 mm. The non-corrosion region of rebar in con- And the gap between PVC pipe and rebar was sealed using glue to
crete was covered with epoxy resin and protected using PVC prevent the infiltration of fresh cement matrix.
L. Hou et al. / Construction and Building Materials 182 (2018) 637–645 639

custom-built loading set-up used in this test. In this set-up, a pair


of spherical hinges was arranged at up and lower end plates of load-
ing frame to ensure a central tensile force. A 100 kN load cell was used
to measure the pull-out force. Two pairs of linear variable difference
transformers (LVDTs) were symmetrically arranged at the loading
and free ends of pull-out specimen to obtain the relative slip between
rebar and matrix. All the test data were collected continuously by a
quasi-static data acquisition system connected with a computer.

2.5. Actual corrosion ratio and corrosion appearance

Fig. 2. Configuration of central pull-out specimens. After the pull-out tests, the corroded rebar was taken out
through splitting the specimens. Then, the matrix bonded on the
2.3. Materials rebar was removed using steel wire brush. At last, the bond region
of corroded rebar was cut out to measure the mass loss. The ratio of
Plain concrete and SFRC were used for pull-out specimens. The tested mass loss Dm to initial mass m0 (Dm/m0) was used to repre-
mixture proportion of concrete by weight was cement:water: sent the actual corrosion ratio qc. The calculated corrosion ratio is
sand:coarse aggregate = 1:0.45:1.73:2.00. The matrix of SFRC was summarized in Table 1. Note that the actual corrosion had a differ-
same as the concrete used. The fraction of hooked steel fiber added ence from the target pre-corrosion ratio. Here, if the difference in
was 0.75% in volume. P.O. 42.5 cement, coarse aggregate with a actual corrosion ratio was within 1%, the corresponding specimens
maximum diameter of 10 mm, and the medium river sand were were considered as one series and the average corrosion ratio was
used to prepare concrete and SFRC. The hooked steel fiber had a used to denote the corrosion level of this series. In addition, con-
length of 35 mm, a length to diameter ratio of 65, an elastic mod- crete and SFRC were simplified as C and SC, and the reinforcement
ulus of 200 GPa, and a tensile strength of 1345 MPa. was denoted by D12, D16 and D20 according to rebar diameter.
Pull-out specimens were cast in plywood molds. Meanwhile, two The Arab number 1, 2, 3 and 4 was utilized to represent different
groups of 100 mm cube were left to measure the compressive sample in the same series. For example, specimen D16-10.4-SC2
strength of concrete and SFRC. All the specimens were cured outdoors represents the second SFRC specimen of the series with 10.4%
for 28 days though covering sand and plastic sheet and watering 1–2 actual average corrosion ratio and 16 mm diameter of rebar.
times every day to remain specimen wet. The cube compressive Fig. 4 shows the typical appearance of corroded rebar in the bond
strength fcu of concrete and SFRC was 59.57 and 52.52 MPa. In addi- region. As shown in Fig. 4, the corrosion at the side close to NaCl
tion, the tested yield strength fy and ultimate tensile strength fu were solution was far severe compared with the back side. The rib damage
460 and 594 MPa for 12 mm rebar, 456 and 586 MPa for 16 mm was aggravated with increasing corrosion ratio and decreasing rebar
rebar, and 439 and 578 MPa for 20 mm rebar, respectively. diameter. At corrosion below about 5%, a slight corrosion pit
occurred along rebar, and then corrosion pit and rib damage aggra-
vated, and even the ribs at the heavy corrosion side have disap-
2.4. Test apparatus and procedure
peared at corrosion ratio beyond about 12% for D12 and D16 series.

Pull-out test was carried out on a 300 kN electrohydraulic servo-


3. Experimental results and discussion
controlled testing machine. The load was applied using a displace-
ment controlled mode at a speed of 0.5 mm/min. Fig. 3 shows a
In this section, the effect of corrosion ratio and cover thickness
to rebar diameter ratio on bond behavior was discussed. Table 1
summarizes the experimental results including nominal bond
strength (su), average nominal bond strength for the same series
(su,av), and failure mode, etc.
The nominal average bond stress s along the bond length is
generally used to represent the local bond approximately, as
expressed by Eq. (2),
P
s¼ ð2Þ
pdl
where, P is pull-out force, l is bond length, and d is nominal rebar
diameter. However, a non-uniform corrosion was presented along
longitudinal length especially for rebar with large corrosion ratio.
And thus it is difficult to measure the diameter after corrosion pre-
cisely. In addition, the nominal diameter of non-corroded rebar was
always used to compute the bond strength without considering the
variation of rebar section in post-corrosion condition where bond
was measured after corrosion without removing corrosion products
[3–6]. Therefore, for simplification, the initial nominal diameter was
still used for calculating the average bond stress in the present
pre-corrosion condition. Bond strength (su) can be taken as the
nominal average bond stress at the peak point. Average slip
between steel bar and matrix is usually used to represent the slip
behavior [27], as expressed by Eq. (3)
sl þ sf
s¼ ð3Þ
Fig. 3. Test apparatus and loading set-up used in this test. 2
640 L. Hou et al. / Construction and Building Materials 182 (2018) 637–645

Table 1
Details and experimental results of test specimens.

