PowerCommand®
SYNC1320
©2007|Cummins Power Generation Inc.|All rights reserved|Specifications subject to change without notice|Cummins Power Generation
and Cummins are registered trademarks of Cummins Inc. PowerCommand, InPower, AmpSentry and “Our energy working for you.” are
trademarks of Cummins Power Generation.
S-1481c (1/08) Page 1 of 2
Control functions Control interface
Synchronizer - The SYNC1320 digital synchronizing Inputs
function will force a multi-genset bus to match the • Synchronize enable
phase, frequency and voltage of the reference bus (e.g. • Fault reset
utility). The synchronizer will operate over a range up to • Gen bus AC voltage (3 or 4 wire)
90-110% of nominal system voltage and up to +3 Hz of • Utility bus AC voltage (3 or 4 wire)
nominal system frequency. The synchronizer includes • B+ power Input 1 (9-32 VDC)
provisions for proper operation even with highly • B+ power Input 2 (9-32 VDC)
distorted voltage waveforms. The synchronizing
function is configurable for either phase synchronization Outputs
(default) or it can be set to maintain a fixed slip • Master frequency bias (connects to kW load share)
frequency which is adjustable. • Master voltage bias (connects to kVar load share)
Sync check (25) - A sync check function is also Configurable customer outputs - Control includes (8)
included with adjustments for phase angle window (5° - output signals (relay drivers) for use by external
20°), voltage window (0.5-10%), frequency window equipment. Default configuration for these signals
(0.001-1 Hz) and time delay (0.5-5 seconds). One of the include: common warning, fail to synchronize, utility bus
configurable outputs is preconfigured to activate when available, genset bus available and sync check OK.
the sync check conditions are met. Serial interface - This communication port allows the
Fail to synchronize warning - Indicates that the control to communicate with a personal computer running
sync check conditions could not be met within the fail to InPower service and maintenance software.
sync time delay setting (default 120 sec, adjustable 10-
900 sec). Starts timing when the synchronizer turns on. Construction
If the fault occurs, the synchronizer will continue running
The SYNC1320 is a single board, potted control module
by default. Optionally it can be configured to stop
that interfaces to external components through locking
synchronizing if the fault occurs and will not resume until
plug-in terminal blocks suitable for wiring up to 2.5 mm
the fault is reset via the fault reset input.
(12 ga).
Environment
Ordering information
The control is designed for proper operation without
SYNC1320 voltage matching master synchronizer, CD,
recalibration in ambient temperatures from -40 °C to
manual, p/n 0541-1359.
+70 °C (-40 °F to +158 °F), and for storage from -40 °C
to +80 °C (-40 °F to +176 °F). Control will operate with
humidity up to 95%, non-condensing and at altitudes up Certifications
to 5000 m (13,000 ft). PowerCommand SYNC1320 meets or exceeds the
The control system is specifically designed for requirements of the following codes and standards:
resistance to RFI/EMI, and to resist the effects of UL508 recognized
vibration to provide a long reliable life when installed in CE Mark
harsh environment. The control includes transient EN 61000-6-2
voltage surge suppression to provide compliance to EN 61000-6-4
referenced standards. ISO 7637, pulses #2, 3a, 3b, 5, 7
ISO9001 - PowerCommand control systems are
designed and manufactured in ISO9001 certified facilities.