Specimen l/mm c/d qc/% qc,av/% su/MPa su,av/MPa su,cal/MPa failure mode
D12-0-C1 60 5.75 0.00 0.00 19.09 18.82 16.84 S
D12-0-C2 60 5.75 0.00 20.00 16.84 S
D12-0-C3 60 5.75 0.00 17.36 16.84 S
D12-0-SC1 60 5.75 0.00 0.00 14.33* 20.85 18.52 PO
D12-0-SC2 60 5.75 0.00 21.31 18.52 PO
D12-0-SC3 60 5.75 0.00 20.39 18.52 PO
D12-4.4-SC1 60 5.75 4.81 4.44 17.45 16.67 16.63 PO
D12-4.4-SC2 60 5.75 4.07 15.89 16.92 PO
D12-5.6-SC1 60 5.75 5.54 5.57 16.69 17.73 16.34 PO
D12-5.6-SC2 60 5.75 5.95 17.37 16.18 PO
D12-5.6-SC3 60 5.75 5.23 19.11 16.46 PO
D12-8.3-SC1 60 5.75 8.06 8.26 15.28 13.33 15.35 PO
D12-8.3-SC2 60 5.75 8.45 11.37 15.19 PO
D12-12.3-SC1 60 5.75 12.30 12.30 12.24 12.24 13.68 PO
D12-16.9-SC1 60 5.75 16.91 16.91 12.63 12.63 11.86 PO
D16-0-C1 80 4.19 0.00 0.00 15.76 14.80 13.64 S
D16-0-C2 80 4.19 0.00 13.79 13.64 S
D16-0-C3 80 4.19 0.00 14.84 13.64 S
D16-0-SC1 80 4.19 0.00 0.00 14.80 14.54 14.99 S-PO
D16-0-SC2 80 4.19 0.00 15.49 14.99 S-PO
D16-0-SC3 80 4.19 0.00 13.32 14.99 S-PO
D16-3.4-SC1 80 4.19 3.50 3.39 15.12 14.13 14.12 S-PO
D16-3.4-SC2 80 4.19 3.28 13.14 14.17 S-PO
D16-5.1-SC1 80 4.19 5.09 5.09 13.82 13.82 13.73 S-PO
D16-9.2-SC1 80 4.19 9.18 9.18 14.18 14.18 12.71 S-PO
D16-10.4-SC1 80 4.19 10.56 10.38 12.06 12.15 12.37 S-PO
D16-10.4-SC2 80 4.19 10.20 12.24 12.46 S-PO
D16-12.9-SC1 80 4.19 12.58 12.88 13.37 13.37 11.86 S-PO
D16-12.9-SC1 80 4.19 13.17 12.29 11.72 S-PO
D16-14.1-SC2 80 4.19 14.08 14.08 11.62 11.62 11.49 S-PO
D20-0-C1 100 3.25 0.00 0.00 10.13 9.44 11.52 S
D20-0-C2 100 3.25 0.00 8.88 11.52 S
D20-0-C3 100 3.25 0.00 9.33 11.52 S
D20-0-SC1 100 3.25 0.00 0.00 13.54 12.90 12.66 S-PO
D20-0-SC2 100 3.25 0.00 12.62 12.66 S-PO
D20-0-SC3 100 3.25 0.00 12.54 12.66 S-PO
D20-4.9-SC1 100 3.25 4.98% 4.86% 11.86 11.76 11.79 S-PO
D20-4.9-SC2 100 3.25 4.73% 12.45 11.84 S-PO
D20-4.9-SC3 100 3.25 4.38% 11.45 11.90 S-PO
D20-4.9-SC4 100 3.25 5.34% 11.29 11.73 S-PO
D20-6.7-SC1 100 3.25 6.20% 6.71% 11.10 10.54 11.58 S-PO
D20-6.7-SC2 100 3.25 7.21% 9.98 11.40 S-PO
D20-8.6-SC1 100 3.25 8.15% 8.56% 10.37 10.82 11.24 S-PO
D20-8.6-SC2 100 3.25 8.96% 11.28 11.10 S-PO
D20-11.0-SC1 100 3.25 10.98% 10.98% 10.71 10.71 10.75 S-PO
Mean 1.01
C.V. 0.11

Note: * this bond strength was not used to calculate su,av due to a difference from su,av beyond 15%; qc,av is the average corrosion ratio.

5.0 8.96 11.0 8.96 failure. The failure mode of tested specimens is listed in Table 1.
3.5 10.2
The failure mode was mainly dependent on c/d of pull-out speci-
14.1 10.2
mens and tension property of matrix material surrounding the
5.5 8.5 16.9 8.5 rebar. The concrete comparison specimens all failed in splitting
even if a large c/d of 5.75 was used. In contrast, SFRC specimens
with c/d of 5.75 failed in pull-out, whereas the rest SFRC specimens
failed in combined splitting and pull-out. This can be mainly attrib-
uted to the improved tension capacity and ductility due to steel
fibers distributed in SFRC. The splitting cracks were restrained
effectively depending on the bridging action of fibers across cracks.
3.5%~5.5% 8.5%~10.2% 11%~16.9% back Fig. 5 shows the typical crack pattern for different failure
modes. For splitting failure, the specimen was separated into two
Fig. 4. Appearance of corroded rebar for D16 series.
parts at the peak load. For pull-out failure, no radial and longitudi-
nal cracking occurred during pull-out of rebar. For combined split-
where, s is the average slip, sl and sf are the slip at the loading and ting and pull-out failure, the splitting crack formed at the loading
free ends. end of specimens when approaching the peak load and then grad-
ually widened and developed to the free end with increasing slip.
3.1. Failure mode As shown in Fig. 5, rebar corrosion within about 15% of mass loss
had a negligible effect on the crack and failure pattern. However,
Three failure modes were showed including splitting (S) failure, the crack width increased apparently with decreasing c/d regard-
pull-out (PO) failure and combined splitting and pull-out (S-PO) less of matrix material. For concrete samples, D12 series with c/d
L. Hou et al. / Construction and Building Materials 182 (2018) 637–645 641

interlocking action between rebar and SFRC was weakened due


D12-0-C D16-0-C D20-0-C
to damage of SFRC teeth between the rebar ribs. However, for
D16 and D20 series, the confinement provided by surrounding
matrix was weakened because of splitting cracking near the peak
load. Consequently, SFRC teeth between ribs may be subjected to
a heavy damage when experiencing a slight slip, which resulted
in a sharp stress reduction at the peak point especially for D20 ser-
(a) ies with a smaller c/d.
As shown in Fig. 6, the residual bond strength increased with
D12-0-SC D16-0-SC D20-0-SC increasing c/d as the peak bond stress did. Here, the residual bond
strength sr is assumed to be the bond stress at the slip of 1.5cr, in
which cr is the center distance between rebar ribs. It is found that
sr varied from 7.48 MPa for c/d of 5.75 to 1.65 MPa for c/d of 3.25.
Note that the residual bond strength was mainly provided by the
friction resistance between rebar and surrounding matrix. The
D16-10.4-SC D16-14.1-SC D20-11.0-SC increasing c/d greatly improved the integrity of specimens during
pull-out of embedded rebar depending on declined splitting crack
width or even no splitting cracking.
Fig. 7 shows the bond-slip curves of SFRC specimens. As shown
in Fig. 7(a)–(c), rebar corrosion greatly affected the bond-slip
behavior. For the ascending branch, both bond stiffness and peak
(b) bond stress of corroded rebar became lower than that of non-
corroded rebar, and an increase in c/d aggravated the bond loss.
Fig. 5. Typical failure patterns of test specimens: (a) concrete specimens; (b) SFRC For the descending branch, the degradation gradient of bond stress
specimens with different corrosion ratios.
decreased with increasing corrosion ratio, especially for D12 series
failing in pull-out. In addition, the drop of bond stress at the peak
point was mitigated for D16 and D20 series with corroded rebar.
of 5.75 showed a slight splitting crack propagation compared with
The deteriorated mechanical interlocking action due to corroded
D16 and D20 series. For SFRC specimens, the splitting crack width
rebar ribs was mainly responsible for the bond strength loss.
increased from 0 mm for c/d of 5.75 to 0.28–0.80 mm for c/d of 4.19
Meanwhile, the rib corrosion damage was relatively severe for
and to 0.72–1.34 mm for c/d of 3.25.
rebar with small diameter at the same corrosion level, resulting
in a more apparent bond stiffness reduction for D12 series com-
pared with other series.
3.2. Bond-slip curves
Note that the bond stress at the slip of 1.5cr may be larger than
the stress at the lower end point of descending branch, such as
Fig. 6 shows bond-slip curves of non-corroded rebar embedded
specimen D16-14.1-SC1 shown in Fig. 7(b). Therefore, the residual
in concrete and SFRC. As shown in Fig. 6, the concrete specimens
bond strength was further taken as the minimum value of the bond
merely had an ascending branch, whereas the SFRC specimens all
stress at the slip of 1.5cr and that at the lower end point of
showed typical three-branch curves including ascending, descend-
descending branch. It is found from Fig. 7 that the residual bond
ing and residual branches.
strength of corroded rebar was not lower than that of non-
Moreover, c/d had a great effect on the bond-slip curves of SFRC
corroded rebar, especially for rebar with corrosion ratio beyond
specimens, especially for the bond behavior around the peak load.
about 6% except for specimen D12-16.9-SC1. This mainly can be
D12 series presented an apparent nonlinear slip behavior around
attributed to two aspects. One is the reduced stress concentration
the peak bond stress. In contrast, D16 and D20 series showed a
on matrix surrounding the damaged ribs, which resulted in rela-
sharp reduction in bond stress at the peak point, and this drop
tively light damage in matrix and thus improved confinement.
was aggravated with decreasing c/d. This phenomenon mainly
The other is the non-uniform corrosion appearance along steel
arose from different failure modes. For D12 series failing in pull-
bar. It may lead to varied contact profiles between rebar and
out, the embedded rebar was still subjected to a strong confine-
matrix within bond length, and thus the friction resistance can
ment from the surrounding SFRC without splitting cracks. The peak
be improved during pull-out of rebar. In contrast, with respect to
bond stress can be maintained within a certain slip until the
the relative residual bond strength (sr/su), it was gradually
enhanced with increasing corrosion ratio regardless of c/d. In
25 detail, sr/su increased from 0.32 to 0.65 for D12 series, from 0.21
D12-0-SC3
to 0.50 for D16 series and from 0.15 to 0.39 for D20 series.
20
3.3. Bond strength
D12-0-C1
15
/MPa

Bond strength su and its average value su,av for all the series are
10 D16-0-C3 summarized in Table 1. For specimens with non-corroded rebar,
bond strength of SFRC specimens was larger than that of concrete
D16-0-SC1 specimens for D12 and D20 series, whereas the bond strength of
5 D20-0-C3 SFRC and concrete specimens was close to each other for D16
D20-0-SC2 series. Note that the compressive strength of SFRC was about
0
0 3 6 9 12 15 18 6.71 MPa lower than that of concrete. If the bond strength is nom-
cu , su,av/fcu of series D16-0-SC and D16-0-C was 2.06
inalized to f0.5 0.5
s /mm
and 1.97 respectively. In other words, the addition of fiber was
Fig. 6. Bond-slip curves of non-corroded rebar in concrete and SFRC. helpful to improve the bond strength due to the fiber bridging
642 L. Hou et al. / Construction and Building Materials 182 (2018) 637–645

25 between pullout and beam tests was inadequate so far. de Almeida


Filho et al. [28] compared the bond between reinforcement and
D12-0-SC3 concrete using RILEM pullout and beam tests, where the same
20
c/d but different l/d were used. The experimental results indicated
that the bond strength obtained from both types of tests was close
15 D12-5.6-SC2
D12-8.3-SC1 to each other although the bond length was 5d and 10d for pullout
/MPa

D12-16.9-SC1 and beam specimens respectively. In general, the bond strength


10 gradually decreases with increasing bond length. In other words,
the bond strength obtained from beam test is expected to be supe-
5 rior to that from pullout test if using a same bond length. However,
D12-12.3-SC1 D12-4.4-SC1 the further comparison study on the pullout and beam tests needs
to be performed to understand the relationship of bond behavior
0
0 3 6 9 12 15 18 obtained from these two types of tests.
s /mm Fig. 8 shows the variation of bond strength with corrosion ratio
for SFRC specimens. As shown in Fig. 8, the bond strength was
(a) correlated to both corrosion ratio and c/d. The bond strength
almost varied with corrosion ratio linearly from 20.85 to 12.63
18 MPa for D12 series, from 14.54 to 11.96 MPa for D16 series, and
D16-0-SC1
from 12.9 to 10.71 MPa for D20 series. The bond strength of
15 D16-3.4-SC1 deformed rebar mainly depended on three aspects: adhesion,
mechanical interlock and friction. And the mechanical interlocking
12 action played a key role because the adhesion failed early and the
D16-5.1-SC1 D16-14.1-SC1 friction mainly determined the residual bond strength. The dam-
/MPa

9 aged ribs due to corrosion weakened the mechanical interlocking


D16-12.9-SC1
effect and resulted in reduction in bond strength. Moreover, D12
6 D16-10.4-SC2
series obtained a relatively large reduction in bond strength com-
3 pared with D16 and D20 series. Bond strength loss was approxi-
D16-9.2-SC1 mate 39%, 20% and 17% at the corrosion ratio of about 17% for
0 D12 series, 14% for D16 series and 11% for D20 series respectively.
0 3 6 9 12 15 18 For D12 series failing in pull-out, the interlocking action of ribs can
s /mm be fully exerted during pull-out, and thus the damage in ribs is
expected to greatly deteriorate the bond strength. In contrast,
(b) D16 and D20 series failed in combined splitting and pull-out, and
the mechanical interlocking action was discounted due to splitting
15 cracking of the surrounding SFRC. Consequently, the bond perfor-
D20-0-SC2
mance of specimens with a large c/d may be more sensitive to
12 the corrosion damage.

9 D20-6.7-SC1 3.4. Bond toughness


/MPa

D20-8.6-SC2
D20-11.0-SC1 Bond toughness was evaluated by the area under bond-slip
6
curves referring to the flexural toughness evaluation method ASTM
C 1609 [29], and can be obtained by
3 Z si
D20-4.9-SC1
Ai ¼ sds ð4Þ
0 0
0 3 6 9 12 15 18
where, Ai is area under bond-slip curve up to the ith target slip si,.
s /mm Note that the target slips were extended to cover the whole

(c)
24
Fig. 7. Bond-slip curves of corroded rebar embedded in SFRC: (a) D12 series; (b) c/d=5.75
c/d=4.19
D16 series; (c) D20 series. 20
c/d=3.25

action. Moreover, bond strength of SFRC and concrete specimens 16


with non-corroded rebar was enhanced with increasing c/d. As
/MPa

12
shown in Table 1, bond strength of SFRC specimens varied from
20.85 MPa for c/d of 5.75 to 12.9 MPa for c/d of 3.25. This can be
u

8
attributed to the improved confinement effect of the surrounding
matrix with an increase in c/d.
4
However, the pullout test was applied rather than beam test in
this study. During pullout testing, the matrix near the loading end 0
is subjected to compression action of loading plate, which is differ- 0 3 6 9 12 15 18
ent from the actual stress state of structural members. In contrast,
c
/%
the flexure test may be close to the actual stress state in structural
members. However, the comparison study on bond behavior Fig. 8. Bond strength between SFRC and rebar with different ratios.
L. Hou et al. / Construction and Building Materials 182 (2018) 637–645 643

descending and residual branches, including the slip sp at the peak improved compared with that of non-corroded rebar. This mainly
point, and 3, 5, 10 and 15 mm. arose from the relatively small bond strength loss but improved
Fig. 9 shows the bond toughness of specimens with corrosion residual bond strength and decreased bond stress drop at the peak
ratio and c/d. It is revealed that the variation of bond toughness point especially for the cases with a large corrosion ratio.
with corrosion ratio is correlated with c/d. For D12 series shown
in Fig. 9(a), the bond toughness of corroded rebar first remained
close to that of non-corroded rebar at corrosion ratio below 8.3%, 4. Bond strength model and discussion
and then reduced at corrosion ratio beyond 12.3%. Although the
ratio of residual bond strength to su (sr/su) of corroded series For the non-corroded specimens, a group of existed bond
D12-12.3-SC and D12-16.9-SC were far larger than that of non- strength models, used for plain concrete proposed by Aslani and
corroded series D12-0-SC, it hardly compensated the toughness Nejadi [30] and for SFRC proposed by Harajli et al. [31], were
loss due to the severe reduction of bond strength. In contrast, for applied to evaluate the bond strength, as expressed by Eq. (5),
D16 and D20 series, the bond toughness of corroded rebar was 8h  0:6  i 0 0:55
>
< 0:679 dc þ 3:88 dl f c for plain concrete
su0 ¼ qffiffiffiffiffiffi  qffiffiffiffiffiffi ð5Þ
>
: 0:78 f cþK c
0 2=3 0
c d
6 2:57 f c for SFRC
200 Ap A3 A5 A10 A15
where, f0c is cylinder compressive strength, taken as 80% of cube
160 compressive strength fcu (0.8fcu) [32]; Kc is fiber confinement factor,
given as K c ¼ 0:45cV f Lf =df , in which Vf, lf and df are the fiber fraction
A /(MPa mm)

120 in volume, fiber length and diameter respectively. If the fiber vol-
ume fraction is equal to 0, then the bond strength model for SFRC
80 degrads into a model for plain concrete.
Based on the plain concrete bond model in Eq. (5), the calcu-
40 lated bond strength ranged from 17.53 to 21.96 MPa for concrete
series and from 16.36 to 20.63 MPa for SFRC series without consid-
0 ering the fiber contribution with increasing c/d from 3.25 to 5.75.
0 4 8 12 16 20 Compared with the experimental results, the calculated strength
c
/% had the maximum overestimation of 17% for D12 series, but an
average overestimation of approximate 27% for D16 and D20 series
(a)
except for D20-0-C series with a deviation up to 86%. In contrast,
150 the predicted bond strength using the SFRC model in Eq. (5) ranged
Ap A3 A5 A10 A15 from 11.52 to 16.84 MPa for concrete specimens with an underes-
timation below 10% for D12 and D16 series but an overestimation
120
of 22% for D20 series. And for SFRC specimens, the calculated bond
strength was 16.66, 14.99 and 12.66 MPa for D12, D16 and D20
90
A /(MPa mm)

series respectively. It indicates a good prediction for D16 and


D20 series failing in S-PO but a 20% underestimation for D12 series
60 failing in PO when using SFRC model in Eq. (5). The comparison
above reveals that the SFRC model proposed by Harajli et al. [31]
is more applicable to predict the bond strength of non-corroded
30
specimens regardless of concrete and SFRC. And thus it was further
applied in the present study.
0 Moreover, if further ignoring the upper limit of the Harajli
0 3 6 9 12 15 model in Eq. (5), the ratio of predicted to tested strength of D12-
c
/% 0-SC series became 0.89 almost satisfying the requirement in engi-
(b) neering field. Also, Campione et al. [24] studied the bond behavior
of rebar embedded in SFRC with c/d up to 6.58, and the experimen-
125 tal details are summarized in Table 2. As the Table shows, the bond
Ap A3 A5 A10 A15
strength calculated based on the Harajli model was 0.64–0.78su
100 but became 0.83–0.91su if ignoring the upper limit requirement
of 2.57f0c 0.5. It is pointed out that the upper limit of bond strength
in the Harajli model was determined based on the specimens with
A /(MPa mm)

75
c/d ranged from 2.30 to 3.18 [33]. However, in the cases with a
large c/d, i.e., 5.75 of D12 series in the present test and 6.58 of
50 c/d used in Campione et al.’s tests [24], the bond strength may be
underestimated using this bond upper limit model due to a supe-
25 rior confinement of SFRC cover. Based on this point, the upper limit
of 2.57f0c 0.5 is suggested to be cancelled within c/d of 6.58 in the
0 current model, but the further investigation needs to be conducted
0 2 4 6 8 10 12 concerning the effect of c/d on the bond strength upper limit of
c
/% SFRC.
As aforementioned in experimental results, the rebar corrosion
(c)
had an apparent effect on the bond strength. Bond strength almost
Fig. 9. Bond toughness of SFRC specimens with corrosion ratio: (a) D12 series; (b) decreased with corrosion ratio in a linear relationship, and the
D16 series; (c) D20 series. degradation gradient was greatly related to c/d. Accordingly,
644 L. Hou et al. / Construction and Building Materials 182 (2018) 637–645

Table 2
Experimental details and results reported by Campione et al. [24].

specimen ld lf/df Vf c d c/d fc kc su su-cal 2.57f0c 0.5 su-cal/su 2.57f0c 0.5/su

Squat 5 60 0 79 12 6.58 22.00 0.00 15.53 12.85 12.05 0.83 0.78


Squat 5 60 0.5 79 12 6.58 26.20 10.67 18.44 15.20 13.10 0.83 0.71
Squat 5 60 1 79 12 6.58 27.50 21.33 19.00 16.85 13.48 0.89 0.71
Squat 5 60 2 79 12 6.58 29.00 42.66 21.52 19.68 13.84 0.91 0.64

a general function considering the coupling effect of corrosion ratio and on the cross section. Berrocal et al. [36] employed a 3D scan-
and c/d is introduced to predict the bond strength, ning technique to determine the local corrosion level, and obtain
 a description of the cross-sectional variation along the bars. But
c
su ¼ su0 - SFRC 1 þ Aqc þ Bqc ð6Þ this high-precision measure is difficult to achieve due to lack of
d the related test apparatus in our laboratory.
where, su0-SFRC denotes the bond strength model for SFRC in Eq. (5); Moreover, in practice, the corroded rebar cannot be cut out to
A and B are the regression coefficients based on tested bond measure the local corrosion level using 3D scanning technique. In
strength. The following equation is obtained through multi- general, it is the corrosion depth that is measured to simply repre-
parameter regression analysis, sent the corrosion level and the change in rebar surface profile.
Correspondingly, the corrosion ratio can be obtained based on
qffiffiffiffiffiffi 2=3  the measured corrosion depth, the relationship between pit and
c þ Kc c
su ¼ 0:78 f 0 c 1  0:004qc  0:003qc ð7Þ average corrosion depth, and correlation of cross-sectional loss
d d with pit and average corrosion, as presented in Campione et al.’s
study [37]. In other words, the corrosion depth and corrosion ratio
The calculated bond strength (su,cal) based on Eq. (7) is summa-
can be represented with each other. Moreover, compared with the
rized in Table 1. The mean and coefficient of variation (C.V.) of the
corrosion depth measure, the measure of corrosion ratio repre-
ratio between calculated and tested bond strength (su/su,cal) were
sented by cross-section loss (equivalent to mass loss) was of high
1.01 and 0.11 respectively. The calculated strength agreed well
precision and simple operation. In addition, the corrosion ratio is
with the tested value, and the proposed equation can be used to
the most-common parameter to represent the rebar corrosion
predict the bond strength of pre-corroded rebar embedded in SFRC
degree and to be used for evaluating the residual mechanical per-
for corroded RC members repaired using SFRC. However, these
formance of corroded RC members. Therefore, the parameter of
equations may be limited to the SFRC reinforced using hooked steel
corrosion ratio was used in the present test and in Eqs. (6) and
fiber due to only this type fiber used in the present study and Hara-
(7). In summary, the bond strength of corroded rebar and SFRC
jli et al.’s studies [31,34]. In addition, owing to a small experimen-
can be obtained based on Eq. (7) and the transformation relation-
tal data in the present study, the Eq. (7) needs to be further verified
ship between corrosion depth and corrosion ratio.
in future experimental study before used in the practice.
Note that the corrosion effect in Eq. (7) was obtained based on
the present experimental data for fiber volume fraction of 0.75%, 5. Conclusions
and may have a limitation for other fiber fractions. In fact, the SFRC
model in Eq. (5) proposed by Harajli et al. [31] was obtained based In this paper, bond-slip behavior between SFRC and pre-
on the bond data for SFRC with fiber volume fraction in the range corroded rebar obtained in a concrete environment was investi-
of 0.5–2.0%. On the other hand, the fiber fraction plays a key role in gated through central pull-out tests. The following conclusions
the bond between rebar and SFRC when remaining the same can be drawn:
parameters of c/d, l/d and compressive strength. If considering a
similar influence of fiber fraction on pre-corroded rebar to that of (1) Compared with concrete comparison specimens failing in
non-corroded rebar, then the proposed Eq. (7) may be used for splitting, SFRC specimens all showed either pull-out failure
other fiber fractions. It is well known that the improved bond with no splitting crack or combined splitting and pull-out
under the addition of fiber mainly lies in the enhancement in failure with longitudinal splitting cracks. Besides, the split-
mechanical interlocking action between rebar and the surrounding ting crack propagation was mainly affected by c/d rather
concrete due to fiber bridging action across splitting cracks. The than rebar corrosion ratio, and the crack width reduced
experimental results revealed that the bond strength was about gradually with increasing c/d from 0.72 to 1.34 mm for c/d
1.79f0.5 0.5 0.5
cu , 1.65fcu and 1.52fcu at the corrosion ratio of about 17%
of 3.25 to 0 mm for c/d of 5.75.
for D12 series, 14% for D16 series and 11% for D20 series respec- (2) All the SFRC specimens showed full three-branch bond-slip
tively, which was far larger than 0.23–0.25f0.5cu for plain round rebar
curves whereas concrete specimens had the ascending
embedded in concrete with c/d of 2.91–5.75 [35]. This means that a branch merely. For non-corroded rebar embedded in SFRC,
good mechanical interlocking action can still be obtained an apparent slip plateau was presented around the peak
especially for D16 and D20 series although the rebar ribs were bond stress for specimens with c/d of 5.75, whereas a sharp
subjected to corrosion damage. As a result, it seems to be feasible reduction in bond stress occurred at the peak point for spec-
to consider a same fiber fraction influence on bond between non- imens with c/d below 4.19. Besides, the residual bond
corroded and pre-corroded reinforcement within obtained strength increased with increasing c/d due to improved con-
corrosion ratio in this test. However, the further experimental finement of surrounding matrix.
study is still needed to evaluate the fiber fraction effect on bond (3) For the bond-slip curves of corroded rebar in SFRC, bond
of pre-corroded rebar and SFRC. stiffness gradually reduced with increasing corrosion ratio
In Eqs. (6) and (7), the corrosion ratio was used rather than a especially for specimens with c/d of 5.75. Meanwhile, the
parameter reflecting the change in roughness of reinforcement residual bond strength of corroded rebar was no lower than
after corrosion. In fact, it is difficult to determine and measure that of non-corroded rebar. Further, the ratio of residual
the surface profile of the corroded reinforcement precisely due to bond strength to bond strength (sr/su) almost increased with
a non-uniform corrosion distribution along the longitudinal length corrosion ratio linearly.
L. Hou et al. / Construction and Building Materials 182 (2018) 637–645 645

(4) The addition of steel fiber can improve the bond strength [9] M. Nili, V. Afroughsabet, Combined effect of silica fume and steel fibers on the
impact resistance and mechanical properties of concrete, Int. J. Impact Eng. 37
between rebar and concrete, especially for specimens with
(8) (2010) 879–886.
c/d of 3.25. For non-corroded rebar, bond strength of SFRC [10] F. Germano, G. Tiberti, G. Plizzari, Post-peak fatigue performance of steel fiber
and concrete specimens was improved with an increase in reinforced concrete under flexure, Mater. Struct. 49 (10) (2016) 4229–4245.
c/d. [11] G. Zhao, C. Huang, Properties and application of steel fiber reinforced concrete,
Ind. Constr. 10 (1989) 3–10 (in Chinese).
(5) Bond strength almost linearly reduced with increasing [12] C. Yi, H. Xie, W. Gao, Effects of steel fiber on the restraining for propagation of
corrosion ratio. Bond strength loss due to rebar corrosion concrete crack and on the permeability of concrete, China, Civil. Eng. J. 37 (3)
was related to c/d and bond failure mode of specimens. (2004) 19–25 (in Chinese).
[13] X. Xie, D. Gao, J. Zhao, Tentative study on the mechanical property under the
D12 series failing in pull-out showed bond strength loss high action of freeze-thaw and carbonation of steel fiber reinforced concrete, J.
up to about 39% at corrosion ratio within 17%, whereas other Xi’an Univ. Archit. Technol. (Nat. Sci. Ed.) 38 (4) (2006) 514–517 (in Chinese).
series failing in combined splitting and pull-out had 20% and [14] S. Iqbal, A. Ali, K. Holschemacher, et al., Strengthening of RC beams using steel
fiber reinforced high strength lightweight self-compacting concrete (SHLSCC)
17% loss at corrosion ratio within 14% for c/d of 4.19 and 11% and their strength predictions, Mater. Des. 100 (2016) 37–46.
for c/d of 3.25. [15] V. Marcos-Meson, A. Michel, A. Solgaard, et al., Corrosion resistance of steel
(6) The variation of bond toughness with corrosion ratio was fibre reinforced concrete – a literature review, Cem. Concr. Res. 103 (2018) 1–
20.
affected by c/d. Bond toughness of series with c/d below [16] S. Abbas, Structural and Durability Performance of Precast Segmental Tunnel
4.19 was improved with increasing corrosion ratio, whereas Linings, University of Western Ontario, Canada, 2014.
that of series with c/d of 5.75 first remained almost [17] D. Homma, H. Mihashi, T. Nishiwaki, Self-healing capability of fibre reinforced
cementitious composites, J. Adv. Concr. Technol. 7 (2009) 217–228.
unchanged at corrosion below 8.3% and then gradually
[18] C. Frazão, J. Barros, A. Camões, A.C. Alves, L. Rocha, Corrosion effects on pullout
reduced. behavior of hooked steel fibers in self-compacting concrete, Cem. Concr. Res.
(7) A modified bond strength model was proposed considering 79 (2016) 112–122.
the coupling effect of rebar corrosion and c/d, and a good [19] J.-L. Granju, S.U. Balouch, Corrosion of steel fibre reinforced concrete from the
cracks, Cem. Concr. Res. 35 (3) (2005) 572–577.
agreement between tested and calculated bond strength [20] S.U. Balouch, J.P. Forth, J.-L. Granju, Surface corrosion of steel fibre reinforced
was obtained. concrete, Cem. Concr. Res. 40 (3) (2010) 410–414.
[21] Code of China, Technical code for repair and strengthening of harbor and
marine structures, JTS 311-2011, Beijing, China, 2011. (in Chinese).
Conflict of interest [22] G. Malumbela, M. Alexander, P. Moyo, Variation of steel loss and its effect on
the ultimate flexural capacity of RC beams corroded and repaired under load,
Constr. Build. Mater. 24 (6) (2010) 1051–1059.
The authors declare that they have no conflict of interest. ß . Yazici, H.S
[23] S ß. Arel, The effect of steel fiber on the bond between concrete and
deformed steel bar in SFRCs, Constr. Build. Mater. 40 (2013) 299–305.
[24] G. Campione, C. Cucchiara, L. La Mendola, M. Papia, Steel-concrete bond in
Acknowledgements lightweight fiber reinforced concrete under monotonic and cyclic actions, Eng.
Struct. 27 (6) (2005) 881–890.
[25] E. Baran, T. Akis, S. Yesilmen, Pull-out behavior of prestressing strands in steel
This study was financially supported by the program of the fiber reinforced concrete, Constr. Build. Mater. 28 (1) (2012) 362–371.
National Natural Science Foundation of China (51408186, [26] D. Gao, L. Xie, H. Zhu, Experimental research on bond property between steel
fiber reinforced high-strength concrete and rebars (in Chinese), Build. Sci. 20
51679080) and the Natural Science Foundation of Jiangsu Province
(3) (2004) 56–60.
(BK20140853). The authors wish to express their gratitude to M.S. [27] F. Xu, Z. Wu, J. Zheng, Y. Hu, Q. Li, Experimental study on the bond behavior of
H. Liu and undergraduate innovation training group headed by J. reinforcing bars embedded in concrete subjected to lateral pressure, J. Mater.
Civil Eng. 24 (1) (2012) 125–133.
Qu for their contribution to part of the experimental work.
[28] F.M. de Almeida Filho, M.K.E.I. Debs, A.L.H.C.E.I. Debs, Bond-slip behavior of
self-compacting concrete and vibrated concrete using pull-out and beam tests,
Mater. Struct. 41 (6) (2008) 1073–1089.
References [29] ASTM, Standard Test Method for Flexural Performance of Fiber-reinforced
Concrete (Using Beam with Third-point Loading), ASTM C 1609, ASTM
[1] M. Maslehuddin, I.M. Allam, G.J. Al-Sulaimani, A.I. Al-Mana, S.N. Abduljauwad, International, West Conshohocken, PA, USA, 2005.
Effect of rusting of reinforcing steel on its mechanical properties and bond [30] F. Aslani, S. Nejadi, Bond behavior of reinforcement in conventional and self-
with concrete, ACI Mater. J. 87 (5) (1990) 496–502. compacting concrete, Adv. Struct. Eng. 15 (12) (2012) 2033–2051.
[2] H.S. Lee, T. Noguchi, F. Tomosawa, Evaluation of the bond properties between [31] M.H. Harajli, B.S. Hamad, A.A. Rteil, Effect of confinement of bond strength
concrete and reinforcement as a function of the degree of reinforcement between steel bars and concrete, ACI Struct. J. 101 (5) (2004) 595–603.
corrosion, Cem. Concr. Res. 32 (8) (2002) 1313–1318. [32] Z. Guo, Strength and Constitutive Relationship of Concrete: Principle and
[3] S. Coccia, S. Imperatore, Z. Rinaldi, Influence of corrosion on the bond strength Application, China Architecture & Building Press, Beijing, 2004 (in Chinese).
of steel rebars in concrete, Mater. Struct. 49 (1–2) (2016) 537–551. [33] M.H. Harajli, M. Hout, W. Jalkh, Local bond stress-slip behavior of reinforcing
[4] C. Fang, K. Lundgren, M. Plos, K. Gylltoft, Bond behaviour of corroded bars embedded in plain and fiber concrete, ACI Mater. J. 92 (4) (1995) 343–
reinforcing steel bars in concrete, Cem. Concr. Res. 36 (10) (2006) 1931–1938. 354.
[5] C. Fang, K. Gylltoft, K. Lundgren, M. Plos, Effect of corrosion on bond in [34] M. Harajli, B. Hamad, K. Karam, Bond-slip response of reinforcing bars
reinforced concrete under cyclic loading, Cem. Concr. Res. 36 (3) (2006) 548– embedded in plain and fiber concrete, J. Mater. Civil Eng. 14 (14) (2002)
555. 503–511.
[6] W.P. Zhang, H. Chen, X.L. Gu, Bond behaviour between corroded steel bars and [35] Z. Wu, X. Zhang, J. Zheng, Y. Hu, Q.B. Li, Bond behavior of plain round bars
concrete under different strain rates, Mag. Concr. Res. 68 (7) (2015) 1–15. embedded in concrete subjected to biaxial lateral tensile-compressive
_
[7] Sß. Yazici, G. Inan, V. Tabak, Effect of aspect ratio and volume fraction of steel stresses, J. Struct. Eng. 140 (4) (2013). 04013089-1-11.
fiber on the mechanical properties of SFRC, Constr. Build. Mater. 21 (6) (2007) [36] C.G. Berrocal, I. Löfgren, K. Lundgren, The effect of fibres on steel bar corrosion
1250–1253. and flexural behaviour of corroded RC beams, Eng. Struct. 163 (2018) 409–425.
[8] H.H. Dinh, G.J. Parra-Montesinos, J.K. Wight, Shear behavior of steel fiber- [37] G. Campione, F. Cannella, L. Cavaleri, Shear and flexural strength prediction of
reinforced concrete beams without stirrup reinforcement, ACI Struct. J. 107 (5) corroded R.C. beams, Constr. Build. Mater. 149 (2017) 395–405.
(2010) 597–606.

Você também pode gostar